Professional Documents
Culture Documents
causes
leading (capacitive) current
C
I
, accounts
for the losses in the resistance of the inductor coil and the
power electronic converter. Ideally, if the system losses can
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
135
be minimized to zero,
a C
I
_
would be leading at perfect quadrature. Then,
oa
V
, which is
lagging and greater than
sa
V
+
+
=
2 / 1 2 / 1 2 / 1
) 3 / 2 ( ) 3 / 2 ( ) (
) 3 / 2 ( ) 3 / 2 ( ) (
3
2
t = t = =
t = t = =
t Sin t Sin t Sin
t Cos t Cos t Cos
K (1)
The actual proposed circuit is too complex to analyze as a
whole, so that it is partitioned into several basic subcircuits,
as shown in Fig.1. The 3-phase system voltage
abc s
V
,
lagging with the phase angle o to the STATCOM output
voltage
abc o
V
,
and differential form of the STATCOM
currents are defined in (2) and (3).
3
2
(
)
3
2
(
) (
3
2
,
(
(
(
(
(
(
(
(
(
+
= =
t
o e
t
o e
o e
t Sin
t Sin
t Sin
s
V
sc
V
sb
V
sa
V
abc s
V
(2)
( )
abc o
V
abc s
V
abc c
i
s
R
abc c
i
dt
d
s
L
,. , , ,
+ = (3)
Where,
s s
R V , ,= and
s
L have their usual connotations.
The above voltages and currents are transformed into dq
frame to give,
| |
T
Cos Sin
s
V
qdo s
V 0
,
o o = (4)
( )
oq sq cd s cq s cq s
V V i L i R i
dt
d
L + = e (5a)
( )
od sd cd s cq s cd s
V V i R i L i
dt
d
L + =e (5b)
The switching function S of the STATCOM can be defined
as follows
(
(
(
(
(
(
+
=
(
(
(
=
)
3
2
(
)
3
2
(
) (
3
2
t
e
t
e
e
t Sin
t Sin
t Sin
m
S
S
S
S
c
b
a
(6)
The modulation index, being constant for a programmed
PWM, is given by,
m
dc
v
peak o
V
MI
3
2 ,
= = (7)
The STATCOM output voltages and dq transformation are
given by,
dc
Sv
abc o
V =
.
(8)
| |
dc
v
T
m
qdo o
V 0 1 0
,
= (9)
The dc side current in the capacitor and its dq
transformation may be written as,
abc c
T
dc
i S i
,
= (10)
| |
T
co
i
cd
i
cq
i m
dc
i
(
= 0 1 0
(11)
The voltage and current related in the dc side is given by
dt
dv
C i
dc
dc
= (12)
Now replacing (11) in (12) yields
cd
dc
i
C
m
dt
dv
= (13)
The complete mathematical model of the STATCOM in dq
frame is obtained as given in (14)
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
136
(
(
(
+
(
(
(
(
(
(
(
(
(
(
(
=
(
(
(
0
0 0
0
o
o
e
e
Cos
Sin
s
L
s
V
dc
v
cd
i
cq
i
C
m
s
L
m
s
L
s
R
s
L
s
R
dc
v
cd
i
cq
i
dt
d
(14)
C. Steady State Analysis
The steady state equations of
cq
I ,
cd
I ,
dc
V ,
c
P ,
c
Q are given
in (15-16) and their responses with the parameters given in
Table 1, are shown in Fig.3. The theoretical results of (15-
16) are verified by the simulation results.
|
|
.
|
\
|
=
= =
o
e
o
o
Sin
s
R
s
L
Cos
M
s
V
dc
V
cd
I
s
R
Sin
s
V
cq
I 0 ,
(15)
( ) | |
( ) o
o
2
2
2
2 1
2
2
Sin
s
R
s
V
c
Q
Cos
s
R
s
V
c
P
=
=
(16)
Table.1
Sl Parameters Symbol Values
1 Frequency
f
50 Hz
2 Angular Frequency e 314 rad/sec
3 RMS line-to-line Voltage
s
V
415V
4 Coupling Resistance
s
R
1.0 O
5 Coupling Inductance
s
L
5.0mH
6 DClink capacitor C
500 F
7 Modulation Index M 0.979
8 Phase angle o 0
5
9 Load Resistance
L
R O 52
10 Load Inductance
L
L
mH 126
11 Load Power factor
|
79 . 0
D. Transient Analysis
The transient responses of the system in (14) are simulated
in MATLAB for an initial condition of V
dc
v 100 = and the
parameters given in Table.1 and are shown in Fig.4 to Fig.5.
