ReGrid: Photovoltaics
#





























ReGrid: Photovoltaics


2

ReGrid: Photovoltaics

Table of Content
1 LEARNING TARGETS ................................................................................................................. 3
2 THE SUN AS A RESOURCE FOR PHOTOVOLTAIC USE .................................................................................... 3
2.1 APPLICATIONS ................................................................................................................................. 4
2.2 POTENTIALS AND POSSIBLE OUTPUT ................................................................................................................... 4
2.3 DEVELOPMENT OF ITS USE ................................................................................................................................. 5
3 PHYSICAL ASPECTS ................................................................................................................. 6
3.1 SOLAR RADIATION (DIRECT/DIFFUSE/GLOBAL/ALBEDO/AIR MASS - AM) ................................................................... 6
3.2 SOLAR RADIATION DURING A DAY/MONTH/YEAR ................................................................................................... 8
3.3 ORIENTATION OF MODULES AND ITS INFLUENCE ON THE OUTPUT ............................................................................. 9
3.4 SOURCES TO RESEARCH FOR SOLAR RADIATION DATA ............................................................................................ 10
4 SYSTEM CONFIGURATION: HOW DOES A PV PLANT WORK? ..................................................................... 11
4.1 GRID-CONNECTED PV PLANT ............................................................................................................................. 11
4.2 OFF-GRID PV PLANT ............................................................................................................................... 12
5 COMPONENTS OF A PV PLANT ............................................................................................................... 14
5.1 SOLAR CELL (CONFIGURATION, FUNCTION PHOTOVOLTAIC EFFECT -, TYPES (MONO, POLY, THIN-FILM)) ........................ 14
5.2 SOLAR MODULE (CONFIGURATION, CURRENT-VOLTAGE CURVE, SPECIFICATION DATA, COMPARISON OF EFFICIENCY) .......... 16
5.3 INVERTER (FUNCTION, TYPES, EFFICIENCY, GRID-CONTROLLED VS. SELF-CONTROLLED, SPECIFICATION DATA) .................... 20
5.4 OTHERS: CHARGE CONTROLLER, ACCUMULATORS, FEED-IN METER, CONNECTION TECHNOLOGY ................................... 22
6 PLANT DESIGN: THE MOST IMPORTANT POINTS TO CONSIDER ................................................................ 23
6.1 LOCATION ............................................................................................................................... 23
6.2 DEFINING TYPE OF PLANT AND PLANT SIZE ......................................................................................................... 23
6.3 MODULES: SELECTING THE RIGHT MODULES AND MODULE WIRING ........................................................................ 24
6.4 EMBEDDING THE INVERTER (MODULE INVERTER, CENTRAL INVERTER, STRING INVERTER, DESIGN ) .............................. 25
6.5 SHADOWING ............................................................................................................................... 26
7 ENERGY YIELD ............................................................................................................... 29
7.1 METEOROLOGICAL DATA ............................................................................................................................... 29
7.2 PERFORMANCE RATIO OF A SOLAR PV PLANT ..................................................................................................... 30
8 CONCLUSIONS ............................................................................................................... 36
FURTHER READING ............................................................................................................... 37
KEYWORD INDEX ............................................................................................................... 37





3

ReGrid: Photovoltaics
1 Learning Targets
In this chapter, the reader will be acquainted with the basics of photovoltaic solar energy. This
technology, which has shown an enormous development in the last years, will represent an im-
portant part of our future energy mix. Therefore, it is important to know its potential and ener-
gy conversion mechanism.
First of all, the chapter introduces the solar energy radiation and its different components. Lat-
er, the different photovoltaic technologies commercially available are briefly introduced. The
chapter continues with the differences arising between grid-connected and off-grid systems as
well as the wide range of applications of photovoltaic solar energy. Finally, the most important
parameters for photovoltaic plant design are presented to the reader.

2 The sun as a resource for photovoltaic use
Approximately 80% of our energy we get from non-renewable energy sources, e.g. fossil fuels.
They have been produced by biomass stored beneath the Earths surface for more than 200
million years. Pollutants and greenhouse gases develop when fossil fuels are converted into
electricity or heat. Thus the atmosphere is damaged and global warming increases. Fortunately,
as the resources are limited, our dependence on fossil fuels is close to its end.
The sun provides the earth with a tremendous amount of energy which triggers many different
effects affecting our lives. Incoming solar radiation causes winds, oceanic currents, evaporation,
condensation (rains), and regulates the temperature of the earth. The remaining energy is dissi-
pated and therefore lost. The huge amount of energy supplied by the sun is illustrated by the
following example: the amount of energy humans consume annually exceeds 4.6 x 10
20
joules,
which is equal to the amount of solar energy that the earth receives in one hour.
With the help of photovoltaics it is possible to convert solar energy into electricity. This is a ze-
ro-emission conversion as no sub-products are emitted during energy production.




4

ReGrid: Photovoltaics
2.1 Applications
There are two main different types of application for PV: Grid-connected and off-grid systems.
Grid-connected PV systems feed their energy production into the grid. Off-grid PV systems refer
to those separated from the grid. In this case, the produced energy is consumed locally.

Off-grid PV systems could be applied in the following areas:
- Water pumping for irrigation or human consumption.
- Solar home systems: Households in rural areas or developing countries.
- Communication antennas and telephone stations.
- Clinics and hospitals.
- Rural business.
- Tourism: Small solar boats, cars.
- Grid-connected systems could be applied in the following areas:
- Large scale energy production with PV power plants.
- Household or industry energy supply.

2.2 Potentials and possible output
But, how much energy can be produced by a PV power plant? The output yield of a PV plant is
commonly measured in kWh/kWp*yr. The unit kilo watt peak (kWp) is the amount of power a
photovoltaic module will produce at standard test conditions. PV plants are rated according to
their size in kWp and this unit gives the amount of energy (measured in kWh) that an installed
kWp produces per year. Depending on the selected technology, a kWp represents an area cov-
ered with PV modules ranging from 6-20 m
2
.
This value strongly depends on the way how the system is installed and irradiation level. PV
plants in northern countries like Germany do not have a high irradiation level and consequently
the output yield ranges between 700-1100 kWh/kWp*yr. By contrast, PV installations in sunnier
countries like Spain show output yields between 1400-1800 kWh/kWp*yr. Nowadays, the coun-
tries with the highest output are India, South Africa, and some regions in the Middle East with
measured output yields exceeding 2000 kWh/kWp*yr.




5

ReGrid: Photovoltaics
2.3 Development of its use
In the last decade, PV solar energy has shown its huge potential. The amount of installed PV
power has rapidly increased. Nowadays, nearly 100 GW of PV power are installed worldwide.
Figure 1 below shows the cumulative installed PV power.

Figure 1: Cumulative installed PV power 2000 to 2012. Source: EPIA (2013)
Due to high subsidies in Germany, Spain, and Italy the market has shown an exponential in-
crease in the capacity. Thus aprox. 22 GW have been installed within the EU in 2011 alone,
hence being by far the largest market in the world. The tendency of the market is to move to
new large markets like USA, India, and China. These countries will play a very important role in
the near future of PV.
Figure 2 shows the new PV installed capacity. The increase in the capacity installed yearly has
been coupled with a strong decrease in the components price. Since 2006, the PV system price
has shown a reduction of more than 50%, e.g. the standard final price in 2006 was around 5500-
6000 /kWp for a residential system, whereas in 2011 the standard final price was 2400-2700
/kWp. The industry still has capacity to reduce the margins and further PV system price reduc-
tions are expected. The grid parity, i.e. the price at which conventional energy sources will be as
expensive as PV, will be reached in the following years.

