Circular CAV units


with system powered mechanical regulator
Type
NROBOVO

Application

Features:
- Pressure independent from 40-1000 Pa.
- Low unit resistance.
- Control accuracy 10% (in the recommended flow range).
- Maintenance free.
- Temperature insensitive (-15C to +100C).
- Can be mounted in any position.
- Factory set, saves commissioning time on site.
- Provision for on-site adjustment across the full volume
scale
Construction:
- Unit casing constructed from galvanized sheet steel, with
sleeve connection with rubber gasket.
- Damper blade: aluminium.
- Damper spindle: stainless steel, Nylon bearings.
- Site volume adjustment via a spindle and volume scale.
- unit leakage rate to class II VDI 3803/DIN 24 194
- Other versions are available on request.
Delivery format:
- The factory setpoint is indicated on the unit.
- When ordering, the required air volume must be indicated.

Specials:
L

NR.Q...: with outlet plenum with


2 circular outlets and electric
heat coil.
NR.N...: as NR.Q but with rectangular
outlet.
NI.N...: as NR.N but with rectangular
construction.

Mounting:
- The required straight inlet duct has to be at least three
times the diameter of the unit.
- Due to the sleeve connection with rubber gasket, no additional screws or tape are required.

80
200
80
120

100
250
100
170

125
250
125
170

140
250
140
170

160
320
160
240

Volume control range (m3/s)

Dimensions
Model
A
D nom.
L

Technical information

Example:
Supply and install, circular, pressureindependent constant volume units
with system powered mechanical regulator, control accuracy 10% of
Vmax. Constructed from galvanized
sheet steel, unit leakage rate to class
II VDI 3803/DIN 24 194 for:
Air volume
m3/s
Unit size
mm
Max. inlet pressure
Pa
Max. discharge sound
dB(A)
Max. radiated sound
dB(A)
complete with:
Barcol-Air control type "V", factory set
with provision for on-site adjustment
across the full volume scale.
Barcol-Air type NROBOVO

70

Specify as:
Types NR.B circular, constant volume units with system powered mechanical regulator keep the air flow constant, independent of the inlet static pressure. These units save commissioning time on site and are suitable either for supply or
return air in new or refurbishment projects.

200
320
200
240

250
320
250
240

315
460
315
340

400
505
400
385

Model Recommended Possible


min - max min - max
80 0.014 - 0.030 0.011 - 0.035
100 0.021 - 0.047 0.019 - 0.061
125 0.033 - 0.074 0.028 - 0.078
140 0.042 - 0.092 0.039 - 0.111
160 0.056 - 0.119 0.050 - 0.139
200 0.083 - 0.186 0.070 - 0.250
250 0.139 - 0.292 0.139 - 0.417
315 0.214 - 0.528 0.167 - 0.833
400 0.344 - 0.792 0.278 - 1.250

NR-1/1
P.O. Box 283, 1440 AG Purmerend, The Netherlands
Phone +31 (0)299 689300 Fax +31 (0)299 436932
www.barcol-air.nl
info@barcol-air.nl

Barcol-Air B.V. 2004.


Changes w/o notice or obligation.

C - UK - 044

Notes:
1. All dimensions are in millimetres.
2. L = installed length.

NR-1/2

Circular CAV units


with system powered mechanical regulator
Type
NROBOVO

velocity

Air volume

min.
ps

at inlet
m/s
80

100

125

140

160

200

250

315

400

2.2
4
6
6.9
2.5
4
6
7.1
2.3
4
6
6.3
2.5
4
6
7.2
2.5
4
6
6.9
2.2
4
6
8.0
2.8
4
6
8.5
2.1
4
6
7.8
2.2
4
6
8.4

m3/s
0.011
0.020
0.030
0.035
0.019
0.031
0.047
0.056
0.028
0.049
0.074
0.078
0.039
0.062
0.093
0.111
0.050
0.081
0.121
0.139
0.069
0.126
0.189
0.250
0.139
0.196
0.294
0.417
0.167
0.312
0.468
0.611
0.278
0.503
0.754
1.056

m3/h
40
72
109
125
70
113
170
200
100
177
265
280
140
222
333
400
180
290
434
500
250
452
679
900
500
707
1060
1500
600
1122
1683
2200
1000
1810
2714
3800

discharge soundlevel (LpA)


