Report: Titel:
Thermal calculation Technical opinion regarding the approval of walls made of Panelit 3D panels
Applicant:
Persons in charge: Leader of working group: Scientific leader: Verification: Start of testing: End of testing: Number of test reports: April 1999 April 1999 3 copies prof.dr hab.inz. Jerzy A.Pogorzelski prof.dr hab.inz. Jerzy A.Pogorzelski
Comments:
TECHNICAL OPINION REGARDING THE APPROVAL OF WALLS MADE OF PANELIT 3D PANELS 1 General 1.1 Basic: commission by the company Aqua International of 29.03.1999 1.2 Subject: walls with 3 layers built with Panelit 3D Panels 1.3 Extent: calculation of thermal conductance made by the company EVG and own calculations 1.4 Materials in use: acc. to: 1 Previous opinion NF-613/A/9 2 Letter from the company Aqua International, 29.03.1999 3 Calculations made by the company EVG Specification of materials according to appendix 2 Discussion of calculations made by the company EVG Calculations acc. to EN ISO 6946, paragraph 6.2 are not applicable because the heat insulation (EPS) is pierced through by steel wires (see sentence 1, paragraph 6.2). 3 Own calculations Calculations acc. to paragraphs 5.1, 5.2 and 7, additional enclosure D.3 PN-EN ISO 6946
RT = 0.13 + 0.10 0.12 + + 0.04 = 3.66 m K / W 1.7 0.035 1 = 0.273 W /(m K) 3.66
U =
Uf = f nf Af = 0.066 W /(m K)
Uk = 0.34 W /(m K)
4 Application Verification of legal limits in accordance with legal regulations for residential buildings.
If heat insulation is penetrated by mechanical fixing devices, the correction value of thermal conductance results in:
where:
APPENDIX 2: Calculation by ITB is based on the configuration below (according to item 1.4, Materials in use)
25 = 10 cm concrete (0.10m; = 1.7W/mK) 12 cm EPS (0.12m; = 0.035W/mK) Thermal transition resistance at the inner surface =0.13 mK/W Thermal transition resistance at the outer surface =0.04 mK/W = 6 m-1 (anchors for walls) f = 17 W/mK (stainless steel) nf = 67 diagonals/m Af = 0.0962 cm (diameter of diagonals is 3.5 mm)
3D Construction System
Thermal Resistance
Thermal insulation of EVG-3D walls has to be calculated as sandwich panel with steel connectors. Basis of calculation is EN ISO 6946, appendix D.3. Standard panel for external walls This type of panel is commonly used for external walls of residential buildings. 100mm (4) EPS, 100 diagonals per m (3.8mm, galvanised): U = 0.70 W/mK (0.123 Btu/ fthF) R = 1.43 mK/W (8.12 fthF/Btu)
50 100 50 3.8mm, galvanised
100mm EPS
Panel with maximum heat insulation This panel type is used for external walls in very cold climates and in areas with extremely hot climate. 150mm (6) EPS, 67 diagonals per m (3.5mm, stainless steel): U = 0.29 W/mK (0.050 Btu/ fthF) R = 3.49 mK/W (20.1 fthF/Btu)
50 150 50 3.5mm, stainless
150mm EPS
Brick walls and concrete frames Conventional walls usually consist of reinforced concrete frames (beams and columns) and brick walls in between. Thermal resistance depends on the ratio of the area of bricks and the area of concrete frames, thickness of walls, and design of bricks (especially number, size, and arrangement of voids inside the brick). Due to all these factors thermal resistance of brick walls varies within a certain range and can be estimated only. For brick walls having a thickness of 200 to 250mm, thermal resistance usually lies in the range of 0.6 to 0.8 mK/W (3.4 - 4.5 fthF/Btu). Therefore, for further calculations the U-value of an average brick wall within a reinforced concrete frame shall be assumed as follows: U = 1.40 W/mK (0.247 Btu/ fthF) R = 0.71 W/mK (4.06 fthF/Btu)
Peheim, 04.09.2006
SAUDI_15.DOC
Energy Consumption
Energy consumption depends, among other factors, on the average outside temperature, required inside temperature, and on the number and size of walls exposed to direct sunlight. Some factors depend on the design of a building and cannot be assumed in general for all buildings. However, the effect of these factors shall be estimated. Basic data regarding climate in Saudi Arabia has been obtained by the German National Weather Service. Maximum average temperature (over a period of 24 hours and 30 days) is assumed to be 32C (Jeddah). According to statistical data this average outside temperature can be assumed for 240 days per year. The difference between inside (20C) and outside is 12C. Since the influence of walls exposed to direct sunlight depends on the design of the building, this influence can be estimated only. Walls exposed directly to sunlight will have a much higher temperature on the surface which leads to a higher heat flux from outside to inside. This additional heat flux will be estimated by adding 3C to the average difference between inside and outside.