2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012
Cumulative installed PV power 2012 in MW
Total 1425 1753 2220 2798 3911 5341 6915 9443 15773 23210 40020 69684 100000
Europe 154 248 389 590 1297 2299 3285 5257 10554 16357 29777 51716 68716
America 146 177 222 287 379 496 645 856 1205 1744 2820 5053 8253
China 19 30 45 55 64 68 80 100 145 373 893 3093 7093
ROW 1106 1298 1564 1866 2171 2478 2905 3230 3869 4736 6530 9822 15938
1425 1753 2220
2798
3911
5341
6915
9443
15773
23210
40020
69684
100000
0
20000
40000
60000
80000
100000
MWp


6

ReGrid: Photovoltaics


Figure 2: New PV installed capacity 2000 to 2012, ROW: Rest of World. Source: EPIA (2013)


3 Physical aspects
In this section, the basics of solar radiation and its main parameters will be presented. The
power output of the solar array is proportional to the solar radiation. It is therefore important
to understand some parameters in order to foresee the yield of the array.

3.1 Solar radiation (direct/diffuse/global/albedo/air mass - AM)
The sun radiates in all regions of the spectrum, ranging from radio waves to gamma rays. Our
eyes are sensitive to wavelengths ranging from 400-750 nm approximately. In this narrow range,
called visible range, the sun emits about 45 % of the total radiated energy.
The solar constant is defined as the power density of the solar radiation in the outer space and
it is equal to 1360 W m
-2
. The surface solar constant is defined as the power density of the solar
278 328 469 578
1114
1539 1575
2529
6330
7437
16817
29665
30000
0
5000
10000
15000
20000
25000
30000
35000
2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012
Total 278 328 469 578 1114 1539 1575 2529 6330 7437 16817 29665 30000
Europe 53 94 142 201 708 1002 987 1972 5297 5803 13367 21939 17000
America 23 31 46 65 92 227 149 212 349 539 983 2234 3200
China 0 11 15 10 9 4 12 20 45 228 520 2200 4000
ROW 202 192 266 302 305 306 427 325 639 867 1947 3292 5800
MWp


7

ReGrid: Photovoltaics
radiation a surface receives at sea level facing the vertical sun on a clear day. This surface solar
constant is equal to 1000 W m
-2
.
The Air Mass (AM) defines how many times a ray of sunlight passes the perpendicular thickness
of the atmosphere. When the sun is located at a height of 90, i.e. at noon of the spring or au-
tumn equinox, the AM is equal to 1. Otherwise, the AM increases with the decreasing of the
suns height.


Figure 3 shows the different radiation components that are available on the earths surface.
Direct radiation is available on clear sunny days. However, cloudy days usually present diffuse
radiation and low direct radiation. The intensity of the radiation varies from a few hundred W
m
-2
for cloudy days up to 1000 W m
-2
for days with clear sky. PV solar modules are able to ab-
sorb both direct and diffuse radiation. However, crystalline-based technologies are more sensi-
tive to direct radiation than to diffuse radiation. Thin-film based technologies show a better
performance than crystalline technologies with diffuse radiation but still have a lower overall
efficiency.
Figure 3: Schematic view of the different radiation types. Source: RENAC


8

ReGrid: Photovoltaics
The albedo represents the amount of light that is reflected in the surroundings of the PV sys-
tem. High albedo values imply higher reflection and high diffuse radiation. Albedo varies from 0
(no reflection) for black bodies up to 0.8-0.9 for fresh snow.

3.2 Solar radiation during a day/month/year
The position of the sun in relation to ones position is given by the zenith angle (
s
) and the azi-
muth (
s
). The zenith angle is the angle between the local vertical and the line that connects the
observer with the sun. The suns azimuth is the deviation of the suns position with respect to
the south. The azimuth of the PV module with respect to the south is noted as () and the incli-
nation is defined as ().


Figure 4: Angle explanation. Source: RENAC

The zenith and the azimuth depend on the local time of the day (t), the day of the year (d), and
the latitude of the observer (). The hour angle (h) is given in degrees and defined as follows:

) 12 (
24
360
= t h (2.1)



9

ReGrid: Photovoltaics
Each day is defined by the declination angle (), which represents the latitude of the sun. The
declination angle is given in degrees and defined as follows:

(

|
.
|

\
|
=
25 . 365
80
360 sin 44 . 23
d
o (2.2)

The zenith and the azimuth angles are given by the following equations:

) cos( cos cos sin sin cos h
S
+ = o o (2.3)

o
o
tan cos ) cos( sin
) sin(
tan

=
h
h
S
(2.4)

3.3 Orientation of modules and its influence on the output
The orientation and inclination of the PV modules determine the amount of irradiation that the
surface receives to a very great extent. They influence the amount of energy finally produced
and it is obviously very important to take them into account. If the modules are not mounted on
a tracking system that follows the position of the sun in order to get a high radiation income,
the modules must be oriented facing south in the northern hemisphere and facing north in the
southern hemisphere. This guarantees the maximum irradiation level for an array throughout
the year. In regions close to the equator, the orientation is not important but a minimum of 10
inclination is necessary in order to evacuate water in case of rain.
The optimum tilt angle of the modules depends strongly on the location. As a rule of thumb, the
angles shall be tilted to an angle equal to the latitude minus 10. However, roof mounted sys-
tems usually incorporate modules that are placed parallel to the roof and use the roof pitch as
their tilt angle. Correcting the tilt angle would not be beneficial, as the added costs will certainly
do not compensate the amount of energy that will be incremented.


10

ReGrid: Photovoltaics

Figure 5: Different orientations and inclinations and the amount of solar radiation received on each surface in com-
parison to an optimum of 30 and facing south. Source: RENAC

Figure 5 shows different orientations and tilt angles and the proportional amount of irradiation
that is lost in comparison to an array that has been placed with an optimum orientation and tilt
angle. Nowadays, some installations are even facing north (!) in the northern hemisphere, as
the price for modules is decreasing rapidly and sometimes only the north face is available.

3.4 Sources to research for solar radiation data
Data from many countries and cities around the world are usually incorporated into the weath-
er data bases of PV design and simulation tools like PVSyst or PV*SOL . However, there are sev-
eral freely accessible solar radiation data:

PVGIS (http://re.jrc.ec.europa.eu/pvgis/index.htm)
NASA (http://eosweb.larc.nasa.gov/sse/)

Furthermore, commercially available radiation data programs like Meteonorm permit the calcu-
lation and weather data in any point of the world. This software permits to export the weather
data to standard PV simulation tools in order to perform yield simulations on a desired exact
location.


11

ReGrid: Photovoltaics
4 System configuration: How does a PV plant work?
In this chapter the working principle of grid-connected and off-grid PV power plants is described
and thus the process of energy conversion from sun radiation to energy fed into the grid illus-
trated.