(a) (b)
Fig.3: Steady State Response: (a)
cq
I
cd
I and
dc
V and (b)
c
P and
c
Q
(a) (b)
Fig.4: Transient Responses: (a)
cq
i and (b)
cd
i
Fig.5: Transient Response of
dc
v
It can be seen that the transient responses take about one and
half power cycle to reach at their steady state values.
III. SMALL SIGNAL MODEL
A. Modeling
For a given operating point, small signal equivalent circuit is
derived based on the following assumption:
i) The disturbance is small,
ii) Hence, the second order terms (products of
variations) are negligible,
iii) The phase nominal value of angle o is small.
With the above assumptions equations. (9) and (11) can be
rewritten as,
dc
v m
dc
V m
dc
v M
dc
MV t
od
v
od
V ) ( + + + = + (17)
cd
i M
cd
MI
dc
i
dc
I
+ = + (18)
o o = Sin ,
1 = o Cos
and 0
0
= o (19)
By using (5), (17), (18) and (19), and applying Laplace
Transformation, we have,
(
(
(
=
(
(
(
(
(
(
+
+
0
) (
) (
0
0
s m V
s V
v
i
i
sC M
M R sL L
L R sL
dc
s
dc
cd
cq
s s s
s s s
o
e
e
(20)
The important transfer functions of the states of the
STATCOM in small signal model can be derived as
) ( ) (
) (
s A
C
s
L
dc
V
s m
s
cq
i e
= (21a)
) (
)
2 2
(
) (
) (
s A
M C
s
R Cs
s
L
s
V
s
s
cq
i
+ +
=
o
(21b)
) (
) (
) (
) (
s A
s
s
R
s
sL C
dc
V
s m
s
cd
i +
= (22a)
) ( ) (
) (
s A
Cs
s
L
dc
V
s
s
cd
i e
o
= (22
b)
) (
) (
) (
) (
s A
s
R
s
sL
dc
MV
s m
s
dc
v +
= (23a)
) ( ) (
) (
s A
s
L
s
MV
s
s
dc
v e
o
= (23b)
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
137
e e
s
R M s
s
L M
s
L
s
R C s
s
CR
s
L s
s
CL s A
2
]
2
}
2
) (
2
{ [
2
2
3 2
) ( + + + + + =
B. Open loop Responses
The
cq
i
,
cd
i
and
dc
v in (21-23) are simulated in MATLAB
with the same parameters given in Table.1 and
also ) ( 5 t u = o and ) ( 1 . 0 t u m = .The responses are shown in
Figs.6 to 7.
(a) (b)
Fig.6: Step Response: (a)
cq
i
Control Block
Fig.9: Proposed Implementing Block
IV. SIMULATION RESULTS
A. Simulation of linear load
The grid phase A voltage and linear load phase A current is
given in Fig.10. It is depicted that power factor of the load is
0.79 and hence at grid also. This power factor will be
improved by using the proposed control strategy and the
effect of variation of DC link voltage.
Fig.10: Grid Phases a Voltage and Phases a Load Current
B. DC- link capacitor charged to 100V:
The controller works and STATCOM functions at the
initial DC link voltage of capacitor 100V with a large spike
at the starting position as shown in Fig.11 of grid phase A
voltage and current It is seen that the power factor improves
from 0.79 as per the L R load taken to unity after one
power cycle as given in Fig.11 (for phase A) as compared to
Fig.10 with a spike of 128A. Fig.12 shows the dynamics of
grid phase A voltage and the STATCOM phase A current
with a spike of 115A.
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
138
Fig.11: Grid Phase a Voltage And Phase a Current
Fig.12: Grid Phase a Voltage and STATCOM Phase a Current
C.DC- link capacitor charged to 550V:
The same model is simulated with initial DC link voltage
of 550V. It is seen that the power factor improves from 0.79
as per the R-L load taken to unity at the starting position
with a current spike of 18A as given in Fig.13 (for phase A)
as compared to Fig.10. Fig.14 shows the dynamics of the
STATCOM current without current spike at the starting
position. Figs.15 and 16 show the dynamics of d and q
axis current of the STATCOM and its transient nature which
dies after half a power cycle. The active and reactive power
generated by the STATCOM is shown in Fig.17 and its
transient nature is shown in Fig.18 respectively. Fig.19
shows that the maximum overshoot of DC link voltage is to
610 volts only. Figs.20 and 21 show the corresponding
dynamics of incremental phase angle ' 'o and incremental
modulation index ' ' m respectively. The grid phase A voltage
and STATCOM phase A output voltage is shown in Fig.22
which shows the STATCOM output voltage is greater than
the grid phase A voltage and lagging with very small angle
which is shown in Fig.23. With the small perturbation of
reference current as shown in Fig.24 (reactive current of
load), very small change in DC link voltage is obtained and
when the reference current goes to its original value the DC
link voltage also returns to its steady state value as shown in
Fig.25.
