8610 Configuration

Page 1 of 77

8610 Configuration
Module Module Options Description 1 2 3 4 Mac& Rains Pharmaceutical Jenbacher Gas Generator JW-316 Pyramid Automation (Zahid)

LED Indicators Insert Card Text Common Alarm Lube Oil Filling Kw over Cooling Tower

1 2 3 4

Common Alarm Digital Input B kW Overload Warning Not Used

Lit Lit Lit Lit

Miscellaneous Options Enable fast loading feature Audible alarm prior to starting All warnings are latched Enable sleep mode Enable manual fuel pump control Support right-to-left languages in module strings Configurable Status Screens Home Page Home Page Mode Displayed Pages Page 1 Page 2 Page 3 Page 4 Page 5 Event Log Display Options Module display Date and time Logging Options Log the following events to the event log Power up Yes Summary Screen Not Used Not Used Not Used Not Used Page 6 Page 7 Page 8 Page 9 Page 10 Not Used Not Used Not Used Not Used Not Used No No No No No No

about:blank

9/19/2013

8610 Configuration

Page 2 of 77

ECU Shutdown alarms Shutdown alarms Electrical trip alarms Log Fuel Level Log When At Rest Data Logging Configuration Data Logging Logged data 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Options Data Log Options

Yes Yes Yes Yes Yes

Latched warnings Yes Unlatched warnings Yes

DC Power On Gen Total Power Gen Current L1 Gen Volts (L1-N) <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

Log Interval 1 minute 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second 1 second

Only log when engine is running Yes Log to USB drive No Keep oldest data No

about:blank

9/19/2013

8610 Configuration

Page 3 of 77

Application ECU (ECM) Options Engine Type Enhanced J1939 Alternative Engine Speed Modbus Engine Comms Port Auto Voltage Sensing Enable Auto Voltage Sensing No Over Voltage During Auto Sensing Trip 277 V PhN Conventional Engine No No RS485 Port

about:blank

9/19/2013

8610 Configuration

Page 4 of 77

Inputs Oil Pressure Input Type Use Module to Measure Oil Pressure No VDO 10 Bar Low Oil Pressure Alarms Alarm Enabled Trip 1.03Bar, 14.94 PSI, 103 kPa Pre-alarm Enabled Trip 1.24Bar, 17.98 PSI, 124 kPa Return 1.38Bar, 20.01 PSI, 138 kPa Coolant Temperature Coolant Temperature Alarm Sender Usage Use sensor as Temperature sensor Input Type Use Module to Measure Coolant Temperature No VDO 120 C Open Circuit Alarm Enable Yes High Coolant Temperature Alarms Alarm Trip 91 C, 196 F Electrical Trip Yes Trip 90 C, 194 F 194 F Pre-alarm Yes Trip 85 C, 185 F Return 82 C, 180 F Low Coolant Temperature Alarms Pre-alarm No Return 75 C, 167 F Trip 70 C, 158 F Coolant Temperature Control

about:blank

9/19/2013

8610 Configuration

Page 5 of 77

Coolant Heater Control Enable No On 50 C, 122 F Off 55 C, 131 F Coolant Cooler Control Enable No Off 70 C, 158 F On 75 C, 167 F Disable when set not available No Fan Control Fan Overrun Delay 0s Fuel Level Sender Usage Use sender as Fuel level sensor Input Type Not used Low Fuel Level Alarm Enable Action Warning Trip 10 % Delay 0s Fuel Pump Control Enable No On 25 % Off 75 % Fuel Monitoring Fuel Tank Size Litres Logging Interval Dial Out On Logging Stable Timer Change Indicating Filling Change Indicating Stable 1000 1m No 0.5s 1% 1% No

about:blank

9/19/2013

8610 Configuration

Page 6 of 77

Fuel Usage Alarm Enable Action Running Rate Stopped Rate Flexible Sensor Sensor Description Sensor Type None Digital Inputs Digital Inputs A - C Digital Input A Function Polarity Action Arming LCD Display Activation Delay Digital Input B Function Polarity Action Arming LCD Display Activation Delay Digital Input C Function Coolant Temperature Switch Polarity Close to Activate Action Arming LCD Display Activation Delay 0s User Configured Close to Activate Indication Always Lube Oil Level Switch 0s User Configured Close to Activate Warning Always 0s No Warning Always Latched 10 % / Hr 10 % / Hr

about:blank

9/19/2013

8610 Configuration

Page 7 of 77

Digital Inputs D - F Digital Input D Function Polarity Action Arming LCD Display Activation Delay Digital Input E Function Polarity Action Arming LCD Display Activation Delay Digital Input F Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Warning Never 0s User Configured Close to Activate Warning Never 0s User Configured Close to Activate Warning Never 0s

Digital Inputs G - I Digital Input G Function Polarity Action Arming LCD Display Activation Delay Digital Input H Function Polarity Action Arming LCD Display Activation Delay Digital Input I Function User Configured User Configured Close to Activate Warning Never 0s User Configured Close to Activate Warning Never 0s

about:blank

9/19/2013

8610 Configuration

Page 8 of 77

Polarity Action Arming LCD Display Activation Delay

Close to Activate Warning Always 0s

Digital Inputs J - K Digital Input J Function Polarity Action Arming LCD Display Activation Delay Digital Input K Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Shutdown Always 0s User Configured Close to Activate Warning Always 0s

about:blank

9/19/2013

8610 Configuration

Page 9 of 77

Outputs Digital Outputs Relay Outputs (Supplied From Emergency Stop Input) Source Polarity Output A Fuel Relay Energise Output B Start Relay Energise Relay Outputs (Volts Free) Source Polarity Output C (N/C) Not Used De-Energise Output D Not Used Energise Relay Outputs (DC Supply Out) Source Not Used Not Used Not Used Common Alarm Digital Input B Not Used Polarity De-Energise De-Energise De-Energise Energise Energise De-Energise