4.1 Grid-connected PV plant
The working principle of a PV plant is simple: Photovoltaic cells are connected in series or paral-
lel in order to obtain the desired current and voltage value for the PV module. Modules are also
connected in series or parallel in order to increase the output voltage or current respectively.
The PV array has some electrical protections for short circuits, maintenance works, or for the
(improbable) case of a lightning strike.
Modules are mounted on structures (typically aluminum anodized) that fix the modules either
to the roof or to the ground. Ground mounted systems usually tilt the inclination angle of the
modules in order to optimize the radiation input during the year. Some ground mounted sys-
tems use trackers (one or two-axes) in order to follow the sun path and increase the amount of
solar radiation received at the surface of the modules. Roof mounted systems usually fix the
modules parallel to the roof if the slope is sufficient for good radiation levels. On the other
hand, tilted systems are also available for flat roofs.
The modules are interconnected using standard electric copper cables. The cross section of the
cables depends on the power of the PV array. Overvoltage and lightning protections have to be
installed at the latest by this time. The PV array is then connected to the inverter, which con-
verts direct current (DC) into alternating current (AC). The inverter incorporates Maximum Pow-
er Point Trackers (MPPT) in order to follow the constantly changing current-voltage output of
the array. The current-voltage output is changing mainly because of changing conditions like
irradiance and temperature. The inverter output is then connected to a meter which registers
the amount of energy that has been fed into the grid.
There are two connection methods to the grid: Full feed-in or net metering. The first method is
commonly used in Germany and the second method is mainly used in the US, although it is now
also permitted in Germany. Full feed-in means that the total production of the PV array is fed
into the grid and there is no possibility of own consumption. There is one meter in order to
measure the sold energy and one meter for energy consumption. On the other hand, net me-
tering uses a single consumption and production meter. The produced energy is first consumed
on-site. In case of exceeding energy, it is fed into the grid; in case of the amount of locally re-
quired energy exceeding the production of the PV array, the additional energy is supplied by the
grid. Figure 6 shows schematically the differences between these two methods.



12

ReGrid: Photovoltaics

Figure 6: Overview. Source: RENAC

4.2 Off-grid PV plant
The working principle of an off-grid PV plant, also called stand-alone system, strongly differs
from grid connected PV systems. In this case, the energy is not fed into a grid, but is either
stored in batteries or it is locally consumed immediately. The PV array slightly differs from the
grid-connected systems and its size is typically much smaller, especially for small stand-alone
applications like solar home systems.
PV modules are interconnected using copper cables and are mounted on stain steel structures
as in grid-connected systems. Overvoltage protections, fuses, and eventually lightning protec-
tions have to be installed as well in both DC and AC side if available. The output of the PV array
is then connected to a controller that controls the charging and discharging of the batteries, the
temperature, the state of charge, and the discharge velocity. The batteries are thus connected


13

ReGrid: Photovoltaics
to an inverter that converts the incoming DC into AC. The inverter is only necessary if AC loads
are used. Figure 7 shows schematically a stand-alone system.


Figure 7: Schematic view of a stand-alone system. The solar modules are connected to a charge controller regulat-
ing the charging and discharging of the batteries. The inverter converts DC to AC, which is supplied to the AC loads.
Source: RENAC

There are lots of different stand-alone systems which might incorporate only some of the com-
ponents previously mentioned. For example, water pumps powered by PV usually do not in-
clude batteries and inverters, but only a controller and a DC water pump. On the other hand, PV
stand-alone systems can become extremely complicated and serve, for example, as back-up
systems for mini-grids. The automatic control of such mini-grids, which usually include diesel
generators and other renewable energy sources like small wind generators, is generally compli-
cated but there are good technical solutions available on the market.


14

ReGrid: Photovoltaics
5 Components of a PV plant
Sunlight can be converted into electricity in a photovoltaic (PV) solar cell, thanks to the photoe-
lectric effect. The solar cells are connected in series and form modules, which are then either
connected to a DC load or connected to inverters in order to convert the DC into alternating
current (AC). The output from the inverters is thus fed into the grid for consumption. This sec-
tion presents the main components of a PV system in detail.

5.1 Solar cell (configuration, function photovoltaic effect -, types (mono, poly,
thin-film))
When semiconductor materials
are exposed to sunlight, elec-
trons excite from the valence
band to the conduction band
creating charged particles
called holes. By doping the sili-
con, i.e. adding tiny amounts of
other materials like boron or
phosphor to the crystalline
structure, p- or n- type semi-
conductors are formed respec-
tively. By bringing them togeth-
er, a p-n junction serves for
creating an electric field within
the semiconductor, which is
able to separate electrons and
holes and which creates a di-
rect current (DC) coming out
from the solar cells through the
contacts. Figure 8 illustrates
this process.

Figure 8: Crystalline solar cell working principle. Sunlight impinges the solar
cells. Some light is reflected at the surface and some light passes the solar
cell unaffected. The rest is absorbed creating electron-hole pairs, which are
separated by an electric field and brought to the contacts. Some electron-
hole pairs recombine before arriving at the contacts and heat the solar cell.
Source: RENAC


15

ReGrid: Photovoltaics
The PV market is clearly dominated by crystalline Si (cSi) based solar cells. Nearly 80% of the
cells on the market are cSi based cells, either monocrystalline or multicrystalline. However,
there are many other technologies available or being investigated. The share of thin-film solar
cells in the PV market is growing as manufacturing costs have been significantly reduced and
their production is easy. Figure 9 shows a schematic view of the different cell technologies avail-
able.

Figure 9: Schematic view of the different solar cell types. Source: RENAC


Monocrystalline and polycrystalline cSi cells are wafer-based with thicknesses varying in the
150-250 m range and sizes from 4 to 6. The wafers are gained from a silicon melt by different
methods, condensed into blocks and then cut with a wire saw. Due to their high purity, a lot of
energy is consumed during the manufacturing process and high temperature processes are
necessary in order to remove defects. Monocrystalline solar cells are more efficient than poly-
crystalline cells. However, the manufacturing costs of polycrystalline cells are lower and thus
their lower efficiency is compensated. The electrical contacts on both front and back-sides are
deposited by screen printing. Then metal strips connect the front side of a cell with the back


16

ReGrid: Photovoltaics
side of the next cell in order to form a string of cells in series. Hence, a module consists of sev-
eral strings of cells interconnected in series or parallel in order to obtain the desired current and
voltage. Crystalline Si solar cells have a silicon nitride antireflection layer which gives them their
characteristic blue color. Figure 10 shows some photographs of cSi solar cells.
Thin-film solar cells (amorphous Si, cadmium telluride, CIGS) are commonly deposited on a
piece of glass. The surface is then prepared with a laser and the electrical contacts are deposit-
ed. The energy consumed for thin-film fabrication is much lower than for cSi solar cells because
the deposition is a low temperature process. Furthermore, the fabrication process is much
quicker than for cSi.