125 Pa

Pa
41
47
70
86
41
47
70
90
41
47
70
75
41
47
70
93
41
47
70
86
41
47
70
111
42
47
70
125
41
47
70
108
41
47
70
123

1. Sound pressure levels below NC 20 are indicated by --.


2. Sound data is determined in a reverberation room at an
independent sound laboratory, according to ISO 3741 and
5135 standards.
3. Lp values are including a room absorption of 10 dB/Oct.
4. For non standard applications and/or selections, please
contact our technical staff.
5. The discharge sound pressure levels are determined with

250 Pa

500 Pa

Radiated soundlevel (LpA)

750 Pa

125 Pa

250 Pa

NC
-------20
---20
--20
22
--21
23
--22
26
--23
N/A
--25
28
-21
26
31

--22
24
-21
26
28
-22
27
28
-23
28
30
-24
29
30
22
25
30
34
22
26
32
36
27
27
33
37
29
29
35
40

500 Pa

750 Pa

------------20
-24
26
22
22
27
29
24
24
28
31
27
25
29
33
24
24
28
31
24
24
29
33

------22
22
-20
24
23
24
23
27
31
27
26
31
33
27
28
32
35
31
29
34
37
28
29
33
35
29
29
34
38

NC
-22
30
32
23
27
34
36
25
28
35
36
27
29
36
39
29
30
37
39
30
32
39
43
35
34
40
45
35
36
42
46
37
38
44
48

22
27
31
36
28
31
35
41
30
33
37
41
32
34
38
44
33
35
39
44
35
37
41
48
39
39
43
50
39
40
45
51
42
42
47
53

---------------------------N/A
---------

the following assumptions for


downstream ductwork including a
diffuser with insulated plenum box:
6. The radiated sound pressure levels
are determined with the following
Hz 125 250 500 1000 2000 4000
dB 5 10 20 30 30 25

-------------------21
--20
24
--21
26
--20
24
--21
25

assumptions for ceiling plenum and


suspended ceiling absorption:

Hz
dB

125 250 500 1000 2000 4000


2
5
10 15 15 20

NR-1/2
P.O. Box 283, 1440 AG Purmerend, The Netherlands
Phone +31 (0)299 689300 Fax +31 (0)299 436932
www.barcol-air.nl
info@barcol-air.nl

Barcol-Air B.V. 2004.


Changes w/o notice or obligation.

C - UK - 044

Model

NR-1/3

Circular CAV units


with system powered mechanical regulator
Type
NROBOVO

p = 125 Pa

500 Hz

1000 Hz

2000 Hz

4000 Hz

NC index

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

NC index

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

NC index

400

250 Hz

315

125 Hz

250

NC index

200

4000 Hz

160

2000 Hz

140

m3/h
40
72
109
125
70
113
170
200
100
177
265
280
140
222
333
400
180
290
434
500
250
452
679
900
500
707
1060
1500
600
1122
1683
2200
1000
1810
2714
3800

Lw radiated sound

1000 Hz

125

m3/s
0.011
0.020
0.030
0.035
0.019
0.031
0.047
0.056
0.028
0.049
0.074
0.078
0.039
0.062
0.093
0.111
0.050
0.081
0.121
0.139
0.069
0.126
0.189
0.250
0.139
0.196
0.294
0.417
0.167
0.312
0.468
0.611
0.278
0.503
0.754
1.056

Lw discharge sound

500 Hz

100

m/s
2.2
4
6
6.9
2.5
4
6
7.1
2.3
4
6
6.3
2.5
4
6
7.2
2.5
4
6
6.9
2.2
4
6
8.0
2.8
4
6
8.5
2.1
4
6
7.8
2.2
4
6
8.4

