Professional Documents
Culture Documents
TWO-MACHINE STABILITY
plicity many system problems have been reduced to this form for
motor or generator but which are known not to affect the large
stability.
The equations of rotor motion for machines 1 and 2, from Eq. 3-8,
can be written as
, ,,2 ~~ * ol ml ** el
kJ lit
H2 d S2 _ _
rj lit
[4-1]
51
their constant values, Tm\ = Tm2. This follows since there are
d 512 ir/
Tal [4-3]
or
dt2 H0
Tai [4-4]
where
H=rk
Since for the case of two machines with no resistance losses in the tie,
the electrical power or torque is given by Eq. 3-1, with #12 being
d%:
dt2
irf ( ElE2 \
Equation 4-6 is similar to Eq. 3-9 for one machine against an infinite
and Pritchard2 for the case of two changes in circuit conditions, and
tion of a fault and its removal. The solution is given for the maxi-
mum allowable switching time for removal of the fault without loss
to solve Eq. 4-6, and Byrd and Pritchard used long hand step-by-
step methods.
obtained as follows:
E\E2 E\E2
or
when
d 312 _ jr/
at 11 q
E\E2 _ *12(before)
* max '1
*12(before) *12(during)
d2S12 TfriTm
dt2 H0
(sin S0 . \ ,
Now, if
or
rf25]2 sin 50
rfr2 r,
This equation was solved for 5i2 in terms of r for various values of
tions.2 The curves of Figs. 4-1 to 4-17, taken from reference 2, give
xi 2 (before)
X\2 (after)
Sin 60-0.I0
55
5.0
5.0
Fig. 4-6.
Sin SQ-0.30
Sin 80n0.25
Sin $o=0.35
56
0.5
0.6
0.7
0.8
0.9
1.0
[Ch. 4
2.0 3.0
Fig. 4.9.
Fig. 4.8.
Sin 6o-0.50
Sin 80 '0.40
TWO-MACHINE STABILITY
57
5.0
5.0
l'0.8
uN0.8
Fig. 411.
Fig. 4.10.
Sin 60-0.60
Sin 80-0.55
Sin 80=0.65
58
5.0
[Ch. 4
Fig. 413.
Fig. 4-15.
Fig. 4-14.
Sin S0'0.80
Sin 80-0.70
Sin 6on0.75
TWO-MACHINE STABILITY
59
Sin 80-0.85
5.0
5.0
These curves represent the solution of Eq. 4-12 for different values
In this way these solutions give directly the critical switching time in
the exception of one special case. This special case will be described
next, after which the use of these curves will be illustrated in this
section by an example.
Special Case (r\ = 0). The solution of Eq. 4-12 requires a special
cos5s
r.>
[4-13]
dt2
H0
rmax sin 50
[4-14]
rmax [4-15]
or
t = , K [4-16]
IZ
1 max
d%
dp.
2 = sin 50 [4.17]
dp
2(Si2 50)
sin Sn
[4-18]
abscissa.
and inertia constant for each of the two machine groups. Machines
>
Q.
00
61
CO
oo
CNJ
00 f
3 "!S
62
[Ch. 4
TW6-MACHINE STABILITY
(5l and 82) as the transmitted load is varied. Plot the variation
Ho 0-
yOOQQQi
Hb 0-
-^msusir-
He Q-
-dmSSLr-
a>-
-\00000 r-
-vJMJ&ay-
-^umsu-
iQQOOOj
1 \S&St!llb'
iJUfiy^J
(0)
(b)'
I 'SiSiSiiI
MJ<S&&&Sb|viMfiff./ yjmaiLr(z)
to
Fig. 4-19.
of sin 5o, the sine of the initial angular displacement (512 initial),
sin 80. These two plots will be used to determine the transmitted
*12(before)
and
*12(during)
r2 =
^(before)
*12(after)
the plot of sin 80 versus initial power to obtain the power correspond-
63
ing to r\ (the power that can be transmitted if the fault is not cleared)
sin 50, which, from the curves plotted in accordance with (2), cor-
[4-19]
12(before)
If rt =0 for any case, use Fig. 4-18 to obtain p and use Eq. 4-16 to
obtain t.
6. Switching time curve. Plot the results of (4) and (5), initial
illustrate the steps in the calculation of the transient stability limits by the method
just outlined. The effect of a fault on one of the parallel transmission lines connect-
0.350
6.6/132
nmwM^
0.165
vicflfififla/
0.51. -'5
125.4/33.0
^ fr
Flg. 4-21. System diagram reactances based on 100,000 kva and rated voltages
6.6, 132, and 33 kv. Machine 1 is rated 50,000 kva at 1.0 power factor. Hi = 1.76
and Ha = 14.1.