Fig.13: Grid Phase a Voltage and Phase a Current
Fig.14: Grid Phase a Voltage and STATCOM Phase Current
Fig.15: Active and Reactive Components of STATCOM Current
Fig.16: Active and Reactive Components of STATCOM Current in
Expansion
Fig.17: Active and Reactive Power Generated By STATCOM
Fig.18: Active and Reactive Power Generated By STATCOM
in Expansion
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
139
Fig.19: DC Link Voltage of STATCOM
Fig.20: Variation of Incremental of Phase Angle o
Fig.21: Variation of Incremental of Modulation Index m
Fig.22: Grid Phase a Voltage and STATCOM Phase
an Output Voltage
Fig.23: Grid Phase a Voltage and STATCOM Phase an Output Voltage
in Expansion
Fig.24: With Change of Load Reactive Current and STATCOM Reactive
Current
Fig.25: DC Link Voltage of STATCOM with Change of Reference
D.DC- link capacitor charged to 600V:
Once again the proposed model is simulated with initial
DC link voltage of 600V.The relevant responses is obtained
without any spike at the starting position as shown Fig.26 of
grid phase a voltage and phase a current.
Fig.26: Grid Phase a Voltage and Phase a Current
V CONCLUSION
In this paper, the STATCOM model has been linearized
by small signal scheme with nominal value of ' ' o and ' ' m .
The system with controller operates transient to steady state
value on 0.03 sec. in case of small signal scheme. The
ISSN: 2277-3754
ISO 9001:2008 Certified
International Journal of Engineering and Innovative Technology (IJEIT)
Volume 2, Issue 5, November 2012
140
transient overshot nearly 525V in case of small signal
scheme. With the small perturbation of reference current
(reactive current of load),very small change in DC link
voltage is obtained as shown in Fig.25 and when the
reference current goes to its original value, the DC link
voltage immediate jumps to its steady state value. The
variation of DC link voltage is applied to the STATCOM
model and higher the DC link voltage lesser is the spike of
the responses. The suitable and appropriate DC link voltage
has been selected as 600V.On overall, the small signal
scheme is better for the operation of the STATCOM in
compensating mode. It must be pointed out that all the
results present here are on the basis of the assumption that
the DC link voltage has stabilized to some significant value
before the control can be applied. However, in practice the
issue of the charging the DC-link voltage to the required
value is quite significant.
REFERENCES
[1] C.L.Wadhwa, Electrical Power Systems, W.Eastern Ltd,
New Delhi,
[2] P.Kundur Power System Stability and Control, EPRI,
P.E.Series, 1994.
[3] M.K.Pal, Voltage Stability Conditions Considering Load
Characteristic,
[4] IEEE Transactions on Power Systems, Vol.7, No.1, pp.243-
249, Feb.1992.
[5] T.V.Cutsem and C.D.Vournas,Voltage Stability analysis in
transient and mid-term time scales, IEEE Transactions on
Power Systems, Vol.11, No.1, pp.146-154, Feb.1994.
[6] T.J.E.Miller Reactive Power Control in Electric Systems
J.Wiley, 1982.
[7] K.R.Padiyar, Power System Dynamics-Stability and
Control, Interline Publishing Ltd, Bangalore, 1996.
[8] C.W.Taylor and A.L.V.Leuven, CAPS: Improving Power
System Stability Using the Time-Over voltage Capability of
Large shunt Capacitor Banks, IEEE Transactions on Power
Delivery, Vol.11, No.2, pp.783-792, April 1996.
[9] Y.H. Song and A.T.John Flexible AC Transmission Systems
(FACTS) IEE Power and Energy series Inc. 1999.
[10] N.G.Hingorani and L.Gyugyi, Understanding FACTS, IEEE
PES, Sponsor, Standard Publishers Distributors New Delhi,
1999.
[11] R.M.Mathur and R.K.Varma, Thyristor based FACTS
Controllers for Electrical Transmission Systems, IEEE Power
Engineering Society, Sponsored, Wiley Interscience, 2002.
