You are on page 1of 48

Models FSVN FSN FXN 8.

0 118 kW
SET FREE VRF

free
R410A

set

Variable refrigerant flow air conditioning systems

Contents
Company profile Product range overview Features and benefits Indoor units Total heat exchanger Outdoor units Control systems Optional parts Hi-Toolkit Set-Free Multimedia 4 6 8 12 28 30 38 43 45 46

Air Conditioning from HITACHI can justifiably be described as the art of exploiting the latest ideas and developments in technology to create a range of innovative products which provide a more comfortable and more productive environment in which people can happily live and work. It is also an art executed with a responsible concern for protecting the environment. Ecological thinking begins at the very first stages of new product design and continues throughout production, installation procedures, equipment and operation. Specifiers and users alike can always be assured that performance and costs are not the only parameters by which HITACHI products can be judged. To achieve success with such objectives on a global scale requires not only enormous resources but also a commitment to the future. As one of the largest companies in the world, with over 347,424 employees, HITACHI is well positioned to undertake this commitment with confidence that comes from successfully responding to the changing needs of people for over 90 years.

worldwide. In 1993 HITACHI invested in a new purpose built, state of the art factory (HAPE) in Barcelona, Spain. The site of the factory was carefully chosen to accommodate further building on its 40,000 square meter site. The creation of a European manufacturing facility and customer training centre helps reduce production costs, speed up delivery times and enables full support to be given to all customers. HITACHIs advanced air conditioning products are specified all over the world, wherever there is a requirement for ultimate performance and cost effective, long term reliability. A wide range of units coupled with a choice of advanced control systems mean HITACHI can provide solutions to meet every possible air conditioning application or specification. Authorised Distributors all over the world contribute their own specialised technical support and practical assistance to provide individual system designs, commissioning and after sales service. HITACHI Authorised Distributors are committed to providing an unrivalled support from a combination of experienced engineers, local product and spare parts stock,

Hitachi Air Conditioning Products Europe HAPE works, Spain

Company profile
HITACHI in Japanese the name means sunrise is at the forefront of research and development turning new ideas and innovations into new products. Of its $80.9 billion sales worldwide in 2005, close to 4.3% was invested in research and development programs. This vast amount of money has given HITACHI the opportunity to conceive many world firsts examples of which include the technologically advanced and acclaimed scroll and semi-hermetic Screw compressors. These have been incorporated in HITACHIs air conditioning systems and water chillers which have revolutionised air conditioning supported in turn by on-going technical support from HITACHI. From the initial product concept at HITACHIs research and development facility in Japan, product development is dedicated to providing the products the customer requires. Product design and development is continuous with priority being given to the use of ecologically friendly refrigerants. To satisfy your cooling and heating requirements and to ensure the optimum indoor environment, consider HITACHI the first and last word in air conditioning.

Hitachi Appliances, Inc. Shimizu works, Japan

Hitachi Air Conditioning Products (M) HAPM works, Malaysia

Hitachi Air Conditioning Products Europe (HAPE works, Spain) has acquired International Standard Quality Management System ISO9001 & ISO 14001 authorisation. HAPE performs thorough product quality control using various environmental tests. Hitachi Set Free Series Indoor units and panels are manufactured according to this ISO certification system.

Hitachi Appliances, Inc. (Shimizu works, Japan) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. Shimizu works perform thorough product quality control using various environmental tests, severe heating testing for compressors, and many others. Hitachi Set Free Series Outdoor units are manufactured according to this ISO certification system.

Hitachi Air Conditioning Products (M) Sdn.Bhd (HAPM works, Malaysia) has acquired International Standard Quality Management System ISO9001 and ISO14001 authorisation. HAPM perform thorough product quality control using various environmental tests. Hitachi Set Free Series RPK Indoor units are manufactured according to this ISO certification system.

Quality control

Product range overview


Hitachis range of Set Free Variable Refrigerant Flow systems has developed significantly in recent years following a great deal of investment in research and testing facilities at Hitachis factories and laboratories. Hitachi has continuously developed sophisticated energy-saving air conditioning systems that reduce CO2 emissions and protect the global environment. The latest offering from Hitachi is the Set Free FSN1 series featuring high energy-saving, easy installation and compact size for next generation buildings. Newly developed, highly efficient 2 blade Fan High efficiency DC Inverter fan module High efficiency DC Inverter Compressor Vector Control DC Inverter High efficiency constant speed compressor Large capacity DC Fan Motor Newly developed, energy saving heat exchanger Supercooling circuit adopted

Indoor Units
Capacity Range [HP]

0.8

1.0
+

1.3

1.5
- +

1.8

2.0
-

2.3

2.5
- +

2.8

3.0

4.0

5.0

6.0

8.0 10.0

In-the-Ceiling Mini In-the-Ceiling Mini 4-Way Cassette


-

4-Way Cassette
- + - + - +

2-Way Cassette Wall Ceiling Floor-Standing Floor-Concealed

- +

- +

- +

- +

- +

- +

- +

- +

- +

- +

- +

- +

Capacity available with dip switch setting


- +

Adjustable by dip switch setting

Outdoor Units
Capacity Range [HP]

10

12

14

16

18

20

24

28

30

32

36

42

RAS-FSVN Series RAS-FSN Series RAS-FXN Series

RAS-3FSVN(E)

RAS-4FSVN(E) RAS-5FSVN(E)

RAS-5FSN/FXN

RAS-8FSN1(E)/FXN(E) RAS-10FSN1(E)/FXN(E) RAS-12FSN1(E)/FXN(E)

RAS-14FSN1 RAS-16FSN1

RAS-16FXN RAS-18FSN1/FXN RAS-20FSN1/FXN

RAS-24FSN1/FXN RAS-28FSN1 RAS-30FXN RAS-32FSN1/FXN

RAS-36FSN/FXN RAS-42FSN/FXN

System Equipment
Capacity Range [m3/h]

250

500

800

1,000

Total Heat Exchanger

High COP
Performance is greatly improved by the high-efficiency, high pressure, inverter driven scroll compressor. Reliability greatly improved by optimised bearing Intake loss and leakage loss largely reduced by asymmetric scroll lap Heat loss largely reduced by oil return structure Accurate oiling to the compressor by improved oiling system Supercooling circuit Performance improved by high-efficiency plate type of heat exchanger
Effect of subcooler

Rotor shape optimized

Neodymium magnet used High-efficiency motor

[C]

95

DC motor AC motor

Peculiar electromagnetic noise to DC compressor cut

Efficiency increased across entire range of rpm used

Compressor rotor

70

2,000

rpm

4,000

6,000

DC Compressor By using DC, the performance is improved at around 30 - 40Hz where the operation time of the inverter compressor is longest. Also, to suppress electromagnetic noise interference and achieve low noise, the rotor has been divided into two and the electric pole displaced.

Refrigerating ability increased by supercooling circuit

Features and benefits

Typical construction example of a conventional system


2 outdoor units installed

SET-FREE FSN Series

Power source, grounding wire

Integral type unit for all product series


All units are assembled and tested at Hitachi factories therefore minimising problems at installation stage.

Transmission line

Power source, grounding wire, transmission line, connecting wire


Power source, grounding wire

Outdoor connecting pipes (gas, liquid)


Gas pipe Gas pipe Liquid pipe

Outdoor connecting kits (gas, liquid)


: Areas where no installation is required in the new series

Liquid pipe

Transmission line

Increased COP and EER

2-Blade Fan
Hitachi unique patented design Noise is reduced by decreasing the number of blades to 2 The length of each blade is longer, increasing air quantity by 25% Motor input decrease by 8%

Increased flexibility in project design


Conventional model
Outdoor unit capacity Min. capacity of indoor units connectable Max. number of indoor units connectable

SET-FREE FSN
Min. capacity of indoor units connectable Max. number of indoor units connectable

5 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 24 HP 28 HP 30 HP 32 HP
( )

0.8 HP 0.8 HP 0.8 HP N/A N/A 1.0 HP N/A 1.0 HP 1.0 HP N/A 1.0 HP N/A

8(8) 13(13) 16(16) N/A N/A 16(16) N/A 16(16) 27(12) N/A 32(12) N/A

0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP 0.8 HP

8 13 16 16 20 20 20 20 27(20)* 31(24)* 32(26)* 32(27)*

Only for 0.8 HP indoor unit maximum connecting number.

Indoor unit selection is easier as the minimum capacity and the maximum number of indoor units to be connected are increased to match the indoor load.

More flexible refrigerant construction conditions


Improved flexibility of design by increasing the pipe length to 150 m max. (equivalent length of 175 m) in FSN series.

