Professional Documents
Culture Documents
V2 N2
=
V1 N1 (16.1)
The sinusoidal primary (applied) voltage V1 is related to the peak flux ⌽m and
supply frequency f1 by a relation
V1 ⳱ 4.44 ⌽mf1n (16.2)
where n is a design constant.
If the applied frequency f1 is increased with the same flux and the same
waveforms, the voltages V1, and V2 will also increase proportionately. But if the
transformer windings are not changed and use the same respective sizes of con-
ductor wire and the same respective number of turns N1, N2, the current ratings
of the two windings, will be unchanged. Increase of the voltages due to increased
frequency, with unchanged current ratings, implies a proportionate increase in
the winding voltampere (VA) ratings, which is equally true for both the primary
and secondary windings.
Φm
Bm =
area of flux path (16.3)
FIG. 2 Two-winding transformer: (a) shell-type core and (b) core B-H loop.
In Fig. 16.2 the intercept Br is known as the residual flux density. The magnetizing
intensity H in Fig. 16.2 is proportional to the magnetizing current in the winding.
Time variations of the current and flux cause iron power losses in the trans-
former core, which appear as heat. When ceramic ferrite rather than iron or
steel laminations is used as the magnetic core material, and when the frequency
is greater than 20 kHz, the working peak flux density then falls from (say)
1.5 T to about 0.3 T. But the iron losses in the ferrite also increase with
frequency so that the usable flux density then falls, and still more expensive
ferrite materials may be desirable. Nevertheless, the economic benefits of using
high-frequency switching are considerable, particularly in portable equipment.
Present (2002) developments are moving toward operating switching frequen-
cies up to 1 MHz, but the consequent problems of electromagnetic interference
(EMI) then become significant.
In the flyback and forward converter connections, described below, unidi-
rectional transformer core excitation is used where only the positive part of the
B-H loop (Fig. 16.2b) is used.
For the push–pull, full-bridge, and half-bridge converter circuits, described
below, there is bidirectional excitation of the transformer core and both the posi-
tive and negative parts of the B-H loop are used.
have equal duty cycles, k. The transformer voltage ratio satisfies the turns ratio
relationship Eq. (16.1) . Voltage V1 is determined by the switch duty ratio k ⳱
Ton/Tp, as for the step-down converter in Fig. 15.2.
Ton S S
V1 = kVs = Vs = 1on Vs = 2 on Vs
Tp Tp Tp (16.4)
The cycle of operation for the circuit of Fig. 16.3 is that conduction occurs
sequentially through switches S1 and S2 with dwell periods between the sequences
in which there is no conduction at all on the primary side. This action is repre-
sented in the waveforms of Fig. 16.4 in which the switch-on periods are repre-
sented by S1 and S4, respectively, and the dwell (off) periods by ⌬.
During the intervals when switch S1 (Fig. 16.3) conducts, then diode D1
also conducts so that D2 is reverse biased. Current iL(t) flows through inductor
L and the output voltage vo(t) is given by
S1on − N2 + N2
vo (t ) = V2 = V1 = Vs
0 N1 N1 (16.5)
The signs in Eq. (16.5) refer to the voltage polarities defined by the ‘‘dots’’ on
the transformer windings in Fig. 16.3.
During the intervals ⌬ when both switches are off, the inductor current iL(t)
splits equally between the two diodes and the output voltage vo(t) is zero.
Tp / 2 Tp
v0 (t ) = v0 (t )
S1 on S2 on (16.6)
Also
Tp
S1on + ∆ = S2on + ∆ = (16.7)
2
The whole period Tp in Fig. 16.4 represents a performance similar to that of
the step-down converter (Fig. 15.1), but of double frequency. Combining Eqs.
(16.5)–(16.7) yields, for 0 k 0.5,
Vo N
=2 2 k
Vs N1 (16.8)
The voltage vL(t) across the inductor, which has an average value of zero, is given
by
N
vL (t ) = 2 Vs − Vo
(T2 ) −∆
p
___
− Vo
Tp / 2
N1 0
(T2 ) −∆
p
___
(16.9)
During the conduction intervals of the switches the current iL(t) smoothly in-
creases. When both switches are off,
iL(t) ⳱ 2iD1(t) ⳱ 2iD2(t) (16.10)
The system currents are given in Fig. 16.4.
FIG. 5 Full-bridge converter: (a) circuit schematic and (b) waveforms for ideal operation.
the inductor is then fed back into the supply. The result is that the
current i1(t) reduces and then reverses so that i1(t) becomes negative.
