DCC Commercial

15- & 20-Ton, Three-Phase


Packaged Air Conditioners
15 Tons Cooling Capacity:
180,000 BTU/h
20 Tons Cooling Capacity:
240,000 BTU/h

Standard Features





R-410A chlorine-free refrigerant


High-efficiency scroll compressor
Copper tube / aluminum fin coils
High- and low-pressure switches
High-capacity, steel-cased filter drier
Built-in filter rack with standard
2 filters (convertible to 4 filters)
Heater kits with single-point entry
Crankcase heaters
Contactor with lugs
24-volt terminal strip
Easy to service
Bottom utility entry
AHRI Certified; ETL Listed

SS-iDCC15

Cabinet Features

Heavy-gauge, galvanized-
steel cabinet with UV-resistant
powder-paint finish
Condenser Hail Guards
Full Perimeter Rail
Sloped drain pan

Contents

Nomenclature............................. 2
Product Specifications................ 3
Heating Kit Data ......................... 5
Airflow Data................................ 7
Expanded Cooling Data............... 9
Dimensions............................... 13
Wiring Diagrams ...................... 17
Accessories.............................. 19
1/13
Supersedes 8/12

Product Specifications

Nomenclature
D
1

C
2

C
3

180
4,5,6

060
7,8,9

3
10

B
11

*
12

*
13

*
14

A *
15 16
Revision Levels
Major & Minor
Factory-Installed Options

Brand
D Daikin

X
A
B
C
D
E
F

Configuration
C Commercial
Application
C Cooling
G Gas Heat
H Heat Pump

Nominal Gross Cooling Capacity


036 3 Tons
102
8 Tons
048 4 Tons
120
10 Tons
060 5 Tons
150
12 tons
072 6 Tons
180 & 181 15 Tons
090 7 Tons
240
20 Tons

H
J
K
L

Nominal Heating Capacity


Gas/Electric
045 45,000 BTU/h
090 90,000 BTU/h
115 115,000 BTU/h
140 140,000 BTU/h
210 210,000 BTU/h
350 350,000 BTU/h
400 400,000 BTU/h

AC/ HP (Factory-Installed Electric Heat)


XXX No Heat
010 10 kW
030 30 kW
015 15 kW
031 30 kW
016 15 kW
045 45 kW
018 18 kW
046 45 kW
020 20 kW
060 60 kW
025 25 kW

Return & Supply air smoke detectors


M

Powered convenience outlet;


Low-ambient kit
Powered convenience outlet;
Return air smoke detector
Powered convenience outlet;
Return & Supply air smoke detectors
Powered convenience outlet;
Supply air smoke detector
Powered convenience outlet; Lowambient kit; Return air smoke detector
Powered convenience outlet; Lowambient kit; Supply air smoke detector
Powered convenience outlet;
Low-ambient kit; Return & Supply
air smoke detectors
Non-powered convenience outlet;
Low-ambient kit; Return air smoke detector
Low-ambient kit; Return air smoke detector
Low-ambient kit; Supply air smoke detector
Low-ambient kit; Return & Supply
air smoke detectors
Return & Supply air smoke detectors

X
S

Factory-Installed Options
Standard Aluminized Heat Exchanger
Stainless-Steel Heat Exchanger

N
O
P

See product specifications for heat size(s) available for each capacity.
Q

Voltage
1 208-230/1/60
3 208-230/3/60

4 460/3/60
7 575/3/60

R
T

Supply Fan/Drive Type/Motor


B
Belt Drive
D
Direct Drive
Factory-Installed Options
X
No Options
A
Downflow Economizer
H
Disconnect Switch (non-fused)
J
Downflow Economizer; Disconnect Switch (non-fused)

No Options
Non-powered convenience outlet
Powered convenience outlet
Low-ambient kit
Return air smoke detector
Supply air smoke detector
Non-powered convenience outlet;
Low-ambient kit
Non-powered convenience outlet;
Return air smoke detector
Non-powered convenience outlet;
Supply air smoke detector
Non-powered convenience outlet;
Return & Supply air smoke detectors
Non-powered convenience outlet;
Low-ambient kit; Supply air smoke detector
Non-powered convenience outlet;
Low-ambient kit

U
V
W
Y

Note: Not all options available for all products.

Factory-Installed Options
Stainless-Steel Heat Exchanger (CPG units only): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.
Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended from 60F
ambient temperature to 35F outside air temperature. On 7- to 20-ton units, cooling operation is extended from 35F ambient temperature
to 0F outside air temperature.
Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.
Electric Heat Kits (CPC and CPH units only): Available in all voltage options.
Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs power to the outlet.
Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit; for use when unit is not running.
Disconnect Switch (non-fused): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit. Please note
that for air conditioning (CPC units) and heat pump models (CPH units), the appropriate electric heat kit must be ordered to be factory-installed along
with the disconnect switch (non-fused) when it is ordered. Please note that for models with a powered convenience outlet option and a disconnect switch
(non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position.
Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.

SS-iDCC15

Product Specifications

Product Specifications 15 Tons

Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s
Evapoartor Motor / Coil
Motor Type (Belt Drive)
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Metering Device
Filter Size (#)
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1
R-410A Refrigerant Charge Cir #2
Evaporator Coil Face Area (ft)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave
Blower Sheave / Belt
Condenser Fan / Coil
Quantity of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ft)
Rows Deep / Fins per Inch
Compressor
Quantity / Type
Compressor RLA / LRA CIR. #1
Compressor RLA / LRA CIR. #2
Electrical Data / Static
Voltage / Phase / Frequency
Standard Max Static
Outdoor Fan FLA / LRA
Total Unit Amps
Min. Circuit Ampacity
Max. Overcurrent Protection (amps)
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)

DCC181***
3B*** B*

DCC181***
4B*** B*

DCC181***
7B*** B*

180,000
134,600
11 / 11.2
88
5039461

180,000
134,600
11 / 11.2
88
5039461

180,000
134,600
11 / 11.2
88
5039461

Std Static
6,000
9.2
3.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
186.2
170.8
20
4 / 16

Std Static
6,000
4.6
3.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
186.2
170.8
20
4 / 16

Std Static
6,000
4.2
3.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
186.2
170.8
20
4 / 16

2 (15" x 12")
1VM50 x "
BK100 x 1/" / BX45

2 (15" x 12")
1VM50 x "
BK100 x 1/" / BX45

2 (15" x 12")
1VM50 x "
BK100 x 1/" / BX45

3
- 1,075
22 / 3
9,000
53.3
2 / 27

3
- 1,075
22 / 3
9,000
53.3
2 / 27

3
- 1,075
22 / 3
9,000
53.3
2 / 27

2 / Scroll
25 / 164
25 / 164

2 / Scroll
12.2 / 100
12.2 / 100

2 / Scroll
9.0 / 78
9.0 / 78

208-230/3/60
1.2
2.4 / 5.2
66.4
73
90
2"
"
1965
2080

460/3/60
1.2
1.2 / 2.6
32.6
36
45
2"
"
1965
2080

575/3/60
1.2
0.9 / 2.2
24.9
27
35
2"
"
1965
2080

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.