Expansion of Operation Range


Can be used with outdoor air temperatures down to -200C

1 Max. pipe length: 150 m 2 Between first branch and indoor unit: 40m or less 3 Height difference between highest and lowest indoor units: 15m or less 4 Height difference between outdoor and indoor units: 50m* 3 1 2

[C] 50
4

RAS-FSG
43C

RAS-FSN1
43C

40 30 20 10 0 -10 -20

15C -5C -15C -5C

15C

-20C

* In case the outdoor unit is installed at a higher level than indoor units.

If the outdoor unit is installed lower than indoor units, the maximum height difference is 40m.

Features and benefits


Improved Demand Control
Control is optimised to suit each customers air conditioning environment.

Cut by external signal


External signal Power consumption Power consumption Cut

NEW Cut by internal signal


Power consumption

NEW

Wave function

Cut

Cut

Time specified Time Construction needed in advance Time Power Cut according to site conditions Cut by time control Minimising capacity down Time

High Static Pressure, Long Duct Bell Mouth


Fan motive energy is reduced by combining with a highefficiency fan External static pressure of 60 Pa as standard

Table 1 : Outdoor Unit 1st Multi-Kit If the equivalent piping length is less than 100m, use the following pipe size:
Pipe size ( Unit RAS-5FSN RAS-8FSN1E RAS-10FSN1E RAS-12FSN1E RAS-14FSN1 RAS-16FSN1 RAS-18FSN1 Gas
5 3 7 7 7

mm) Multi-kit Liquid


3 3 3 1 1 1 5 5 5 3 3 3 3

/8 /4 /8 /8 /8

/8 /8 /8 /2 /2 /2 /8 /8 /8 /4 /4 /4 /4

E-102SN E-102SN E-102SN E-162SN E-162SN E-162SN E-242SN E-242SN E-242SN E-302SN E-302SN E-302SN E-302SN

11/8 11/8 11/8 11/8 11/4 (13/8) 11/4 (13/8) 11/2 11/2

Refrigerant piping connections


In an outdoor unit piping connections are easily conducted from any three directions: front, rear or downwards

RAS-20FSN1 RAS-24FSN1 RAS-28FSN1 RAS-32FSN1 RAS-36FSN RAS-42FSN

In case that the equivalent piping length is more than 100m use the following pipe size:
Pipe size ( Unit RAS-5FSN RAS-8FSN1E RAS-10FSN1E RAS-12FSN1E RAS-14FSN1 RAS-16FSN1 RAS-18FSN1 RAS-20FSN1 RAS-24FSN1 RAS-28FSN1 RAS-32FSN1 RAS-36FSN RAS-42FSN Gas
3 7

mm) Multi-kit Liquid


1 1 1 5 5 5 3 3 3 7 7 7 7

/4 /8

/2 /2 /2 /8 /8 /8 /4 /4 /4 /8 /8 /8 /8

E-102SN E-102SN E-162SN E-242SN E-242SN E-302SN E-302SN E-302SN E-302SN E-302SN E-302SN E-302SN(*) E-302SN(*)

11/8 11/8 11/8 11/4 (13/8) 11/4 (13/8) 11/4 (13/8) 11/4 (13/8) 11/2 (15/8) 11/2 (15/8) 13/4 13/4

* please refer to applications department

The pipe size must be the same as the piping connection hole of the Outdoor Unit. Table 2 : 1st Multi-Kit Last Multi-Kit
Total Capacity of Indoor Units HP<16 6< _HP<9 9< _HP<13 13< _HP<16 16< _HP<18 18< _HP<26 26< _HP<36 36< _HP<42 42< _HP Pipe size ( Gas
5 3 7

mm) Multi-kit Liquid


3 3 3 1 1 5 3 3 3

/8 /4 /8

/8 /8 /8 /2 /2 /8 /4 /4 /4

E-102SN E-102SN E-102SN E-162SN E-162SN E-242SN E-302SN E-302SN E-302SN

11/8 11/8 11/8 11/2 11/2 11/2

11

Set Free RPIM Technical Description


Installation New design Requires minimum installation space Greater noise reduction The new RPIM units have been designed specifically for situations where only a reduced installation space is available. This is possible due to the positioning of the piping and electrical work which means no space is required from the sides of the units: Left Side Sling Bolts

Suspension Bracket

Bolts Sling Bolts

Right Side Suspension Bracket Servicing In order to benefit from the minimum required installation space, access to the electrical box and refrigerant piping is enabled from the suction air side of the unit for easy maintenance. Following the same concept as the refrigerant piping and electrical box, drain piping connection work is also easily accessible from the suction air side of the unit. The RPIM is fitted with a new type of air filter to allow for easy maintenance even with an installed air duct.

Mini In the ceiling


Noise Reduction Resulting from an accurate study of airflow distribution, turbulence reduction and an improved fan unit, the new RPIM unit focuses specifically on reduced noise which makes it an excellent option for installations that require a very low noise level or extremely quiet indoor unit. Static Pressure RPIM units have been provided with 2 Static Pressure levels regulations: Low static pressure (factory setting for standard installations without an air duct). High static pressure (Optional setting where an air duct installation is necessary).

General Data
Model Power Supply Nominal Cooling Capacity kW Nominal Heating Capacity kW Indoor Fan
Air Flow Rate (Hi/Me/Lo) (SP-00) m3/min

RPIM-0.8 FSN1E AC 1, 230V 1~ 50Hz 2.2 2.5

RPIM-1.0 FSN1E

2.8 3.2

8/8/6

8/8/6

Static Pressure
Level 2 Level 1

mmAq mmAq W

45/30 10/5 25

45/30 10/5 25

Fan Motor (Output)

Sound Pressure Level (overall A scale)


SP(Low) High/Low

dB(A)

31/27

31/27

Outer Dimensions
Height Width Depth

mm mm mm kg

274 702 600 30 R410A (Nitrogen-Charged in factory for Corrosion-Resistance) Flare Nut Connection (with Flare Nuts)

274 702 600 30

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

mm(in.) mm(in.) mm

6.35(1/4) 12.7( /2) 25 DE


1

6.35(1/4) 15.88(5/8) 25 DE

Approximate Packing Measurement Standard Accessories Remote Control SW m3 0.5 Air Filter PC-P2HTE 0.5

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the SET FREE system, and is base in JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB 19C WB Outdoor Air Inlet Temperature: 35C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB 7.0 C WB Outdoor Air Inlet Temperature: 6.0 C DB Pipe Length: 7.5 meters Pipe Height: 0 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The sound pressure level is based on the following conditions: 1.5 meters beneath the unit (no ceiling under the unit), 1m from suction duct and 2m from discharge duct. Voltage of the power source is 380V. In case of the power source of 240V, the sound pressure level increases by about 1dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

13

Set Free RPI Technical Description

Slim design Slim design Adjustable fan speed Adjustable static pressure Drain Pump as standard Air Filter as standard
197mm Minimum 5mm

Less than 197mm in height, this unit can be fitted practically any existing false ceiling or formerly ducted space, without substantial modification.

120mm

False Ceiling (0.8 ~ 1.5HP)

Broader range of external static pressure up to 150 Pa. Flexibly supports a wide range of installation conditions at site, e.g. longer ducts. Increased flexibility and extended ducting now available, provides full temperature control even to remote areas. Adjustable air flow and fan speed control. Wide selection Full line-up from model 0.8HP to 6.0HP. Drain-up mechanism Drain-up mechanism is built in the units as standard.

In the ceiling

An electronic sensor monitors the water level and automatically activates the pump when draining becomes necessary. Return Air (2.0-6.0HP) Available as bottom or rear entry. Suction filter equipped as standard New RPI unit is equipped with a filter as standard.

Econofresh Kit
As part of the Set Free range the Econofresh can provide up to 100% fresh air and has the ability to provide free cooling via dampers when the outdoor ambient temperature is below the temperature required indoors. Available for 5.0HP unit.

