User-Machine Interfaces SFT2841 Setting and Operating Software Welcome Window Presentation General Screen Organization Use of the Software Configuration of a Sepam Network UMI on Front Panel Presentation Advanced UMI Access to Data White Keys for Current Operation Blue Keys for Parameter and Protection Setting Data Entry Principles Default Parameter Setting Commissioning: Principles and Method
172 173 173 174 175 176 177 182 182 183 183 184 186 188 189 191 192 193 194 195 195 196 197 198 199 200 201 202 203 204
63230-216-208C1
171
Commissioning
Generators
b Sinusoidal AC current generator v 50 or 60 Hz frequency (according to the country) v Single-phase type, adjustable from 0 to 50 Arms v With connector suited to the built-in test terminal box in the current input connection diagram b Sinusoidal AC voltage generator v 50 or 60 Hz frequency (according to the country) v Single-phase type, adjustable from 0 to 150 Vrms v With connector suited to the built-in test terminal box in the voltage input connection diagram b DC voltage generator v Adjustable from 24250 V DC v For adaptation to the voltage level of the input being tested v With electric cord and clamps, wire grip or touch probes
Metering Devices
b 1 ammeter, 0 to 50 Arms b 1 voltmeter, 0 to 150 Vrms
Computer Equipment
b PC with minimum configuration v Microsoft Windows 98/XP/2000/NT 4.0 v 133 MHz Pentium processor v 64 MB of RAM (or 32 MB with Windows 98) v 64 MB free on hard disk v CD-ROM drive b SFT2841 software b CCA783 serial connection cord between the PC and the Sepam relay
Documents
b Complete connection diagram of Sepam and additional modules, with: v Phase current input connection to corresponding CTs via the test terminal box v Residual current input connection v Phase voltage input connection to corresponding VTs via the test terminal box v Residual voltage input connection to corresponding VTs via the test terminal box v Logic input and output connection v Temperature sensor connection v Analog output connection b Hardware BOMs and installation rules b All Sepam parameter and protection settings, available in paper format
192