5.2 Solar module (configuration, current-voltage curve, specification data,
comparison of efficiency)
Solar modules are composed of solar cells in series and parallel in order to obtain a desired final
power, which is determined by a modules current and voltage. The amount of solar cells in
crystalline modules varies typically between 36 and 72 cells. The solar cells are embedded in a
glass-EVA-solar cell-Tedlar sheet-Aluminum frame in order to protect them from weather condi-
tions. Bypass diodes are placed on the back side of the module in order to avoid high power
output losses due to shadowing.
The solar cells (and modules) are characterized by their electric characteristics. Solar cells be-
have similarly to diodes and therefore the electrical characteristics of a solar cell and a module
are represented by using current-voltage curves (I-V curve). Figure 11 shows the I-V curve of a
Figure 10: On the left hand side, a monocrystalline solar cell is presented. On the right hand side, a polycrystal-
line solar cell is shown. Note the tonality differences between both cells. The monocrystalline structure produc-
es a homogeneous color whereas the polycrystalline solar cell shows different colors for each crystalline orien-
tation. Source: RENAC


17

ReGrid: Photovoltaics
solar cell and gives the electrical behavior of different current-voltage ranges. I
sc
represents the
short circuit current, i.e. the value at which the current is at maximum and where the voltage is
equal to zero. V
oc
represents the open circuit voltage, i.e. the value at which voltage is at its
maximum and where the current is equal to zero. The green line represents the resulting power
curve (power = current x voltage).The maximum power point (MPP) is the current and voltage
value at which the power output of the solar cell is at its maximum. The maximum of the green
line will give the current value of the MPP (I
mpp
) and from here the voltage value of the MPP
(V
mpp
) can be found by using the I-V curve.


Figure 11: I-V and power curve of a solar cell. The blue line represents the I-V curve of the solar cell (MPP = maxi-
mum power point). Source: RENAC
The I-V curve of a module strongly depends on the incoming irradiation. The output current of a
solar cell directly relates to the incoming irradiation: The higher the irradiation, the more elec-
tron-hole pairs are produced and therefore the current increases. On the other hand, the volt-
age slightly varies with varying radiation. Figure 12 shows I-V curves of a solar module for dif-
ferent irradiation levels.


18

ReGrid: Photovoltaics

Figure 12: Dependence of the I-V curve on the irradiation level. Source: RENAC
Module data sheets typically incorporate a similar I-V curve for the total module as well as the
most important parameters of a module that are necessary for system sizing. Figure 13 shows a
data sheet of a module. The electrical parameters (V
OC
, V
MPP
, I
SC
, I
MPP
, maximum system voltage,
and temperature coefficients) are included. The peak power, measured in watt-peaks (Wp), de-
fines the power at which the module is rated. Additionally, the sizes and weight of the modules
as well as mechanical properties are included. Data sheets also include the corresponding com-
pliant certifications.


19

ReGrid: Photovoltaics

Figure 13: Module data sheet with module data parameters and specifications. Source: Q-Cells

The performance of the solar cells varies with the temperature. As the cells get hot, current and
voltage vary, hence diminishing the power output of the cell. For this reason, temperature coef-


20

ReGrid: Photovoltaics
ficients of current, voltage, and output are given. With these parameters it is possible to simu-
late the real behavior of the module on the field. PV magazines for experts like Photon or Pho-
tovoltaic prepare an extensive yearly report with all modules available on the market. Nowa-
days, more than 2,000 different modules with different technologies are available. Table 1 pre-
sents a comparison of the main PV technologies, their efficiencies, and the surface needed for
an installation of 1 kWp.

Material Module efficiency Surface needed for 1 kWp
Monocrystalline Si 14-20 % 7.5-5.5 m
2
Polycrystalline Si 11-16 % 6-9 m
2
Cadmium Telluride 9-12 % 10-11 m
2
Copper-Indium-
Gallium-Selenide
(CIGS)
10-13 % 8-10 m
2
Amorphous Si (aSi,
aSi/cSi)
5-9 % 11-20 m
2
Table 1: Comparison of different technologies, their standard module efficiency, and the surface needed for 1 kWp.

5.3 Inverter (function, types, efficiency, grid-controlled vs. self-controlled, spec-
ification data)
The inverter is responsible for the conversion of
DC into AC and for the regulation of voltage and
frequency. There are mainly two types of invert-
ers: Single- and three-phase inverters. Single-
phase inverters deliver AC to one phase of a pow-
er transmission line, whereas three-phase invert-
ers deliver AC to all three phases of a power
transmission line. Small systems, typically below 5
kWp, commonly use single phase inverters be-
cause one line is enough to absorb the power de-
livered by a PV system. Larger systems commonly
use three-phase inverters (the electricity delivered
by the PV system is split into three parts, each be-
ing delivered to one of the three phases), which
give more freedom with regard to system sizing.
Figure 14: Principle scheme of single- and three-phase
inverters. Source: RENAC


21

ReGrid: Photovoltaics
It is also possible to connect multiple single phase inverters to
form a three-phase system. In this case, the power difference
between phases shall not exceed 5 kW as defined by the grid
utility.
Because the maximum output power is wanted, the Maxi-
mum Power Point has to be known. However the MPP of the
PV array is continuously changing due to changes in the irra-
diation, which is why inverters do need electronic power de-
vices that are able to follow the changes in current and volt-
age. Inverters therefore commonly incorporate Maximum
Power Point Trackers (MPPT) in order to guarantee that the
inverter adjusts to the MPP. The response velocity to changes
in the irradiation, accuracy, and efficiency of the MPPTs de-
termines the efficiency of the inverter.

Some inverters additionally incorporate transformers. They serve for matching the voltage of
the grid and the galvanic separation in case of thin-film based systems. Transformers typically
have an efficiency of 90-95 % and furthermore they cause additional costs. Therefore, inverters
without transformers are being intensively studied and some companies do offer already
transformerless inverters with the same features as inverters which incorporate transformers.
However, grid utilities in some countries still do not accept transformerless inverters.
The efficiency of an inverter is defined as follows:
DC IN
AC OUT
P
P
,
,
= q (2.5)
Equation 2.5 comprises the losses caused by the transformer (if available), MPPT, and all other
losses caused by current conversion.
Inverters can also be categorized depending on their working principle. The grid-controlled in-
verters use the grid voltage for determining the switch-on and -off pulses for the internal elec-
tronic devices. As a consequence of this technique, the quality of the outcoming frequency sig-
nal is low and does not present a complete sinusoidal shape. By incorporating power electron-
ics, the quality of the signal can be improved. Self-commutated inverters do have a more com-
plex internal structure that allows for a better sinusoidal signal formation. They are commonly
used for stand-alone systems, but also for grid-connected systems.
Regarding system sizing, there are many parameters that have to be taken into account. The
nominal power, the MPPT range, the maximum input voltage, the maximum DC current are pa-
rameters that are commonly used for system design. Furthermore, one has to bear in mind that
the thin-film based modules require transformers in order to separate the modules from the
grid galvanically.