General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Air Flow Rate
Rated Low

RPI-0.8 FSN1E

RPI-1.0 FSN1E

RPI-1.5 FSN1E

RPI-2.0 FSN1E

RPI-2.5 FSN1E

RPI-3.0 FSN1E

RPI-3.5 FSN1E

RPI-4.0 FSN1E

RPI-5.0 FSN1E

RPI-6.0 FSN1E

RPI-8.0 FSNE

RPI-10 FSNE

AC 1, 230V, 50 Hz kW 2.2 2.8 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0

kW m3/min m /min mmAq mmAq mmAq W dB (A) mm mm mm kg


3

2.5 8 7 4 2.5 40 34/31 197 1020 574 33.5

3.2 8 7 4 2.5 40 34/31 197 1020 574 33.5

5.0 10 9 4 2.5 55 35/32 197 1020 574 33.5

6.3 16 13 8 5 2 65 33/29 274 1074 643 43

8.5 19 15 8 5 2 65 35/30 274 1074 643 45

9.0 22 17 12 8 4 150 35/31 274 1074 643 45

10.0 22 17 12 8 4 150 35/31 274 1074 643 45

12.5 30 28 12 8 2 225 37/35 274 1464 643 51

16.0 35 31 12 8 2 225 39/36 274 1464 643 52

18.0 36 32 12 8 2 385 40/39 274 1464 643 52

25.0 66 58 22 18 1250 54/51 475 1580 600 85

31.5 75 67 22 18 1250 55/52 475 1580 600 87

Static Pressure
Level 3 Level 2 Level 1

Fan Motor (Output)

Sound Pressure Level (Overall A Scale)


High/Low

Outer Dimensions
Height Width Depth

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

R410A (Nitrogen Charged in Factory for Corrosion-Resistance) Flare Nut Connection (with Flare Nuts) mm(in.) mm(in.) mm m3 6.35(1/4) 12.7( /2) 32 0D 0.16
1

Brassed connection 9.53(3/8)


5

6.35(1/4) 12.7( /2) 32 0D 0.16


1

6.35(1/4) 12.7( /2) 32 0D 0.16


1

6.35(1/4)
5

9.53(3/8)
5

9.53(3/8)
5

9.53(3/8)
5

9.53(3/8)
5

9.53(3/8)
5

9.53(3/8) 9.53(3/8) 25 0D 0.50 25 0D 0.50

15.88( /8) 15.88( /8) 15.88( /8) 15.88( /8) 15.88( /8)* 15.88( /8)* 15.88( /8)* 19.05(3/4) 22.20(7/8) 32 0D 0.36 32 0D 0.36 32 0D 0.36 PC-P2HTE 32 0D 0.36 32 0D 0.48 32 0D 0.48 32 0D 0.48

Packing Measurements Remote Control switch

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

*R410A (Std. Accessory pipe to be used)

2. The Sound Pressure Level is based on the following conditions: 1.5 meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

Model Combined Indoor Unit Model Outer Dimensions


Height Width Depth

EF-5GE RPI-5FSN1E

mm mm mm Kg

254 1350 + 59 270 12.5 1

Net Weight Damper Motor Quantity Approximate Packaging Measurement Standard Accessories

m3

0.13 Fresh Outdoor Air Inlet Thermistor

15

RCIM Technical Description

Features Quiet Operation Compact Size Improved Flexible Piping Uniform square panel size for 600 x 600 ceiling Panel sizes are standardised to a 700mm square to facilitate the installation in grid ceiling. European standard module is 600mm. Compact, thin and weight can be installed in a small space The height of the units is just 295mm, and weight is 17Kg and so they can be installed in a reduced space inside a false ceiling. Quiet operation By employing DC motor the electromagnetic noise is reduced. The following table lists air flow rates for RCIM.
RCIM-1.5FSN Air Flow Rate Hi Medium Low 38 35 33 RCIM-2.0FSN

The RCIM 4-way cassette type indoor unit benefits from quiet operation, DC fan, uniform panel sizing, weight, ceiling operation, adjustable, reduced mounting size, compact size, and improved flexible piping.

Standard operation dB(A) 42 39 37

Easy Installation and maintenance

Mini 4-way cassette

Electrical box is located inside grill, which enables easier access to the electrical components, without opening the false ceiling. A pocket is provided for each of the four panel corners. so that the body height can be easily adjusted without removing the panel. High ceiling adaptability satisfies a wide variety of requirements This model has been adapted for high ceiling (3.5m high) installations by incorporating speed-up taps. This feature provides comfortable air conditioning in suburban stores and showrooms.
High Ceiling 1.5HP Standard Speed-up (1) Speed-up (2) Below 2.5 2.5 to 2.9 2.9 to 3.9 Ceiling Height 2.0HP Below 2.7 2.7 to 3.1 3.1 to 3.5

Fan motor input reduced by DC motor


Body

The DC fan motor greatly improves efficiency compared to conventional products that use AC motors. In addition, air blasts are reduced by controlling the rotation speed of the fan.
The Body can be aligned with the celing surface by moving the body upward or downword with the packets

Panel Corner Packet

The motor input is reduced by employing a ferrite magnetic surfacemounted rotor, centralized winding system and split core system. The motor efficiency is improved in all aspects, and is 50% smaller and lighter than conventional machines. Equipped with drain up mechanism with high pump lift A drain pump lift of up to 600mm from the ceiling surface is achieved by employing a drain-up mechanism with high pump lift (500mm in the previous model).

General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Air Flow Rate (Hi/Med/Lo) Fan Motor Sound Pressure Level
(Overall A Scale) (Hi/Med/Lo)

RCIM-1.0FSN

RCIM-1.5FSN

RCIM-2.0FSN

AC 1, 230V, 50 Hz kW kW m3/min W 2.8 3.2 13/12/11 52 4.5 5.0 15/13.5/12 52 5.6 6.3 16/14/12 52

dB(A)

36/34/32

38/35/33

42/39/37

Outer Dimensions
Height Width Depth

mm mm mm kg

295 570 570 17

295 570 570 17 R410A (Nitrogen Charged in Factory for Corrosion-Resistance) Flare Nut Connection (With Flare Nuts)

295 570 570 17

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line

mm(in.) mm(in.)

6.35(1/4) 12.7( /2)


1

6.35(1/4) 12.7( /2)


1

6.35(1/4) 15.88(5/8)

Condensate Drain

mm m3

VP32 OD 0.13

VP32 OD 0.13 P-N23WAM Plaste. White (4.1Y8.5 / 0.7)

VP32 OD 0.13

Packing Measurements Adaptable Air Panel Model Colour (Munsell Code) Outer Dimensions
Height Width Depth

mm mm mm kg m3

35 700 700 3.5 0.07

35 700 700 3.5 0.07 PC-P2HTE or PC-LH3A

35 700 700 3.5 0.07

Net Weight Packing Measurements Remote Control Switch

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The Sound Pressure Level is based on the following conditions: 1.5 meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

17

Set Free RCI Technical Description

New design air panel The air panel was revised to give a fresh and simple design. Prevention of smudging and short-circuiting is also taken into account. Extremely Quite Operation Uses a blade design resulting in an exceptionally quiet fan. HI-stream fan achieves the lowest level of noise, 28 dB (A) (RCI-1.0FSN1E). Silent Operation Slim Air Panel Drain Pump as standard Compact, low height units The height of the units is just 298mm so they can easily be installed in a small space. The units require limited ceiling space which enables improved work efficiency in installation behind the ceiling.
Inside of ceiling

298mm

Indoor unit body 3HP

False ceiling

Air panel

High ceiling adaptability satisfies a wide variety of requirements This model is adaptable to a high ceiling with a height of 4.2m by using speed-up taps. These features allow comfortable air conditioning in high street stores.

4-way cassette

(m) High Ceiling 1.0/1.5/2.0/2.5 HP 4-way Standard Speed-up (1) Speed-up (2) 2.7 3.0 3.5 3-way 3.0 3.3 3.6 2-way 3.3 3.5 3.0/3.5/4.0/5.0/6.0 HP 4-way 3.2 3.6 4.2 3-way 3.6 4.0 4.3 2-way 4.0 4.2 -

NOTES For setting 3 and 2 directions, the separately sold 3-way outlet parts set is necessary. Speed up (1) and Speed-up (2) can be selected through RCS by using C5 option.

Wireless controller (option) See page 43. Fresh air intake Connection of fresh air intake can be taken in by connecting the duct beside indoor unit. The control duct fan will operate only when unit is operating giving good air recirculation and comfort.
Motor Efficiency (%) DC Motor Efficiency increased by 40%
(motor input halved)

Branch duct Available across the range for added flexibility

AC Motor

Revolutions per Min. (rpm)

DC Fan Motor with Outstanding Efficiency The DC fan motor greatly improves efficiency compared with conventional products having an AC motor. Also, air blasts are reduced by controlling the rotation speed of the fan. Drain-up mechanism is equipped as standard. Anti-mould filter is equipped as standard.