It will be noted that the turn ratio of the step-down transformers is not the same
as the ratio of the rated voltages of the circuits which they connect. Therefore, if
132 kv, the rated voltage of the high-tension circuit, is chosen as the " unit " or
"base " voltage for the system, the per unit value of the low-tension rated voltage
will be 125.4/132 = 0.95; or the low-tension base voltage will be 34.7 kv. (See
Appendix I, Volume I.) Since the base voltage of the low-tension circuit is greater
H,l.76 0.350
o.i5o r^smsmu-
0.511
-'50 0.116
than 33 kv, the rated voltage upon which the reactances are given, the per unit
reactances of this part of the system must be decreased by the ratio (125.4/132 )2 =
(0.95)2 = 0.902. The reactance of the equivalent motor then becomes 0.902 X
0.131 = 0.118, and the reactance of the receiving end transformer becomes 0.902 X
65
The turn ratio of the step-up transformers corresponds to the ratio of the rated
voltages of the circuits; therefore the base voltage on the generating station side
of these transformers will be equal to the rated voltage for that circuit, and no
The transformers are connected A-Y and solidly grounded on the high sides as
1.230
1.210
1.190
1.170
1.150
1.130
1.0
1.110
0.9
0.8
XI
OJ
1.090
1.070
1.050
1.030
1.010
0.7
1-
t 0.6
>
- 0.5
\ 0.4
0.990
'0.3
0.970
0.2
0.950
0.1
0.930
Trnax
Per Unit
Power
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Sin S0
Fig. 4-23. Per unit power and rmax vs. sin So for the equivalent system of Fig. 4.22.
TABLE 4-1
Displacements between the Two Machines. If rated voltages are normally held on
the high-tension side of the step-up transformers and on the low-tension side of the
step-down transformers, the current can be determined for any value of power
transfer. If the current is known, the magnitudes of the voltages E\ and 2 which
exist behind the machine reactances and the angle 50 between them can be cal-
culated.
The magnitudes of the internal voltages and the angle between them for various
values of load are tabulated in Table 4.1 and used to plot the two curves of Fig. 4-23.
One curve shows the relation between the initial power transfer and the sine of the
initial angle 4o between the internal voltages. The other curve shows the relation
H.lfc.2
between the function Tmtx = and sin 5o. E\ and 2 are the internal voltages
of machines 1 and 2, respectively, and X12 is the total reactance between the points
at which these voltages are maintained (see Fig. 4-22) *i2(before) = 0.511 + 0.150 +
0.350
v 0000.0.0.0./^)
0.175 i 0.175
0.150 . 0.118
u.iou U.IIO /^
(0)?
(V)ys&smsu-r-^smsmj@
(b)
0.0438
Fig. 4-24. Reactance diagram with a three-phase fault at the midpoint of one of
3. Calculation of Reactances During and After the Fault, (a) Three-phase fault
at the center of one line. The equivalent reactance x/ of a three-phase fault is zero.
Therefore, (b) of Fig. 4-24 can be obtained from (a) by one A-Y transformation.
(0.749 X 0.356)
r\ = = - = 0.1535
*12<during) 7.192
*12(before) 1104:
r2 = = = 0.863
*12(after) 1-279
(6) Double-line-to-ground fault at the center of one line. The equivalent reactance
67
sequence reactances of the system viewed from the point of fault. Three steps in
*12(before) 1.104
i = = ~r~^r: = 0.461
f2 = 0.863, being the same for all types of faults at one location
0.350
0.118
Xf (L-L-G Foult)
I 7 I__L.
(c)
0.749 0.356
s-\ 0.749
Note. The assumption is made that the negative sequence reactance of the system is
equal to the positive sequence reactance when viewed from the point of fault; and
that the zero sequence reactance of the transmission lines is equal to 3.5 times their
positive sequence reactance, mutual reactance between the two circuits being negli-
68
[Ch. 4
TWO-MACHINE STABILITY
TABLE 4-2
Per
Unit
10.95
(n-0.1535
Switching
Time,
Sin 5o
Power
.1 max
?ll max
Vr^ma*
r2 = 0.863)
Second
0.825
0.995
0.80
0.933
1.177
0.1807
4.65
0.127
0.0273
0.75
0.843
1.134
0.1741
4.57
0.2365
0.0518
0.70
0.763
1.097
0.1684
4.49
0.353
0.0784
0.65
0.690
1.067
0.1638
4.43
0.450
0.1016
0.60
0.623
1.041
0.1598
4.38
0.554
0.1265
0.55
0.560
1.020
0.1566
4.33
0.666
0.1538
0.50
0.500
1.001
0.1537
4.29
0.783
69
TABLE 4-3
Per
Unit
Power
10.95
Switching
Time,
Second
Sin Jo
-* max
fl* max
vVi7.max
(n = 0.461
r2- 0.863)
0.825
0.995
0.80
0.933
1.177
0.5426
8.07
0.353
0.0437
0.75
0.843
1.134
0.5228
7.92
0.702
0.0886
0.70
0.763
1.097
0.5057
7.79
1.01
0.1297
0.65
0.690
1.067
0.4919
7.68
1.32
0.1719
0.60
0.623
1.041
0.4799
7.59
1.671
0.2202
0.55
0.560
1.020
0.4702
7.51
2.081
0.2771
0.50
0.500
1.001
0.4615
7.38
2.574
0.3460
70
[Ch. 4
TWO-MACHINE STABILITY
Data for switching time curves for a number of loads have been determined by
use of the curves of Fig. 4-23 and the master curves (Figs. 4-1 to 4-17) and are
From the data given in Tables 4.2 and 4-3, the switching time curves shown in
Fig. 4-26 (by the full lines) were plotted. The dotted curve is for a three-phase
fault on one of the parallel lines very near the sending end high-tension bus. The
calculations for this case of r\ = 0 and rj = 0.863 are summarized in Table 4.4,
~ -.0
0.9
8 8
8,0.7
! 0.6
& 0.5
* 0.4
fe0.3
5 0.2
.s
I 0.1
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Fig. 4.26. Permissible fault duration versus initial power transfer for the system
given by Fig. 4.22. Note. Full load on machine 1 of Fig. 4.21 is 0.5 per unit power.