SS-iDCC15

Product Specifications

Product Specifications 20 Tons


DCC240
***3B*** B*

DCC240
***4B*** B*

DCC240
***7B*** B*

240,000
181,000
10.0 / 10.1
88
5039462

240,000
181,000
10.0 / 10.1
88
5039462

240,000
181,000
10.0 / 10.1
88
5039462

Evapoartor Motor / Coil


Motor Type (Belt Drive)
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Metering Device
Filter Size (#)
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & 2
Evaporator Coil Face Area (ft)
Rows Deep / Fins per Inch

Std Static Belt Drive


7,000
12.7
5.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
200 ozs.
20
4 / 16

Std Static Belt Drive


7,000
6.4
5.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
200 ozs.
20
4 / 16

Std Static Belt Drive


7,000
5.1
5.0 - 1,725
TXV
20 x 25 x 2 (6)
1"
200 ozs.
20
4 / 16

Belt Drive Evap Fan Data


# of Wheels (D x W)
Motor Sheave
Blower Sheave / Belt

2 (15" x 15")
1VP60 x 1"
BK100 x 1/" / BX46

2 (15" x 15")
1VP60 x 1"
BK100 x 1/" / BX46

2 (15" x 15")
1VP60 x 1"
BK100 x 1/" / BX46

Condenser Fan / Coil


Quantity of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ft)
Rows Deep / Fins per Inch

3
- 1,075
22 / 3
7,200
53.3
2 / 27

3
- 1,075
22 / 3
7,200
53.3
2 / 27

3
- 1,075
22 / 3
7,200
53.3
2 / 27

Compressor
Quantity / Type
Compressor RLA / LRA Cir.

2 / Scroll
33.3 / 239

2 / Scroll
17.9 / 125

2 / Scroll
12.8 / 80

208-230/3/60
1.4
2.4 / 5.2
86.5
95
125
2"
"

460/3/60
1.4
1.2 / 2.6
45.8
50
60
2"
"

575/3/60
1.4
0.9 / 2.2
33.4
37
45
2"
"

2085
2202

2085
2202

2085
2202

Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s

Electrical Data / Static


Voltage / Phase / Frequency
Standard Max Static
Outdoor Fan FLA / LRA
Total Unit Amps
Min. Circuit Ampacity
Max. Overcurrent Protection (amps)
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.

SS-iDCC15

Product Specifications

Airflow Data 15 Tons


Standard Belt Drive Down Shot
ESP
(" HO)

Turns Open
0

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.2

---

---

---

---

---

---

---

---

---

---

7203

2.18

6718

1.84

0.4

---

---

---

---

---

---

7306

2.54

6777

2.14

6257

1.80

5711

1.48

0.6

---

---

7477

2.97

6899

2.51

6323

2.10

5716

1.72

5103

1.39

---

---

0.8

7112

2.96

6467

2.46

5795

2.01

5101

1.61

---

---

---

---

---

---

1.0

5983

2.38

5190

1.89

---

---

---

---

---

---

---

---

---

---

1.2

4426

1.71

---

---

---

---

---

---

---

---

---

---

---

---

High-Static Belt Drive Down Shot


ESP
(" HO)

Turns Open
0

4
CFM

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

BHP

1.0

---

---

---

---

---

---

---

---

---

---

1.2

---

---

---

---

---

---

---

---

6927

3.39

1.4

---

---

---

---

---

---

6739

3.52

5602

2.65

1.6

---

---

---

---

6587

3.69

5245

2.67

---

---

CFM

6
BHP

CFM

BHP

7120

3.26

6223

2.55

5924

2.61

---

---

---

---

---

---

---

---

---

---

1.8

---

---

6419

3.84

4877

2.70

---

---

---

---

---

---

---

---

2.0

6261

4.01

---

---

---

---

---

---

---

---

---

---

---

---

Notes
Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
High-static airflow requires installation of high kit (HSKT180) or factory-built high-static model.
Unit factory shipped with the sheave set at 2.5 turns open.

SS-iDCC15

Product Specifications

Airflow Data 20 Tons


Standard Belt Drive Down Shot
ESP
(" HO)

Turns Open
0

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.2

---

---

---

---

---

---

---

---

---

---

---

---

9664

4.05

0.4

---

---

---

---

---

---

---

---

9570

4.08

9197

3.82

8702

3.51

0.6

---

---

---

---

---

---

9038

3.82

8460

3.46

7949

3.14

---

---

0.8

---

---

8171

2.93

7630

3.70

7068

2.79

---

---

---

---

---

---

1.0

---

---

7901

2.85

7203

3.42

---

---

---

---

---

---

---

---

1.2

7344

4.35

---

---

---

---

---

---

---

---

---

---

---

---

High-Static Belt Drive Down Shot


ESP
(" HO)

Turns Open
0

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

1.0

---

---

---

---

---

---

---

---

9090

5.79

8297

5.06

7479

3.62

1.2

---

---

---

---

---

---

8774

5.60

7914

4.83

6989

4.07

---

---

1.4

---

---

---

---

8471

5.43

7549

4.63

---

---

---

---

---

---

1.6

---

---

8209

6.14

7194

4.45

---

---

---

---

---

---

---

---

1.8

7967

6.02

6883

5.01

---

---

---

---

---

---

---

---

---

---

2.0

6594

4.87

---

---

---

---

---

---

---

---

---

---

---

---

Notes
Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
High-static airflow requires installation of high kit (HSKT240) or factory-built high-static model.
Unit factory shipped with the sheave set at 2.5 turns open.

