Module and Application Description

PROCONTROL P
Input, Output Signal conditioning

Output Module for Analog Signals


Publication No. D KWL 6329 94 E, Edition 04/96 Replacing D KWL 6329 94 E, Edition 10/94

8fold, 0/4 to 20 mA

81AA03-E/R1210
Signal input from the PROCONTROL bus
All telegrams transmitted on the station bus are received by the module via its standard interface. Transfer takes place seri ally. The processing section therefore performs a serial/parallel conversion of the data. The module is able to receive telegrams with the following ad dress information: - System address - Station address - Module address - Register address 0 ... 3 1 ... 249 0 ... 58 0 ... 255

Application
The output module is used to output analog signals in the signal ranges 0 to 20 mA or 4 to 20 mA. The module contains 8 function units. It is thus possible to out put 8 different analog signals simultaneously.

Features
The module can be plugged into any PROCONTROL station. It incorporates a standard interface to the PROCONTROL station bus. The signals to be outputted are received by the unit in the form of telegrams from the PROCONTROL bus system via the station bus. The telegrams are checked for error-free transfer by means of the parity bits before being outputted. Digital-to-analog conversion is performed with a 12-bit res olution. The analog signal outputs are short-circuit-proof and pro tected against mutual interference. They have a common refer ence conductor. The analog inputs are isolated from the mod ule's internal voltage and from the PROCONTROL bus. Within the module, the signals are transferred to the outputs via optocouplers. The output signals can be simulated individually. Whenever an internal monitoring circuit responds, this is indi cated on the module's front panel by an SG (module distur bance) and an ST (general disturbance) disturbance annun ciation.

Based on its programming, the processing section determines which telegrams are to be evaluated and assigns the analog values to the appropriate memory location in the output regis ter (see Data communication with the module").

Receive monitoring
The module is provided with a time monitoring feature which supervises the incoming telegrams for proper cyclic renewal. If any of these telegrams is missing (e.g. due to failure of the send module), the module responds as follows: - It sets the disturbance bit of the received input value. This results in the analog output being set on the AP03 function block in accordance with the setting for disturbance bit eval uation. - The Receive monitor responding" bit is set in the diagnosis register, and the ST fault lamp lights up.

81AA03/R1210

Operating modes
Function blocks The function blocks listed below are provided on the module for outputting analog signals. The abbreviated type designa tion is given for each function block. Function block Text element including specification of operating mode Outputting through analog process outputs Selection of operating mode When selecting the module's operating mode via the TXT1 function block, STR (binary control) is the only option per mitted. Output ranges The following output ranges may be configured with the AP03 function blocks (output function blocks for analog process out puts) for each function unit: 0... 100 % = 0... 20 mA (standard setting) 0... 100 % = 4... 20 mA If the output signal exceeds the output range specified, the current signal outputted will be increased accordingly until the current limitation feature intervenes at approximately 23 mA. Allocating the outputs of the function units Any one of the module's analog outputs can be allocated by the user to the output of any AP03 function block. Abbreviation TXT1 AP03 Structuring the analog signal outputs Structuring is performed by means of appropriate user specifi cations for the AP03 function blocks. The AP03 function block permits: - Signal expansion, i.e., linear mapping of an input value range AS ... ES to the output value range 0 ... 100 %. AS = Beginning of the expansion range, i.e., the input value which is mapped to the output value 0 %. ES = End of the expansion range, i.e., the input value which is mapped to the output value 100 %. - Setting of the output ranges 0 ... 20 mA or 4 ... 20 mA. - Disturbance evaluation, if the disturbance bit of the received input signal has been set. The cycle time needed for processing the defined structure is determined by the module and entered into the module regis ter 205. Simulation of output signals The output signals can be simulated individually via the PDDS (EDS). In the simulation mode, the processing section substitutes the simulated values for the values received from the bus during normal operation. As soon as the simulation is stopped via the PDDS (EDS), the module again uses the values transmitted over the bus.

81AA03/R1210

Data communication with the module


Signal allocation The addresses of all telegrams whose data are to be outputted are programmed in the module. This enables the module to determine (by comparing the addresses) which of the data telegrams received have to be processed. The allocation of the individual converted signals to the module outputs at which they are to be made available is also programmed. It is pos sible to allocate the same signal to several module outputs. To enable the output module to be addressed individually (e.g. for simulating an output signal), it is given a unique address. The system and station addresses are identical for all modules contained in the same PROCONTROL station. They are set collectively and automatically on the modules via the station bus control module. The module address is set automatically when the module is plugged into the appropriate slot in the PROCONTROL station.

Diagnosis and annunciation functions


Disturbance annunciations on the module Disturbances are indicated on the module's front-panel by red LEDs: - Disturbance - Module disturbance ST SG

The "ST" LED indicates all module disturbances, as well as disturbances occurring in data communication with the mod ule. The "SG" LED indicates module disturbances. Disturbance signals transferred to the annunciation sys tem The alarm annunciation system and the control diagnosis sys tem (CDS) receive disturbance annunciation signals from the output module via the bus. Diagnosis The incoming telegrams, the generation of telegrams to be transmitted and internal signal processing are monitored for errors in the processing section of the module (self-diagno sis). In the event of a disturbance, the type of disturbance is filed in the diagnosis register and, at the same time, a disturbance an nunciation is sent to the PROCONTROL system. When requested, the module transfers a telegram with the data stored in the diagnosis register (register 246). The contents of the diagnosis register, the annunciations trans mitted over the general disturbance line, the annunciations on the CDS, and the ST annunciation are shown in Fig. 1. The annunciation "Parameter fault" may appear in the diagno sis register for the following reasons: - Limits of expansion range (inputs AS and ES of function block AP03) not plausible. The annunciation "Processing fault" may appear in the diagno sis register for the following reasons: - No valid structure list. - Disturbance of internal module voltages. - Hardware disturbance on the module. The annunciation "Process channel fault" may appear in the diagnosis register for the following reasons: - Disturbance of internal module voltages. - Hardware disturbance in the process section.