Curve
-L-G
ine
L_
<
It
Sec. 15]
71
severe than those at the center of a line. See Fig. 4-27 for a com-
for a three-phase fault located near the high-tension bus. The bus
faults or faults near the buses, because they are more severe, are in
general considered in greater detail than faults along the line. There-
fore, any method which will decrease the severity of faults near the
1.4
1.3
i,
=J
"-;
Fig.
0>
o.89 nrvi)
Hi = 56 H2 = I90
'30
,Fou*-Lo
COtic
nA
Sg^ou
Lto
i^tVo
le_
0.1
0.2
0.3
Switching-Time-in Seconds
0.8
0.9
1.0
4-27. Switching time curves for three-phase faults near center of line and
72
[Ch. 4
TWO-MACHINE STABILITY
to clear the faulty circuit. The use of a high-tension bus allows for
1.5
1.4
1.3
1.2
I.
o 0.
Q.
|0.
Fig.
oil
IJl-o cHj
fro
Gen. i i
iT Gen. 3
3x
"-Fault
* Vault
111
Lot
LEf^nJSussing
_ High-Tension Bussing
0.1
0.2
0.3
0.8
0.9
1.0
4.28. Switching time curves for double-line-to-ground faults with low- and
high-tension bussing.
clearing of the fault at both ends of the circuit with balanced relays;
than for simultaneous clearing if the time for the first breaker to
Sec. 15]
73
switching time curve (c) for sequential opening of the line breakers
(it was assumed that the second breaker and relay required as much
time to clear as the first breaker and relay after the opening of the
1.2
i.o
0.9
0.8
I -7
s.
.* 0.6
fc0.5
a.
0.4
0.3
0.2
0.1
^^
^^
^^
^5
0.8
0.9
Fig. 4-29. Switching time curves for three-phase faults at generator high-tension
realize fully the possible increase in the transient stability limit made
number of high-tension bussing stations for a given line and for given
number and types of faults expected as well as upon the breaker and
Valuable data from automatic oscillographs have been and are being
74
[Ch. 4
TWO-MACHINE STABILITY
l.l
i.o
0.9
0.8
0.7
| 0.5
0.4
0.3
0.2
O.I
0.35 J>0J^55_cH_D0134_t:, 0 03
Vault
-8_
"*
--^
~-'
0.1
0.2
Fig. 4.30. Switching time curves showing gains realized by use of an intermediate
double-line-to-ground fault.
probability for the occurrence of bus faults or faults just off the
state conditions are obtained usually with one line out or a sec-
and switching times are long, the intermediate high-tension bus may
lower the average transient stability limits for certain types of faults
and relays.
Sec. 15]
75
Fig. 4-31. This shows the gain that may be realized by the use of a
1.60
1.50
1.40
1.30
1.20
1.10
1.00
t 0.90
0.80
5 0.70
0.60
0.50
0.40
0.30
0.20
0.10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 I.I
Fig. 4-31. Power-switching time curves for various kinds of faults and the effect
Gen.
Mot.
o-
-o
* Fault
'Line-ground fault
transformer reactance)
Line-ground fault
- Reactance in .neutral
^3-phose fault
76
[Ch. 4
TWO-MACHINE STABILITY
4.32 shows the gains for particular switching times for different values
that as the switching times decrease the gains are decreased, and
2.00
1.80
1.60
.40
1.20
.1.00
<
0.80
0.60
0.40
0.20
t=0
t = 0.2
t = 0.4
t = 0.6
t = cc
12 3 4 5 6
near bus vs. reactance in transformer neutrals. 8 per cent transformer reactance
that the gains realized for this system by increasing the reactance in
the neutral rapidly drop off above two or three times transformer
reactance.