SS-iDCC15

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) 15 Tons


Three-Phase Units @ 208 / 240V
MCA

MOP

Actual kW
@ 240V

Recommended
Airflow Range

98
141
185

100
150
200

28.8
43.2
57.6

5250 - 6750 CFM


5250 - 6750 CFM
5250 - 6750 CFM

MCA

MOP

Actual kW
@ 480V

Recommended
Airflow Range

49
71
92

50
80
100

28.8
43.2
57.6

5250 - 6750 CFM


5250 - 6750 CFM
5250 - 6750 CFM

MCA

MOP

Actual kW
@ 575V

Recommended
Airflow Range

EHK7-31

41

45

28.8

5250 - 6750 CFM

EHK7-46

59

60

43.2

5250 - 6750 CFM

EHK7-60

78

80

57.6

5250 - 6750 CFM

Model
DCC181***3B
EHK3-31
EHK3-46
EHK3-60
480-Volt Units @ 480V
Model
DCC181***4B
EHK4-31
EHK4-46
EHK4-60
575-Volt Units @ 575V
Model
DCC181***7B

Maximum Circuit Ampacity


Maximum Overcurrent Protection (Amps)
Note: When using electric heat kit, the single-point kit installed in the unit
is needed to meet
UL requirements.

KW Correction Factors
kW Correction Factor
Supply Voltage
Correction Factor

240

230

220

210

208

0.93

0.82

0.78

0.76

kW Correction Factor
(for 480V Units)

kW Correction Factor
(for 575V Units)

Supply Voltage

460

440

430

Supply Voltage

560

550

540

Correction Factor

0.92

0.84

0.8

Correction Factor

0.95

0.91

0.88

For other voltage, use voltage / 480

SS-iDCC15

Multiply rated kW by correction factor to get actual kW.

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) 20 Tons


Three-Phase Units @ 208 / 240V
MCA

MOP

Actual kW
@ 240V

Recommended
Airflow Range

103
146
189
232

125
150
200
250

28.8
43.2
57.6
72

7200 - 8500 CFM


7200 - 8500 CFM
7200 - 8500 CFM
7200 - 8500 CFM

MCA

MOP

Actual kW
@ 480V

Recommended
Airflow Range

51
73
95
116

60
80
100
125

28.8
43.2
57.6
72

7200 - 8500 CFM


7200 - 8500 CFM
7200 - 8500 CFM
7200 - 8500 CFM

MCA

MOP

Actual kW
@ 575V

Recommended
Airflow Range

43
61
79
97

45
70
80
100

28.8
43.2
57.6
72

7200 - 8500 CFM


7200 - 8500 CFM
7200 - 8500 CFM
7200 - 8500 CFM

Model &
Heat Kit Usage

DCC240***3B
EHK3-31
EHK3-46
EHK3-60
EHK3-75
480-Volt Units @ 480V
Model
DCC240***4B
EHK4-31
EHK4-46
EHK4-60
EHK4-75
575-Volt Units @ 575V
Model
DCC240***7B
EHK7-31
EHK7-46
EHK7-60
EHK7-75

Maximum Circuit Ampacity


Maximum Overcurrent Protection (amps)
Note: When using electric heat kit, the single-point kit installed in the unit is needed to meet UL requirements.

KW Correction Factors
kW Correction Factor
Supply Voltage
Correction Factor

240

230

220

210

208

0.93

0.82

0.78

0.76

kW Correction Factor
(for 480V Units)

kW Correction Factor
(for 575V Units)

Supply Voltage

460

440

430

Supply Voltage

560

550

540

Correction Factor

0.92

0.84

0.8

Correction Factor

0.95

0.91

0.88

For other voltage, use voltage / 480

Multiply rated kW by correction factor to get actual kW.

SS-iDCC15

SS-iDCC15

4800

6000

6750

4800

6000

6750

67

103

171.2 177.5 194.5

0.72

MBh

S/T

67

116

284

16

0.65

127

300

12

0.45

115

282

16

0.62

126

297

13

0.43

105

254

21

0.72

112

273

18

0.60

122

288

14

0.41

154.4 160.0 175.3

108

262

19

0.74

167.3 173.4 189.9

109

264

18

0.78

71

59

63

67

121

323

16

0.67

132

342

12

0.46

120

320

16

0.64

131

338

13

0.44

109

289

21

0.73

116

311

18

0.61

127

328

14

0.42

150.7 156.2 171.1

112

298

19

0.76

163.3 169.2 185.4

114

301

18

0.80

168.2 174.3 191.0

71

59

63

67

127

368

16

0.69

139

389

12

0.48

126

365

17

0.66

137

385

13

0.45

115

329

21

0.76

122

354

18

0.63

133

374

14

0.44

147.0 152.4 167.0

118

339

19

0.79

159.3 165.1 180.9

119

342

18

0.82

164.1 170.1 186.3

71

59

63

67

133

414

16

0.71

145

438

12

0.49

132

410

16

0.68

144

433

12

0.47

120

370

21

0.79

128

398

18

0.66

139

420

14

0.46

139.7 144.8 158.6

124

381

19

0.82

151.3 156.9 171.9

125

385

18

0.86

155.9 161.6 177.0

71

59

63

67

138

458

15

0.72

150

484

11

0.50

136

453

15

0.69

149

479

12

0.48

124

409

20

0.79

132

440

17

0.66

144

464

13

0.46

129.4 134.1 146.9

128

421

18

0.82

140.2 145.3 159.2

129

425

17

0.86

144.4 149.7 164.0

115

71

24

228

100

HI PR

LO PR

107

246

22

0.70

117

260

18

0.53

124

271

13

0.34

106

256

24

0.81

113

276

23

0.73

116

123

291

18

0.55

127

131

304

13

0.35

135

313

11

117

314

23

0.75

121

323

20

128

331

18

0.56

132

342

17

136

346

13

0.36

141

356

11

116

332

25

0.86

119

342

22

0.89

Shaded area reflects ACCA (TVA) conditions

110

292

25

0.83

114

301

22

0.38

123

357

23

0.77

127

368

20

0.80

143

394

13

0.38

148

406

12

0.39

121

374

24

0.89

125

385

22

0.93

129

402

22

0.80

133

415

20

0.83

134

141

425

18

0.61

145

438

16

0.63

147

150

443

13

0.39

155

457

11

0.40

156

461

11

125

413

23

0.90

129

426

20

0.94

131

430

20

133

444

21

0.81

138

458

19

0.84

139

463

18

146

469

17

0.61

150

484

15

0.63

152

488

15

0.66

155

489

12

0.39

160

504

11

0.41

162

509

10

0.43

High and low pressures are measured at the liquid and suction access fittings.

