Internally Fused Capacitor Bank Unbalance Calculations

Date : 17-Nov-08
Customer: SSEM/ Saudi Electricity Company
Bank Catalog Number : CEB08037N0308F1
SystemOperating Voltage :
System Frequency :
Reactor :
Capacitor Unit Construction
Rated kVAR :
705
Rated Voltage :
10987
# Series Groups :
5
# Parallel Packs :
15

33 kV
60 Hz.
14.00 mH

Su
Nu

S
Pt
Pa
P
G

Rated Capacitance :
15.492
uF
Rated Group Cap. :
77.459
uF
Show Difference Current (Y/N) :
N
f
Ve
%Ve
Vcu
%Vcu
% of
Number
Nominal
% of
of
Affected
Affected Affected Nominal
Operated Elements Elements
Unit
Unit
Fuses
Voltage
Voltage
Voltage Voltage
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14

1998
2127
2273
2442
2638
2867
3141
3472
3882
4400
5079
6005
7345
9454
13261

100.0%
106.5%
113.8%
122.3%
132.0%
143.5%
157.2%
173.8%
194.3%
220.3%
254.3%
300.6%
367.7%
473.3%
663.9%

9988
10066
10155
10257
10375
10514
10679
10880
11127
11441
11851
12411
13221
14496
16798

Suggested Unbalance Settings


Setting (A) Time (sec.)
Alarm :
0.63
5.00
Trip :
1.42
0.10
Calculations based on IEEE C37.99-2000.

100.0%
100.8%
101.7%
102.7%
103.9%
105.3%
106.9%
108.9%
111.4%
114.5%
118.7%
124.3%
132.4%
145.1%
168.2%

Bank Construction
Rated Bank Voltage (kV) :
38.1
Rated 3 Phase kVAR :
12690
# Series Groups :
2
# Parallel Units / Phase :
3
# Parallel Units / Phase in Left Wye :
1
Parallel Units in Affected String :
1
0=Grounded, 1=Ungrounded wye* :
1
Note: Failures are always calculated in Left Wye.
Id
Vng
In
Ig
Difference
Neutral
in Neutral
Neutral to
Current
Neutral to
Current,
Ground
Ground
Between
Equal
Voltage
Wyes (A)
Current
Wyes
0.00
15.75
33.68
54.27
78.15
106.20
139.60
180.04
230.02
293.35
376.22
489.32
652.88
910.36
1375.25

CTR:
Relay:

0.00
0.28
0.59
0.95
1.37
1.86
2.45
3.15
4.03
5.14
6.59
8.57
11.44
15.95
24.10

Internally Fused Capacitor Bank Unbalance Calculations


Date : 17-Nov-08
Customer: SSEM/ Saudi Electricity Company
Bank Catalog Number : CEB08037N0308F1
SystemOperating Voltage :
System Frequency :
Reactor :
Capacitor Unit Construction
Rated kVAR :
705
Rated Voltage :
10987
# Series Groups :
5
# Parallel Packs :
15

33 kV
60 Hz.
14.00 mH

Su
Nu

S
Pt
Pa
P
G

Rated Capacitance :
15.492
uF
Rated Group Cap. :
77.459
uF
Show Difference Current (Y/N) :
N
f
Ve
%Ve
Vcu
%Vcu
% of
Number
Nominal
% of
of
Affected
Affected Affected Nominal
Operated Elements Elements
Unit
Unit
Fuses
Voltage
Voltage
Voltage Voltage
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14

1998
2119
2256
2413
2592
2800
3045
3337
3690
4127
4682
5409
6403
7845
10125

100.0%
106.1%
113.0%
120.8%
129.8%
140.2%
152.4%
167.0%
184.7%
206.6%
234.4%
270.8%
320.5%
392.7%
506.8%

9988
10030
10078
10133
10196
10268
10354
10456
10579
10731
10925
11179
11526
12029
12825

Suggested Unbalance Settings


Setting (A) Time (sec.)
Alarm :
0.63
5.00
Trip :
1.42
0.10
Calculations based on IEEE C37.99-2000.