Sec. IS]
77
manner. Figure 4-33 shows the gains realized as the switching time
general decrease the transient stability limit for the other types of
2.2
2.0
1.8
1.6
w 1.4
= 1.0
0.8
0.6
0.4
0.2
* 12% Reoctonce
^^8% Reactance
^"^4% Reactance
x0% Reactance
0.1
0.2
0.6
0.7
0.8
tension bus.
fault and fault locations rather than increase it, so that a more
one 220-kv line will have approximately the same reactance as four
than two circuits are used, the switching out of one line does not
Figure 4-34 shows the relative transient stability limits for a system
78
[Ch. 4
TWO-MACHINE STABILITY
lower voltage circuits for this case equals the parallel reactance of the
two higher voltage circuits. The system having lower voltage cir-
cuits without high-tension bussing is, for the case considered, the
3.
2.
2.
2,
2.
?.
!1.
Q.
I,
I.
0.
oajrj \ iSjoqfep
1111
I3#-
Steady State
*6- .9
-5J^
^.6 .9 ^.
s&
1 .9
**7
All Lines In
-0-
3 ,9 &
** >
-i
-o-iJ
6 .9
4i^o-
S6
, .9
B 2L .9 *is
6 .9
5.F
1 .9
"r
.9
<>.6
A--
bad
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Sec. IS]
79
fault before the generator rotor has reached as great an angular dis-
3.0
2.8
'1.4
1.2
1.0
0.8
0.6
0.4
o-f
0.
0000000
0.I ,
1 ti b Infinite
o]-i|-p bus
H = 2.60u - 0.3
TT5OTWr
I line fault
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.6 0.9 1.0 I.I
Fig. 4-35. Comparison of stability limits for faults on stub feeder against faults
system. That is, a 100 per cent increase in the inertia of a generator
of 41 per cent. Figure 4-36 shows the gains that can be realized by
Figure 4-37 shows the gains realized in the transient stability limit
80
[Ch. 4
TWO-MACHINE STABILITY
I,
I.
5 i.
i '<
i o,
0,
1 0.3
H 3.38
[7
H-2.60
0.2
2.2
2.0
1.8
1.6
- 1.2
5 1.0
0.8
0.6
0.4
0.2
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Fig. 4-37. Switching time curve showing the effect of change in ucj on transient
stability.
0.
0000000
0.3 0
| K Infinite
^nreflnonn ^
I K bus
Vj
can be neglected.
For this case, we can again start with the equation of motion of the
d2(h ~ h) d2S12
-/Tal Ta2\
[4.20]
dt2 dt*
d/dd\2 dS/d2S\
zero when
,5,
mS%)
This is the general form of the equal area criterion and applies when
This criterion may be applied for the case of two machines when
operating conditions.
maintained.
currents, and power factors which existed in the system before the
fault occurred, the magnitudes and angles of the voltages behind the
S2
[Ch. 4
TWO-MACHINE STABILITY
of the fault and after the fault has been cleared (Section 2, Volume I)
the fault (Section 10). The driving point and transfer impedances
may be obtained for each machine for each circuit condition (Section
7, Volume I).
MJ'O0W>
rO-WWV '.OD'OW"1D-i
KMM/W nWGGa^-o-i
lo)
(b)
system.
machines 1 and 2, calculated by Eq. 1-6, are shown in Figs. 4-39 (a)
and 4-39 (b), respectively. These curves are shown separately for
The angle 50 is the initial value of the angle 512 between the volt-
ages E\ and E2. At the instant the fault occurs, the electrical torque
torque
E\E2
Tal = Ti - Tel
Ti sin an
12
Sec. 16]
83
^22 ^12
la)
8,
The torque Tai, which is the difference between Ti and the ordinate
will increase.
4. Determination of critical
while the relative acceleration was positive and 512 was increasing
come and the relative velocity of the machines will become zero just
84
[Ch. 4
TWO-MACHINE STABILITY
method.
values of 512 from 50 to S/ for the conditions which existed with the
machines at which the fault can be cleared from the system with-
out causing instability. In this way Ss, the critical switching angle,
required for the angle between the two machines to equal S, (Sec-
one curve giving angle between machines (512) versus time can be
used.
the other end of the line), a curve for (Tai/Hi Ta2/H2) corre-
added to Fig. 4-40. If such values of Si2 (Ssi and Ss2) can be found
that the sum of the areas under the three curves is zero, the system
Fig. 4.41.
for a sustained fault. In this particular case the area under the
there is a value of 512 at which the area under the curve (Tai/Hi
Tai/Hz) is zero for the conditions existing with the fault on the
system.
T<a/H2) for the conditions existing after the fault is cleared. If the
service of a portion of the system. The angle S\2 will at first increase.
With increasing values of 512 the area under Curve C in Fig. 4-40
the case shown the system will not lose synchronism on the first
mine the maximum load that can be thrown on one of two syn-
. Etc 4,42
the motion of the two systems (Eq. 4-1) as follows (assuming system 1
Hi d% ElE2 .
vj at #12
H2d% Ar^l2
*7 dr x12
86
[Ch. 4
TWO-MACHINE STABILITY
d%
Hi
d% irf
dt2
Ho
o2
where
Tai Tm
EiE2
*12
sin 5x2
^12
.(Tal Ta2\
d%
dt2
t4-27]
[4-28]
[4-29]
[4.30]
[4-31]
Equation 4.31 is the same as Eq. 4-22, for which the criterion for
stability is
jC(S?S)*"0
[4-32]
where Ta\ and Ta2 are expressed for this case by Eqs. 4-29 and 4-30,
respectively.
of 512.