Output E Output F Output G Output H Output I Output J

Virtual LEDs LED Configuration Source Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Polarity Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit Lit

LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10 LED 11 LED 12 LED 13 LED 14 LED 15 LED 16 LED 17 LED 18 LED 19 LED 20

about:blank

9/19/2013

8610 Configuration

Page 10 of 77

Timers Start Timers Start Delay Remote Start Off Load 5s Remote Start On Load 5s Telemetry Start 5s Start Timers Pre-heat Pre-heat Bypass Engage Attempt Engage Rest Delay Crank Cranking Time Crank Rest Time Smoke Limit Smoke Limit Off Safety On Delay Warming Up Time Sensor Fail Delay 0s 0s 2.0s 1.6s 0.5s 16s 10s 0s 0s 1m 0s 2.0s

Load/Stopping Timers Load Timers Transfer Time / Load Delay 0.7s Breaker Close Pulse 0.5s Breaker Trip Pulse 0.5s Stopping Timers Return Delay Cooling Time ETS Solenoid Hold Fail to Stop Delay Generator Transient Delay Module Timers Interface Timers Page Timer 5m Scroll Timer 2s 30s 1m 0s 30s 0.0s

about:blank

9/19/2013

8610 Configuration

Page 11 of 77

Generator Generator Options Generator Options Alternator Fitted Yes Poles 4 AC System VT fitted 3 Phase, 4 Wire No Primary 111 V PhPh Secondary 110 V PhPh Generator Phase Rotation Enable Yes Phase Rotation L1-L2-L3 Generator Rating kW Rating 700kW 824kVA kVAr Rating 434kVAr 0.85pf Power factor 0.85pf Breaker Control Enable Breaker Alarms Fail to Open Delay 1.0s Fail to Close Delay 1.0s Generator Voltage Under Voltage Alarms Alarm Yes Action Shutdown Trip 319V PhPh 80.0 % Pre-alarm Yes Trip 350V PhPh 87.8 % Loading Voltage Loading Voltage 359V PhPh 90.0 % Enable Alarm Yes Action Shutdown Nominal Voltage 398V PhPh Over Voltage Alarms Pre-alarm Yes No

about:blank

9/19/2013

8610 Configuration

Page 12 of 77

Return 440V PhPh 110.4 % Trip 459V PhPh 115.2 % Alarm Trip 480V PhPh 120.4 %

about:blank

9/19/2013

8610 Configuration

Page 13 of 77

Generator Frequency Under Frequency Alarms Alarm Yes Action Shutdown Trip 40.0 Hz 80.0 % Pre-alarm Yes Trip 42.0 Hz 84.0 % Loading Frequency Loading Frequency 45.0 Hz 90.0 % Enable Alarm Yes Action Shutdown Nominal Frequency 50.0 Hz 100.0 % Over Frequency Alarms Pre-alarm Yes Return 54.0 Hz 108.0 % Trip 55.0 Hz 110.0 % Alarm Yes Trip 57.0 Hz 114.0 % Generator Current Generator Current Generator Current

Generator Current Options Generator Current Options CT Primary (L1,L2,L3,N) CT Secondary Full Load Rating Earth CT Primary 1600 A 5 Amp 1300 A 1600 A

about:blank

9/19/2013

8610 Configuration

Page 14 of 77

Generator Current Alarms Overcurrent Alarm Immediate Warning Yes IDMT Alarm Yes Trip 100 % 1300 A Time Multiplier Action 36 Shutdown

Negative Phase Sequence Enable Action Shutdown Trip Level 20 % Delay 0s Short Circuit Enabled Action Trip 200 % 2600.0 A Time Multiplier Earth Fault Enable Action Trip Level 30 % 390.0 A Time Multiplier 0.5 Shutdown Yes 0.01 Yes Shutdown No

about:blank

9/19/2013

8610 Configuration

Page 15 of 77

Generator Power Overload Protection Overload Protection Pre-alarm Trip 90 % 630 kW Return 80 % 560 kW Delay 5s Alarm Action Trip 100 % 700 kW Delay 5s Load Control Dummy Load Control Enable Outputs in Scheme 1 Trip 20 % 140 kW Trip Delay 5s Return 50 % 350 kW Return Delay 5s Load Shedding Control Enable Outputs in Scheme 1 Outputs at Start 1 Trip 80 % 560 kW Trip Delay 5s Return 70 % 490 kW Return Delay 5s Transfer Time / Load Delay 0.7s Reverse Power Reverse Power Alarm Enabled Action Electrical Trip Trip 80 kW Delay 2.0s Yes No No Shutdown Yes Yes

about:blank

9/19/2013

8610 Configuration

Page 16 of 77

Mains Decoupling R.O.C.O.F. Alarm Enable Trip 0.13 Hz/s Vector Shift Alarm Enable Trip 6.0 Voltage Alarms Undervolts No Trip 362V PhPh Delay 0s Overvolts No Trip 438V PhPh Delay 0s Frequency Alarms Under Freq. No Trip 47.0 Hz Delay 0s Over Freq. No Trip 50.5 Hz Delay 0s Synchronising Synchronising Sync No No