General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Air Flow Rate (Hi/Med/Lo) Fan Motor Sound Pressure Level
(Overall A Scale) (Hi/Med/Lo)

RCI-1.0FSN1E RCI-1.5FSN1E RCI-2.0FSN1E RCI-2.5FSN1E RCI-3.0FSN1E RCI-3.5FSN1E RCI-4.0FSN1E RCI-5.0FSN1E RCI-6.0FSN1E

AC 1, 230V, 50 Hz KW KW m3/min W 2.8 3.2 13/12/11 56 4.5 5.0 15/14/12 56 5.6 6.3 16/14/12 56 7.1 8.5 20/17/15 56 8.0 9.0 26/23/20 56 9.0 10.0 26/23/20 56 11.2 12.5 32/28/24 108 14.0 16.0 34/29/25 108 16.0 18.0 37/32/27 108

dB(A)

32/30/28

32/30/28

32/30/28

32/30/28

34/32/30

34/32/30

38/35/33

39/37/35

42/40/36

Outer Dimensions
Height Width Depth

mm mm mm kg

248 840 840 23

248 840 840 23

248 840 840 24

248 840 840 24

298 840 840 26

298 840 840 26

298 840 840 29

298 840 840 29

298 840 840 29

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

R410A (Nitrogen Charged in Factory for Corrosion-Resistance) Flare Nut Connection (With Flare Nuts)

mm(in.) mm(in.) mm m
3

6.35(1/4) 12.7( /2) 32 OD 0.22


1

6.35(1/4) 12.7( /2) 32 OD 0.22


1

6.35(1/4) 15.88( /8) 32 OD 0.22


5

9.53(3/8) 15.88( /8) 32 OD 0.22


5

9.53(3/8) 15.88( /8) 32 OD 0.26 P-G23WA2


5

9.53(3/8) 15.88( /8) 32 OD 0.26


5

9.53(3/8) 15.88( /8)* 32 OD 0.26


5

9.53(3/8) 9.53(3/8) 15.88(5/8)*15.88(5/8)* 32 OD 0.26 32 OD 0.26

Packing Measurements Adaptable Air Panel Model Colour (Munsell Code) Outer Dimensions
Height Width Depth

Spring White (4.1Y8.5/0.7)

mm mm mm kg m
3

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

37 950 950 6 0.08

Net Weight Packing Measurements Standard Accessories

Suspension Brackets

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The Sound Pressure Level is based on the following conditions: 1.5 meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

19

Set Free RCD Technical Description

Quiet operation and low height design for any ceiling. Quiet Operation Reduced weight and size simplify handling for easier renewal. Slim line design New Air panel, perfect fit for any ceiling The length of the 3HP type is reduced from 1,320mm to 860mm, the height is also reduced and the volume is decreased by about 50%. The reduced weight of 30kg also makes handling much easier.

398mm 298mm

odel New M (50%)

860mm 1,320mm

de nt M o Curre %) (100

Low-profile design allows installation in a small space inside of ceiling. A compact turbo fan simplifies the structure and reduces the height to 298mm, for easy installation.

Compact Turbo Fan Inside of Ceiling

298mm
Ceiling

2-way cassette

Top-class noise control due to compact turbo fan. The three-dimensional twisted wings of the compact turbo fan greatly reduce noise and electromagnetic disturbance is minimised by PWM (Pulse Width Modulation) control. Simple Maintenance Auto-louvers are not flocked, therefore the unit does not accumulate dirt and is easy to clean. Speed-up tap ensures comfortable air conditioning even when installed in high ceiling areas. Even rooms with a high ceiling can be comfortably air-conditioned by setting the speed-up tap with the remote control switch.

General Data
Model Power Supply Nominal Cooling Capacity kW Nominal Heating Capacity kW Indoor Fan
Air Flow Rate (Hi/Med/Lo)

RCD-1.0FSN

RCD-1.5FSN

RCD-2.0FSN AC 1, 230V, 50 Hz

RCD-2.5FSN

RCD-3.0FSN

RCD-4.0FSN

RCD-5.0FSN

2.8 3.2

4.5 5.0

5.6 6.3

7.1 8.5

8.0 9.0

11.2 12.5

14.0 16.0

m3/min W

8/7/6 35

12/10/8.5 35

15/13/11 35

19/16/14 55

22/19/16 55

29/24/21 35 x 2

34/29/25 35 x 2

Fan Motor Sound Pressure Level


(Overall A Scale)

dB(A)

34/32/30

35/32/30

35/32/30

38/34/31

40/36/33

40/36/33

43/40/36

Outer Dimensions
Height Width Depth

mm mm mm kg

298 860 620 27

298 860 620 27

298 860 620 27

298 860 620 30

298 860 620 30

298 1,420 620 48

298 1,420 620 48

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

R410A (Nitrogen-Charged for Corrosion-Resistance) Flare Nut Connection

mm (in.) mm (in.) m
3

6.35 (1/4) 12.7 (1/2) 32 0D

6.35 (1/4) 12.7 (1/2) 32 0D

6.35 (1/4) 15.88 (5/8) 32 OD

9.53 (3/8) 15.88 (5/8) 32 0D

9.53 (3/8) 15.88 (5/8) 32 0D

9.53 (3/8) 15.88 (5/8) 32 0D

9.53 (3/8) 15.88 (5/8) 32 0D

Approximate Packing Measurements Adaptable Air Panel Model Colour Outer Dimensions
Height Width Depth

0.23 P-G23DWA1

0.23 P-G23DWA1

0.23 P-G23DWA1

0.23 P-G23DWA1

0.23 P-G23DWA1

0.37 P-G46DWA1

0.37 P-G46DWA1

Silky White (2.5Y 8.9/1)

mm mm mm kg

30+10 1,100 710 6

30+10 1,100 710 6

30+10 1,100 710 6

30+10 1,100 710 6

30+10 1,100 710 6

30+10 1,660 710 8

30+10 1,660 710 8

Net Weight Approximate Packing Measurements Standard Accessories

m3

0.10

0.10

0.10

0.10

0.10

0.15

0.15

Suspension Brackets

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The Sound Pressure Level is based on the following conditions: 1.5 meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

21

RPK-FSN2M Technical Description

Stylish Design Easy Maintenance Compact & Lightweight Design

Stylish Design and Easy Maintenance New flat panel design across all models. This flat panel allows for easy maintenance. Compact and Light Weight Design Designed with ease of installation in mind this new space saving model also uses a high proportion of light weight parts reducing the unit weight. The new 1.0HP and 1.5HP models have a reduced weight of just 10kg. Wireless or Wired Control The indoor unit is equipped with a wireless receiver kit inside as a standard accessory. The wired remote control switch, PC-P1HE is also applicable. Easy switching from wireless to wired remote controller is possible by using the dip switch built into the receiver part.

Wall mounted

General Data
Model Power Supply Nominal Cooling Capacity kW Nominal Heating Capacity kW Sound Pressure Level
(Overall Scale) (Hi-Me-Lo)

RPK-1.0FSN2M

RPK-1.5FSN2M

RPK-2.0FSN2M AC 1 230V / 50Hz

RPK-2.5FSN2M

RPK-3.0FSN2M

RPK-4.0FSN2M

2.8 3.2

4.5 5.0

5.6 6.3

7.1 8.5

8.0 9.0

11.2 12.5

dB(A)

38/36/34

40/38/36

41/39/37

43/40/37

43/40/37

49/46/43

Outer Dimensions
Height Width Depth

mm mm mm kg

280 780 210 10

280 780 210 10

295 1030 208 12

333 1150 245 18

333 1150 245 18

333 1150 245 18

Net Weight Refrigerant Air Flow Rate (Hi/Me/Lo) Fan Motor Connections Refrigerant Piping
Liquid Line Gas Line Condensate Drain

R410A (Nitrogen Charged in Factory for Corrosion-resistance) m3/min W 10/8/7 20 11/10/9 20 14/12/10 30 17/16/14 30 17/16/14 30 22/20/17 30

Flare-Nut Connection (with Flare Nuts)

mm(in.) mm(in.)

6.35(1/4) 12.7( /2) VP16


1

6.35(1/4) 12.7( /2) VP16


1

6.35(1/4) 15.88( /8) VP16


5

9.53(3/8) 15.88( /8) VP16


5

9.53(3/8) 15.88( /8) VP16


5

9.53(3/8) 15.88(5/8) VP16

Packing Measurement (approx.) Remote Control Switch m3 0.07 0.07 0.11 0.13 0.13 0.13

PC-P2HTE or PC-LH3A

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB 19C WB Outdoor Air Inlet Temperature: 35C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Pipe Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The Sound Pressure Level is based on the following conditions: 1.0 meters beneath the unit, 1.0 meters from discharge grille Voltage of the power source for the indoor fan motor is 230V The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

23

Set Free RPC Technical Description

Quiet operation, easy installation and space saving design Versatile mounting To expand installation and positioning options, HITACHI has added a second drain pipe connector, one more than conventional units. Refrigeration pipes have also been improved and can now be connected at the left, right or rear of the unit.

Rear Side Drain piping

Space saving design Hitachis unique feature Stylish design Space saving design Easy installation Quiet Operation An innovative fan and heat exchanger design led to the creation of todays ultra-slim ceiling unit. Fully adjustable mounting brackets permit close fitting to the ceiling to make installation possible in even the smallest area. Less than 163mm of vertical space are required for installation. Quiet Operation The ceiling unit is equipped with a highly efficient, multi-blade centrifugal fan that generates a powerful yet gentle airflow throughout the room. A redesigned aerodynamically tested air panel minimises operational sound even at high fan speeds.

Ceiling suspended
Easier installation By enabling refrigeration piping to be tucked-in close to each indoor unit, piping layout and installation have been made much easier. Anti-mildew filter Anti-mildew filter is equipped as a standard accessory.