H1*
'S^gi^>'
(b)
Fig. 4.43.
REFERENCES 87
REFERENCES
and Edith Clarke, General Electric Review, February 1934, pages 87-92.
CHAPTER 5
MULTI-MACHINE PROBLEM
frequency.
the initial conditions and the accelerating torques under the transient
flow conditions.
step by step.
well selected so that the effect of other faults for different system con-
characteristics is obtained.
Elfh-T -T T
~ , 2 1 * ml J. el
ttj at
Ho d Qo
Hn d Sn _
kj at
The electrical torque at normal speed (from Eq. 1.6), for n machines
Ei . EiE2 . . .
t ^2 . EiE2 . .
^22 ^12
^2n
F2 Ki F
^(nl)n
the angular displacement of the machines (S12, 813, 523, " " S(n-i)n)'
lined in Section 12, when the inertia constants of each machine and
methods are not simple in their application and for this reason are not
following equations:
- Ei . E\E2 . . . -E1-E3 . ,. .
E2 E\Ei2 E2IL3
E3 . Ei\Ei% , E2E3
fault is on, when the first breaker opens, and when the faulty section
or fault is removed from the system. That is, for the different
hi, #22i <?33> #12. ^13. and 023 must be determined in order to obtain
an, <*22. 33. 12. 13. and a23. (See Section 7, Volume I.)
That is, this step in the procedure is to determine E\, E2, and 3,
groups; 8i, 82, and 53, the initial angular displacements of thesethree
voltages; and Tmi, Tm2, and Tm3, the initial shaft torques on the
three machines. The initial shaft torques are usually taken equal
When the circuit constants and the initial voltages behind transient
written from Eqs. 5-3 for the case when the fault is on, when it is
the accelerating torque constants ki, k^, and k3 for each machine,
Hn
sheet can now be set up (Table 5-1). The following form is for a
TABLE 51
klTal(n-l)
k2Ta2(n-l)
3?a3(n-l)
512 = 5152
513 =5153
523 =52 53
(512 a12)
(512 + 012)
(S13 13)
(5l3 + 13)
(S23 23)
(523 + 23)
TABLE 5-1Continued
r lJS2 /. ^
Z12
1^2 , .
Z12
1.E3 . , .
^13
E1E3 .... .
-^13
2^3 . , .
^23
2^3 . ,. . ,
Z23
El .
Zn
El .
/S22
El .
Z33
out until the time is reached at which there is a change in the circuit
.. . . , , Ua(nl)fbefore) T 7a(nl)(after)J
A5(n-V = A5(7>-^) + *
It is well to plot the angular displacement of the machines (6%, 82, 83)
against time (t) as the work proceeds; the shape of these curves will
94
[Ch. 5
MULTI-MACHINE PROBLEM
other groups.
I.I26/-2.T
Fig. 5-1.
a positive phase sequence system diagram drawn up with a common leva base.
reactance of the machines of the same group, and reducing the system to the
Sec. 19]
95
MULTI-MACHINE METHODS
identity of points of known voltage and power flow sufficient for establishing
the equivalent load flow. The load flow diagram, with loads represented as
shunt impedance loads, is made up as shown in Fig. 5.1 from which the
H2=7.65
H,-5.5
S $ Fault-
5.33+j 4.83
.154 KW
Unity P. F. converter
load disconnected
with occurence of
fault
to be disconnected from the system with the occurrence of the system fault.
The impedance diagram (Fig. 5-2) for calculation of the impedances between
machine groups with the fault on, first breaker cleared, and second breaker
I, for method.)
96
MULTI-MACHINE PROBLEM
5. The swing curve sheets are made up from a summary of data (Table 5-2).
6. The swing curve calculations are carried out (see Table 5-3); and the swing
170
160
150
140
130
120
110
100
90
80
60
! 50
! 40
i 30
i 2
10
- 10
-20
-30
-40
-50
-60
Fault on
Calculated
Swing Curves
\y
'
n<?
'
&
*2.