Figure 15: Principle of single- and three-
phase inverters each feeding into one
phase. Source: RENAC


22

ReGrid: Photovoltaics
5.4 Others: Charge controller, accumulators, feed-in meter, connection tech-
nology
Charge controllers are used in stand-alone systems for controlling the system. The output volt-
age of the PV array has to be matched with the voltage of the battery, which is typically rated to
12 V, 24 V, or 48 V. Since the voltage of the PV array continuously changes with the weather
conditions, the charge controller plays an important role as it matches both voltages. It com-
monly includes a MPPT in order to optimize the output of the array. Controllers also protect the
batteries from overcharging or deep discharges, which might damage the battery irreversibly.
The batteries play a very important role in stand-alone systems, as storage is required in most
applications. Rechargeable lead-acid batteries are commonly used, as their price is moderate in
comparison to other technologies. Furthermore, lead-acid batteries work appropriately with
low currents, which is common for PV systems. However, there are many other rechargeable
batteries available such as Li-Ion batteries or Ni-Cd.
The feed-in meter in a grid-connected installation is necessary in order to determine the energy
that has been fed into the grid. They are commonly installed close to the consumption meter (if
available). Otherwise, a meter at the feed-in point has to be installed first by the utility. In case
of net-metering, smart meters are necessary. These meters are able to measure simultaneously
the energy consumed and the energy supplied by the grid.




23

ReGrid: Photovoltaics
6 Plant design: The most important points to consider
The design of a PV plant is a complicated process where optimization plays an important role.
The location of the array and shadowing strongly determine the power output. It is therefore
important to be aware of their influence and select appropriate components for each location.
This section presents the parameters that have to be taken into consideration while designing a
PV array: Location, shadowing, and components.

6.1 Location
The location of a solar plant must be carefully investigated during sizing and prior to installation.
A badly selected location can have a strong impact on the output and performance of the sys-
tem. An on-site visit to a potential location is therefore strongly recommended.
First, it is important to determine whether the building or the field is suitable for a PV installa-
tion. For this reasons as much information as possible regarding the following parameters has to
be obtained:

- Location description and site plan.
- Take photographs for clear understanding and shadowing analysis.
- Planned system size, technology and installation.
- Orientation by compass and inclination.
- Future access and roof openings.
- Soil quality and type. Type of roofing. Structure mounting possibilities.
- Usable space, roof, or faade.
- Shadowing objects like houses nearby, trees and growing vegetation, chimneys, win-
dows, overhead cables (telephone and electricity),
- Cable lengths, wiring routes and method.
- Lightning and earthing protection available?
- Investigate the future position of the feed-in point and whether there is enough place
for inverters, junction boxes, meters,
- Special subsidies related to the location (cropland, former military land).
- Draw a plan with measures and distances.
- Shade analysis with special equipment.

6.2 Defining type of plant and plant size
The type and size of a PV system depends on many factors: Customer, economic situation, tech-
nical and material viability, situation, radiation characteristics, and many other characteristics.
Typically, these parameters are intensively studied and several configurations are prepared.
Subsequent to a simulation and commercial feasibility studies the best configuration is selected.


24

ReGrid: Photovoltaics
It is recommended to consider different technologies when sizing a system. Some technologies
perform well under determined weather conditions. For example, thin-film modules perform
better than cSi modules under diffuse light or high temperatures. By contrast, cSi modules per-
form better under high radiation levels. Similarly to the weather conditions, the negative influ-
ence of shadows is lower for certain module technologies. For example, shadowing is critical in
case of cSi but thin-films do not decrease their output as much as cSi does.
Regarding ground mounted systems, there has to be a minimum distance of two meters to any
road or something similar in order to avoid dust formation. If economically viable, use protect-
ing fences that avoid burglary and leave enough distance in order to avoid shadowing.
Enough distance (> 10 cm) to any roof edge has to be left in roof mounted systems in order to
avoid excessive wind loads on the PV array. One has to bear in mind during system sizing that
mounted modules have an additional interstitial space of at least 1-2 cm caused by module
clamps which serve for fixation to the mounting system.

6.3 Modules: selecting the right modules and module wiring
The selection of appropriate modules for an installation is a difficult process. Usually, a company
has supply contracts with manufacturers so that the selection is already limited. The customer
probably has a limited budget and/or a limited area to install. Therefore, the amount and type
of modules is limited. For example, roof mounted systems usually have cSi modules rather than
thin-film modules because the area is limited and the customer wants to install as much power
as possible. The use of thin-film modules for ground mounted systems is growing, as the mod-
ule price, which is the most expensive part of an installation, is getting lower. The use of semi-
transparent PV modules is interesting for building integrated PV systems as an architectural
component.
In case of two modules being connected in series, the module wattages and voltages are added
together whereas the current remains the same. But in case of two modules being connected in
parallel, the module wattages and the current are also added together but here the voltage re-
mains the same. The interconnection of several modules in series, also called string, and in par-
allel gives the final PV array. By increasing the voltage in a string, the wiring losses diminish.
However, the system voltage is commonly limited to 1000 V due to the physical limitations of
the inverters and modules. Thin-film modules have much higher voltages than cSi modules due
to their composition. Therefore, the amount of modules in a string is limited.
Weather conditions have to be considered prior to installation. In case of less direct radiation,
thin-film modules are recommended due to their better performance under diffuse radiation,
but cSi modules are recommended in case of high direct radiation.
Module wiring is mainly divided in two parts: DC and AC side. There are some rules of thumb in
order to size the wiring. Typically, the power losses caused by the DC cables shall not exceed 1
%. On the AC side (after inverter), the power losses must not exceed 3 %.



25

ReGrid: Photovoltaics
6.4 Embedding the inverter (module inverter, central inverter, string inverter,
design )
The inverters can be classified according to their connection to the modules. There are mainly
three different types of inverters: Module inverters, string inverters, and central inverters. Each
connection concept presents advantages and disadvantages. The selection of one of these con-
cepts depends on many parameters and it has to be optimized during sizing. Figure 16 introduc-
es schematically the different inverter configurations.


Figure 16: Different inverter configurations: Central, string, and module inverters. Source: RENAC

Module inverters are small inverters located at the back side of the modules. The advantage of
module inverters consists in quickly transforming the current from DC to AC, hence avoiding DC
cables and losses. Since there is only one PV module per inverter, the MPPT works very accu-
rately. However, nowadays the installation costs are much higher than for external inverters.
Their use is marginal nowadays and only a few companies offer this possibility.
String inverters are commonly used in small and medium sized installations, like household or
small ground mounted installations. Since they are easy to install, many installers prefer to in-
stall them also for large field installations. Central inverters manage a few module strings and
typically have one MPPT. String inverters are prepared for both indoor and outdoor installation.
Their size varies depending on the rated power but they are usually smaller than 50 x 50 x 30
cm. Generally, string inverters are rated from less than 1 kWp up to 12-20 kWp. The advantage
of this concept consists in their close location to the PV array so that the DC wiring is reduced,
hence reducing losses and wiring costs. Additionally, in case of failure, the system continues


26

ReGrid: Photovoltaics
working and only a small part of the system does not work. This effect does not happen with
central inverters, where the entire system is stopped if an inverter failure occurs.
Central inverters connect many module strings. They usually have more than one MPPT in order
to optimize the power output of each string and always convert directly into a three-phase sys-
tem. The rated power of a central inverter varies from 25-50 kWp up to 2.5-5 MWp. Their size
varies from 0.5-1 m
3
up to container-sized inverters that are placed with cranes. Central invert-
ers commonly incorporate transformers. Their use is recommended in very large installations as
the inverter price-per-watt ratio diminishes with increasing size. However, wiring costs increase
as the strings are located far away from the inverter. Central inverters are commonly placed in
the middle of a ground mounted PV installation in order to diminish wiring costs. They are
mostly located outdoors and are prepared for bad weather conditions with a rated protection
level of IP 65.
Inverter sizing is a difficult task. The voltage and current values of each string coming out from
the PV array have to match the limits of the inverter. Large inverters, i.e. central and some string
inverters, are able to interconnect more than one string and therefore it becomes complicated.
The sizing procedure starts selecting an inverter and a module type and a desired peak power.
Then, bearing in mind the different voltage and current limit values of the inverter, different
string combinations which match the inverter requirements have to be considered. Voltage and
current values must be corrected with the temperature coefficients at the maximum and mini-
mum ambient temperatures as the temperature strongly influences PV sizing. The final configu-
ration, i.e. the amount of modules and inverters, is selected depending on the size and budget
of the project.