Lw radiated sound

250 Hz

80

Lw discharge sound
125 Hz

velocity

inlet spigot

p = 250 Pa

38
46
50
52
42
50
54
55
43
51
55
55
47
51
56
57
46
52
56
58
46
53
57
60
51
54
59
X
49
56
60
63
51
57
61
65

37
44
48
50
41
47
51
53
42
48
53
53
44
49
53
55
45
50
54
55
45
51
55
58
48
52
56
X
47
53
57
60
49
54
58
62

dB
35 34
42 39
46 43
47 45
40 38
45 42
49 46
51 48
40 38
46 43
50 47
51 48
41 38
46 43
51 48
53 50
43 40
47 44
51 48
53 50
43 40
48 44
52 49
55 52
45 41
49 45
53 50
X X
45 42
50 46
54 51
57 54
46 43
50 47
55 52
59 56

34
39
43
45
39
41
46
48
39
42
47
48
37
43
48
50
41
43
48
50
40
44
49
52
40
45
50
X
42
45
50
54
43
46
51
55

28
32
37
39
33
35
40
42
33
36
41
41
30
36
41
43
35
36
41
43
34
37
42
46
33
38
43
X
35
38
44
47
36
39
44
49

25
29
34
35
29
32
37
39
29
33
38
38
28
33
38
40
31
34
39
40
31
35
39
43
31
35
40
X
32
36
41
44
34
37
42
46

25
29
31
21
29
33
34
24
32
36
36
31
35
40
41
31
37
41
43
32
39
43
46
34
37
42
X
31
38
42
45
32
38
42
46

22
26
28
19
25
29
31
21
27
32
32
29
34
38
40
32
37
41
42
31
37
41
44
32
36
40
X
30
36
40
43
33
38
42
46

dB
21 20
25 24
26 26
19 19
24 23
28 27
30 29
20 20
26 25
30 29
31 30
26 26
31 31
36 36
38 38
31 29
35 33
39 37
41 39
31 30
36 34
40 39
43 42
33 29
37 33
41 38
X X
31 29
36 33
40 38
43 41
30 29
34 33
39 38
43 42

20
24
26
20
22
27
29
21
24
29
30
21
27
32
34
27
29
34
36
25
29
34
37
25
30
35
X
26
29
34
38
26
29
34
38

20
22
18
23
25
19
22
27
27
22
27
29
21
22
27
29
19
22
27
31
18
23
28
X
19
22
28
31
20
23
28
33

-------20
--20
20
--24
26
-21
26
27
-23
28
31
-22
27
X
-21
26
30
-21
26
30

43
53
57
58
49
56
60
62
50
57
62
62
52
58
62
64
52
59
63
64
55
60
64
67
57
61
65
69
59
62
66
69
61
63
68
71

44
51
55
56
48
54
58
60
49
55
59
60
50
56
60
62
51
56
61
62
55
57
62
65
55
58
63
66
59
59
64
67
61
60
65
69

dB
45 45
48 45
52 50
54 51
47 45
51 48
56 53
57 55
47 45
52 49
57 54
57 54
49 47
53 50
57 54
59 56
49 47
53 50
58 55
59 56
55 54
54 51
59 56
62 59
53 51
55 52
60 57
64 61
58 56
56 53
61 58
64 61
60 57
57 54
62 58
66 62

45
45
50
51
45
48
53
55
45
49
54
54
47
49
54
56
47
50
55
56
52
51
55
59
51
51
56
60
54
52
57
60
55
53
58
62

42
39
44
45
39
42
46
48
39
42
47
48
41
43
48
50
41
43
48
50
48
44
49
52
44
44
49
54
49
45
50
54
50
46
51
55

36
36
40
42
36
39
43
45
36
39
44
45
38
40
45
47
38
40
45
47
43
41
46
49
41
42
47
51
44
43
48
51
46
43
48
52

22
32
36
37
28
35
39
41
31
38
43
43
36
42
46
48
37
44
48
49
41
46
50
53
40
44
48
52
41
44
48
51
42
44
49
52

22
29
33
34
26
32
36
38
28
34
38
39
35
41
45
47
38
43
48
49
41
43
48
51
39
42
47
50
42
42
47
50
45
44
49
53

dB
24 26
27 26
31 31
33 32
26 26
30 29
35 34
36 36
27 27
32 31
37 36
37 36
34 35
38 38
42 42
44 44
37 36
41 39
46 44
47 45
43 44
42 41
47 46
50 49
41 39
43 40
48 45
52 49
44 43
42 40
47 45
50 48
44 43
41 40
46 44
50 48

26
26
31
32
26
29
34
36
27
31
36
36
31
33
38
40
33
36
41
42
37
36
40
44
36
36
41
45
38
36
41
44
38
36
41
45

25
22
27
28
22
25
29
31
25
28
33
34
27
29
34
36
27
29
34
36
33
29
34
37
29
29
34
39
33
29
34
38
34
30
35
39

--22
23
-20
24
26
-22
26
27
23
26
31
33
25
28
32
34
32
30
34
38
27
28
33
37
31
28
33
36
32
28
33
37

1. Sound data is determined in a reverberation room at an


independent sound laboratory, according to ISO 3741 and
ISO 5135 standards.