The voltage relationships can be summarised as
v1 ⳱ ⳲVs (16.11)
N2 V V
v2 = V1 = 1 = ± s
N1 n n (16.12)
3. If switches T2 and T3 are then switched off and switches T1 and T2 are
switched on again, the negative current flows through diode D4, the
transformer primary winding, and diode D1 back into the positive sup-
ply terminal, falling to zero and then reversing. The diagram Fig. 16.5b
indicates the current paths during the actions of the transistors and
diodes in each period of the cycle.
FIG. 7 Waveforms for ideal operation of a full-wave bridge rectifier load supplied by a
full-bridge converter.
v2(t) ⳱ 0. When i1(t) has fallen to zero, it then increases in the reverse direction
through T2 and T3 up to the magnitude i1(t) ⳱ IL/n, when v1(t) ⳱ nv2(t) ⳱ ⳮnVL.
During the reversal of i1(t) the freewheeling action causes the voltage v1(t) across
L1 to be vL(t) ⳱ ⳲVs. It then follows that v1(t) ⳱ 0 and
di1 V
=± s
dt L1 (16.15)
Although switching on takes place at zero voltage, the switching off of full current
occurs at full voltage, which imposes a severe duty on the switches.
The peak-to-peak value of input current i1(t), from Fig. 16.5b is therefore
I1 (peak to peak) ⳱ 10 A
Now Vs ⳱ 300 V and L1 ⳱ 30 H. During switching the peak-to-peak current
is the interval described as di1 in Eq. (16.15) . Therefore, the transient interval
dt is given by
L1 30 × 10 −6
dt = di1 = 10 × = 1 µs
VS 300
At a switching frequency of 20 kHz each cycle period occupies a time
1 1
t= = = 50 µs
f 20 × 10 −3
Each switching interval dt therefore occupies 1/50 of the periodic time and there
are two switchings per cycle. The switching or commutation actions take 2 s/
cycle. This means that there is zero voltage for 2 s in each 50-s cycle so that
the net voltages v1(t) and v2(t) are lowered by 2/50, or 4%. The resultant output
voltage is therefore
VL ⳱ 0.96V2 ⳱ 28.8 V
When transistor T is switched off, the inductor current iL(t) circulates through
diode D2 so that the output voltage is negative and decreasing linearly.
Tp
v L (t ) = −Vo
τ1 (16.18)
Over a complete switching period Tp, the average inductor voltage is zero
1 VS τ1 Tp
VL (av) = ∫ − Vo + (−Vo ) = 0
Tp n 0 τ1 (16.19)
FIG. 9 Practical single-switch forward converter: (a) circuit schematic and (b) wave-
forms.
Also, during switch-on, the core flux ⌽ ramps up to satisfy the relation
τ1 dΦ
Vs = N1
0 dt (16.22)
Even if the load current is effectively constant due to a large value of filter
inductance L, the input current i1(t) will increase. Current i1(t) in Fig. 16.9b,
includes the hypothetical transformer magnetizing component im(t), flowing
through the magnetizing inductance Lm and acting to increase the flux against
the opposition of the magnetic reluctance. Current im(t) increases linearly from
zero to Im. By Kirchhoff’s node law
i3 (t )
i1 (t ) = + im (t )
n (16.23)
1 1 1
f = = =
TP Ton + Toff 2τ1 + τ2 (16.25)
Any leakage flux between winding 1 and 2 will cause a voltage ringing overshoot
on the device, which may be greater than 2Vs. Therefore it is important to have
very tight magnetic coupling between windings 1 and 2. Leakage between these
two windings and winding 3 will cause overlap in the conduction of D2 and D3
during commutation, ramping the edges of the current waveforms. The presence
of the leakage inductance will force a finite rate of fall of the current i3 and
growth of i4 or a finite rate of fall of i4 and growth of i3 because i3 Ⳮ i4 ⳱ iL,
which is constant. The coupling with winding 3 cannot be as tight as between
the windings 1 and 2 because of the construction. There will usually be a different
number of turns, and also because of the insulation requirements, the output must
be well insulated from the incoming power supply.
Since there can be no average dc voltage across the ideal filter inductor L,
when T is off, the input voltage to L is zero, and when T is on, it is Vs/n. Therefore,
f τ1Vs
VL = (16.26)
n
For a lossless system the input power is equal to the output power, Pout ⳱ Pin.