Sync Options Options Enable Syncronising No Governor Interface Internal Analogue Output Reversed No Action Adjust To Nominal Frequency AVR Output Internal Analogue Output Reversed No

about:blank

9/19/2013

8610 Configuration

Page 17 of 77

Action Check Sync Dead Bus

Adjust To Nominal Voltage

Voltage 52V PhPh 52V PhPh Check Sync Low Frequency High Frequency Voltage Phase Angle -0.1 Hz 0.2 Hz 3V PhPh 5 3V PhPh

Fail To Sync Alarm Action Electrical Trip Delay 1m MSC Link MSC Link MSC Failure Action MSC Alarms Disabled Action Too few modules action Minimum modules on MSC link Load Control Load Options Load Control Mode None Reactive Load Control Mode None Ramp Ramp Speed 3.0 % %/s Load Demand Starting options Start all sets initially Balance engine hours No Hours 167 Calling for less sets 70 % Calling for more sets 80 % Insufficient Capacity Action None Delay 1s AVR Warning None None 1

about:blank

9/19/2013

8610 Configuration

Page 18 of 77

Loss Of Excitation Pre-alarm Trip 25.0 % % Return 20.0 % % Alarm Action Shutdown Trip 35.0 % % Delay 1s AVR Trim Alarm Action None Delay 0s Bus Bus Settings AC System 3 Phase, 4 Wire Phase Rotation L1-L2-L3 Bus Phase Rotation Enable No Phase Rotation L1-L2-L3 No No

about:blank

9/19/2013

8610 Configuration

Page 19 of 77

Engine Engine Options ECU (ECM) Options Engine Type Enhanced J1939 Alternative Engine Speed Modbus Engine Comms Port Disable ECM Speed Control Sensing Options Disable ECM Speed Sensing Magnetic Pickup Fitted No Flywheel Teeth Startup Options Enable Multiple Engage Attempts Engage Attempts Start Attempts Loss of Sensing Signal Magnetic pickup open circuit Overspeed Options Overspeed Overshoot 0 % Overshoot Delay 0s Droop Enable No 4.0 % CAN Options Engine Hours Module to Record Engine Hours No DPF Regeneration Control Enable Automatic Speed Switch Enable Default Dataset ECU ECU Wakeup No 2 3 Shutdown Shutdown 190 No Conventional Engine No No RS485 Port No

about:blank

9/19/2013

8610 Configuration

Page 20 of 77

Enable No Periodic Wakeup Time 1h Coolant Measurement Persistance No

about:blank

9/19/2013

8610 Configuration

Page 21 of 77

CAN Alarms CAN Data Fail CAN ECU Data Fail Action Shutdown Arming From Safety On Activation Delay 0s DM1 Signals ECU Amber Action Warning Arming Always Activation Delay 0s ECU Red Action Shutdown Arming Always Activation Delay 0s ECU Malfunction Action Warning Arming Always Activation Delay 0s ECU Protect Action Warning Arming From Safety On Activation Delay 0s Advanced Water In Fuel Action Warning Arming Always Activation Delay 0s After Treatment Action Warning Arming Always Activation Delay 0s Gas Engine Options Gas Engine Timers Choke Timer Gas On Delay 2s 2s

about:blank

9/19/2013

8610 Configuration

Page 22 of 77

Ignition Off Delay 2s Cranking Options Crank disconnect on oil pressure No Check oil pressure prior to starting No Crank Disconnect Generator Frequency Engine Speed Oil Pressure Charge Alternator 6.0 V DC Generator Voltage 322V PhPh Manual Crank Hold Start Button To Crank No Manual Crank Limit 30s 21.0 Hz 600 RPM 1.03Bar, 14.94 PSI, 103 kPa No No

about:blank

9/19/2013

8610 Configuration

Page 23 of 77

Speed Settings Under Speed Alarm No Action Shutdown Trip 1200 RPM Pre-alarm No Trip 1260 RPM Return 1350 RPM Over Speed Pre-alarm No Return 1620 RPM Trip 1650 RPM Alarm Trip 1710 RPM Plant Battery Voltage Alarms Undervolts Yes Pre-alarm 16.0 V DC Return 18.0 V DC Delay 1m Overvolts Yes Return 29.5 V DC Pre-alarm 30.0 V DC Delay 1m Charge Alternator Alarm Use Module for Charge Alternator No Alarm Disabled Trip 4.0 V DC Delay 5s Pre-alarm Trip 6.0 V DC Delay 5s Enabled

about:blank

9/19/2013

8610 Configuration

Page 24 of 77

Inlet Temperature Inlet Temperature Alarms Alarm No Action Shutdown Trip 95 C, 203 F Pre-alarm No Trip 85 C, 185 F Return 80 C, 176 F

about:blank

9/19/2013

8610 Configuration

Page 25 of 77

Communications Communications Options Module Identification Site identity Genset identity RS232 Port Basic Serial Port Configuration Slave ID 10 Baud Rate 19200 Port Usage No Modem Modem Settings Alarm numbers No