134

377

19

0.58

139

389

17

0.60

126

442

16

0.88

0.79

109

300

17

0.59

149

419

19

0.98

160.7 165.5 179.1 192.3 157.0 161.6 175.0 187.8 153.3 157.8 170.8 183.3 149.5 154.0 166.6 178.8 142.0 146.3 158.3 169.9 131.6 135.5 146.6 157.4

128

284

20

0.77

140

389

21

0.42

S/T

120

264

22

0.87

128

410

11

0.66

MBh

110

279

11

0.37

121

393

16

0.87

103

268

16

0.57

142

372

20

0.97

LO PR

253

20

0.76

133

346

21

0.41

22

0.84

122

360

11

0.63

236

0.35

115

345

16

0.84

0.55

137

327

19

0.94

HI PR

0.73

128

304

21

0.40

0.81

117

316

11

0.61

174.2 179.3 194.1 208.3 170.1 175.1 189.6 203.5 166.1 171.0 185.1 198.6 162.0 166.8 180.5 193.8 153.9 158.5 171.5 184.1 142.6 146.8 158.9 170.5

110

303

16

0.81

S/T

129

287

19

0.91

MBh

121

111

267

21

0.39

104

282

11

0.60

LO PR

16
270

256

19

0.79

21

0.89

238

0.37

0.58

HI PR

0.76

0.85

115

63

105

179.4 184.7 199.9 214.5 175.2 180.4 195.3 209.6 171.0 176.1 190.6 204.6 166.9 171.8 186.0 199.6 158.5 163.2 176.7 189.6 146.8 151.2 163.6 175.6

106

257

14

0.40

119

59
172.3 178.6 195.6

95

Entering Indoor Wet Bulb Temperature

85

Outdoor Ambient Temperature

S/T

99

LO PR

243

18

0.58

109

71

75

MBh

21

226

0.69

S/T

158.1 163.8 179.5

MBh

HI PR

102

12
265

LO PR

16

251

19

233

0.41

120

HI PR

0.60

110

12
268

LO PR

16

253

18

236

0.43

HI PR

0.63

0.75

63

S/T

59

176.4 182.8 200.3

MBh

Airflow

IDB: Entering Indoor Dry Bulb Temperature

75

70

IDB

65

Product Specifications

Expanded Cooling Data 15 Tons

10

4800

6000

6750

4800

6000

6750

67

71

59

63

67

71

59

63

67

71

59

63

67

71

59

63

67

71

59

63

115
67

71

29

233

102

HI PR

LO PR

109

251

28

0.87

119

265

27

0.79

127

276

23

0.64

108

262

29

0.94

115

281

29

0.90

119

126

297

27

0.81

130

26

112

297

29

0.96

116

307

26

120

320

29

0.93

123

330

24

131

338

27

0.84

135

349

21

139

353

23

0.68

143

363

Shaded area reflects AHRI (TVA) conditions

134

310

23

0.66

138

320

21

0.70

118

339

29

0.99

122

349

26

1.00

126

365

29

0.96

130

376

26

0.99

146

402

24

0.70

151

414

21

0.73

124

381

28

1.00

128

393

24

1.00

132

410

28

0.99

136

423

25

1.00

137

144

433

27

0.90

148

447

24

0.93

150

153

452

23

0.73

158

466

21

0.75

159

470

20

128

421

26

1.00

132

434

23

1.00

133

439

21

136

453

27

1.00

140

467

23

1.00

142

472

21

149

479

25

0.90

153

493

23

0.94

155

498

22

0.98

High and low pressures are measured at the liquid and suction access fittings.

137

385

27

0.86

141

397

25

0.89

129

451

23

1.00

158

499

22

0.73

163

515

20

0.76

165

520

19

0.80

0.90

112

306

24

0.87

152

427

23

1.00

166.5 169.7 177.7 189.6 162.6 165.7 173.6 185.2 158.7 161.8 169.4 180.8 154.8 157.8 165.3 176.4 147.1 149.9 157.0 167.5 136.3 138.9 145.5 155.2

131

290

26

0.96

143

397

22

0.79

157

S/T

123

270

26

1.00

131

418

20

0.97

147

MBh

112

285

21

0.69

123

401

24

1.00

135

17
494

106

273

24

0.85

145

380

24

1.00

127

21
474

LO PR

259

25

0.94

136

353

24

0.76

152

24
449

26

0.97

125

367

20

0.94

142

25
417

240

0.66

117

352

23

1.00

130

447

18

0.56

0.82

139

333

25

1.00

123

429

23

0.75

HI PR

0.90

131

310

24

0.74

145

406

26

0.93

0.94

120

323

20

0.91

136

377

27

0.99

180.3 183.8 192.5 205.4 176.1 179.6 188.1 200.6 172.0 175.3 183.6 195.8 167.8 171.0 179.1 191.1 159.4 162.5 170.1 181.5 147.6 150.5 157.6 168.1

113

309

23

1.00

124

398

18

0.56

162

S/T

132

293

25

1.00

117

381

23

0.75

152

MBh

124

113

272

25

0.72

138

361

26

0.92

139

15
510

107

288

20

0.89

129

335

28

0.98

131

19
488

LO PR

23
276

261

24

0.98

118

349

18

0.54

156

22
463

25

1.00

111

335

23

0.72

147

22
430

243

0.69

132

317

26

0.89

134

461

16

0.59

0.86

124

295

27

0.94

126

442

20

0.78

HI PR

0.95

114

307

18

0.52

149

419

23

0.96

0.98

107

294

23

0.70

140

389

24

1.00

185.8 189.3 198.3 211.6 181.4 184.9 193.7 206.6 177.1 180.5 189.1 201.7 172.8 176.1 184.5 196.8 164.2 167.3 175.2 187.0 152.1 155.0 162.3 173.2

