Plumbing sizing

OFFICER&NCO BUILDING

ANA KANDAK, AFGHANISTAN

OBJECTIVE:
The objective of this report is to calculate water, sewer pipes and electric water heater sizing of OFFICER&NCO building in Kandak Afghanistan.

BUILDING COMPONENTS:
The building is a one floor barracks building

6 water closets. 6 ablutions in two lavatories 6 showers 1 janitor sink

Water pipe Sizing: The size of the water pipes is calculated according to IPC 2006, each section is labeled as shown below and calculated using the below tables 604.3, E103.3(2), E103.3(3), E103.3(4), E103.3(5), E103.3(6), figure 103.3(6). All fixtures are considered as public use WC: Water closet LAV: Lavatory SH: Shower JS: Janitor sink

Hot-Water Demand per Fixture (ASHRAE Handbook-HVAC Applications) XX (User entered data) EWH-0x (Based On the Table Titled, "Hot Water Demand per Fixture for Various Types of Buildings" for "Office Building," Final Temperature: 140 F) Water heater entering water temperature = 50.0 F 10.0 C Water heater leaving water temperature = 140.0 F 60.0 C DEMAND FACTOR = STORAGE CAPACITY FACTOR = 2.00 Fixture Qty. Basin, public lavatory Kitchen Sinks Showers Washers Laundry Sinks Janitor Sink Ablutions Service Sinks 0 0 6 0 0 1 6 0 (gph) 0.00 0.00 30.00 0.00 0.00 20.00 6.00 0.00 Total (gph) 0 0 180 0 0 20 36 0 0.30

Maximum possible demand = Probable maximum demand = BASIC WATER HEATER SIZE FROM ASHRAE CALCULATIONS Storage tank capacity = Heater element capacity = Sum of element capacities =

236 gph 70.8 gph 71 gph 15.6 kW 142 gal 536 l

Tank usable water before dilution = Storage tank usable capacity =

80 % 113 gal 536 l

Total usable water per hour =

184 gal

ADJUSTED WATER HEATER SIZE FROM EQUIPMENT SCHEDULE. NOTE: DECREASING HEATER ELEMENT CAPACITY WILL INCREASE TANK SIZE.

Sum of element capacities (kW) = Heater or coil capacity =

15.0 kW 68.2 gph

Storage tank capacity =

145 gal 548 l

Tank usable water before dilution = Total usable water per hour =

80 % 184 gal

The results are shown in the following table which is done according to E103.3 (1)

1
description

4
length (ft)

5
Pipe size ('')

6
equivalent length of valves and fittings (ft)

7
total equivalent length col.4 and col.6 (100ft)

8
friction loss per 100ft of pipe selected

9
friction loss in equivalent length col.8 X col.7 (PSI)

10 excess pressure over friction losses (PSI)

A B C D E F G H I service and cold water distribution piping

Minimum pressure available at main Highest pressure required at fixture (Table604.3) Meter loss 2.00 meter . . . Tap in main loss 2.0 tap (Table E103A) Static head loss 1.5 X 0.43 Special fixture loss backflow preventer Special fixture lossFilter Special fixture lossOther Total overall losses and requirements (Sum of Lines B through H) Pressure available to overcome pipe friction (Line A minus Lines B to H) AB BC CD DE EF FG GH HI IJ Total pipe friction losses (cold) Difference ( Line J minus Line K)

36.75 15 0 0.18 0.65 0 0 0 15.83

20.92 FU 78 78 42 12 10 8 6 4 2 40.56 40.56 29.32 15.65 14.34 12.92 11.32 9.47 7.13 2.56 10.17 1.09 18.14 1.57 1.57 2.76 1.61 1.41 2.00 2.00 1.50 1.50 1.50 1.00 1.00 1.00 0.75 6.00 0.50 0.50 6.50 0.50 0.00 0.00 0.00 2.00 0.09 0.11 0.02 0.25 0.02 0.02 0.03 0.02 0.03 1.57 1.57 1.04 1.09 0.85 4.11 4.11 2.93 10.60 0.13 0.17 0.02 0.27 0.02 0.06 0.11 0.05 0.36 1.19 19.73