Open Space 163mm Concealed 150mm (2,0, 2,5 and 3,0 HP)

General Data
Model Power Supply Nominal Cooling Capacity kW Nominal Heating Capacity kW Indoor Fan
Air Flow Rate (Hi/Me/Lo)

RPC-2.0FSNE

RPC-2.5FSNE

RPC-3.0FSNE

RPC-3.5FSNE

RPC-4.0FSNE

RPC-5.0FSNE

RPC-6.0FSNE

AC 1, 230V, 50 Hz 5.6 6.3 7.1 8.5 8.0 9.0 9.0 10.0 11.2 12.5 14.0 16.0 16.0 18.0

m3/min W

15/13/10 75

18/16/12 75

21/17/15 75

21/17/15 75

30/24/19 145

35/28/21 145

37/32/27 145

Fan Motor (Output) Sound Pressure Level


(Overall A Scale) (Hi/Med/Lo)

dB(A)

44/42/38

46/43/41

48/45/42

48/45/42

49/45/39

49/46/41

50/48/44

Outer Dimsensions
Height Width Depth

mm mm mm kg

163 1,094 625 28

163 1,314 625 31

163 1,314 625 31

163 1314 625 31

225 1,314 625 35

225 1,574 625 41

225 1574 625 41

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

R410A (Nitrogen-Charged in Factory for Corrosion-Resistance) Flare Nut Connection (With Flare Nuts)

mm (in.) mm (in.) mm

6.35(1/4) 15.88(5/8) 25 0D

9.53(3/8) 15.88(5/8) 25 0D

9.53(3/8) 15.88(5/8) 25 0D

9.53(3/8) 15.88(5/8) 25 0D

9.53(3/8) 15.88(5/8) 25 0D

9.53(3/8)

9.53(3/8)

15.88(5/8) 15.88(5/8)* 25 0D 25 0D

Approximate Packing Measurements Standard Accessories Colour (MUNSELL Code) m3 0.24 0.29 0.29 0.29 Mounting Bracket Spring White (4.1Y 8.5/0.7) 0.36 0.43 0.43

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter *R410A (Std. Accessory pipe to be used).

2. The Sound Pressure Level is based on the following conditions: 1.0 meters Beneath the Unit, 1.0 m from discharge grill. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

25

Set Free RPF/RPFI Technical Description

Space-saving slim unit, only 220mm in depth Floor mounted indoor units RPF Floor Type Slim design, only 200mm deep Low height, only 630mm Light unit Low sound level Effective use of space by window With a height of 630mm, may be installed by a window leaving plenty of window space. Best installed in a perimeter zone. Low height Only 630mm. Slim line design only 220mm in depth allowing the unit to be installed without spoiling the style or beauty of the room.

Floor concealed indoor units RPFI Compact design 620mm in height 220mm in depth

Concealed Floor Mounted


Compact design for limited space inside of perimeter wall. So compact that it fits into even the smallest space. Special emphasis placed on interior design compatibility as well as space saving design, allowing it to fit perfectly into the space below a bay window. Optional location for remote control switch Install the PC-P1HE under the plastic cover

Floor mounted

General Data
Model Power Supply Nominal Cooling Capacity kW Nominal Heating Capacity kW Air Flow Rate (Hi/Me/Lo) Fan Motor Sound Pressure Level (Overall A Scale) Outer Dimensions
Height Width Depth

RPF-1.0FSNE

RPF-1.5FSNE

RPF-2.0FSNE

RPF-2.5FSNE

RPFI-1.0FSNE

RPFI-1.5FSNE

RPFI-2.0FSNE

RPFI-2.5FSNE

AC 1, 230V, 50 Hz 2.8 3.2 8.5/7/6 20 4.5 5.0 12/10/9 28 5.6 6.3 16/14/11 45 7.1 8.5 16/14/11 45 2.8 3.2 8.5/7/6 20 4.5 5.0 12/10/9 28 5.6 6.3 16/14/11 45 7.1 8.5 16/14/11 45

m /min W

dB(A)

35/32/29

38/35/31

39/3632

42/38/34

35/32/29

38/35/31

39/36/32

42/38/24

mm mm mm kg

630 1045 220 19

630 1170 220 23

630 1420 220 33

630 1420 220 34

620 863 220 19

620 988 220 23

620 1238 220 27

620 1238 220 28

Net Weight Refrigerant Connections Refrigerant Piping


Liquid Line Gas Line Condensate Drain

R410A (Nitrogen Charged in Factory for Corrosion-Resistance) Flare Nut Connection (with Flare Nut)

R410A (Nitrogen Charged in Factory for Corrosion-Resistance) Flare Nut Connection (with Flare Nut)

mm(in.) mm(in.) mm m3

6.35(1/4) 12.7( /2) 18.5 0D 0.22


1

6.35(1/4) 12.7( /2) 18.5 0D 0.24


1

6.35(1/4) 15.88( /8) 18.5 0D 0.29


5

9.53(3/8) 15.88( /8) 18.5 0D 0.29


5

6.35(1/4) 12.7( /2) 18.5 0D 0.22


1

6.35(1/4) 12.7( /2) 18.5 OD 0.23


1

6.35(1/4)
5

9.53 (3/8)

15.88( /8) 15.88 (5/8) 18.5 0D 0.25 18.5 0D 0.25

Packing Measurements Colour (Munsell Code)

Spring White (4.1Y 8.5/0.7)

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the HITACHI standard split system, and are based on the JISB 8616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27.0 C DB 19.0 C WB Outdoor Air Inlet Temperature: 35.0 C DB Heating Operation Conditions Indoor Air Inlet Temperature: 20.0 C DB Outdoor Air Inlet Temperature: 7.0 C DB 6.0 C WB Piping Length: 7.5 meters DB: Dry Bulb; WB: Wet Bulb

OD: Outer Diameter

2. The Sound Pressure Level is based on the following conditions: 1.0 meters from the unit, 1.0 meters from floor level. Voltage of the power source for the indoor fan motor is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration when installing the unit.

27

Set Free KPI Technical Description

Structure Outdoors Outdoor air Air discharge Air filter (for discharge)

Provides a comfortable environment by control interlocking with air conditioning units. Controllable using the remote control switch for the air conditioning unit. Can be controlled in various ways using the remote control switch for the air conditioning unit (PC-P2HT). Functions Simultaneous RUN/STOP switch both for air conditioning units and heat exchanging unit

Air supply fan

Indoor air Indoors

Individual operation of heat exchanging unit Fan speed control (high/medium/low)

Electrical components box Air supply

Ventilation mode selection (automatic/heat exchange/bypass)*1 Pre-cool/pre-heat control (interlocking start with delay in 30 or 60 minutes)*1 ON/OFF timer (every half hour, maximum 24 hours) Increased air supply operation Specific alarm display
*1 Required option to be selected at remote control switch.

Fixed Type Heat Exchanging Element The newly developed fixed type heat exchanging element with high temperature exchange efficiency equivalent to the rotor type element, has been adopted for the new total heat exchangers (Temp Exchange Efficiency: 77% <in case of 500m3/h type unit>). In addition, reliability is increased due to reduction of moving parts. Low weight with simple unit structure: 33kg (in case of 500m3/h type unit).

Automatic selection of most suitable ventilation mode Depending on temperature conditions both outdoors and indoors, the most suitable ventilation mode is automatically selected, designed for energy efficiency.

Total heat exchanger


Other Characteristics Quiet operation with low noise level of 32.5-33.5 dB (A) (at Hi Tap of KPI 5021 Type) has been realised by improving the flow path configuration. Operation not only with SET-FREE Series Indoor Unit, but also with UTOPIA Series Indoor Unit. Connectable to H-LINK System with Central Station or with CS-NET in Operation with Indoor Unit. Flexible Duct Installation: The connecting direction of duct at outdoor side (OA,EA) can be changed according to the condition of the installation site (2 directions). Reduced packing material for environment protection. The wood for the packing use has been reduced for environment protection. Can also be installed upside down.