6.5 Shadowing
Shadowing of PV modules must be avoided if possible. It is often underestimated and leads to
strong decrease in the output yield of the PV array. If a solar cell within a module is shaded, it
will generate less current than neighboring solar cells. The solar cell becomes reverse biased,
receives current from other solar cells, and dissipates power in form of heat. If the module does
not have bypass diodes mounted, this effect might lead to irreversible damages of the solar cell
and module.
Shadowing is sometimes unavoidable. Correct shadow analysis is thus necessary in order to
avoid large power output reduction. The use of a professional camera-based shade analyzer like
HORI catcher or Solar Pathfinder is strongly recommended. Such systems are based on photo-
graphs that serve for shadow investigation. Professional shade analyzers incorporate special
software that allows for shadow recognition and loss estimation for each daytime and date.
The influence of shadowing on the output and performance of the solar array must always be
investigated with PV system simulation software like PV*Sol or PVSyst. These programs incorpo-
rate AutoCAD-based 3D shadowing simulation tools that permit the evaluation of losses caused
by shadowing.


27

ReGrid: Photovoltaics

There are several types of shading. They are listed here:

1. Direct shadowing: This particular case of shadowing causes strong losses in the output
yield of the PV system. In this case, a shadowing object is placed close to modules and
shades the PV array constantly. The closer the shadowing object is to the array, the
darker the shadow is and the less diffuse light reaches the module surface, the more
problematic the situation gets. .

2. Temporary shadowing: This is caused by natural conditions, like snow, leaves, soiling, etc.
This effect is especially important in ground mounted systems in rural areas, where the
PV arrays come much easier in contact with dust. The tilt angle of the array shall exceed
10 in order to allow self-cleaning and water evacuation after raining. In snowy regions,
the lower part of the module is commonly covered a long period of time. Therefore, a
horizontal arrangement of the modules is recommendable in order to minimize losses.
In this case, the snow will cover only one string of the modules and the bypass diodes
will avoid high shadowing losses.
3. Self-shading: A bad system design might cause shading on modules caused by other
modules that have been placed ahead. As a rule of thumb, the modules located in a row
must be separated from each other approximately 4-6 times the height of the tilted
module. Generally that depends strongly on the latitude where the system is installed. It
has to be calculated for each project separately.Under these conditions, mutual shading
is avoided. Figure 17 shows schematically the minimum separation between module
rows.




28

ReGrid: Photovoltaics

Figure 17: Separation between module rows in order to avoid mutual shading. Source: RENAC

Last but not least, shadowing of other components like inverters and cables is desired. Shadow-
ing leads to lower working temperatures, hence allowing for longer lifetimes and better perfor-
mance of the components.




29

ReGrid: Photovoltaics
7 Energy yield
The economic feasibility of solar photovoltaic plants critically depends on the electricity yield,
which is a function of both the meteorological conditions and the performance of the solar pho-
tovoltaic plant itself. Firstly, as the energy production of solar PV systems is strongly dependent
on the irradiance reaching the PV modules, a profound knowledge of the climate conditions at
the given location is of capital importance. Secondly the quality of the components used in the
plant, the layout of the plant itself and a professional engineering will affect the performance of
the plant and consequently the energy yield of the plant. In this section, both climate data and
plant performance and their impact in the energy yield of the plant will be analyzed in detail.
7.1 Meteorological data
Relevant meteorological data for the yield of a solar PV plant are mainly solar radiation, tem-
perature and wind speed. We will focus in this section in the most important factor, namely so-
lar radiation.
Solar radiation is not constant during different years and therefore measurements must be con-
ducted over long periods. Climate data supplied by third-party service providers has usually
been recorded with an instrument mounted horizontally, so that it sees the whole sky. Referring
to Figure 3, this means that the type of radiation recorded is global radiation, with the compo-
nents direct and diffuse radiation. The total irradiance on a horizontal surface on Earth (also
called global irradiance) E
global,hor
is therefore the sum of the direct irradiance E
dir,hor
and the dif-
fuse irradiance E
diff,hor
on the horizontal surface:

Instruments mounted horizontally do not record reflected radiation (albedo). Climate data is
provided in the form of a typical meteorological year (TMY). A TMY of a climatological parame-
ter dataset (e.g. global radiation) is a year which should be representative of the dataset, in or-
der to give the most likely scenario for this parameter or group of parameters. The time step is
usually hourly and the plane orientation horizontal. It is recommended to use longtime averag-
es (10 to 20 years) to build typical meteorological years as basis for yield estimations.
As mentioned in previous sections the energy yield of a PV plant is optimized by adjusting array
orientation and tilt. The optimal orientation is heading to the equator (so for example in the
Northern Hemisphere the optimal orientation is south. Regarding tilt a rule of thumb to maxim-
ize annual energy production is to choose a tilt angle close to latitude. Slight variations depend
on local weather conditions. Consequently the relevant radiation to estimate the energy yield
will not be the radiation on a horizontal but on a tilted plane.
The global irradiance on a tilted surface is composed of the, the diffuse sky irradiance and the
ground reflection (a component that does not exist for horizontal surfaces):

being E
global,tilt
the global irradiance on a tilted surface, E
dir,tilt
direct irradiance on a tilted surface,
E
diff,tilt
diffuse sky irradiance on a tilted surface and E
refl,tilt
the ground reflection on a tilted sur-
tilt refl tilt diff tilt dir tilt global E E E E , , , , + + =
hor diff hor dir hor global E E E , , , + =


30

ReGrid: Photovoltaics
face. The different components of global radiation on a tilted surface must be now inferred
from the components of global radiation on the horizontal plane, E
dir,hor
and E
diff,hor,
which are
the components

provided by third-party weather data providers. Calculations for the direct ra-
diation are straightforward and based on trigonometric relations. For the calculation of the dif-
fuse and reflection components in the plane of the PV array a model will be necessary. An iso-
tropic model assumes that the intensity of diffuse sky radiation is uniform over the sky dome.
Hence, the diffuse radiation incident on a tilted surface depends on the fraction of the sky
dome seen by it. Furthermore the reflected radiation incident on a tilted surface also depends
on the fraction of the ground seen by it. An isotropic model is not the most accurate model
available; however it is amply sufficient to get enough accuracy. Using this model the global
radiation on a tilted plane will be given by the expression:



being the incidence angle of direct irradiance on the array,
s
is the elevation angle of the sun,
the PV array tilt angle and represents the ground albedo (reflectance).
7.2 Performance ratio of a solar PV plant
The performance ratio (PR) is a parameter that describes the performance and the quality of PV
systems. It is independent of system size and irradiance and time period chosen. Low values of
PR indicate high overall losses due to high module temperature, incomplete use of irradiance by
reflection from the module front surface, soiling, component failures, etc.
The performance ratio is calculated as the ratio of energy delivered to the load per day and kWp
(Final Yield Yf) and the theoretically available energy (reference yield Yr).
PR = Y
f
/ Y
r