[12] A.T. Johns, A.Ter-Gazarian and D.F.Wame,Flexible ac
transmission systems (FACTS), IEE Power and Energy
Series, London, U.K.
[13] R.M.Mathur and R.K. Varma, Thyristors-based FACTS
Controllers for Electrical Transmission Systems, IEEE Press,
Wiley-Interscience Publication.
[14] L.T. Moran, P.D.Ziogas and G.Joos, Analysis and Design of
a Three-Phase Synchronous Solid- State Var Compansator,
IEEE Trans. Industry Application, Vol. 25, No. 4, 1989, pp.
598-608.
[15] C.Shauder and H.Mehta, Vector analysis and control of
advanced static VAR compensators, IEE Proc, 140, No. 4,
July 1993.
[16] A. Draou, M. Benghanem and A. Tahiri, Multilevel
Converter and VAR Compensation, Power Electronics
Handbook, pp.599-611, Academic Press, 2001.
[17] M.Sengupta,J.K Moharana and A.Sengupta, Study on an
Advanced Static VAR Compensator switched from a Space
Vector PWM inverter Analysis, simulation and comparison
with the conventional sinusoidal PWM, NPEC 2003, IIT
Bombay,16-17 Oct 03 pp 72-78.
[18] G.C.Cho, N.S.choi, C.T.Rim, and G.H.Cho, Modeling,
Analysis and Control of STATIC VAR Compensator using
three level inverter, IEEE, Ind.Socity, Annual Meet,
page837-843, 1992.
[19] G.C.Cho,N.S.choi,C.T.Rim,and G.H.Cho, Analysis and
Controller Design of STATIC VAR Compensator Using
Three-Level GTO Inverter,IEEE,Transations on Power
Electronics,Vol.11,No.1,page57-65,January 1996.
[20] D.M.Brod and D.W.Novotny, Current control of VSI-
PWMinverterIEEETrans.Industrial Appl, Vol.IA-21, pp.562-
570, July/Aug.1985.
[21] S.Buso, L.Malesani and P.Mattavelli, Comparison of Current
Control Techniques for Active Filter
ApplicationIEEETrans.Industrial Electronics, Vol.45, No.5,
pp.722-729, October 1998.
[22] P.S.sensarma, K.R.Padiyar and V.Ramnarayanan, Analysis
and Performance Evaluation of a Distribution STATCOM for
Compensating Voltage Fluctuations, IEEE Transaction on
Power Delivery, Vol.16, No.2, pp.259- 264, April 2001
[23] A.M. Kulkarni and K.R. Padiyara, Design of Reactive
Current and Voltage Controllers of Static Condenser, Power
and Energy System, Vol.19, No.6, pp.397-410, 1997
[24] S.K.Das and J.K.Moharana Modeling, Design Analysis and
Simulation of Small Signal Control Strategy on a STATCOM
for Reactive Power Compensation, NSPEES-12,Sept.29-
30,GIET,BBSR,pp-17-23,2012
AUTHORS PROFILE
Sarat Kumar Das was born on 20
th
Feb 1982 in patanaraipur, Remuna,
Balasore, Odisha, India. He obtained his 10
TH
from J.N.V, Bagudi, and
Balasore in 1998 and +2 SC FROM S.C.C, Mitrapur, Balasore in 2000. He
got his Bachelors degree (B.Tech) in Electrical Engineering from CET,
Bhubaneswar in 2007. He completed his Masters degree in Power
Electronics & Drives from Bengal Engineering and Science University,
Shibpur, Howrah, West Bengal in 2010. His research interests include
Power Electronics and its application to high performance of FACTS
devices, especially in the STATCOM.
Jayakrushna Moharana was born on 17
th
June 1964 in Khirkona, Balasore,
and Odisha, India. He obtained his HSC from U.N.Academy, Khirkona, and
Balasore in 1980. He also obtained his Intermediate and Bachelors degree
in Science (Chemistry) from Bhadrak College, Bhadrak under Utkal
University, Odisha in the year 1982 and 1984 respectively. He got his
Bachelors degree (equivalent) in Electrical Engineering from Institution of
Engineers, Kolkata, West Bengal in 1990. He completed his Masters
degree as well as Ph.D in Power Electronics from Bengal Engineering and
Science University, Shibpur, Howrah, West Bengal in 1999 and 2012. His
research interests include Power Electronics and its application to high
performance of FACTS devices, especially in the STATCOM.