Various Control Examples of Total Heat Exchanger


Standard Connection 1 Example of System SET-FREE PC-P1H Outlook of System Component of System PC-P1HE UTOPIA PC-P1H T.H.E+PC-P1H PC-P1H Able to control up to 16 Indoor Units and Total Heat Exchanger Units Remote Control Switch (PC-P1H) Able to control with PC-P1H directry PSC-5S :TOTAL HEAT EXCHANGER ( T.H.E ) Central Station (PSC-5S) 2 3 H-LINK :INDOOR UNIT

Able to control up to 128 Indoor Units consist of 16 refrigeration series Central Station (PSC-5S) Remote Control Switch (PC-P1H)

1 ~ 5 :NEW AVAILABLE SYSTEM

Hitachi Computer Control Network System CS-NET (version 7) 4 H-LINK 5 H-LINK

Example of System

PC-P1H Outlook of System Component of System

CS-NET

PC-P1H

CS-NET

PC-P1H

CS-NET

Able to control up to 128 Indoor Units consist of 16 refrigeration series CS-NET Remote Control Switch (PC-P1H)

General Data
Model Power Supply Air Flow Rate (m3/min) Hi Me Lo External Pressure (mmAq) Hi Me Lo Temperature Exchange Efficiency (%) Hi Me Lo Enthalpy Exchange Efficiency for Heating/Cooling (%) Sound Pressure Level
(Overall A Scale) at 1.5m from the unit (under)*3

KPI-2521

KPI-5021 AC 1, 230V, 50 Hz

KPI-8021

KPI-10021

4.1 4.1 2.75 6.5 4 2 78 78 83 69/62.5 69/62.5 74/68 26.5-27.5 25-26 21-22 275 735 780

8.3 8.3 5.8 15 6 3 77 77 82 67/61.5 67/61.5 73/68 32.5-33.5 30-31 23.5-24.5 317 1016 888 33 0.46

13.3 13.3 11.1 14 10 7 78 78 80.5 71/64.5 71/64.5 73/68 33.5-34.5 32-33 30-31 398 1004 1164 61 0.70 36-37 34-35

16.6 16.6 14.5 16 10 8 79 79 81 70/64.5 70/64.5 73/67

Hi Me Lo Hi Me Lo

31.5-32.5 398 1231 1164 72 0.84

Outer Dimensions
Height Width Depth

Net Weight Approx Packing Measurement

Kg m3

21 0.26

NOTES: *1 KPI-10021 has different units according to the applied power supply, 220-240v, 50Hz and 200V/60Hz *2 Use it under the following conditions. KPI-8021: 29Pa or more, KPI-10021: 49Pa or more *3 The sound pressure level is based on the following conditions; 1.5 meter beneath the unit and this data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. *4 The sound pressure is based on the total heat exchange mode. In case of the bypass ventilation mode, the sound pressure level increased by approximately 1dB(A).

29

Set Free FSVNE (Mini Heat Pump) Technical Description Outdoor units
General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Cabinet Colour Sound Pressure Levels (Night Shift) Outer Dimensions
Height Width Depth

RAS-3FSVNE

RAS-4FSVNE

RAS-5FSVNE

AC 1, 230V, 50 Hz kW kW 8.0 9.0 11.2 12.5 Natural Grey (1.0Y8.5/0.5) dB(A) 46(42)/47 47(43)/48 50(46)/51 14.0 16.0

mm mm mm kg

800 850 315 68 R410A

1,240 950 315 90

1,240 950 315 97

RAS-3FSVNE

Net Weight Refrigerant


Flow control

Micro-Computer Control Expansion Valve Hermetic (Rotary) 2YC63BXD 1 kW 1.7(4) Hermetic (Scroll) EK405AHD 1 2.2(4) Hermetic (Scroll) EK405AHD 1 3.0(4)

Compressor
Model Quantity Motor Output (Pole)

Heat Exchanger Condenser Fan


Quantity Air Flow Rate Motor Output (Pole)

Multi-Pass Cross-Finned Tube Propeller Fan 1 m3/min W 52 0.05(8)x1 2 88 0.05(8)x1+0.07(8)x1 Flare Nut Connection mm(in.) mm(in.) kg 9.53 15.88 1.75 9.53 15.88 2.8 9.53 15.88 3.0 99 0.05(8)x1+0.07(8)x1 2

Refrigerant Piping
Liquid Line Gas Line

Refrigerant Charge

RAS-4FSVNE / RAS-5FSVNE

Wiring Holes
Power Supply Control Circuit

mm mm

26.5 26.5

26.5 26.5

26.5 26.5

Connecting Wire between Indoor and Outdoor unit Approximate Packing Measurement m3 0.34 0.5 0.5 2 2 2

NOTES: 1. The cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB (80F DB) 19.0C WB (66.2F WB) Outdoor Air Inlet Temperature: 35C DB (95F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB (68F DB) Outdoor Air Inlet Temperature: 7C DB (45F DB) 6C WB (43F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

2. The sound pressure level is based on following conditions. In case of cooling operation mode. In case of heating operation mode, the sound pressure level increases by approximately 1~2dB. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. Voltage of the power source is 230V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

Set Free FSN1(E) (Heat Pump) Technical Description Outdoor units


General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Energy Efficiency Rate (EER) COP Cabinet Colour (Munsell Code) Sound Pressure Levels (Night Mode) dB(A) Outer Dimensions
Height Width Depth

RAS-5FSN

RAS-8FSN1(E)

RAS-10FSN1(E) AC 3, 380-415V, 3~ 50Hz

RAS-12FSN1(E)

RAS-14FSN1

RAS-16FSN1

kW kW

14.0 16.0 3.45 3.87

22.4 25.0 3.72 4.36

28.0 31.5 3.54 4.07 Natural Grey (1.0Y8.5/0.5)

33.5 37.5 3.39 3.71

40.0 45.0 3.22 3.97

45.0 50.0 3.10 3.99

52/(47)

56/(51)

58/(53)

60/(55)

61/(56)

62/(57)

mm mm mm kg

1,645 630 750 160

1,745 950 750 215

1,745 950 750 225 R410A Microprocessor-controlled Expansion Valve Hermetic (Scroll)

1,745 950 750 225

1,745 1,210 750 335

1,745 1,210 750 335

Net Weight Refrigerant


Flow Control

Compressor
Quantity Power

kW

1 3

1 4.80

1 6.00 Multi-Pass Cross-Finned Tube Propeller Fan

1 7.20

1+1 4.80+4.40

1+1 6.00+4.40

Heat Exchanger Outdoor Fan


Quantity Air Flow Rate Motor (output)

m3/min W mm(in.) mm(in.) kg A

1 138 160

1 172 380

1 185 380

1 210 380

1 210 380

1 210 380

Refrigerant Piping
Liquid Line Gas Line

Flare-Nut and/or Flange Connection (Factory supplied) 9.53(3/8) 15.88(5/8) 5.4 9.6 9.53(3/8) 19.05(3/4) 7.0 14 9.53(3/8) 22.20(7/8) 8.5 20 12.70(1/2) 25.40(1) 9.0 22 12.70(1/2) 25.40(1) 13.0 29 12.70(1/2) 28.60(11/8) 13.0 34

Refrigerant Charge Maximum Current Approximate Packing Measurement

m3

0.87

1.44

1.44

1.44

1.81

1.81

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the SET FREE system, and is based on JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB (80F DB) 19.0C WB (66.2F WB) Outdoor Air Inlet Temperature: 35C DB (95F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB (68F DB) Outdoor Air Inlet Temperature: 7C DB (45F DB) 6C WB (43F WB) OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters DB: Dry Bulb; WB: Wet Bulb

2. The sound pressure level is based on following conditions: 1 meter from the frontal surface of the unit. 1.5 meters from floor level Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit. 3. In case of Night Shift conditions, the noise level decreases 5 dB (A). 4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).

31

Set Free FSN1(E) (Heat Pump) Technical Description Outdoor units


General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Energy Efficiency Rate (EER) COP Cabinet Colour (Munsell Code) Sound Pressure Levels (Night Mode) dB(A) Outer Dimensions
Height Width Depth

RAS-18FSN1

RAS-20FSN1

RAS-24FSN1 AC 3, 380-415V, 3~ 50Hz

RAS-28FSN1

RAS-32FSN1

kW kW

50.4 56.0 3.50 3.91

56.0 63.0 3.14 3.70

69.0 77.5 3.25 3.92 Natural Grey (1.0Y8.5/0.5)

80.0 90.0 3.03 3.87

90.0 100.0 3.01 3.85

62/(57)

62/(57)

63/(58)

64/(59)

64/(59)

mm mm mm kg

1,745 1,910 750 460

1,745 1,910 750 460

1,745 2,430 750 675 R410A Microprocessor-controlled Expansion Valve Hermetic (Scroll)

1,745 2,430 750 720

1,745 2,430 750 720

Net Weight Refrigerant


Flow Control

Compressor
Quantity Power

kW

1+1 6.00+5.60

1+1 7.20+5.60

1+4 1.40+4x4.40 Multi-Pass Cross-Finned Tube Propeller Fan

1+5 1.40+5x4.40

1+5 1.40+5x4.40

Heat Exchanger Outdoor Fan


Quantity Air Flow Rate Motor (output)

m3/min W

2 210 380+275

2 344 380+275

2 382 380+275

2 382 380+275

2 382 380+275

Refrigerant Piping
Liquid Line Gas Line

Flare-Nut and/or Flange Connection (Factory supplied) mm(in.) mm(in.) kg A 15.88(5/8) 28.60(11/8) 19 34 15.88(5/8) 28.60(11/8) 19 38 15.88(5/8) 28.60(11/8) 23 50 19.05(3/4) 31.75(11/4) 25 63 19.05(3/4) 31.75(11/4) 26 77

Refrigerant Charge Maximum Current Approximate Packing Measurement

m3

1.81

2.82

3.57

3.57

3.57

NOTES: 1. The nominal cooling and heating capacity is the combined capacity of the SET FREE system, and is based on JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB (80F DB) 19.0C WB (66.2F WB) Outdoor Air Inlet Temperature: 35C DB (95F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB (68F DB) Outdoor Air Inlet Temperature: 7C DB (45F DB) 6C WB (43F WB) OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters DB: Dry Bulb; WB: Wet Bulb

2. The sound pressure level is based on following conditions: 1 meter from the frontal surface of the unit. 1.5 meters from floor level Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit. 3. In case of Night Shift conditions, the noise level decreases 5 dB (A). 4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).