2. Lw in dB/Oct. (re 1pW) are sound


power levels for discharge sound
and case radiated sound. Figures
less than 17 dB are indicated by
-.

3. NC index figures are sound pressure


levels allowing for 10 dB room
absorption. Figures less than NC 20
are indicated by --.

NR-1/3
P.O. Box 283, 1440 AG Purmerend, The Netherlands
Phone +31 (0)299 689300 Fax +31 (0)299 436932
www.barcol-air.nl
info@barcol-air.nl

Barcol-Air B.V. 2004.


Changes w/o notice or obligation.

C - UK - 044

Model data refering to

NR-1/4

Circular CAV units


with system powered mechanical regulator
Type
NROBOVO

1. Sound data is determined in a reverberation room at an


independent sound laboratory, according to ISO 3741 and
ISO 5135 standards.

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

NC index

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

NC index

29
33
39
41
34
37
43
44
37
39
45
45
44
46
51
53
48
49
54
56
48
50
54
57
50
49
53
57
48
49
53
56
52
52
56
59

NC index

28
35
43
44
33
38
46
47
37
42
49
50
42
46
53
55
45
48
55
56
47
51
57
60
48
49
55
58
48
50
55
58
49
51
55
59

4000 Hz

42
44
47
49
47
47
50
52
47
48
51
51
49
49
51
53
49
50
52
53
49
51
53
56
53
52
53
57
51
53
54
57
53
54
55
59

dB
31 33
33 34
38 37
40 39
36 37
37 37
41 40
43 42
38 39
39 39
43 42
44 43
45 47
45 46
49 49
51 51
49 49
49 48
52 51
54 52
49 50
50 50
53 52
57 56
53 52
51 49
54 51
58 55
50 49
51 49
53 51
57 54
50 50
50 49
52 51
56 55

33
35
37
39
37
38
40
42
39
40
42
43
42
43
45
47
45
45
47
49
44
45
47
50
48
46
48
52
44
46
48
51
45
46
47
52

32
31
33
35
36
34
36
38
39
38
40
41
41
39
40
42
41
39
41
42
40
39
40
44
43
40
41
45
40
40
41
44
41
41
41
46

25
25
28
30
29
28
31
33
32
31
33
34
36
34
37
40
37
36
39
41
39
38
41
44
40
38
40
44
38
38
40
43
38
38
40
44

53
59
62
69
58
63
66
72
60
65
68
73
62
66
69
74
64
67
70
75
65
69
72
77
69
70
74
79
69
72
75
80
72
73
77
82

55
59
62
67
60
63
66
70
62
64
68
70
63
65
68
72
65
66
69
72
66
67
71
75
69
69
73
77
69
70
74
77
71
72
76
79

dB
56 56
58 56
61 60
64 62
61 60
61 60
65 64
68 65
62 61
63 61
67 65
68 65
64 63
64 62
67 66
70 67
65 64
64 63
68 67
70 67
65 64
66 64
70 68
72 70
69 68
67 65
71 69
74 71
68 66
68 66
72 70
74 71
70 68
70 67
74 72
76 73

56
57
61
62
60
61
65
65
61
62
66
65
62
62
67
67
63
63
67
67
63
64
69
69
66
65
70
71
64
66
71
71
66
67
72
72

53
52
56
56
57
55
60
59
57
56
61
58
59
57
61
60
59
57
62
60
59
58
63
63
62
59
64
64
59
60
65
64
60
61
66
66

46
48
52
52
51
51
55
56
51
52
56
55
53
53
57
57
53
54
58
57
53
55
59
60
57
56
60
61
55
57
61
61
57
58
62
63