Total heat energy transfer through the external wall per year EVG-3D wall (100mm EPS): U = 0.70 W/mK W = (12+3C)240d24h/d0.70W/mK = 60.5 kWh/m EVG-3D wall (150mm EPS): U = 0.29 W/mK W = (12+3C)240d24h/d0.70W/mK = 25.1 kWh/m average brick wall and frame: U = 1.40 W/mK W = (12+3C)240d24h/d0.70W/mK = 121.0 kWh/m
Difference of heat transmittance per year For a villa with 450m of living area the total area of outside walls shall be estimated as being 450m, as well. This number is based on experience and can vary depending on the architectural design. Difference in heat flux between EVG-3D buildings and conventional buildings is as follows: Standard EVG-3D wall (100mm EPS) - conventional brick wall W = (121.0 - 60.5)450 = 27 000 kWh/year Maximum EVG-3D wall (150mm EPS) - conventional brick wall W = (121.0 - 25.1)450 = 43 000 kWh/year Above values represent the additional heat energy entering an average building with 450m of living area through the external walls when using conventional brick walls instead of EVG-3D walls. Additional consumption of electrical energy depends on thermal efficiency of A/C machines and cannot be estimated.
Peheim, 04.09.2006 SAUDI_15.DOC
Heat energy transfer through the external EVG-3D wall (100mm EPS): U = 0.70 W/mK W = (29+8C)450m0.70W/mK = 11.7 kW EVG-3D wall (150mm EPS): U = 0.29 W/mK W = (29+8C)450m0.29W/mK = 4.8 kW average brick wall and frame: U = 1.40 W/mK W = (29+8C)450m1.40W/mK = 23.3 kW
Difference of maximum cooling load For a villa with 450m of living area the difference in maximum cooling load between EVG-3D buildings and conventional buildings is as follows: Standard EVG-3D wall (100mm EPS) - conventional brick wall P = 23.3 - 11.7 = 11.7 kW Maximum EVG-3D wall (150mm EPS) - conventional brick wall P = 22.3 - 4.8 = 18.5 kW Above values represent the additional A/C capacity required to cool down a building during the hottest days of a year when using conventional brick walls instead of EVG3D walls. Subsequent design of A/C machines depends on thermal efficiency of these machines and cannot be estimated.
Peheim, 04.09.2006
SAUDI_15.DOC
Peheim, 04.09.2006
SAUDI_15.DOC
Appendix
Climate data for Jeddah, Saudi Arabia by the German National Weather Service. CLIMATE DATABASE Jeddah (Dschidda) (Saudi Arabia)
average average days> abs. daily average daily abs. rel. average average 1.0 average max. max. daily min. min. humid. watert. rainfall mm daily h. in C in C in C in C in C in % in C in mm rainfall sunshine 34.0 28.5 23.3 19.0 11.4 66 k.A. 14.7 1 0.0 36.0 29.1 23.4 18.7 11.6 60 k.A. 7.5 0.2 0.0 42.0 31.0 25.4 20.4 13.0 58 k.A. 1.8 0.4 0.0 44.5 33.5 27.5 22.2 14.0 57 k.A. 5.7 0.3 0.0 48.2 35.4 29.6 24.5 16.4 57 k.A. 1.1 0.2 0.0 49.0 36.6 30.8 25.3 20.0 59 k.A. 0 0 0.0 45.0 37.7 32.0 26.7 21.1 56 k.A. 0.1 -0.1 0.0 44.0 37.2 32.0 27.2 22.3 59 k.A. 0 0 0.0 48.0 35.8 31.0 26.2 20.3 68 k.A. -0.1 -0.1 0.0 44.5 34.9 29.2 24.2 15.6 67 k.A. 0.3 0.1 0.0 38.0 32.4 27.2 22.2 15.5 62 k.A. 12.2 1 0.0 36.0 29.6 24.7 20.0 11.4 60 k.A. 10.7 0.6 0.0 49.0 33.5 28.0 23.1 11.4 61 k.A. 54 4 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Year
Thermal Capacity of Standard Wall Panels (100mm EPS, 100 truss wires)