Set Free FSN1(E) (Heat Pump) Technical Description Outdoor units


General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Energy Efficiency Rate (EER) COP Cabinet Colour (Munsell Code) Sound Pressure Levels (Night Mode) dB(A) Outer Dimensions
Height Width Depth

RAS-36FSN AC 3, 400V, 3~ 50Hz W W 101.0 113.0 3.01 3.47 Natural Grey (1.0Y8.5/0.5) 64(59)

RAS-42FSN

118.0 132.0 3.02 3.43

65(60)

mm mm mm kg

1,745 3,390 750 920 R410A Microprocessor-controlled Expansion Valve Hermetic (Scroll)

1,745 3,390 750 970

RAS-24/28/32FSN

Net Weight Refrigerant


Flow Control

Compressor
Quantity Power

kW

1+4 4.9+5.6x4 Multi-Pass Cross-Finned Tube Propeller Fan 3

1+5 4.9+5.6x4

Heat Exchanger Condenser Fan


Quantity Air Flow Rate Motor Output

3 554 380+275x2

m3/min W

554 380+275x2

Refrigerant Piping
Liquid Line Gas Line

Flare-Nut and/or Flange Connection (Factory supplied) mm(in.) mm(in.) kg A 19.05(3/4) 38.1(1-1/2) 31 70.4 19.05(3/4) 38.1(1-1/2) 32 81.7

Refrigerant Charge Maximum Current Approximate Packing Measurement

RAS-36/42FSN

m3

4.99

4.99

NOTES: 1. The cooling and heating capacities show the capacities is the combine capacity of the SET FREE system, and is based on JIS 158616. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB (80F DB) 19.0C WB (66.2F WB) Outdoor Air Inlet Temperature: 35C DB (95F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB (68F DB) Outdoor Air Inlet Temperature: 7C DB (45F DB) 6C WB (43F WB) OD: Outer Diameter Pipe Length: 7.5 Meters Pipe Height: 0 Meters DB: Dry Bulb; WB: Wet Bulb

2. The sound pressure level is based on following conditions: 1 meter from the frontal surface of the unit. 1.5 meters from floor level Voltage of the power source is 400V The above data was measured in an anechoic chamber, so reflected sound should be taken into consideration when installing the unit. 3. In case of Night Shift conditions, the noise level decreases 5 dB (A). 4. The COP and EER have been calculated with RCI-FSN1E units. (Indoor unit input power excluded).

33

Set Free FXN (Heat Recovery) Technical Description Outdoor units


General Data
Model RAS-8 FXNE RAS-10 FXNE RAS-12 FXNE AC 3, 400V, 50Hz kW W 22.4 25.0 28.0 31.5 33.5 37.5 Natural Grey 45.0 50.0 50.0 56.0 RAS-16 FXN RAS-18 FXN

Power Supply Nominal Cooling Capacity Nominal Heating Capacity Cabinet Colour Sound Pressure Levels (Night Shift) dB(A) 56(51) 58(53)

60(55)

62(57)

56.0

RAS-8/10/12FXNE

Outer Dimensions Height Width Depth Net Weight Refrigerant Flow control Compressor Model E405AHD E505DH -49D2Y Quantity Motor Output (Pole) kW 1+1 1.8(4)+ 3.7(2) Heat Exchanger Condenser Fan Quantity Air Flow Rate Motor Output (Pole) Refrigerant Piping Gas Line Low Gas Line High Refrigerant Charge Wiring Holes Power Supply Control Circuit Connecting Wire between Indoor and Outdoor unit Approximate Packing Measurement m3 1.44 1.44 1.44 2.82 2.82 2 2 2 2 2 mm mm 56 26.5 56 26.5 56 26.5 56 26.5 56 26.5 mm(in.) mm(in.) kg 19.05(3/4) 15.88(5/8) 8.5 m3/min W 1 138 380(8) 1 172 380(8) 1+1 2.3(4)+ 4.4(2) 1+1 3.7(4)+ 4.4(2) Multi-Pass Cross-Finned Tube Propeller Fan 1 185 380(8) 2 210 380(8) 0 172+172 380(8) 1+1x2 3.0+4.4 (2)x2 1+1x3 1.4(4)x1+ 4.4(2)x3 E405AHD E605DH mm mm mm kg 1,745 950 750 295 1,745 950 750 305 1,745 950 750 305 R410A Micro-Computer Control Expansion Valve Hermetic (Scroll) E405AHD E655DH E405AHD E605DHx2 E405AHD E605DHx3 1,745 1,910 750 527 1,745 1,910 750 570

RAS-16/18/20FXN

Flare-Nut and/or Flange Connection (Factory supplied) 22.2(7/8) 19.05(3/4) 9.5 25.4(1) 19.05(3/4) 10.0 28.6(11/8) 22.2(7/8) 19.0 28.6(11/8) 22.2(7/8) 19.0

NOTES: 1. The cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984. Cooling Operation Conditions Indoor Air Inlet Temperature: 27C DB (80F DB) 19.0C WB (66.2F WB) Outdoor Air Inlet Temperature: 35C DB (95F DB) Heating Operation Conditions Indoor Air Inlet Temperature: 20C DB (68F DB) Outdoor Air Inlet Temperature: 7C DB (45F DB) 6C WB (43F WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter

Set Free FXN (Heat Recovery) Technical Description Outdoor units


General Data
Model Power Supply Nominal Cooling Capacity Nominal Heating Capacity Cabinet Colour Sound Pressure Levels (Night Shift) Outer Dimensions Height Width Depth Net Weight Refrigerant Flow control Compressor Model E405AHD E605DHx3 mm mm mm kg 1,745 1,910 750 570 1,745 2,430 750 712 R410A Micro-Computer Control Expansion Valve Hermetic (Scroll) E405AHD E605DHx4 E405AHD E655DHx 65D2Yx5 Quantity Motor Output (Pole) kW 1+1x3 1.8(4)+ 4.4(2)x3 Heat Exchanger Condenser Fan Quantity Air Flow Rate Motor Output (Pole) m3/min W 2 172+172 380(8) +275(6) Refrigerant Piping Liquid Line Gas Line Low Gas Line High Refrigerant Charge Wiring Holes Power Supply Control Circuit Connecting Wire between Indoor and Outdoor unit Approximate Packing Measurement m3 2.82 3.57 3.57 3.57 2 2 2 2 mm mm 56 26.5 70 26.5 70 26.5 70 26.5 mm(in.) mm(in.) mm(in.) kg 2 210+172 380(8) +275(6) 2 210+172 380(8) +275(6) 2 210+172 380(8) +275(6) 1+1x4 1.4(4)+ 4.4(2)x4 1+1x5 1.4(4)+ 4.4(2)x5 E405AHD E655DHx 65D2Yx5 1+1x5 1.4(4)+ 4.4(2)x5 1,745 2,430 750 755 1,745 2,430 750 755 dB(A) 62(57) 62(57) 63(58) 63(58) kW W 56.0 63.0 RAS-20 FXN RAS-24 FXN RAS-30 FXN RAS-32 FXN

AC 3, 400V, 50Hz 69.0 77.5 Natural Grey 85.0 95.0 90.0 100.0

RAS-24/30/32FXN

Flare-Nut and/or Flange Connection (Factory supplied) 15.88(5/8) 28.6(11/8) 22.2(7/8) 19.0 15.88(5/8) 28.6(11/8) 25.4(1) 26.0 19.05(3/4) 19.05(3/4) 31.75(11/4) 31.75(11/4) 28.6(11/8) 26.0 28.6(11/8) 26.0

NOTES: 2. The sound pressure level is based on following conditions. In case of cooling operation mode. In case of heating operation mode, the sound pressure level increases by approximately 1~2dB. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. Voltage of the power source is 400V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.