81AA03/R1210

Module operating Diagnosis register 246 Bit Type 15 S 14 S 13 S 12 S 11 0 10 S 9 D 8 S 7 0 6 0 5 0 4 S 0 3 S 2 0 1 0 0 CDS messages *) Parameter fault Process channel fault Processing fault Checksum error detected Timer defective Module restart executed Bus deactivation defective 6615 6600 6601 6602 6604 6605 6606

Receive monitoring responded Event mode fault

6610 6612

ST Module not operating Wrong firmware PROM Hardware defect of processing section EEPROM not valid Processing initialization active Module not accessible from bus Module transmitter disconnected by bus control module Module address not within 0-58 Hardware defect of bus interface SG

1

1

SST

1

SSG

D = Dynamic annunciations are cancelled after the contents of the diagnosis register has been transmitted S = Static annunciations disappear automatically upon deactivation 0 = Not used

Figure 1: Diagnosis messages of 81AA03

*) The control diagnosis system (CDS) provides a description for every message number. This description comprises: - Information about cause and effect of the disturbance - Recommendations for its elimination. This makes for fast elimination of disturbances. 4

Station bus
SS

USB USA Z

ZD ZD ZD SRA *

X11 d30 d32 b32 z32 b02 b14 d26 d18

81AA03-E/R1210

Terminal designations

Function diagram

The PCB is equipped with the connectors X11 and X21.

+ Parallel/serial conversion Interface Operational functions User functions EEPROM User functions RAM Multiplexer Digital/ analog converter
u i i i u u i u i u z20 z18 z16 z14 z12 z10 z08 z06 z04 z02 Z5 Z4 Z3 Z2 Z1 AA5 AA4 AA3 AA2 AA1

Processor

Shared memory

81AA03/R1210

Connector X21 contains all process inputs and outputs. Connector X11 contains the station bus connection and the operating voltages USA and USB.

* To ensure proper functioning of the module, terminal X11/d18 has to be connected to ZD (one connection per rack).

z32

z30

z28

z26

z24

z22

X21

Z8

Z7

Z6

AA8

AA7

AA6

81AA03/R1210

Mechanical design
Board size: Connector: 6 units, 1 division, 160 mm deep to DIN 41612 1 x for station bus connection, 48-pole, edge connector, type F (connector X11) 1 x for process connection, 32-pole, edge connector, type F (connector X21) Weight: approx. 0.55 kg

Contact assignments for process connector X21

View of contact side:

b 02 04 06
X 11

z AA1 Z1 AA2 Z2 AA3 Z3 AA4 Z4 AA5 Z5 AA6 Z6 AA7 Z7 AA8 Z8

View of connector side:

08 10 12 14 16 18 20 22 24

X 21

26 28 30 32

81AA03/R1210

Side view and front panel

ABB
ST Disturbance

 X11

ST

SG

SG Module disturbance

X21

ABB
81AA03

 EPROM programmed, Order number: GJR2394141Pxxxx

xxxx = Position number indicating applicable software version.

81AA03/R1210

Technical data
In addition to the system data, the following values apply: Power supply Module operating voltage, USA/USB Current consumption with USA/USB = 24 V Current consumption with USA/USB = 30 V Power dissipation with USA/USB = 24 V Power dissipation with USA/USB = 30 V Reference potential ZD, bus section Reference potential Z1 ... Z8, process section Potential isolation between process section and bus section Output values Output current (impressed current), nominal signal range Max. load impedance Outputs Overrange current Accuracy Accuracy, referenced to 100 % of the signal value 20 mA on delivery (23 C) due to effects of temperature, ageing, voltage range v 0.1 % v 0.4 % v 0.02 % v 0,1 % < 50 ppm/K (typ. 30 ppm/K) 12 bits 12 bits 0/4 ... 20 mA v 500 W short-circuit and open-circuit-proof 23 mA max. 19.5 ... 30 V, typ. 24 V 160 mA + output current @ 1.0 140 mA + output current @ 0,8 3.9 W + output current @ 24 V @ 1.0 4.2 W + output current @ 30 V @ 0.8 0V 0V 500 V

Quantizing error Linearity error Response to temperature changes Resolution, at 0 ... 20 mA at 4 ... 20 mA Processing time For complete module For the first function unit For each further function unit, additionally Initialization time Upon connection of supply voltage or plugging in the module Noise immunity (of the process outputs) ESD acc. to IEC 801/2 EMC acc. to IEC 801/4 Destruction acc. to IEC 801/5, Draft: IEC TC 65 (Sec) 137

v 95 msec incl. expansion v 25 msec v 10 msec

1 ... 22 sec

8 kV to front panel 1 kV burst 1 kV to reference potential

ORDERING DATA Order number for complete module: Type designation: 81AA03-E/R1210 Technical data are subject to change without notice! Order number: GJR2394100R1210

81AA03/R1210

ABB Kraftwerksleittechnik GmbH P . O. Box 100351, D-68128 Mannheim Phone (0621) 381 2712, Telefax (0621) 381 4372 Telex 462 411 107 ab d
Printed in Germany (DEPPC/R21 0496 0,3 BID)