GSM Modem SMS Message centre number SMS Recipient numbers Advanced Initialisation Strings

Init (not auto answer) E0S7=60S0=0&S0&C1&D3 Init (auto answer) E0S7=60S0=2&S0&C1&D3 Hangup H0 Connection Settings Master inactivity timeout Connect delay Retries Retry delay Repeat cycle delay RS485 Port Basic Slave ID 10 Baud Rate 19200 Advanced 5s 60s 4 5s 10s

about:blank

9/19/2013

8610 Configuration

Page 26 of 77

Master inactivity timeout 5s Ethernet Port Dynamic Host Configuration Protocol Obtain IP Address Automatically No Names Domain Name Host Name Vendor Name IP Addresses IP address 0 . 0 . 0 . 0 Subnet Mask 255 . 255 . 255 . 0 Gateway Address 0 . 0 . 0 . 0 DNS Address 0 . 0 . 0 . 0 Preferred Connection Address 0 . 0 . 0 . 0 Modbus Modbus Port Number 502

about:blank

9/19/2013

8610 Configuration

Page 27 of 77

Scheduler Exercise Scheduler Enabled Run Mode Schedule Period Week Day Start Time Duration Monday 00:00 00:00 Week Day Start Time Duration Monday 00:00 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 Monday 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 No Off Load Weekly

about:blank

9/19/2013

8610 Configuration

Page 28 of 77

Maintenance Alarm Maintenance Alarm 1 Enable Description Action Engine run hours Enable alarm on due date Maintenance interval Maintenance Alarm 2 Enable Description Action Engine run hours Enable alarm on due date Maintenance interval Maintenance Alarm 3 Enable Description Action Engine run hours Enable alarm on due date Maintenance interval Maintenance alarm 3 Warning 10 hrs No 1 months No Maintenance alarm 2 Warning 10 hrs No 1 months No Maintenance alarm 1 Warning 10 hrs No 1 months No

about:blank

9/19/2013

8610 Configuration

Page 29 of 77

Alternative Configurations Alternative Configuration Options Alternative Configuration Options Default Configuration Main Configuration

about:blank

9/19/2013

8610 Configuration

Page 30 of 77

Expansion 2131 Input Modules 2131 Input Modules 2131 Input Modules DSENet ID 0 DSENet ID 0 2131 Expansion Enable Expansion Enabled Yes Link Lost Alarm Action Warning

about:blank

9/19/2013

8610 Configuration

Page 31 of 77

Analogue Input A Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Cooling Tower Out Water Pressure Input Type 10 Bar Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 32 of 77

Analogue Input B Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Cooling Tower In Water Pressure Input Type 10 Bar Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 33 of 77

Analogue Input C Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Gas In Pressure Input Type User defined Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 34 of 77

Analogue Input D Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Oil Pressure Input Type 10 Bar Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 35 of 77

Analogue Input E Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Engine In Water Pressure Input Type User defined Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 36 of 77

Analogue Input F Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name Engine Out Water Pressure Input Type User defined Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 37 of 77

Analogue Input G Sensor Description Sensor Type Pressure Sensor Measured Quantity Current Sensor Name After Cooler In Water Pressure Input Type 10 Bar Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 0.00Bar, 0.00 PSI, 0 kPa Low Pre-alarm Enable Low Pre-alarm Trip 1.17Bar, 16.97 PSI, 117 kPa Low Pre-alarm Return 1.24Bar, 17.98 PSI, 124 kPa Low Alarm String High Pre-alarm Enable High Pre-alarm Return 1.40Bar, 20.30 PSI, 140 kPa High Pre-alarm Trip 1.50Bar, 21.75 PSI, 150 kPa High Alarm Enable Action None High Alarm 1.60Bar, 23.21 PSI, 160 kPa High Alarm String Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 38 of 77

Analogue Input H Sensor Description Sensor Type None Analogue Input I Sensor Description Sensor Type None Analogue Input J Sensor Description Sensor Type None

about:blank

9/19/2013

8610 Configuration

Page 39 of 77

2133 Input Modules 2133 Input Modules 2133 Input Modules DSENet ID 0 DSENet ID 0 2133 Expansion Enable Expansion Enabled Yes Link Lost Alarm Action Warning

about:blank

9/19/2013

8610 Configuration

Page 40 of 77

Analogue Input A Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 1 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input B Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 2 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 41 of 77

Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input C Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 3 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input D Flexible Sensor High No No Flexible Sensor Low No No Always Flexible Sensor High No No Flexible Sensor Low No

about:blank

9/19/2013

8610 Configuration

Page 42 of 77

Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 4 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input E Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 5 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 43 of 77

Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input F Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 6 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input G Sensor Description

No

Flexible Sensor Low No

No

Flexible Sensor High

Always No

No

Flexible Sensor Low No

No

Flexible Sensor High

about:blank

9/19/2013

8610 Configuration

Page 44 of 77

Sensor Type Temperature Sensor Sensor Name Cyl # 7 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input H Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 8 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F No No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 45 of 77

Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Flexible Sensor High No No Flexible Sensor Low

about:blank

9/19/2013

8610 Configuration

Page 46 of 77

DSENet ID 1 DSENet ID 1 2133 Expansion Enable Expansion Enabled Yes Link Lost Alarm Action Warning

about:blank

9/19/2013

8610 Configuration

Page 47 of 77

Analogue Input A Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 9 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input B Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 10 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 48 of 77

Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input C Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 11 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input D Flexible Sensor High No No Flexible Sensor Low No No Always Flexible Sensor High No No Flexible Sensor Low No

about:blank

9/19/2013

8610 Configuration

Page 49 of 77

Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 12 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input E Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 13 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 50 of 77

Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input F Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 14 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input G Sensor Description

No

Flexible Sensor Low No

No

Flexible Sensor High

Always No

No

Flexible Sensor Low No

No

Flexible Sensor High

about:blank

9/19/2013

8610 Configuration

Page 51 of 77

Sensor Type Temperature Sensor Sensor Name Cyl # 15 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input H Sensor Description Sensor Type Temperature Sensor Sensor Name Cyl # 16 Wide Range Yes Input Type Type K Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F No No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 52 of 77

Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Flexible Sensor High No No Flexible Sensor Low

about:blank

9/19/2013

8610 Configuration

Page 53 of 77

DSENet ID 2 DSENet ID 2 2133 Expansion Enable Expansion Enabled Yes Link Lost Alarm Action Warning

about:blank

9/19/2013

8610 Configuration

Page 54 of 77

Analogue Input A Sensor Description Sensor Type Temperature Sensor Sensor Name 07 After Cooler out Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input B Sensor Description Sensor Type Temperature Sensor Sensor Name 08 After Cooler In Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 55 of 77

Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input C Sensor Description Sensor Type Temperature Sensor Sensor Name After Cooler Out Water Temp Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input D Flexible Sensor High No No Flexible Sensor Low No No Always Flexible Sensor High No No Flexible Sensor Low No

about:blank

9/19/2013

8610 Configuration

Page 56 of 77

Sensor Description Sensor Type Temperature Sensor Sensor Name Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input E Sensor Description Sensor Type Temperature Sensor Sensor Name After Turbo Temp Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 57 of 77

Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input F Sensor Description Sensor Type Temperature Sensor

No

Flexible Sensor Low No

No

Flexible Sensor High

Sensor Name Oil Cooler Out Oil Temp Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input G Sensor Description Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 58 of 77

Sensor Type Temperature Sensor Sensor Name 2133 ID2 Flexible Sensor G Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input H Sensor Description Sensor Type Temperature Sensor Sensor Name 2133 ID2 Flexible Sensor H Wide Range Yes Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F No No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 59 of 77

Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Flexible Sensor High No No Flexible Sensor Low

about:blank

9/19/2013

8610 Configuration

Page 60 of 77

DSENet ID 3 DSENet ID 3 2133 Expansion Enable Expansion Enabled Yes Link Lost Alarm Action Warning

about:blank

9/19/2013

8610 Configuration

Page 61 of 77

Analogue Input A Sensor Description Sensor Type Temperature Sensor Sensor Name 06 Engine In Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 62 C, 144 F Low Pre-alarm Enable Low Pre-alarm Trip 63 C, 145 F Low Pre-alarm Return 64 C, 147 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 70 C, 158 F High Pre-alarm Trip 75 C, 167 F High Alarm Enable Action Shutdown High Alarm 85 C, 185 F High Alarm String Analogue Input B Sensor Description Sensor Type Temperature Sensor Sensor Name 03 Oil Cooler Out Oil Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None No Always 06 Engine In Water Temp Yes Yes Flexible Sensor Low No No From Safety On

about:blank

9/19/2013

8610 Configuration

Page 62 of 77

Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input C Sensor Description Sensor Type Temperature Sensor Sensor Name 02 Cooling Tower Out Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input D Flexible Sensor High No No Flexible Sensor Low No No Always Flexible Sensor High No No Flexible Sensor Low No

about:blank

9/19/2013

8610 Configuration

Page 63 of 77

Sensor Description Sensor Type Temperature Sensor Sensor Name 04 Oil Cooler In Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input E Sensor Description Sensor Type Temperature Sensor Sensor Name 01 Cooling Tower In Water Temp Wide Range Yes Input Type 3 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 64 of 77

Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input F Sensor Description Sensor Type Temperature Sensor

No

Flexible Sensor Low No

No

Flexible Sensor High

Sensor Name 05 Oil Cooler In Oil Temp Wide Range Yes Input Type 2 Wire PT100 Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input G Sensor Description Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 65 of 77

Sensor Type Temperature Sensor Sensor Name Wide Range No Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Analogue Input H Sensor Description Sensor Type Temperature Sensor Sensor Name Wide Range No Input Type Not used Sensor Alarms Alarm Arming Low Alarm Enable Action None Low Alarm 103 C, 217 F Low Pre-alarm Enable Low Pre-alarm Trip 117 C, 243 F No No Always Flexible Sensor High No No Flexible Sensor Low No No Always

about:blank

9/19/2013

8610 Configuration

Page 66 of 77

Low Pre-alarm Return 124 C, 255 F Low Alarm String High Pre-alarm Enable High Pre-alarm Return 140 C, 284 F High Pre-alarm Trip 150 C, 302 F High Alarm Enable Action None High Alarm 160 C, 320 F High Alarm String Flexible Sensor High No No Flexible Sensor Low

about:blank

9/19/2013

8610 Configuration

Page 67 of 77

2152 Output Modules 2152 Output Modules Advanced Advanced Advanced

Advanced Options Protections Disable Protections Are Disabled Protections Disabled Alarm Action Coolant Level Protection Override Out Of Sync Out Of Sync Angle 16 Out Of Sync Timer 0.2s Other Timers Syncronisation Delay 3s Dead Bus Run-on 0s Mains Decoupling Supervision 1.0s PLC PLC Logic PLC Functions 1-4 Function 1 Function Polarity Action Arming LCD Display Activation Delay Function 2 Function Polarity Action Arming LCD Display Activation Delay Function 3 User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s No Never Indication Disabled

about:blank

9/19/2013

8610 Configuration

Page 68 of 77

Function Polarity Action Arming LCD Display Activation Delay Function 4 Function Polarity Action Arming LCD Display Activation Delay