125

279

26

0.86

128

410

16

0.58

163

S/T

118

259

27

0.92

121

393

21

0.78

153

MBh

108

274

18

0.51

142

372

24

0.95

140

15
515

101

262

22

0.68

133

346

25

1.00

132

18
493

LO PR

248

26

0.84

122

360

16

0.56

158

21
467

27

0.89

115

345

20

0.75

148

20
434

231

0.49

137

327

24

0.92

136

466

16

0.61

0.66

128

304

25

0.98

128

447

20

0.82

HI PR

0.81

117

316

16

0.54

151

423

22

1.00

0.86

110

303

20

0.72

141

393

22

1.00

163.6 167.2 178.6 190.9 159.8 163.3 174.4 186.5 156.0 159.4 170.3 182.0 152.2 155.5 166.1 177.6 144.6 147.7 157.8 168.7 133.9 136.8 146.2 156.3

129

287

24

0.89

130

414

16

0.61

S/T

121

267

25

0.95

122

397

20

0.81

MBh

111

282

16

0.53

143

376

23

1.00

105

270

20

0.71

135

349

23

1.00

LO PR

256

23

0.87

123

363

16

0.59

24

0.93

116

349

20

0.78

238

0.51

138

330

23

0.96

0.68

130

307

24

1.00

HI PR

0.84

119

320

16

0.57

0.89

112

306

20

0.76

177.2 181.1 193.5 206.9 173.1 176.9 189.0 202.0 169.0 172.7 184.5 197.2 164.9 168.5 180.0 192.4 156.6 160.1 171.0 182.8 145.1 148.3 158.4 169.3

131

290

23

0.93

S/T

123

270

24

1.00

MBh

112

285

16

0.55

106

273

19

0.74

LO PR

259

22

0.91

23

0.97

240

0.53

0.71

HI PR

0.88

0.94

63

105

S/T

59

95

Entering Indoor Wet Bulb Temperature

85

Outdoor Ambient Temperature

182.6 186.5 199.3 213.1 178.3 182.2 194.7 208.1 174.1 177.9 190.0 203.1 169.8 173.5 185.4 198.2 161.3 164.9 176.1 188.3 149.4 152.7 163.2 174.4

75

MBh

Airflow

IDB: Entering Indoor Dry Bulb Temperature

85

80

IDB

65

Product Specifications

Expanded Cooling Data 15 Tons (cont.)

SS-iDCC15

SS-iDCC15

5600

7000

7875

5600

7000

7875

67

67

112

313

18

0.66

122

330

14

0.45

111

310

19

0.63

121

327

14

0.43

101

279

24

0.72

108

300

21

0.60

118

317

16

0.42

205.8 213.4 233.8

104

288

22

0.75

223.0 231.2 253.3

105

290

21

0.78

71

59

63

67

117

356

18

0.67

127

375

14

0.47

115

352

19

0.64

126

372

14

0.44

105

317

24

0.74

112

341

21

0.62

122

361

16

0.43

200.9 208.3 228.2

108

327

22

0.77

217.7 225.7 247.2

110

330

21

0.80

224.2 232.4 254.6

71

59

63

67

122

405

18

0.69

134

428

14

0.48

121

401

19

0.66

132

423

15

0.46

110

361

25

0.76

118

389

21

0.64

128

411

16

0.44

196.0 203.2 222.6

114

373

22

0.79

212.4 220.1 241.2

115

376

21

0.83

218.8 226.8 248.4

71

59

63

67

128

456

18

0.72

140

481

14

0.50

127

451

19

0.69

139

476

14

0.48

116

407

24

0.79

123

438

21

0.66

134

462

16

0.46

186.2 193.0 211.5

119

419

22

0.82

201.8 209.1 229.1

121

423

21

0.86

207.8 215.4 236.0

71

59

63

67

133

503

17

0.73

145

531

13

0.50

131

498

18

0.69

143

526

13

0.48

120

449

23

0.80

127

483

20

0.67

139

510

15

0.46

172.5 178.8 195.9

123

463

20

0.83

186.9 193.7 212.3

125

468

20

0.87

192.5 199.5 218.6

115

71

28

251

97

HI PR

LO PR

103

270

26

0.71

112

285

21

0.54

120

298

15

0.34

102

282

28

0.82

109

303

26

0.73

112

119

320

21

0.56

122

126

334

15

0.36

130

344

13

113

345

26

0.75

117

356

23

123

364

21

0.57

127

376

19

131

380

15

0.37

136

392

13

112

365

28

0.87

115

376

26

0.90

Shaded area reflects ACCA (TVA) conditions

106

321

28

0.84

110

330

25

0.38

119

393

26

0.78

122

405

24

0.81

138

433

15

0.38

142

446

13

0.39

117

411

28

0.90

121

423

25

0.93

124

442

26

0.81

128

456

23

0.84

130

136

467

21

0.61

140

481

19

0.63

141

145

487

15

0.39

149

502

13

0.41

151

507

13

121

454

26

0.91

125

468

24

0.94

126

472

23

129

488

24

0.81

133

503

22

0.84

134

508

21

141

516

20

0.62

145

532

18

0.64

146

537

17

0.67

150

538

14

0.40

154

554

12

0.41

156

560

12

0.43

High and low pressures are measured at the liquid and suction access fittings.

130

415

21

0.59

134

428

19

0.61

122

486

18

0.88

0.79

105

330

19

0.59

144

460

22

0.99

214.3 220.7 238.8 256.3 209.3 215.5 233.3 250.4 204.4 210.4 227.7 244.4 199.4 205.3 222.2 238.5 189.4 195.0 211.1 226.5 175.4 180.6 195.5 209.8

123

313

23

0.78

135

428

24

0.43

S/T

116

291

25

0.87

124

451

13

0.66

MBh

106

307

13

0.37

116

432

19

0.88

100

294

19

0.58

137

409

23

0.98

LO PR

279

23

0.76

129

380

25

0.41

25

0.85

118

396

13

0.64

259

0.36

111

379

18

0.84

0.56

132

359

22

0.94

HI PR

0.73

124

334

24

0.40

0.82

113

348

13

0.62

232.2 239.1 258.8 277.7 226.8 233.5 252.8 271.3 221.4 228.0 246.7 264.8 216.0 222.4 240.7 258.4 205.2 211.3 228.7 245.4 190.1 195.7 211.8 227.4

106

333

18

0.82

S/T

125

316

22

0.91

MBh

117

107

293

24

0.39

101

310

13

0.60

LO PR

18
297

281

22

0.80

24

0.89

262

0.37

0.58

HI PR

0.77

0.86

111

63

105

239.2 246.2 266.5 286.1 233.6 240.5 260.3 279.4 228.0 234.8 254.1 272.8 222.5 229.1 247.9 266.1 211.4 217.6 235.5 252.8 195.8 201.6 218.2 234.2