32
38
41
48
37
42
45
51
41
46
49
54
46
50
53
58
49
52
55
60
51
55
58
63
52
53
57
62
51
54
57
62
53
54
58
63

33
37
40
45
38
41
44
48
41
43
47
49
48
50
53
57
52
53
56
59
52
53
57
61
53
53
57
61
52
53
57
60
55
56
60
63

dB
35 37
37 37
40 41
43 43
40 41
40 41
44 45
47 46
42 43
43 43
47 47
48 47
49 51
49 50
52 54
55 55
53 53
52 52
56 56
58 56
53 54
54 54
58 58
60 60
57 56
55 53
59 57
62 59
54 53
54 53
58 57
60 58
54 54
54 53
58 58
60 59

37
38
42
43
41
42
46
46
43
44
48
47
46
46
51
51
49
49
53
53
48
49
54
54
51
50
55
56
48
50
55
55
49
50
55
55

36
35
39
39
40
38
43
42
43
42
47
44
45
43
47
46
45
43
48
46
44
43
48
48
47
44
49
49
43
44
49
48
44
45
50
50

28
29
33
34
32
32
36
37
35
35
39
37
39
38
42
43
41
40
44
45
43
42
46
48
44
41
46
48
42
42
46
47
42
42
46
48

500 Hz

49
48
50
52
53
51
53
55
53
52
54
55
55
53
54
56
55
53
55
56
55
54
55
59
58
55
56
60
56
56
57
60
57
57
57
62

500 Hz

52
54
56
58
56
57
59
61
57
58
60
61
58
59
61
63
59
59
61
63
59
60
62
65
63
61
63
67
60
62
64
67
62
63
64
69

Lw radiated sound

2000 Hz

400

dB
52 52
54 53
59 56
61 58
57 56
58 56
62 59
64 61
58 57
59 57
63 60
64 61
60 59
60 58
64 61
66 63
61 60
61 59
64 62
66 63
61 60
62 60
65 62
69 66
65 64
63 61
66 63
70 67
64 62
65 62
67 64
71 67
66 64
66 63
68 65
72 69

Lw discharge sound

1000 Hz

315

250 Hz

250

125 Hz

200

51
55
61
63
56
59
65
66
58
60
66
66
59
61
66
68
61
62
67
69
62
64
68
71
66
65
69
73
65
66
70
73
68
68
72
75

NC index

160

49
56
64
65
54
59
67
68
56
61
68
69
58
62
69
71
60
63
70
71
61
65
71
74
65
66
72
75
66
68
73
76
68
70
74
78

4000 Hz

140

m3/h
40
72
109
125
70
113
170
200
100
177
265
280
140
222
333
400
180
290
434
500
250
452
679
900
500
707
1060
1500
600
1122
1683
2200
1000
1810
2714
3800

2000 Hz

125

m3/s
0.011
0.020
0.030
0.035
0.019
0.031
0.047
0.056
0.028
0.049
0.074
0.078
0.039
0.062
0.093
0.111
0.050
0.081
0.121
0.139
0.069
0.126
0.189
0.250
0.139
0.196
0.294
0.417
0.167
0.312
0.468
0.611
0.278
0.503
0.754
1.056

Lw radiated sound

1000 Hz

100

m/s
2.2
4
6
6.9
2.5
4
6
7.1
2.3
4
6
6.3
2.5
4
6
7.2
2.5
4
6
6.9
2.2
4
6
8.0
2.8
4
6
8.5
2.1
4
6
7.8
2.2
4
6
8.4

250 Hz

80

Lw discharge sound
125 Hz

velocity

inlet spigot

p = 750 Pa

2. Lw in dB/Oct. (re 1pW) are sound


power levels for discharge sound
and case radiated sound. Figures
less than 17 dB are indicated by
-.

3. NC index figures are sound pressure


levels allowing for 10 dB room
absorption. Figures less than NC 20
are indicated by --.

NR-1/4
P.O. Box 283, 1440 AG Purmerend, The Netherlands
Phone +31 (0)299 689300 Fax +31 (0)299 436932
www.barcol-air.nl
info@barcol-air.nl

Barcol-Air B.V. 2004.


Changes w/o notice or obligation.

C - UK - 044