User Configured Close to Activate Warning Always 0s

User Configured Close to Activate Warning Always 0s

PLC Functions 5-8 Function 5 Function Polarity Action Arming LCD Display Activation Delay Function 6 Function Polarity Action Arming LCD Display Activation Delay Function 7 Function Polarity Action Arming LCD Display Activation Delay Function 8 Function Polarity Action Arming User Configured Close to Activate Warning Always User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s

about:blank

9/19/2013

8610 Configuration

Page 69 of 77

LCD Display Activation Delay 0s PLC Functions 9-12 Function 9 Function Polarity Action Arming LCD Display Activation Delay Function 10 Function Polarity Action Arming LCD Display Activation Delay Function 11 Function Polarity Action Arming LCD Display Activation Delay Function 12 Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s

PLC Functions 13-16 Function 13 Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Warning Always 0s

about:blank

9/19/2013

8610 Configuration

Page 70 of 77

Function 14 Function Polarity Action Arming LCD Display Activation Delay Function 15 Function Polarity Action Arming LCD Display Activation Delay Function 16 Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s

PLC Functions 17-20 Function 17 Function Polarity Action Arming LCD Display Activation Delay Function 18 Function Polarity Action Arming LCD Display Activation Delay Function 19 Function Polarity User Configured Close to Activate User Configured Close to Activate Warning Always 0s User Configured Close to Activate Warning Always 0s

about:blank

9/19/2013

8610 Configuration

Page 71 of 77

Action Warning Arming Always LCD Display Activation Delay 0s Function 20 Function Polarity Action Arming LCD Display Activation Delay User Configured Close to Activate Warning Always 0s

Configurable Gencomm Pages Configurable Gencomm Pages Configurable Gencomm Pages Page 166 Register Value 0<Not 1 Used> 2<Not 3 Used> 4<Not 5 Used> 6<Not 7 Used> 8<Not 9 Used> 10<Not 11 Used> 12<Not 13 Used> 14<Not 15 Used> 16<Not 17 Used> 18<Not 19 Used> 20<Not 21 Used> 22<Not 23 Used> 24<Not 25 Used> Register Value 6465 6667 6869 7071 7273 7475 7677 7879 8081 8283 8485 8687 8889 <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> Register Value 128<Not 129 Used> 130<Not 131 Used> 132<Not 133 Used> 134<Not 135 Used> 136<Not 137 Used> 138<Not 139 Used> 140<Not 141 Used> 142<Not 143 Used> 144<Not 145 Used> 146<Not 147 Used> 148<Not 149 Used> 150<Not 151 Used> 152<Not 153 Used> Register Value 192<Not 193 Used> 194<Not 195 Used> 196<Not 197 Used> 198<Not 199 Used> 200<Not 201 Used> 202<Not 203 Used> 204<Not 205 Used> 206<Not 207 Used> 208<Not 209 Used> 210<Not 211 Used> 212<Not 213 Used> 214<Not 215 Used> 216<Not 217 Used>

about:blank

9/19/2013

8610 Configuration

Page 72 of 77

26<Not 27 Used> 28<Not 29 Used> 30<Not 31 Used> 32<Not 33 Used> 34<Not 35 Used> 36<Not 37 Used> 38<Not 39 Used> 40<Not 41 Used> 42<Not 43 Used> 44<Not 45 Used> 46<Not 47 Used> 48<Not 49 Used> 50<Not 51 Used> 52<Not 53 Used> 54<Not 55 Used> 56<Not 57 Used> 58<Not 59 Used> 60<Not 61 Used> 62<Not 63 Used> Page 167

9091 9293 9495 9697 9899

<Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

154<Not 155 Used> 156<Not 157 Used> 158<Not 159 Used> 160<Not 161 Used> 162<Not 163 Used> 164<Not 165 Used> 166<Not 167 Used> 168<Not 169 Used> 170<Not 171 Used> 172<Not 173 Used> 174<Not 175 Used> 176<Not 177 Used> 178<Not 179 Used> 180<Not 181 Used> 182<Not 183 Used> 184<Not 185 Used> 186<Not 187 Used> 188<Not 189 Used> 190<Not 191 Used>

218<Not 219 Used> 220<Not 221 Used> 222<Not 223 Used> 224<Not 225 Used> 226<Not 227 Used> 228<Not 229 Used> 230<Not 231 Used> 232<Not 233 Used> 234<Not 235 Used> 236<Not 237 Used> 238<Not 239 Used> 240<Not 241 Used> 242<Not 243 Used> 244<Not 245 Used> 246<Not 247 Used> 248<Not 249 Used> 250<Not 251 Used> 252<Not 253 Used> 254<Not 255 Used>