102

16
283

59
229.7 238.1 260.9

95

Entering Indoor Wet Bulb Temperature

85

Outdoor Ambient Temperature

S/T

96

LO PR

21

268

0.40

71

75

MBh

24

249

HI PR

0.58

0.70

115

210.7 218.4 239.3

105

291

14

0.42

116

S/T

99

LO PR

276

19

0.60

106

MBh

22

256

0.72

S/T

228.3 236.7 259.3

MBh

HI PR

100

14
294

LO PR

18

279

21

259

0.44

HI PR

0.63

0.76

63

S/T

59

235.2 243.8 267.1

MBh

Airflow

IDB: Entering Indoor Dry Bulb Temperature

75

70

IDB

65

Product Specifications

Expanded Cooling Data 20 Tons

11

12

5600

7000

7875

5600

7000

7875

67

71

59

63

67

71

59

63

67

71

59

63

67

71

59

63

67

71

59

63

115
67

71

121

31
103

285
110

306

30

0.84

120

323

26

0.69

128

337

21

0.51

107

324

32

0.92

114

348

30

0.87

118

125

368

26

0.70

129

133

384

21

0.53

137

396

19

113

369

32

0.95

116

380

29

120

397

30

0.89

124

409

27

131

419

26

0.73

135

432

24

139

437

21

0.54

144

451

19

0.56

118

415

31

0.99

122

428

27

1.00

126

446

30

0.93

130

460

27

0.96

137

471

26

0.75

141

486

23

0.78

146

492

21

0.56

151

507

19

0.58

152

122

458

29

1.00

126

473

25

1.00

127

24

130

493

28

0.93

134

509

25

0.97

135

514

21

142

521

24

0.76

146

537

22

0.79

148

542

17

151

543

19

0.57

156

560

17

0.59

157

566

33

256

99

HI PR

LO PR

105

276

33

0.88

115

291

31

0.79

122

304

27

0.64

104

288

34

0.94

111

309

33

0.91

114

121

327

31

0.82

125

30

108

327

34

0.97

112

337

30

115

352

33

0.93

119

363

28

126

372

31

0.84

130

383

24

134

388

27

0.68

138

400

Shaded area reflects AHRI (TVA) conditions

129

341

27

0.67

133

351

24

0.71

114

372

34

1.00

117

384

29

1.00

121

401

33

0.96

125

413

30

1.00

141

441

27

0.71

145

455

24

0.73

119

419

32

1.00

123

432

28

1.00

127

451

33

1.00

131

465

28

1.00

132

139

476

31

0.90

143

491

28

0.94

144

148

497

27

0.73

152

512

24

0.76

154

517

23

123

463

30

1.00

127

477

26

1.00

129

482

24

131

498

30

1.00

135

514

26

1.00

137

519

24

143

526

29

0.91

148

542

26

0.94

149

548

25

0.99

High and low pressures are measured at the liquid and suction access fittings.

132

423

31

0.87

136

436

28

0.90

124

496

27

1.00

153

549

25

0.74

157

566

23

0.77

159

571

22

0.80

0.91

108

337

28

0.87

147

469

26

1.00

221.9 226.2 236.9 252.8 216.8 221.0 231.4 246.9 211.6 215.7 225.9 241.0 206.5 210.5 220.4 235.1 196.1 199.9 209.4 223.4 181.7 185.2 194.0 206.9

126

319

30

0.97

138

436

26

0.80

S/T

118

296

30

1.00

126

460

24

0.98

MBh

108

313

24

0.69

119

441

27

1.00

102

300

28

0.85

140

417

27

1.00

LO PR

284

29

0.94

131

388

27

0.77

30

0.98

120

404

23

0.95

264

0.67

113

387

27

1.00

0.82

134

366

28

1.00

HI PR

0.91

126

340

28

0.74

0.94

116

355

23

0.92

240.5 245.1 256.7 273.9 234.9 239.4 250.7 267.5 229.3 233.7 244.8 261.1 223.7 228.0 238.8 254.8 212.5 216.6 226.9 242.0 196.8 200.6 210.1 224.2

109

340

27

1.00

S/T

127

322

28

1.00

MBh

119

109

299

28

0.72

103

316

23

0.89

LO PR

27
303

287

28

0.99

29

1.00

267

0.70

0.86

HI PR

0.96

0.99

114

21
301

0.90

111

379

24

0.75

143

23
477

247.7 252.5 264.4 282.1 241.9 246.6 258.3 275.5 236.2 240.7 252.1 269.0 230.4 234.8 246.0 262.4 218.9 223.1 233.7 249.3 202.7 206.7 216.4 230.9

104

26
288

0.50

132

359

27

0.93

131

512

18

0.62

S/T

98

LO PR

30

273

0.66

124

334

28

0.99

123

491

22

0.83

MBh

31

254

HI PR

0.81

113

348

19

0.55

145

465

26

1.00

0.87

106

334

24

0.73

136

432

25

1.00

218.1 222.9 238.1 254.6 213.1 217.7 232.6 248.6 208.0 212.5 227.1 242.7 202.9 207.3 221.5 236.8 192.8 197.0 210.4 225.0 178.6 182.5 194.9 208.4

125

316

27

0.90

125

455

18

0.61

S/T

117

293

28

0.96

117

436

23

0.82

MBh

107

310

19

0.53

138

413

27

1.00

101

297

23

0.71

130

384

26

1.00

LO PR

281

27

0.88

119

400

18

0.59

28

0.93

112

383

23

0.79

262

0.51

133

363

26

1.00

0.69

125

337

27

1.00

HI PR

0.84

114

351

18

0.57

0.90

108

337

23

0.77

236.3 241.5 258.0 275.8 230.8 235.9 252.0 269.4 225.3 230.3 246.0 263.0 219.8 224.6 240.0 256.6 208.8 213.4 228.0 243.7 193.5 197.7 211.2 225.8

126

319

26

0.94

S/T

118

296

28

1.00

MBh

108

313

18

0.56

102

300

22

0.75

LO PR

284

26

0.92

27

1.00

264

0.54

0.72

HI PR

0.89

0.94

63

105

S/T

59

95

Entering Indoor Wet Bulb Temperature

85

Outdoor Ambient Temperature

243.4 248.7 265.7 284.1 237.8 242.9 259.6 277.5 232.1 237.2 253.4 270.9 226.4 231.4 247.2 264.3 215.1 219.8 234.8 251.0 199.3 203.6 217.5 232.5

75

MBh

Airflow

IDB: Entering Indoor Dry Bulb Temperature

85

80

IDB

65

Product Specifications

Expanded Cooling Data 20 Tons (cont.)