'
/>
TABLE 5-2
ki = 4.92 k3 = 4.91
kz = 3.53 kt = 5.76
Ei = 1.138
3 = 1.126
E-t = 1.19
4 = 1.125
Si = 23.5
h = -2.7
S2 = 19.4
54 - -10.1
Circuit Impedances
Zn = 0.880/63.9
Zu = 55.5/90.8
Z22 = 0.311/86.3
Zu = 58.1/86.9
Z33 = 0.587/77.1
Z23 = 8.85/95.7
Z44 = 0.519/75.6
Z24 = 9.25/91.8
Z12 = 1.81/88.5
Z34 = 19.9/92.5
Zn = 0.884/63.8
Z13 = 33.7/91.0
Z22" = 0.330/85.8
Zu = 30.2/87.7
ZS3 = 0.598/76.8
Z23 = 5.36/95.8
Z44 = 0.537/75.1
Z24 = 4.80/92.5
Z12 = 1.73/88.7
Z84 = 10.1/93.0
Z11 = 0.900/63.4
Z13 = 11.03/91.7*
Z22 = 0.443/82.0
Zu = 9.94/89.7
Z33 = 0.663/74.4
22s = 1.76/96.6
Z44 = 0.590/71.5
Zu = 1.58/94.5
Z12 = 1.41/89.2
Z84 = 3.41/95.4
Fault on:
TABLE 5-3
0.40
2.523
11.241
60.455
1.019
14.634
93.067
-0.017
-1.766
-12.952
-1.086
-9.5*
-54.317
-32.61
73.41
114.77
106.02
147.38
41.37
-34.11
-31.11
74.21
0.*
2.262
8.718
49.214
1.1*
13.616
78.433
-0.048
-1.749
-11.186
-1.013
-8.479
-44.752
-29.22
60.40
93.97
89.62
123.19
33.57
-30.72
-27.72
61.20
SO 61)
0.*
1.920
6.456
40.496
1.441
12.4*
64.818
-0.116
-1.701
-9.437
-1.060
-7.466
-36.273
-24.32
49.93
76.77
74.26
101.09
26.84
-25.82
-22.82
*.73
49. 13
Sec. 19]
9<
MULTI-MACHINE METHODS
<
cc
f^
^c
ro
^o
CN
O 00
CO ro
rs
-r
^O
CN U-3
t*
r^
CM
CO
00
r*
t~
iO
^1
oc
CN 00
- NO
-t-
vO
co
r-
rO
<
iO
00'
00
ic
in
Ov
c-
cc
O Ov
to iO
^H
t>
CN
iO
r<->
0O
100
[Ch. 5
MULTI-MACHINE PROBLEM
OS
<
<
ta
i^
IO
-f
-r
vQ
r*)
^^
C N O IO ^O 1
f*5
i^
r-g
rs
-f
CN
-^
0 \ ^ 0 10 1
c"
rs
Cf.
rs
CN
CN
-r
-T
f^
00
TjOOlN|
-*
-r
ro
c3
1/3 CO O IN
MULTI-MACHINE METHODS
101
vO
\r
rs
vo
NO
Ov
]>-
LO
Th
Ov
Tt<
t- *-.
CN
ro
CN
CO
io
CO
CS CN
t* *-H
Ov
vC
CO
CN
cv
vO
T*
CN
U-v
NO
Ov
CO
t^
ON
~H
00
IO
CN
y~i
00
CN
Ov
CO
Tt*
CN
O t~
CO
+1
102
[Ch. 5
MULTI-MACHINE PROBLEM
H 00
CN O
~H CN
CO t^.
to *^.
fO <0
NO ro
t^. Tj<
- io
8S
ro OS
ro
CN 00
IO
io
* vO
gg:
CO
1*) ro
Ov Ov
Ov OO
O Tj"
iO ro
vO
<
t^ -H
oo
oo
oO
oo
o '
t^ r~
t* vO
Ov
Ov
CN CN
11
IO NO
-* 1
co ~H
to *>.
Ov CN
Ov o.
^o
Ov ro
iO -ej*
00 Ov
vO O0
~0 ">
O vO
CN
rN
t- 1^
H r^
vo v2>
io Ov
Ov OO
OO vO
r- CO
O -H
t~
oo
0.30
0.4591
0.3637
-0.*19
-0.2689
0.0208
0.0279
0.0405
0.0415
0.2421
0.2242
0.2772
0.2789
0.0574
0.0455
0.4056
0.0978
0.0567
-0.0001
, .... 2
0.25
0.3919
0.29*
-0.2459
-0.2120
0.0254
0.0244
0.0368
0.0384
0.2246
0.1974
0.2753
0.2701
0.0490
0.0367
0.*67
0.1741
0.0348
-0.0208
* I* U.15
0.20
0.3272
0.2267
-0.17*
-0.1387
0.0226
0.0216
0.0326
0.0347
0.1992
0.1641
0.2541
0.2427
0.0409
0.0203
0.2913
0.2940
+0.0067
-0.0603
0.16
0.2674
0.1*2
-0.0939
-0.0587
104
plil
MULTI-MACHINE PROBLEM
IT;
t-
E?
<
r~ 00 to
IO Ov
vC
ro 00
3 ro
r^
* m is
Ot
-f
-<* <
vO CO
f)
Ov rC t-
-*
f^)
IO CN
rvi
vo <o
r^
~H O0 *^.
-*
CN
-r
co 10
rc
vC
CS
rC IO I-
JO *
ir,
O <0
3C
** *o
rg
fi O
I0 **
Sec. 19]
105
MULTI-MACHINE METHODS
vO
O0 ov
r^
i^
Ov
v ON
.* o
<*
Ov
CN
>*
IO Ov
IO
t-- *-*
OO
'* r~
c^
to
O0
00
J^
-*
Ov vO
>o
O0 -^
O O0
t r~
T-^H ro
CO ro
Ov
Ov
Ov
Ov
00
Ov Ov
8S
*-i t^.