K L

Designation Pipe section (from diagram) Cold water Distribution piping

Required pressure at water supply: 2.5 Bar

GPM

line

PSI

FOR THE REST WATER LINES:


By using (PLUMPING CODE)" "Equivalent Fixture Units" to compute the hot and cold water demands for fixtures:

For shower (106): FIXTURE SH SP JS TOTAL F.U For water closets: FIXTURE WC TOTAL F.U NO. OF FIXTURE 6 F.U 5 T.F.U 30 30 37.5 DIAMETER OF PIPE(mm) NO. OF FIXTURE 6 6 1 F.U 4 2 2 T.F.U 24 12 2 38 37.5 DIAMETER OF PIPE(mm)

WATER HAMMER ARRESTOR TYPE (WHA). Cold water line T.F.U = 6WCX5F.U+6ABX1.5F.U = 39 F.U. Use WHA type C. Hot water line T.F.U = 6ABX1.5F.U = 9 F.U. Use WHA type A.

Drainage pipe sizing:

The size of the drain pipes is calculated according to IPC 2006, using TABLE 709.2, TABLE 709.1, and TABLE 710.1(1)

Latrines JS TOTAL 1 SH 6 WC 6 Ablution 0 FLOOR DRAIN 8 Total (FU) 55 Main pipe size 2 inches

For first floor: FIXTURE SHOWERS FLOOR DRAINS WATER CLOSET JANITOR SINK NO. OF FIXTURE 6 8 F.U 2 2 T.F.U 12 16

24

TOTAL

55

Vent Pipe Sizing: The size of the Vent Pipe is calculated according to IPC 2006, using TABLE 916.1 NO. of Fixture 3+2 2+2 1 1+2+ 3 3+1 1 LENGTH DIAMETER (ft) (mm) 11.5 27.2 11.5 19 11.5 11.5 50 50 50 32 32 32

FIXTURE 3WC+2FD 2WC+2FD 1WC 1JS+2FD+3SH 3SH+1FD 1FD

F.U 4+2 4+2 4 2+2 +2 2+2 2 2+4 +2+ 3

T.F.U 16 12 4 12 8 2

8FD+6WC+6SH +1JS

8+6+6+ 1

55

50

Roof Drain Sizing: FOR ZONE1 The size of semicircular roof gutters is calculated according to IPC 2006, using TABLE 1106.6

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF ROOF GUTTER (inches)

91

480

1% 4

The size of vertical conductors and leaders is calculated according to IPC 2006, using TABLE 1106.2

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF LEADER (inches)

91

480

1% 3

FOR ZONE2 The size of semicircular roof gutters is calculated according to IPC 2006, using TABLE 1106.6

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF ROOF GUTTER (inches)

91

505

1% 4

The size of vertical conductors and leaders is calculated according to IPC 2006, using TABLE 1106.2

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF LEADER (inches)

91

505

1% 3

FOR ZONE3 The size of semicircular roof gutters is calculated according to IPC 2006, using TABLE 1106.6

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF ROOF GUTTER (inches)

91

530

2% 4

The size of vertical conductors and leaders is calculated according to IPC 2006, using TABLE 1106.2

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF LEADER (inches)

91

530

2% 3

FOR ZONE4 The size of semicircular roof gutters is calculated according to IPC 2006, using TABLE 1106.6

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF ROOF GUTTER (inches)

91

423

1% 4

The size of vertical conductors and leaders is calculated according to IPC 2006, using TABLE 1106.2

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF LEADER (inches)

91

423

1% 3

FOR ZONE5 The size of semicircular roof gutters is calculated according to IPC 2006, using TABLE 1106.6

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF ROOF GUTTER (inches)

91

390

1% 4

The size of vertical conductors and leaders is calculated according to IPC 2006, using TABLE 1106.2

RAINFALL RATE (mm\h) HORIZONTALLY PROJECTED ROOF AREA (square feet) SLOPE DIAMETER OF LEADER (inches)

91

390

1% 3