SS-iDCC15

Product Specifications

Dimensions

88/
133

50/

Supply
22

22
48

2 x 21

2 x 60

Return

5/

Vertical Discharge (Top of Unit)

Gas Inlet Location ( NPT)

9
46/

SS-iDCC15

Flue Vent

13

Product Specifications

Unit Clearances
Maintain an adequate clearance around the unit for safety, service, maintenance, and
proper unit operation. Leave a total clearance of 75 on the main control panel side
of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace.
Leave a clearance of 48 on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and
condenser airflow. Do not install the unit beneath any obstruction.
Install the unit away from all building exhausts to inhibit
Ingestion of exhaust air into the units fresh-air intake.

36 minimum
roof overhang

Electrical Entrance Locations


12/

3/
High-Voltage
Entrance
3/

14

LowVoltage
Entrance

SS-iDCC15

Product Specifications

15-Ton Units
Corner Weight A
Corner Weight B
Corner Weight C
Corner Weight D
Shipping Weight
Operating Weight

Weights (lbs.)
590
582
492
401
2080
1965

20-Ton Units
Corner Weight - A
Corner Weight - B
Corner Weight - C
Corner Weight - D
Unit Shipping Weight
Unit Operating Weight

Evaporator Coil

Supply

Provisions for forks have been included in the unit base frame. No
other fork locations are approved.
Unit must be lifted by the four lifting holes located at the
base frame corners.
Lifting cables should be attached to the unit with shackles.
The distance between the crane hook and the top of the unit
must not be less than 60.
Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be
of sufficient length so that cables do not come in contact
with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb.
These struts are intended to protect unit base frame from
fork lift damage. To remove the struts, extract the sheet
metal retainers and pull the struts through the base of the
unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work
should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb
Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions
for proper curb installation. Curbing must
Compressor 1
be installed in compliance with the National 40
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
While rigging the unit, the center of gravity will
cause the condenser end to be lower than the
supply air end.
Bring condenser end of unit into alignment
with the curb. With condenser end of the
unit resting on curb member and using curb
Compressor 2
as a fulcrum, lower opposite end of the unit
until entire unit is seated on the curb. When a
rectangular cantilever curb is used, take care
58
to center the unit. Check for proper alignment
Corner & Center-of-Gravity Locations
and orientation of supply and return openings
with duct.

Return

Roof Curb Installation Rigging

Weights (lbs)
655
535
510
420
2235
2120

To assist in determining rigging requirements, unit weights are shown to the right.
Note: These weights are calculated without installed accessories.

SS-iDCC15

15

Product Specifications

Roof Curb Installation


Curb installations must comply with local codes and should follow the established guidelines of the National Roofing
Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check
for adequate fastening method prior
to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is
responsible for field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary
for the assembly of the sheet metal curb is included in the curb accessory package.
Determine sufficient structural support before locating and mounting the curb and package unit.
Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb
before mounting the package unit. Our full perimeter curbs include duct connection frames to be assembled
with the curb. Cantilevered-type curbs are not available from the factory.
Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.
Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot
penetrate supply and return duct openings.
Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct
installation after unit placement
is not recommended.
See the manual shipped with the roof curb for assembly and installation instructions.

123 Curb Top O.D.


119 Curb Top O.D.

17/

17/

17/
74
Curb O.D.
61

61

78 Curb
Top O.D.

23

1 Typ.

Insulated
Panels

11

1
123 Curb Bottom O.D.

16

1
Typ.

77 Curb Bottom O.D.

SS-iDCC15

Product Specifications

Wiring Diagram
BK
BK

PB

RD

POWER SUPPLY
208V-240V-460V-575V
3 ph / 60hZ

RD
OR
OR
OR

RD

BK

BL

OR

BK

RD

OR

BK
L1

BK

GRND

T1

BK

L2

BC

BL

L3

T2

L1

T1

T3

L2

CC
2

BL

L3

T2

L1

T3

CC
1

T1

L2

L3

T2

T3

BL
BL

GR
BK

BK

RD

BL

OR

RD

RD
PU

BL

C
FC1

BK

RD

YL

RD

BK

YL

BR

PU
OR

CCH2
COMP
2

T3

PU

YL

BK

COMP
1

T2
T3

BR

BK

GR

OR
BK

3
240v
460v
575v

BL

OR
RD

YL

CCHR2
PU

SEE NOTE 3
PLF 2

YL
BL

TB2

BL

PK

CM3

LPS1

S1
S2

RD

BR
PU

TB1

YL

BL

BK

BR

YL

BR
PU
1

RD

BL

2
3
PLF 1
5
6

BR

RD
RD

BL

GR
RD

W1

BL

BR
W2

PU

NO

GR

COM

XFMR-C

BL
WH

K1

K1

GR
BL

Y2

R
XFMR-R

RD

RD
PU

NOTE #2

BR

RD

YL

EBTDR

WH
PU

GR

CM1

GR
RD

GR

BL
PU

CM2

PU

Y1

BK BK

BK

YL
HPS1

WH

WH

TB1

BK

PU BR
BL

LPS2

BL

YL

BK

GR

6
4

1
208v

24V

GR

YL
HPS2

PU

9
7

YL

CCHR1
BL

BK

PU BR PU BR

BL

C
FC3

BK
RD
YL

T1

RD

CCH1

BK

BR

BK
RD
YL

T1
T2

C
FC2

BL

OR

RD

Warning

BK

BK

YL

RD

YL

EM

Wiring is subject to change. Always


refer to the wiring diagram or the
unit for the most up-to-date wiring.

BK

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

OR
RD

RD

BL

OR

PU
NC

C
SPEED UP

M1

M2

WH
PU

++

TO THERMOSTAT

SS-iDCC15

SEE NOTE 4

0140L00958 REV A

17

Product Specifications

Wiring Diagram (cont.)