-^ IO
i O
oo
oo
*-H ~-!
vO ^
co *-
CO CN
CN O
Ov
CO
to
CN
CO
vO
106
[Ch. 5
MULTI-MACHINE PROBLEM
vO
Ov t*
O -<
w CO
CO w
t #
vo vo
CN CN
00 ^H
ro O
CO
CN Ov
Ov CN
00 CO i*
tO Tf to
Ov ON -< CO
CO CO CO O
s-< vo
# ro
vo vo
* CN
O0 00
>o
to
i Tf
IO <0
CO iO
vo io
CO CO
*-t -t
OO
oo
oo
oo
oo
OO
oo
OOOO
11
00 CN
vo CO
"O CN
CO *
CN O
O l-
*-< CN
CN vo
ro v
t- vo
vO CO
to to
C> -* ^ iO
O0 O O Ov
Tf Ov O t*
H vo CO vo
to
T o
NO O
to Tf
00 I
NO to
CN CN
O vo
Sec. 19]
107
MULTI-MACHINE METHODS
NO <0
C*
SS
ss
oo *-H
Ov C-
IT)
SO
IO
O0
Ov 00
Ov
IO T-H
Ov
io O
v-H *
vO
00
vo
^H
CN
oo
eC
vo
rO
<o r^
-*
IO t^>
CN
*- t*
u->
O CS
av
CO
CO
T-t T-H
IO
Ov
iO vO
r-
-*
CN
t-
CO
IO ~H
*-<
f*
~^
co
108
[Ch. S
MULTI-MACHINE PROBLEM
<o
*~
-i o
00
00
r^
fN
rO
00
w 00
00
00
CO
ro
\O rs
O0
vo
00
00
IO
io
IO
IO
00 ^H
-r
00
CN
CN
oo
r*
CO
00
vo
NO
00
CO -Th
t^
<*
Ov
Ov
*H O
to
CN
o\
vo
Ov
oo
Oo
CN
cm
Sec. 19]
109
MULTI-MACHINE METHODS
<o
t^
00
ON <0
ON
CO
CN
CN CN
ON
^,
<*
* ON
NO
00
O IO
NO
*0
Q ON
O -*
CO
NO
00
00 00
00
CO
t^. ON
00
Ov
00
NO
<>*
OO
ON
ON
tO CO
C- r-
CO
CO
CN *0
CO ~*
oo
OO
how the system will behave for the different fault locations are
reactance.
swing curve sheet for each machine group such as that shown in
Table 5-4. The swing curve calculation forms (Table 5-4) are
initial air gap power, magnitude, and phase angle of the voltage
"Before Fault."
4. The swing curve is started. First the fault is applied, (a) With
jj
t-
<
<
<
<
a'
c-
CJ
-h
**
h"
5?
-M
i2
ud
S0
-*';
uk
E3
3S
H II
>
3<
111
<-sl
U ffl
CDF
w if.
5 1*
irpD
gjj-3
JsS;: *
Sec. 19]
MULTI-MACHINE METHODS
***s 0-*"'
S39J33p III
-j )U3lU33E[dSIQ
*--aa2a2
ss**
"J V a -
a-02 a
2a0* a
Za02 a
-62 a
2*- a
6*62 a
3-622 a
-a03 a
a*- a
8a'oe
-6*08 *
2 0N aovd
*X1+V*"V-,"(V
a*3
26* S
62a a
8a3a +
8*6a -
4-0 a
-O- a
-na *
04-a a
3aaa1*
*2*a0*
Za*-2*
608*-a*
N0iivinoivo 3 Ay no
".(
62a a
**50"a
0*aa a
0a0a %
a5a +
0-a*a
(nms)
It6'Oa*
24-'aa+v^
--6*-*
--a6a *X
JUCQ I'll.Mill
M.--.>..- V
MX aaO a
N *a1a a
"* a *
'*--a
-V -*a8a *
ff* aiqi
anbioj.
6aa
-aa a
*8aa +
*6a
ttVO +
fault) the air gap power is read for each machine group, (b) The
feeding the faulted circuit, or with the fault only partially cleared as a
result of opening only one breaker, the procedure is the same except
power outputs of all machine groups are read at the time interval for
breaker opening, and the average value used for determining the
network conditions or until the swing curve has been carried far
period.
read directly from electrical instruments. See Fig. 5-5 and Fig. 5-6
for views of a-c network analyzer and instrument panel for quick and
200
It
160
150
140
130
120
110
100
'/
//
//
s'
^.
//
>
o 80
oo oooooc
.1
^~.2
~T3
3-
-.4
0.