100<Not 101 Used> 102<Not 103 Used> 104<Not 105 Used> 106<Not 107 Used> 108<Not 109 Used> 110<Not 111 Used> 112<Not 113 Used> 114<Not 115 Used> 116<Not 117 Used> 118<Not 119 Used> 120<Not 121 Used> 122<Not 123 Used> 124<Not 125 Used> 126<Not 127 Used>

Register Value 0<Not 1 Used> 2<Not 3 Used> 4<Not 5 Used>

Register Value 6465 6667 6869 <Not Used> <Not Used> <Not Used>

Register Value 128<Not 129 Used> 130<Not 131 Used> 132<Not 133 Used>

Register Value 192<Not 193 Used> 194<Not 195 Used> 196<Not 197 Used>

about:blank

9/19/2013

8610 Configuration

Page 73 of 77

6<Not 7 Used> 8<Not 9 Used> 10<Not 11 Used> 12<Not 13 Used> 14<Not 15 Used> 16<Not 17 Used> 18<Not 19 Used> 20<Not 21 Used> 22<Not 23 Used> 24<Not 25 Used> 26<Not 27 Used> 28<Not 29 Used> 30<Not 31 Used> 32<Not 33 Used> 34<Not 35 Used> 36<Not 37 Used> 38<Not 39 Used> 40<Not 41 Used> 42<Not 43 Used> 44<Not 45 Used> 46<Not 47 Used> 48<Not 49 Used> 50<Not 51 Used>

7071 7273 7475 7677 7879 8081 8283 8485 8687 8889 9091 92 93 9495 9697 9899

<Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

134<Not 135 Used> 136<Not 137 Used> 138<Not 139 Used> 140<Not 141 Used> 142<Not 143 Used> 144<Not 145 Used> 146<Not 147 Used> 148<Not 149 Used> 150<Not 151 Used> 152<Not 153 Used> 154<Not 155 Used> 156<Not Used> 157 158<Not 159 Used> 160<Not 161 Used> 162<Not 163 Used> 164<Not 165 Used> 166<Not 167 Used> 168<Not 169 Used> 170<Not 171 Used> 172<Not 173 Used> 174<Not 175 Used> 176<Not 177 Used> 178<Not 179 Used>

198<Not 199 Used> 200<Not 201 Used> 202<Not 203 Used> 204<Not 205 Used> 206<Not 207 Used> 208<Not 209 Used> 210<Not 211 Used> 212<Not 213 Used> 214<Not 215 Used> 216<Not 217 Used> 218<Not 219 Used> 220<Not Used> 221 222<Not 223 Used> 224<Not 225 Used> 226<Not 227 Used> 228<Not 229 Used> 230<Not 231 Used> 232<Not 233 Used> 234<Not 235 Used> 236<Not 237 Used> 238<Not 239 Used> 240<Not 241 Used> 242<Not 243 Used>

100<Not 101 Used> 102<Not 103 Used> 104<Not 105 Used> 106<Not 107 Used> 108<Not 109 Used> 110<Not 111 Used> 112<Not 113 Used> 114<Not 115 Used>

about:blank

9/19/2013

8610 Configuration

Page 74 of 77

52<Not 53 Used> 54<Not 55 Used> 56<Not 57 Used> 58<Not 59 Used> 60<Not 61 Used> 62<Not 63 Used> Page 168

116<Not 117 Used> 118<Not 119 Used> 120<Not 121 Used> 122<Not 123 Used> 124<Not 125 Used> 126<Not 127 Used>

180<Not 181 Used> 182<Not 183 Used> 184<Not 185 Used> 186<Not 187 Used> 188<Not 189 Used> 190<Not 191 Used>

244<Not 245 Used> 246<Not 247 Used> 248<Not 249 Used> 250<Not 251 Used> 252<Not 253 Used> 254<Not 255 Used>

Register Value 0<Not 1 Used> 2<Not 3 Used> 4<Not 5 Used> 6<Not 7 Used> 8<Not 9 Used> 10<Not 11 Used> 12<Not 13 Used> 14<Not 15 Used> 16<Not 17 Used> 18<Not 19 Used> 20<Not 21 Used> 22<Not 23 Used> 24<Not 25 Used> 26<Not 27 Used> 28<Not 29 Used> 30<Not 31 Used>

Register Value 6465 6667 6869 7071 7273 7475 7677 78 79 8081 8283 8485 8687 8889 9091 9293 9495 <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

Register Value 128<Not 129 Used> 130<Not 131 Used> 132<Not 133 Used> 134<Not 135 Used> 136<Not 137 Used> 138<Not 139 Used> 140<Not 141 Used> 142<Not Used> 143 144<Not 145 Used> 146<Not 147 Used> 148<Not 149 Used> 150<Not 151 Used> 152<Not 153 Used> 154<Not 155 Used> 156<Not 157 Used> 158<Not 159 Used>