35

Changeover Box

The new Changeover boxes from Hitachi are compatible with FXN Set Free Heat Recovery systems. Piping connections are reduced from 5 (3 from outdoor unit and 2 into indoor unit) to 3 (2 from outdoor unit and 1 into indoor unit). The height of the Changeover boxes is as low as 197mm and the installation time is reduced due to the strainer being installed at manufacturing stage. The flexible location of the electrical box is another advantage of this new model as it enables easier access for servicing and it can be positioned at either side of the Changeover box.

Technical Description
General Data
Model Power Supply Nominal Capacity No of Max.I/D Unit Dimensions
HxWxD

CH-4.0NE

CH-8.0NE AC 1, 230V, 50 Hz

CH-12.0N

HP

HP<4 4

4HP<8X 8

8<HP12 5

mm kg

197x345x299 10

197x345x299 10

197x345x299 11

Weight Connections Refrigerant Piping Refrigerant Piping From Outdoor Unit


High Pressure Gas Pipe Low Pressure Gas Pipe

Flare-Nut and/or Flange Connection (Factory supplied)

mm(in) mm(in)

12.70(1/2) 15.88(5/8)

15.88(5/8) 19.05(3/4)

19.05(3/4) 22.2(7/8)

To Indoor Unit
Indoor Gas Pipe

mm(in)

15.88(5/8)

19.05(3/4)

22.2(7/8)

37

Control systems
H-Link Transmission System
This system connects the control wires for the outdoor and indoor units across two or more refrigerant systems. Regardless of the order or number of units to be connected, all the units can be controlled once they have been connected. By this method, design flexibility is very high, installation is easy and total costs are reduced. Furthermore, central control is possible by connecting CS-NET web to H-LINK wiring located in the room next to the room where CS-NET web is installed.

CS Net Web

CS-NET web

Computer System Network for the remote control and monitoring of air conditioning installation.
CS-NET web is a standalone central controller that can control up to 128 indoor units and up to 16 outdoor units connected to the Hitachi H-Link communication system. Using its Ethernet port, CS-NET Web connects to the Local Area Network or Internet (using a DSL router), allowing remote parameter setting and monitoring. CS-NET web client software is accessed directly through Internet Explorer and uses a Java application for remote control and monitoring. A useful feature is that two levels of access are available depending on the user type: User access, allowing monitoring and setting of the unit Installer access, allowing also Timer setting and change of system configuration

Touch Screen
The touch screen allows the continuous monitoring and control of the CS NET WEB data. 2 mounting positions are possible: TS001 + TS001-TS (Table Support) TS001 + TS001-WS (Wall Support)

Touch Screen

39

Unit Setting
Different setting of the unit can be programmed remotely using CS-NET Web.

Timer
4 year timer can be stored in the CS-NET Web remotely, allowing it to run standalone without a PC or manual operation.

System Status and Historical Data


Different readings from the unit can be accessed remotely in order to give fast assistance for maintenance and monitoring of the system. These parameters are stored locally for several days to ease maintenance.

Specifications of HARC-BX

Type Connectable Qty Control Run/Stop & Alarm* Operation Mode Set Temp Fan Speed Louver Position RC. Sw.Permission/Prohibition Alarm Code IU Inlet Air Temp IU Outlet Air Temp Outdoor Air Temp Thermo-ON/OFF Remark Maximum Wiring Length

Standard 64 Monitor Control

Option A 64 Monitor Control

Option B 32 Monitor

Use PC-P2HTE or PC-2H2 1000m (Bus Total length)

*Alarm for monitor only

Lon Works interface

Gateway Interface to LON WORKS BMS Systems


Using HARC-BX allows control of up to 5 setting points and remote monitoring of up to 9 valves. By connecting HARC-BX to H-LINK, a group of up to 16 remote controls can be used and up to 64 indoor units can be controlled.

HARC-BX

41

PC-P2HTE
Remote Control Switch with Seven Day Timer This remote controller can control up to 16 indoor units, has a large LCD display and an internal thermostat. It has a weekly timer function allowing four different schedules to be set over seven days. There is also a self diagnostic function and all indoor unit functions including alarm codes can be accessed and displayed by this controller. Can control up to 16 indoor units Weekly timer function Full fault diagnostic facility Frost protection facility Energy Saving Option

PC-LH3A
Wireless Remote Control Switch A wireless remote control switch that provides simple one-touch operation and can control two or more units simultaneously. No wiring work is required and the receiver kit is integral in wall mounted units. A receiver kit PC-RLH11 is required for all other models. Wireless Remote Control For use in place of hard wired PC-P2HTE Receiver PC RLH4 required with CS Net and central station.

PC-P5H1
Simplified Remote Control Switch Smaller than the conventional remote controller the main function is temperature adjustment. It is ideal for a variety of applications such as hotels, restaurants and offices because it is easy to use. It can control a maximum of 16 indoor units similar to the standard hard wired controller and displays alarm codes on a simple LED panel. Simple and easy to use On/off temperature and fan speed control Limited range of diagnostic functions

Remote controllers
PSC-5S
Centralised Remote Control Switch The Central Station enables centralised control of up to 16 groups of indoor units (256 units in total). It features a wide range of functions, including a large liquid crystal display screen remote start/stop and alarm code display. Simple control for large installations Max of 256 units Remote control grouping

PSC-5T
7-Day Timer The 7-Day Timer allows long-term unattended control. By connecting this timer to the optional remote control switch or central station daily ON/OFF operation control throughout the week is available. The ON/OFF setting is available three times a day in two different patterns. Two types of weekly schedule (A and B) can be set, and can easily be changed for summer and winter operation Settings are all digitally displayed, allowing operations and settings to be easily checked

Optional parts

43

Indoor Units
4-Way and Mini 4-Way Cassette Type

Item Receiver Kit for Wireless Control

RCI-1.0-6.0FSN1E PC-RLH8 (on the panel) PC-RLH11 (wall mounted)

2-Way Cassette Type

Item Receiver Kit for Wireless Control

RCD-1.0-5.0FSN PC-RLH9 (on the panel) PC-RLH11 (wall mounted)

Mini Wall Mounted Type

Item Wireless Remote Controller Wired Remote Controller

RPK-0.8-4.0FSNM PC-LH3A PC-P1HE

In-the-Ceiling, Wall, Floor and Ceiling Type

Item

RPI (0.8-5.0HP), RPK (0.8-4.0HP), RPC (2.0-5.0HP), RPF (1.0-2.5HP), RPFI (1.0-2.5HP)

Receiver Kit for Wireless Control (with 5m cable) PC-RLH11 (wall mounted)

Control System Compatibility

Item Remote Control Switch*1 PC-P1H (without cable) Wireless Remote Control Switch*2 Half-size Remote Control Switch 7-Day Timer Centralised Remote Control Switch*3 Remote Control Cable PSC-5S PC-P5H PSC-5T PC-LH3A (new)

RPI-FSN

RCI-FSN

RCD-FSN

RPK-FSN

RPC-FSN

RPF(I)-FSN

KPI

PRC-10E1, 15E1, 20E1, 30E1 for PC-P1H

3P Connector Cable Remote Sensor Computer Controlled Network System

PCC-1A THM-R2A

CS-NET

*1 As the PC-P1H does not include a remote control cable, prepare one in the field, or use PRC-10E1, 15E1, 20E1, 30E1. *2 PC-LH3 can be used instead of PC-LH3A. *3 Supply 220V or 240V

Set Free Selection Software Hi-toolKit

Quick and reliable Simple and user friendly Free of charge

Hitachi has developed a new programme to design Set Free systems which meet building consultants and technical advisors requirements. The software allows the user to proceed quickly and easily through the phases of selection of a system through to the complete project. Your project in just 6 clicks... Product Selection This software allows the user the flexibility to choose the required number of indoor and outdoor units and control systems either by model or capacity. Refrigeration Schematic Automatic calculation of pipe sizes and multikits. Option for automatic or manual drawings which can be exported into CAD software. Electrical Drawing Electrical drawing showing the power supply, communication cables, accessories and control systems. Specification Using the selected information the software allows the user to produce a full product specification in word format. Schedule of Equipment This shows a list of the number of Hitachi systems chosen, pipework and wiring digrams and the refrigerant charge required.

Hi-toolKit

Commissioning Automatically produces dip switch settings, equipment list and commissioning checklist.

45

Set Free Multimedia

The Set Free Multimedia software has been specifically designed in order to help promote Hitachi Set Free VRF to consultants and end users. Features & Benefits Guide Technical explanations of key components Selection Programme Examples of installations across Europe. The multimedia is user friendly and is based around sophisticated 3D computer animation and audio commentary A useful presentation mode is also available which is ideal for presenting to customers.

47

Specifications in this catalogue are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. Omitting typing errors. Hitachi Europe Ltd Whitebrook Park Lower Cookham Road Maidenhead Berkshire SL6 8YA United Kingdom

Distributed by:

email: aircon.enquiries@hitachi-eu.com www.hitachiaircon.com

HELGB-SF-004

You might also like