.5
.6
.7
.6
.90
- 10
-20
-30
-40
^s
Time in seconds
-50
-60
. -70
-80
-90
-100
-1 10
"
- -
115
Time
Sec. 19]
MULTI-MACHINE METHODS
116
[Ch. 5
MULTI-MACHINE PROBLEM
Fig. 5.6. Central instrument and control panel showing generator units and
carried forward. This allows for a full play of ingenuity on the part
this way the swing curve calculation time may be reduced. After a
time interval may be found to be small, and the time interval can be
increased. Usually, the time interval should not be larger than that
four times the original value, must be used for all succeeding compu-
tations. For the time interval at which this change is made, the
the new acceleration constant to the angular change for the two
preceding time intervals. This follows, since the angular change for
the two preceding intervals is in each case for only half as long a time.
From that point on, the calculation proceeds in the normal manner.
The sample swing curve sheet of Table 5.5 shows the manner
second.
118
ICh. 5
MULTI-MACHINE PROBLEM
le =
- ete
*dc
[5.4]
Ic = armature current,
xd
Section 25.
of synchronous con- , , , . , , ,
tion 28, this effect can be taken into account by subtracting from
the difference of the mechanical torque and the air gap electrical
Sec. 20]
119
SPECIAL CONSIDERATIONS
V-J$
Z C|+j|
->M/ -\SXXLr-
Z" f|+j*l
-M - 1000/-
-pfI M\h
i i i -Y.j^
\MA/ '<QQlr-
-V _
Ttt
IX
=&
Fig. 5-8
7-
1 A
S=^fM [5<6]
When A5 is the change in angle from the (re 1) to the reth in-
terval, Eq. 5-7 gives the per unit slip at the (re J^) interval.
per unit speed for what is considered a fairly large rate of change of
for example, the case of a 60-cycle system which during the swing
speed is
10
5 = = 0.00925
360 X 60 X 0.05
or the speed
5=1-5 = 0.99075
governor characteristics.
this load during the swing more nearly to represent actual conditions.
used are either (1) constant shunt impedance or (2) constant shunt
chronous motor load, will pull out of step before the major synchro-
When the small machine has definitely gone out of step and has
upon the rest of the system may be obtained for the remainder of
directly to ground.
current, voltage, and power flow during the swing. Such informa-
tion may be used to check the performance and setting of relays, and
a relatively small effect on the system and whose identity was not
maintained.
plished by means of the general network equations for real and reac-
122
[Ch. 5
MULTI-MACHINE PROBLEM
a-c network analyzer is used, voltage and current in any part of the
network being studied may be read directly while the swing curve
and zero phase sequence may be read directly from the corre-
Real Power
E3 . E1E3 . E2E3
P3 = -5 sin a33
^33 ^13
^23
Reactive Power
77^ 77 77 77 77
6\\ Ai2
77^ 77 77
z22 z12
77^ 77 77
Q3 = -^r sin 033 + -^- sin (513 - 013) + :=~ sin (523 - 023)
^13
E2E3
^23
E2E3
These are equations for positive phase sequence real and reactive
Fig. 5.9.
Sec. 21]
123
for P\ for the different conditions, fault on, first breaker cleared, etc.,
and 823. Since 5l2 and 823 are known at the various time intervals
The vector expression for the positive phase sequence current from
vector):
T - i-i
~J
[5-10]
Vol El lal Za
[5-11]
P. (Real Power)
analysis by application of
is of particular advantage
124
[Ch. 5
MULTI-MACHINE PROBLEM
which have been studied were found to be entirely stable and would
J 0.2T5
j 0.085 . J 0.483
0.09+J 0.151
</ 3 0 Foult
g J-49 Q
change, generating power for the loads in their own areas. It was
Sec 22]
125
case it was possible to neglect all line resistance except in the lines
40
30
-JO
5 -50
,-70
-90
Time in Seconds
S^o
i*s
cating the system is stable although the fault has not been cleared
system with the application of the fault and because of the increase
voltage and power factor can be determined during the swing at any
bus or relay location. See Fig. 5-15 for system conditions slightly
if the swing current had not been considered, the current at c could
126
[Ch. 5
MULTI-MACHINE PROBLEM
which depend upon the current and voltage existing during and
800
700
600
S. 500
400
300
200
100
Relo
y Se
ting
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2
Time in Seconds
1100
1000
900
eoo
700
600
~ 500
400
300
200
100
ela
ys
ett
inq
^Initial
Current
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 I.I 1.2
Time in Seconds
1400
1300
1200
1100
1000
900
I 800
<
= 700
600
500
400
300
200
100
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 l.I
Time in Seconds
Relo
y Set
ting
4_
Initiol Load
Current
1400
1300
1200
MOO
1000
900
eoo
700
600
500
400
300
200
100
-~-
pt
"-
^ Power Fo<
11
^5
9r Fqc
tor-e
us d
toward e
Relay Setting
'^.
l1i
Voltage-Bus c
^ II:
'oltag
!-Bu'
70
80 tT
90
100
REFERENCES
1. " Load Studies on the D-C Calculating Table," Part I, by W. C. Hahn, General
"Load Studies on the D-C Calculating Table," Part II, by W. C. Hahn, General
1130-1138.
Components, by Edith Clarke, John Wiley and Sons, Inc., New York, 1943.