With Y
f
being the energy delivered to the grid per year and kWp (e.g.: Yf = 1200 kWh /
year*kWp [h/year]) and Y
r
being the theoretically available energy, which is the global irradi-
ance on tilted plane divided by the reference irradiance G (1 kW/m2) (e.g.: Yr = 2,100 kWh
/m2*year/1 kW/m2 = 2,100 [h/year]). Y
r
defines the solar radiation resource for the PV sys-
tem. It is a function of the location, orientation of the PV array, and weather variability and pro-
vides the Peak Sun Hours
1
(PSH) during the year.
The closer the PR value determined for a PV plant approaches 100 %, the more efficiently the
respective PV plant is operating. Summarizing the performance ratio represents proportion of
the energy that is actually available for export to the grid after deduction of energy losses. The
following figure represents a schematic representation of a solar PV plant and the sources of
energy losses which consequently will have an influence on the PR value.

1
PSH refers to the solar insulation at a particular location if the sun were shining at its maximum value of 1kW/m2
for a certain number of hours.
|
.
|

\
|
+ |
.
|

\
| +
+ =
2
1
2
1 |

u cos cos
sin
cos
, ,
,
, hor global hor diff
s
hor dir
tilt global E E E E


31

ReGrid: Photovoltaics

Figure 18: Losses affecting PR and yield on solar PV systems. Source: RENAC
Following we will briefly elaborate on the different influencing factors, that is to say, sources of
energy losses.
Shading losses
As explained in section 6.5, shading can cause high losses of performance for solar energy sys-
tems, in particular for photovoltaic systems. Derate factors for shading must be taken into ac-
count for situations when PV modules are shaded by nearby buildings, objects, or other PV
modules and array structure.
Very simple instruments can be used to estimate obstacles height and azimuth angles easily. A
solar position diagram with a trigonometrically subdivided height axis and a regular 180 azi-
muth axis is the basis for such an instrument.
This diagram must be copied onto a transparen-
cy, which is then bent in a semicircle. The ob-
server looks through this diagram to the objects
and can directly read height and azimuth angles.

The result is a polygonal approximation of the
surroundings silhouette drawn into the solar
position diagram. More sophisticated instru-
ments, with higher associated costs, like the
ones introduced in section 6.5 can also be used.
For PV arrays consisting of multiple rows of PV modules and array structure, the shading derate
factor should be changed to account for losses occurring when one row shades an adjacent row.
Spacing between rows is a compromise between optimizing the use of space and self-shading
losses. The plant designer decides what will be the separation between module rows. An ex-
pression that can be used is the following:
Figure 19: Shadow analysis using sunpath indicator.
Source: RENAC


32

ReGrid: Photovoltaics



being d the separation between module rows (in m), L the height of the PV-array (in m), the
module inclination (in ), the ground inclination () and the solar elevation () at the worst
irradiation day. The obtained separation d between module rows guarantees that at noon on
the worst irradiation day, that is to say, the day where the sun at noon has the lowest elevation,
there will not be any self-shading between rows.
Furthermore the quotient L/D is equivalent to the Ground Cover Ratio (GCR), defined as the
ratio of the PV array area to the total ground area. This metric can be used to predict yields per
land-area. Ground coverage ratio values depend on the geographical location, type of system
(fixed, 1-axis or 2-axis tracking) and the shading derate factor. They vary typically between 60%
and 20% percent (for solar plants with 2-axis tracking systems).
Temperature losses
Temperature affects negatively the performance of PV modules. To determine the variation of
P
mpp
at different temperatures the following expression issued
P
mpp
(T) = P
mpp
(STC)* (1+T x T
k
)
being P
mpp
(STC) the rated power of the module at Standard Test Conditions (STC, 25C ambient
temperature and radiation on the module 1000W/m
2
), P
mpp
(T) the module power at another
conditions and T
k
the corresponding temperature coefficient. The temperature T which must be
plugged into the expression is not the ambient temperature, but the module temperature. The
temperature of the module cells can be estimated by using the expression:
T
cell
= T
amb
+ (NOCT-20)*G/800
where NOCT is the Nominal Operating Cell Temperature expressed in C (usually given by the
module manufacturer in the module data sheets and G the irradiance in W/m
2
. If NOCT is not
given, 48C is recommended as a reasonable value which describes well most of the commonly
used PV modules.
Inverter losses
During the conversion of direct current (DC) produced by PV generators to alternating current
(AC) that is the one fed into the grid carried out by inverters losses occurs. Therefore the effi-
ciency of the inverter needs to be taken into account, but not only at rated power. Photovoltaic
inverters operate at the rated power for only very few hours in any year. Due to the changing
solar irradiance, the inverters predominantly operate under part load. Therefore, it is very im-
portant that photovoltaic inverters have high efficiencies even when operating under part load
conditions.
(

+
+

= ) cos(
) tan(
) sin(
|
o
|
L d


33

ReGrid: Photovoltaics

Figure 20: Inverter efficiencies at different load conditions. Source: RENAC
Here the maximum inverter efficiency is 95,5% at the half of inverters nominal rating. In Euro-
pean Efficiency definition inverter spends 48% of its working time at that level.

Therefore weighted inverter efficiencies have been defined for different geographical regions,
which take into account the inverter efficiency at different load conditions. The best know ones
are the euro efficiency and the Californian Energy Comission (CEC) efficiencies:


Since the radiation in Arab countries corresponds more to California values, the method accord-
ing to CEC has to be prefered to determine the weighted inverter efficiency for MENA re-
gions.Another factor contributing to DC/AC conversion losses is the sizing ratio between invert-
er and solar PV array. A too under dimensioned inverter cannot process all the power delivered
by the generator under peak load conditions and overheating can occurs. Temperature derating
occurs, which means the inverter reduces its power to protect components from overheating.
On the other side, it is not recommended to oversize inverters, since losses due to permanent
part-load operation may be high. Figure 21 shows an example of relative energy yield compared
to maximum available depending in the inverter to PV array sizing ratio which is valid for conti-
nental European conditions. The invterter design ratio in Arab regions may differ, therefore, the


34

ReGrid: Photovoltaics
inverter size should be adjusted to the regional radiation conditions. Appropriated inverter to
PV array sizing ratio depend on the local weather conditions.

Figure 21: Impact of inverter size on system yield. Source: RENAC
Other sources of losses are wiring losses, soiling, etc. The following figure shows two represen-
tations, a list and graphic representation obtained from the software PVSYST, of the factors in-
fluencing the performance ratio of a solar PV plant and its impact given by the derating factor.