Register Value 192<Not 193 Used> 194<Not 195 Used> 196<Not 197 Used> 198<Not 199 Used> 200<Not 201 Used> 202<Not 203 Used> 204<Not 205 Used> 206<Not Used> 207 208<Not 209 Used> 210<Not 211 Used> 212<Not 213 Used> 214<Not 215 Used> 216<Not 217 Used> 218<Not 219 Used> 220<Not 221 Used> 222<Not 223 Used>

about:blank

9/19/2013

8610 Configuration

Page 75 of 77

32<Not 33 Used> 34<Not 35 Used> 36<Not 37 Used> 38<Not 39 Used> 40<Not 41 Used> 42<Not 43 Used> 44<Not 45 Used> 46<Not 47 Used> 48<Not 49 Used> 50<Not 51 Used> 52<Not 53 Used> 54<Not 55 Used> 56<Not 57 Used> 58<Not 59 Used> 60<Not 61 Used> 62<Not 63 Used> Page 169

9697 9899

<Not Used> <Not Used>

160<Not 161 Used> 162<Not 163 Used> 164<Not 165 Used> 166<Not 167 Used> 168<Not 169 Used> 170<Not 171 Used> 172<Not 173 Used> 174<Not 175 Used> 176<Not 177 Used> 178<Not 179 Used> 180<Not 181 Used> 182<Not 183 Used> 184<Not 185 Used> 186<Not 187 Used> 188<Not 189 Used> 190<Not 191 Used>

224<Not 225 Used> 226<Not 227 Used> 228<Not 229 Used> 230<Not 231 Used> 232<Not 233 Used> 234<Not 235 Used> 236<Not 237 Used> 238<Not 239 Used> 240<Not 241 Used> 242<Not 243 Used> 244<Not 245 Used> 246<Not 247 Used> 248<Not 249 Used> 250<Not 251 Used> 252<Not 253 Used> 254<Not 255 Used>

100<Not 101 Used> 102<Not 103 Used> 104<Not 105 Used> 106<Not 107 Used> 108<Not 109 Used> 110<Not 111 Used> 112<Not 113 Used> 114<Not 115 Used> 116<Not 117 Used> 118<Not 119 Used> 120<Not 121 Used> 122<Not 123 Used> 124<Not 125 Used> 126<Not 127 Used>

Register Value 0<Not 1 Used> 2<Not 3 Used> 4<Not 5 Used> 6<Not 7 Used> 8<Not 9 Used> 10<Not 11 Used>

Register Value 6465 6667 6869 7071 7273 7475 <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

Register Value 128<Not 129 Used> 130<Not 131 Used> 132<Not 133 Used> 134<Not 135 Used> 136<Not 137 Used> 138<Not 139 Used>

Register Value 192<Not 193 Used> 194<Not 195 Used> 196<Not 197 Used> 198<Not 199 Used> 200<Not 201 Used> 202<Not 203 Used>

about:blank

9/19/2013

8610 Configuration

Page 76 of 77

12<Not 13 Used> 14<Not 15 Used> 16<Not 17 Used> 18<Not 19 Used> 20<Not 21 Used> 22<Not 23 Used> 24<Not 25 Used> 26<Not 27 Used> 28<Not 29 Used> 30<Not 31 Used> 32<Not 33 Used> 34<Not 35 Used> 36<Not 37 Used> 38<Not 39 Used> 40<Not 41 Used> 42<Not 43 Used> 44<Not 45 Used> 46<Not 47 Used> 48<Not 49 Used> 50<Not 51 Used> 52<Not 53 Used> 54<Not 55 Used> 56<Not 57 Used>

7677 7879 8081 8283 8485 8687 8889 9091 9293 9495 9697 98 99

<Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used> <Not Used>

140<Not 141 Used> 142<Not 143 Used> 144<Not 145 Used> 146<Not 147 Used> 148<Not 149 Used> 150<Not 151 Used> 152<Not 153 Used> 154<Not 155 Used> 156<Not 157 Used> 158<Not 159 Used> 160<Not 161 Used> 162<Not Used> 163 164<Not 165 Used> 166<Not 167 Used> 168<Not 169 Used> 170<Not 171 Used> 172<Not 173 Used> 174<Not 175 Used> 176<Not 177 Used> 178<Not 179 Used> 180<Not 181 Used> 182<Not 183 Used> 184<Not 185 Used>

204<Not 205 Used> 206<Not 207 Used> 208<Not 209 Used> 210<Not 211 Used> 212<Not 213 Used> 214<Not 215 Used> 216<Not 217 Used> 218<Not 219 Used> 220<Not 221 Used> 222<Not 223 Used> 224<Not 225 Used> 226<Not Used> 227 228<Not 229 Used> 230<Not 231 Used> 232<Not 233 Used> 234<Not 235 Used> 236<Not 237 Used> 238<Not 239 Used> 240<Not 241 Used> 242<Not 243 Used> 244<Not 245 Used> 246<Not 247 Used> 248<Not 249 Used>

100<Not 101 Used> 102<Not 103 Used> 104<Not 105 Used> 106<Not 107 Used> 108<Not 109 Used> 110<Not 111 Used> 112<Not 113 Used> 114<Not 115 Used> 116<Not 117 Used> 118<Not 119 Used> 120<Not 121 Used>

about:blank

9/19/2013

8610 Configuration

Page 77 of 77

58<Not 59 Used> 60<Not 61 Used> 62<Not 63 Used>

122<Not 123 Used> 124<Not 125 Used> 126<Not 127 Used>

186<Not 187 Used> 188<Not 189 Used> 190<Not 191 Used>

250<Not 251 Used> 252<Not 253 Used> 254<Not 255 Used>

about:blank

9/19/2013