Pout = VL I L
Pin = Vs Iin( av) = Vs [I1( av) − I2( av) ]
VL I L = Vs [I1( av) − I2( av) ] (16.27)
The energy stored in the transformer core is incidental and basically undesirable
for the operation of this converter. The only inductive stored energy necessary
for operation is that in L, the output filter. Since only one quadrant of the magnetic
B-H loop is employed this form of converter is generally restricted to lower
power applications.
N1
i2 (t ) = im (t )
N2 (16.28)
The voltage v1(t) across the transformer primary is also the voltage vm(t) across
the transformer magnetising reactance Lm, when i2(t) is flowing,
− N1
v1 (t ) = Vs
N2 (16.29)
N1 VS Tm
kVs − =0
N 2 Tp (16.30)
Tm N
=k 2
Tp N1 (16.31)
For a transformer to be totally demagnetised before the next cycle begins, the
maximum value that Tm/Tp can have is 1ⳮk. Thus the maximum duty ratio with
a given turns ratio is
N2
(1 − kmax ) = km
N1 (16.32)
or
1 n
kmax = =
1 + N2 / N1 n + 1
With an equal number of turns for the primary and the demagnetizing windings
n ⳱ 1 and the maximum duty ratio in such a converter is limited to 0.5.
di
Vs = Lm
dt
Since the on time dt ⳱ 13.2 s, the change of current di in that interval is
If the actual regulated supply voltage is used in the calculation the value Vs
becomes
Vs ⳱ 0.9 ⳯ 300 ⳱ 270 V
Then
270
dim = × 0.088 = 0.0792 A
300
VS N
v1 (t ) = Vs v2 (t ) = = VS 2
n N1 (16.33)
dΦ
N1 = Vs (16.34)
dt
The primary current i1(t) also ramps to provide the mmf needed to drive the flux
(largely) across the airgap, which contains a stored magnetic energy 1⁄2L1i21.
In the switch-on intervals the time variation of the transformer core flux
is obtained from Fig. 16.10b and Eq. (16.34)
FIG. 10 Ideal flyback converter in continuous current mode: (a) circuit schematic and
(b) ideal waveforms.
VS
Φ (t ) = Φ ( 0 ) + t
N1 (16.35)
ˆ (t ) = Φ(τ ) = Φ(0) + Vs τ
Φ 1 1
N1 (16.36)
dΦ
v2 (t ) = −VL v1 (t ) = −nVL = N1 (16.37)
dt
The voltage across the open transistor switch T is
vT (t ) = Vs + nVL (16.38)
But the net change of flux in the transformer core over one complete switching
period must be zero in the steady state. Equating the flux transitions between
Eqs. (16.36) and (16.39) gives
VS V
τ1 = L τ2
N1 N2
or
VL N2 τ1 N2 k
= =
VS N1 τ2 N1 1 − k (16.40)
where k is the duty ratio 1/TP ⳱ 1/(1 Ⳮ 2). The voltage ratio realised in a
flyback converter depends on k such that
VS
VL < for k < 0.5
n
VS
VL > for k > 0.5
n
VS
VL = for k = 0.5
n
The effect of duty ratio k on the voltage transfer relationship corresponds exactly
to the performance of the buck–boost dc–dc chopper circuit, described in Chapter
15.
1 1
f = =
τ1 + τ2 + τ3 TP (16.43)
Now the power flow is equal to the energy stored per cycle multiplied by the
frequency. From Eq. (16.43) an increase of 1 would decrease the frequency. In
circuit design it would seem logical to choose a turns ratio so that nVL is greater
than VS, but this choice is not always made. If the design choice is n ⳱ VS/VL,
then 1 ⳱ 2, and the power is a maximum when 3 ⳱ 0 and f ⳱ 1/(1 Ⳮ 2).
The peak values IL of the load current, illustrated in Fig. 16.12, are seen to be
i
IˆLa = Io + ma = 2Io for discontinuous operation
2
i
IˆLb = Io + mb = 1.05Io for continuous operation (16.45)
2
FIG. 12 Comparison of flyback converter operation (1 ⳱ 2): (a) discontinuous opera-
tion and (b) continuous operation.
Comparing the necessary inductance values for the two cases, from Eqs. (16.46)
and (16.47) gives
Lb
= 20
La (16.48)
The result of Eq. (16.48) does not mean that the inductor must be physically 20
times bigger for the continuous conduction case. Comparison of the maximum
stored energy is a better indicator of the necessary physical size.