100.0%
100.4%
100.9%
101.5%
102.1%
102.8%
103.7%
104.7%
105.9%
107.4%
109.4%
111.9%
115.4%
120.4%
128.4%

Bank Construction
Rated Bank Voltage (kV) :
38.1
Rated 3 Phase kVAR :
12690
# Series Groups :
2
# Parallel Units / Phase :
3
# Parallel Units / Phase in Left Wye :
2
Parallel Units in Affected String :
2
0=Grounded, 1=Ungrounded wye* :
1
Note: Failures are always calculated in Left Wye.
Id
Vng
In
Ig
Difference
Neutral
in Neutral
Neutral to
Current
Neutral to
Current,
Ground
Ground
Between
Equal
Voltage
Wyes (A)
Current
Wyes
0.00
15.70
33.43
53.61
76.80
103.72
135.34
173.02
218.68
275.17
346.83
440.74
569.17
755.44
1049.97

CTR:
Relay:

0.00
0.14
0.29
0.47
0.67
0.91
1.19
1.52
1.92
2.41
3.04
3.86
4.99
6.62
9.20

Internally Fused Capacitor Bank Unbalance Calculations


Date : 17-Nov-08
Customer: SSEM/ Saudi Electricity Company
Bank Catalog Number : CEB08038N0304F1
SystemOperating Voltage :
System Frequency :
Reactor :
Capacitor Unit Construction
Rated kVAR :
742
Rated Voltage :
9199
# Series Groups :
4
# Parallel Packs :
12

13.8 kV
60 Hz.
3.48 mH

Su
Nu

S
Pt
Pa
P
G

Rated Capacitance :
23.259
uF
Rated Group Cap. :
93.036
uF
Show Difference Current (Y/N) :
N
f
Ve
%Ve
Vcu
%Vcu
% of
Number
Nominal
% of
of
Affected
Affected Affected Nominal
Operated Elements Elements
Unit
Unit
Fuses
Voltage
Voltage
Voltage Voltage
0
1
2
3
4
5
6
7
8
9
10
11

2088
2231
2395
2585
2807
3072
3392
3786
4283
4932
5811
7072

100.0%
106.8%
114.7%
123.8%
134.5%
147.1%
162.4%
181.3%
205.1%
236.2%
278.3%
338.7%

8352
8366
8382
8400
8422
8448
8479
8518
8567
8630
8716
8840

Suggested Unbalance Settings


Setting (A) Time (sec.)
Alarm :
3.50
5.00
Trip :
6.50
0.10
Calculations based on IEEE C37.99-2000.

100.0%
100.2%
100.4%
100.6%
100.8%
101.2%
101.5%
102.0%
102.6%
103.3%
104.4%
105.8%

Bank Construction
Rated Bank Voltage (kV) :
15.9
Rated 3 Phase kVAR :
8904
# Series Groups :
1
# Parallel Units / Phase :
4
# Parallel Units / Phase in Left Wye :
2
Parallel Units in Affected String :
2
0=Grounded, 1=Ungrounded wye* :
1
Note: Failures are always calculated in Left Wye.
Id
Vng
In
Ig
Difference
Neutral
in Neutral
Neutral to
Current
Neutral to
Current,
Ground
Ground
Between
Equal
Voltage
Wyes (A)
Current
Wyes
0.00
15.49
33.26
53.85
77.98
106.67
141.32
184.03
237.97
308.22
403.53
540.21

CTR:
Relay:

0.00
0.82
1.75
2.83
4.10
5.61
7.44
9.68
12.52
16.22
21.23
28.42

0.000
1.630
3.500
5.666
8.206
11.224
14.870
19.364
25.039
32.432
42.460
56.842