C O MP O N E N T L E G E N D

CC1

T2
T2

T1
T1

C O MP 1

T3

CC1

T3
C
R CCF1
F

B L O W E R C O NT AC T O R

CC

C O MP R E S S O R C O N T A C T O R
C R ANK C AS E HE AT E R

CCH

2 0 8 -2 4 0 /4 6 0 /5 7 5 /3 /6 0

CC1

L3

C M1

C M2

R CCF2

C C HR
CM

C R ANK C AS E HE AT E R R E L AY

C MR

C O N D E N S E R MO T O R R E L A Y

C O N D E N S E R MO T O R

C O MP
DC

DE F R O S T C O NT R O L

DF T

D E F R O S T T H E R MO S T A T

C O MP R E S S O R

E C ON

E C O N O MI Z E R

E BTD

E L E C T R O N I C B L O W E R T I ME D E L A Y

E MR

E V A P O R A T O R MO T O R R E L A Y

R E L AY

EM
FC

E V A P O R A T O R MO T O R

G ND

E Q U P I ME N T G R O U N D
H IG H P R E S S U R E S W IT C H

F A N C A P A C IT O R

HP S
C
R CCF3
F

T2
CC2

C M3

CC2

T2

T1
T1

C O MP 2

CC2

T3

BC

T2

BC

T3

BC

HV DR

H IG H V O L T A G E D E F R O S T R E L A Y

LP S

L O W P R E S S U R E S W IT C H

L V DR

L O W V O L T AG E DE F R O S T R E L AY

PB

P O W E R D IS T R U B T IO N B L O C K

P LF

F E MA L E P L U G / C O N N E C T O R

R VC

R E V E R S IN G V A V L E C O IL

RCCF

R U N C A P A C I T O R F O R ^J
C O MP R E S S O R A N D F A N
T E R MI N A L B L O C K ( 2 4 V S I G N A L )

TB1
TB2
TR

T3

S U P P L Y V O L T AG E

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.

L2

L1

BC

T E R MI N A L B L O C K ( L 1 )
T R A N S F O R ME R

T1
EM

NO T E S :

C C H1

C C H2

1 . R E P L A C E ME N T W I R E MU S T B E S A ME S I Z E A N D
T Y P E IN S U L A T IO N A S O R IG IN A L (A T L E A S T 105 C )
U S E C O P P E R C O NDU C T O R O NL Y .
2. U S E C O P P E R C O N D U C T O R S O N L Y
++ U S E N . E . C . C L A S S 2 W I R E
3 . E C O N O MI Z E R P L U G L O C A T E D I N T H E R E T U R N A I R
C O MP A R T ME N T , R E MO V E MA L E P L U G , A T T A C H
F E MA L E P L U G T O T H E E C O N O MI Z E R A C C E S S O R Y .
4 . F O R T W O S T A G E O P E R A T I O N R E MO V E W 1 T O W 2
W I R E J U MP E R .
5 . F O R 2 0 8 V O P E R A T I O N MO V E B L A C K W I R E F R O M
T E R MI N A L 3 T O T E R MI N A L 2 O N 2 4 0 V
T R A N S F O R ME R .

2 0 8 -2 4 0 V
O R A P P R O P R IA T E
IN P U T V O L T A G E

S2

TB1

TR

S1
24V

E B T DR
R

F A C T O R Y W IR IN G

E B T DR

L IN E V O L T A G E
L O W V O L T AG E

LP S 1
HP S 1

P LF 1

++

O P T IO N A L
H IG H V O L T A G E

CC1

2 STAGE COOLING

CC2

LP S 2

T H E R MO S T A T
F IE L D W IR IN G

F IE L D W IR IN G

HP S 2
6

3 9

P LF 2

H IG H V O L T A G E
L O W V O L T AG E

WIRE CODE

BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
PK PINK
PU PURPLE
RD RED
WH WHITE
YL
YELLOW
YL/PK YELLOW WITH
PINK STRIP
BL/PK BLUE WITH
PINK STRIP

CCHR2

6
CCHR1

S E E NO T E 4
R

W2

W1

Y/
Y2

TB1

T H E R MO S T A T

Y1

++

S E E U N IT R A T IN G P L A T E F O R T Y P E A N D S IZ E
O F O V E R C U R R E N T P R O T E C T IO N

C
S E E NO T E 3

W1

WH

W1

GR

RD

Y1

YL

Y1

Y/Y2

PK

Y2

BL

OR

W2

BR

W2

TB1

STAT

Wiring is subject to change. Always


refer to the wiring diagram or the
unit for the most up-to-date wiring.

E B T DR

Warning

BC

0140L00959 REV A

18

SS-iDCC15

Product Specifications

Accessories
Field Accessory
Item #

Description

Fits
Model Sizes

FieldInstalled

14CURB180240

14" Roof Curb

15-20 tons

25FD180240

25% Manual Fresh Air Damper

15-20 tons

25MFD180240

25% Motorized Fresh Air Damper

15-20 tons

DNBBS180240

Burglar Bar Sleeves: Includes Supply and Return

All Models

CDK180

Concentric Duct Kit

15 tons

CDK240

Concentric Duct Kit

20 tons

FactoryInstalled

Convenience Outlet: Powered

All Models

Convenience Outlet: Non Powered

All Models

Disconnect Switch (non-fused)

All Models

DNECONGS180240

Downflow Economizer (for model #s 1210 & below)

15-20 tons

DNECONGS180240B

Downflow Economizer

15-20 tons

Electric Heat Kits


HAKT36300

High-Altitude Kit

HSKT180

High-Static Kit

HSKT240

High-Static Kit

All Models

15 tons

20 tons

Horizontal Barometric Relief Damper

15-20 tons

HZCURB180240ED

Horizontal Discharge Curb End Discharge

15-20 tons

HZCURB180240SDN

Horizontal Discharge Curb


Side Discharge; duct openings on non-service side

15-20 tons

HZCURB180240SDS

Horizontal Discharge Curb


Side Discharge; duct openings on service side

15-20 tons

GHRC-1

Hurricane Restraint Clip

All Models

LAKT03

Low-Ambient Kit

15-20 tons

LPKT180300

LP Conversion Kit

15-20 tons

PE1802402

Power Exhaust 208/230v

15-20 tons

PE1802404

Power Exhaust 460v

15-20 tons

SS-iDCC15

Smoke Detector

All Models

Stainless-Steel Heat Exchanger (Type 409)

15-20 tons

19

Product Specifications

Notes

Daikin reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. 2013 Daikin Industries, Inc. Houston, Texas Printed in the USA.

20

SS-iDCC15