16.6.3.3 Peak Stored Energy in the Transformer
The peak energy stored can be expressed in terms of the transformer inductance
L and the peak current of the load. For the discontinuous conduction condition
of Sec. 16.6.3.1,
1 ˆ2
Wa = La I La (16.49)
2
Substituting from Eqs. (16.45) and (16.46) into Eq. (16.49) gives
1 Vτ
Wa = × s 1 × 4Io2 = Vs τ1 Io
2 2Io (16.50)
1 ˆ2
Wb = Lb I Lb (16.51)
2
Substituting from Eqs. (16.45) and (16.47) into Eq. (16.51) gives
1 Vτ
Wb = × s 1 × (1.05) × Io2
2
2 0.1Io
1.1
= Vs τ1Io × = 5.51Vs τ1I o (16.52)
0.2
The ratio of the peak stored energies for the two cases is
Wb
= 5.51
Wa (16.53)
Equation (16.53) shows that in the continuous conduction condition about 5.5
times the stored energy capability is required, compared with discontinuous opera-
tion, although only about one half of the peak current is needed.
16.6.3.4 Energy Storage in the Transformer
The type of transformer used in the circuits of Figs. 16.8 and 16.9 and 16.10 is
the shell type of structure shown in Fig. 16.2, with the addition of an air gap of
length g in the center leg. An ideal transformer with an infinitely permeable core
stores no energy. It is a poor material for storing energy but is good for guiding
flux. In a transformer or inductor with a ferromagnetic core, an air gap is required
in which to store the magnetic energy. The design requirement is tight magnetic
coupling between primary and secondary windings but also a small air-gap length.
As discussed in Sec. 16.2 above, the ferrite core then has a peak flux density Bm
⳱ 300 mT at frequencies higher than 20 kHz.
The current density in the windings around the central limb of the core is
limited by the i2R heating. The volumes of copper in the primary and secondary
are about the same in a well-designed transformer, even though the numbers of
turns and wire sizes may be very different. Let the flux path in the core center
leg have the contour dimensions width W times length L. Then the maximum
energy stored in an air gap of volume W ⳯ L ⳯ g is found to be
But, from Eqs. (16.50) and (16.52), the energy conversion rate with continuous
operation is therefore
Wa P 71.6
Pa = = a = = 13 W
Tp 5.51 5.51
winding, closely coupled to winding 1 with the same number of turns (Fig. 16.13).
If VL tries to rise to a voltage greater than Vs/n, then a negative voltage greater
than Vs is induced in the windings 1 and 3. The effect of winding 3 and D2 is to
clamp the maximum voltage of windings 1 and 3 at ⳮVs and winding 2 at ⳮVs/
n, i.e., it will prevent VL becoming greater than Vs/n.
When T is switched off, the current commutates from winding 1 to winding
3 (instead of 2) and the stored energy is fed back to the supply instead of into
the output circuit. This prevents the rise of VL from becoming greater than Vs/n
and also limits vDS to 2Vs.
Note that it is easier to wind windings 1 and 3 closely coupled because
they have the same numbers of turns and can be wound together fully interlaced,
so that the leakage flux between them and the corresponding leakage reactance,
is very small. This is called a bifilar winding.
Windings 1 and 3, which are ‘‘live’’ on the incoming mains supply, have
to be well insulated from winding 2, which is connected to the output circuit of
the power supply. This insulation is governed by international standards. It means
that the leakage between windings 1, 3, and 2 cannot be as small as between 1
and 3 because of the amount of insulation and the differing number of turns and
wire sizes.
I L ( av ) nτ2
= = 10
I1( av) τ1
Therefore,
1
I1( av) = = 0.1 A
10
For a switching frequency f ⳱ 50 kHz,
1 1
Tp = = = 0.02 ms
f 50 × 103
1 T 1
__p __
I1( av) Tp = Iˆ1 τ1 __ = Iˆ1
2 2 2
0.6 × 2
L= = 7.5 mH
0.42
which is a typical practical value.
Example 16.5 A flyback converter operates from a 300-V dc supply in
discontinuous mode at a frequency of 35 kHz. The transformer turns ratio is 10:
1. When the duty cycle is 0.4, the output voltage is 25 V. Calculate the three
time periods shown in Fig. 16.11.