35

ReGrid: Photovoltaics

Figure 22: Representations of factors influencing the performance ratio. Source: PVSYST
Typical values for the performance ratio of a solar PV system range between 60% and 80% de-
pending upon the size and performance of the plant. Taking into account that Y
f
in the following
expression is the energy delivered to the grid per year and kWp
PR = Y
f
/ Y
r

good estimations of the energy yield of the plant can be obtained. Lets carry out a small exam-
ple. Assuming a PV system of 4 kW
p
rated power with a performance ratio of 0.75 on a location
with 2100 peak sun hours of solar radiation per year the expected energy yield of a will be:
Yield = 0.75 * 2,100 * 4.0 = 6,300 kWh per year
A more detailed calculation of the expected yield of a solar PV plant can be obtained using
simulation software. The input is usually in the form of hourly climate data (radiation, tempera-
ture, etc). The yield is then calculated for all the hours of a typical year using the given climate
data and software algorithm and then summed up to provide a specific energy yield per year.



36

ReGrid: Photovoltaics
8 Conclusions
To sum up, PV is a zero-emission energy source that will play an important role in the short-
term future of the energy mix. In a couple of years, increasing electricity prices of conventional
energy sources and strongly decreasing prices of PV components will lead to producing energy
with PV, which will be more cost-efficient than purchasing energy from the grid operator.
This chapter has presented the basics of solar radiation and photovoltaic energy conversion.
Furthermore, the main commercially available PV technologies and components have been de-
scribed, including their advantages and disadvantages. The chapter has additionally shown the
differences in the working principles of grid-connected and off-grid PV plants. Finally, the main
parameters, that has to be taken into consideration when designing a PV plant, has been intro-
duced and it was shown how to deal with them.


37

ReGrid: Photovoltaics
Further reading
Weblinks
http://pvcdrom.pveducation.org/index.html
www.solarbuzz.com
http://www.solarexpert.com/GlossaryPV.html
http://www.pvresources.com/en/glossary.php
http://www.windsun.com/Solar_Panels/pv_glos.htm

Grid connected PV
Solar Energy International; Photovoltaics: Design & Installation Manual; ISBN-10: 0865715203;
2004
DGS/earthscan; Planning and Installing Photovoltaic Systems; ISBN: 978-1-84407442-6; 2008

Off-grid PV
Hankins, Marc; Solar Electric Systems for Africa; ISBN-10: 0850924537; 1995
Ecofys; Stand-Alone Photovoltaic Applications; ISBN: 9781873936917; 1999


Keyword index
Accumulator An apparatus by means of which energy can be stored.
Alternating Current (AC) An electric current that reverses direction periodically
AM Airmass defines how many times a ray of sunlight passes the perpendicular thickness of
the atmosphere. When the sun is located at a height of 90, i.e. at noon of the spring or autumn
equinox, the AM is equal to 1. Otherwise, the AM increases with the decreasing of the suns
height.
Albedo or reflection coefficient The diffuse reflectivity or reflecting power of a surface. It is de-
fined as the ratio of reflected radiation from the surface to incident radiation upon it.
Array A collection of electrically connected photovoltaic (PV) modules.
Battery A device that converts the chemical energy contained in its active materials directly into
electrical energy by means of an electrochemical oxidation-reduction (redox) reaction.
Bypass Diode A diode connected in parallel with a PV module to provide an alternate current
path in case of module shading or failure.


38

ReGrid: Photovoltaics
Charge controller An electronic device which regulates the voltage applied to the battery sys-
tem from the PV array. Essential for ensuring that batteries obtain maximum state of charge and
longest life.
Crystalline Silicon A type of PV cell made from a single crystal or polycrystalline slice of silicon.
Current (Amperes, A) The flow of electric charge in a conductor between two points having a
difference in potential (voltage).
Diffuse Radiation Radiation received from the sun after reflection and scattering by the atmos-
phere and ground.
Diode Electronic component that allows current flow in one direction only. See Blocking Diode
& Bypass Diode
Direct Current (DC) Electric current flowing in only one direction.
Efficiency The ratio of output power (or energy) to input power (or energy). Expressed in per-
cent.
EVA (ETHYLENE VINYL ACETATE) An encapsulant used between the glass cover and the solar
cells in PV modules. It is durable, transparent, resistant to corrosion, and flame retardant.
Feed-in meter A grid-connected installation necessary in order to determine the energy that
has been fed into the grid.
Frequency The number of repetitions per unit time of a complete waveform, expressed in Hertz
(Hz).
Grid Term used to describe an electrical utility distribution network.
Grid Connected PV System A PV system in which the PV array acts like a central generating
plant, supplying power to the grid.
Inverter In a PV system, an inverter converts dc power from the PV array/battery to ac power
compatible with the utility and ac loads.
Irradiance The solar power incident on a surface. Usually expressed in kilowatts per square me-
ter. Irradiance multiplied by time equals Insolation.
Irradiation - The solar radiation incident on an area over time. Equivalent to energy and usually
expressed in kilowatt-hours per square meter.
I-V Curve The plot of the current versus voltage characteristics of a photovoltaic cell, module, or
array. Three important points on the I-V curve are the open-circuit voltage, short-circuit current,
and peak power operating point.
Joule (J) Unit of energy equal to 1/3600 kilowatt-hours.
Kilowatt (kW) One thousand watts. A unit of power.
Kilowatt Hour (kWh) One thousand watt-hours. A unit of energy. Power multiplied by time
equals energy.


39

ReGrid: Photovoltaics
Load The amount of electric power used by any electrical unit or appliance at any given time.
Load Current (A) The current required by the electrical device.
Maximum Power Point That point on an I-V curve that represents the largest area rectangle
that can be drawn under the curve. Operating a PV array at that voltage will produce maximum
power.
Maximum Power Tracking Operating the array at the peak power point of the array's I-V curve
where maximum power is obtained.
Multicrystalline Material that is solidified at such as rate that many small crystals (crystallites)
form. The atoms within a single crystallite are symmetrically arranged, whereas crystallites are
jumbled together. These numerous grain boundaries reduce the device efficiency. A material
composed of variously oriented, small individual crystals. (Sometimes referred to as polycrystal-
line or semicrystalline).
Off-grid system System living in a self-sufficient manner without reliance on one or more public
utilities.
Open Circuit Voltage The maximum voltage produced by an illuminated photovoltaic cell, mod-
ule, or array with no load connected. This value will increase as the temperature of the PV ma-
terial decreases.
Peak Watt The amount of power a photovoltaic module will produce at standard test conditions
(normally 1,000 w/m2 and 25 cell temperature).
Photovoltaic System An installation of PV modules and other components designed to produce
power from sunlight and meet the power demand for a designated load.
Semiconductor A material that has a limited capacity for conducting electricity. The silicon used
to make PV cells is a semiconductor.
Short Circuit Current (Isc) The current produced by an illuminated PV cell, module, or array
when its output terminals are shorted.
Stand-Alone PV System A photovoltaic system that operates independent of the utility grid.
Thin Film PV Module A PV module constructed with sequential layers of thin film semiconduc-
tor materials.
Tilt Angle The angle of inclination of a solar collector measured from the horizontal.
Transformer A device that transfers electrical energy from one circuit to another through induc-
tively coupled conductors.
Volt (V) The unit of electromotive force that will force a current of one ampere through a resis-
tance of one ohm.
Zenith Angle The angle between directly overhead and the line intersecting the sun. (90- ze-
nith) is the elevation angle of the sun above the horizon.



40

ReGrid: Photovoltaics



http://www.renac.de/en/projects/regrid/