Vs ⳱ 300 V VL ⳱ 25 V n ⳱ 10 k ⳱ 0.4
From Eq. (16.42) ,
τ1 nVL 100 × 25
= = = 0.833
τ2 Vs 300 (Ex. 16.5a)
Therefore,
τ3 kV
= 1− k − s
Tp nVL
0.4 × 300
= 1 − 0.4 −
10 × 25
= 1 − 0.4 − 0.48 = 0.12
1 1
Tp = = = 28.6 µs
f 35 × 10 3
Therefore,
3 ⳱ 0.12 ⳯ 28.6 ⳱ 3.43 s
From Eq. (16.43) ,
Tp ⳱ 1 Ⳮ 2 Ⳮ 3
Therefore,
0.833τ2 + τ2 = 25.17
25.17
τ2 = = 13.73 µs
1.833
τ1 = 0.833τ2 = 0.833 × 13.73 = 11.44 µs
The calculated values of 1, 2, 3 can be checked by the use of Eq. (16.43)
Example 16.6 For the flyback converter of Example 16.5 the output volt-
age is adjusted to be 30 V. What is the required value of duty cycle and what
are the three time periods 1, 2, and 3?
Vs ⳱ 300 V VL ⳱ 30 V n ⳱ 10
Now nVL ⳱ Vs. From Eq. (16.42) or (16.40) it is seen that 1 ⳱ 2, and when
Vs ⳱ nVLk ⳱ 0.5. From Eq. (16.41) ,
nVL k
= =1
Vs 1 − k − τ3 / Tp
Therefore,
τ3
k = 1− k −
Tp
τ3
= 1 − 2k = 1 − 1 = 0
Tp
Therefore,
3 ⳱ 0
Tp ⳱ 1 Ⳮ 2 ⳱ 21
Therefore,
Tp 28.6
τ1 = τ2 = = = 14.3 s
2 2
Example 16.7 In the flyback converter of Example 16.4 the load current
falls by 50% while the frequency and output voltage remain constant. Calculate
the time duration 3 of the zero flux period in the transformer
When the load current IL falls by 50%, the load power PL also falls by
50%, and so does the load energy Wout:
0.6
Wout = 0.5 × = 0.3 mJ
103
If the input and the load powers are equal, then
1 2
Win = Wout = LI1
2
2Wout 0.3 103 0.6
I12 = = 2× × =
L 103 7.5 7.5
Therefore,
I1 ⳱ 0.283 A
In the Fig. 16.12, with 1 ⳱ 2, the time periods 1 and 2 that had a value 0.01
ms in Example 16.4 reduce by a factor 1/兹2. Therefore,
1 ⳱ 2 ⳱ 0.01 ⳯ 0.707 ⳱ 0.00707 ms
But the overall period Tp remains at 0.02 ms because the frequency is constant.
From Fig. 16.12,
3 ⳱ Tp ⳮ 21 ⳱ 0.02 ⳮ 0.014 ⳱ 0.006 ms
PROBLEMS
Push–Pull Converter
16.1 A push–pull dc-to-dc converter has a transformer step-down ratio 1:3.5
and is supplied by a 60 V battery. The industrial load has a dc resistance
RL ⳱ 23.4 ⍀. Calculate the average load current with the duty ratio
values (a) 0.05, (b) 0.25, and (c) 0.45.
16.2 For the push–pull converter of Problem 16.1, what is the maximum induc-
tor voltage when k ⳱ 0.45?
16.3 For the push–pull converter of Problem 16.1, what is the average value
of the diode currents when both controlled switches are off, if k ⳱ 0.45?
Full-Bridge Converter
16.4 A full-bridge converter with rectified load operates from a dc power
supply of 120 V. The transformer has a step-down ratio of 8.33:1 and a
leakage reactance of 20.4 H. At a switching frequency of 20 kHz the
converter delivers a load current of average value 40 A. What is the
average output voltage?
16.5 A full-wave bridge converter with a rectified load operates from a dc
power supply Vs ⳱ 120 V. The transformer has a step-down turns ratio
of 8.33:1. At a switching frequency of 20 kHz the average load current
kHz from a 300-V dc supply. The output voltage is 30 V and the maxi-
mum output current is 1 A. Calculate (a) the switch on time, (b) the peak
primary current, and (c) the maximum stored energy.
16.15 A flyback converter operates from a 330-V dc supply in discontinuous
mode at a frequency of 42 kHz. The transformer turns ratio is 10:1. When
the duty cycle is 0.60, the output voltage is 52.3 V. Calculate the three
time periods in the switching cycle.
16.16 At a certain value of duty cycle the output voltage from the flyback
converter of Problem 16.15 is 33 V. Calculate the duty cycle and the
time periods of the switching cycle.