At around half the weight of traditional copper conductor based busbar trunking, Canalis KSR can be fitted in many installations by one person. Its lightness means it needs fewer mechanical fixings, making it even faster to install. Fast installation allows contractors to meet the extremely short deadlines that are becoming increasingly common in todays building market. Canalis KSR busbar sections are linked by joint kits bolted in place, complete with an expansion joint that ensures a secure, safe and easy-tomake connection. Silver-to-silver contacts provide excellent conductivity at all joints.
This simple connection method makes it easier to install the distribution system safely, first time. Canalis KSR is one of the safest rising main busbar trunking systems available. Interlocks on the tap-off units prevent live loads being connected or disconnected. The busbar sections are finger-safe to IP2X, even when no tap-off units are fitted. All of which means that tap-off units can be safely connected to a live system if this is unavoidable.
KSR rising main is a specific version of KSA busbar trunking for energy distribution to each floor of a multi-storey building. KSR retains all the construction principles of KSA trunking for horizontal distribution, in particular:
I
Aluminium conducting bars are equipped with bi-metal silver copper laminate saddles fitted at the points of contact in the joints and tap-off outlets The jointing block with spring-loaded contacts, locked by 1/4-turn fastening (this block, which also absorbs the expansion of the conductors, eliminates any mechanical stress at the fire barrier) Tap-off outlets with automatic closing shutters Degree of protection is IP54
A E
G G
A B C D E F G
A B C D E F G
5
Page 8
Page 19 - 21
Page 9
Fixings
Page 20
Page 10
Tap-off units
Page 22 - 23
Page 11
Accessories
Page 20
Page 12
Feeder lengths
Page 20
Page 13
Page 21
A
2
1 fire barrier, placed at the level of passage through the floor slab, eliminating any risk of fire propagation from one floor to another via the trunking. The fire barrier, which has been tested by the laboratory of the University of Gand (Belgium) conforms to the requirements of standard ISO834. According to report 7296, the following results were obtained:
I I I
Thermal insulation : 120 minutes Flame resistance : 120 minutes Stability : 120 minutes
A casing of galvanised sheet steel which is crimped closed This casing, shaped and ribbed by rolling, provides excellent resistance to bending and twisting. Two casing widths cover the whole range:
I I
75mm wide sheet steel with RAL 7032 grey finish for 400A rating 113mm wide sheet steel with RAL 7032 grey finish for 630 and 800A ratings
Aluminium fitted with bi-metal silver-plated copper/aluminium laminate riders electrically welded to junctions and tap-off positions for 400 to 800A ratings. The lamination is a patented process by which the copper and aluminium molecules are fused together under extreme pressure
6
3
Fibreglass reinforced polyester isolators at 250mm intervals. These hold the conductors securely within the casing A special protected earth (PE) conductor of the same type as the live conductors with a cross-section 1/2 of the phase cross-section. It is connected to the casing at each junction Tap-off outlets on the front face of the trunking at 500mm intervals. They are connected to the isolators to form a block, holding the bars. They have a shuttered outlet which is opened and closed automatically when connectors or tap-off units are plugged in, or removed A mechanical and electrical jointing device Electrical connection is via a block with spring and silver graphite contacts. This block absorbs the differential conductor/casing expansion of each length equally. It simultaneously connects all the live conductors, ensures continuity of the protective earth conductor and its connection with the casing. The electrical connection is made by a 1/4 screw turn for each conductor
To enable to pass from floor to floor of a multi-story building. Fire resistance of the barriers is 2 hours (A120) conforming to ISO834
I
Riser support fire barrier length The first floor is a combined base support length for the complete riser including the fire barrier. This is a standard length 1150m.
700
Made to measure fire barrier length Subsequent floor fire barriers are made to measure lengths to alter the length of a run between floor to floor heights. These components are manufactured from 900mm to 2300mm in multiples of 5mm. They do not have tap-off outlets.
450
L = 900 - 2300
450 - 1850
I Supply cable
The feed can be from one end (end feed) or along a run (centre feed). They can be connected by aluminium or copper cables fitted with suitable cable lugs. There is an undrilled aluminium gland plate which will accept cable glands. This plate can be replaced by a plate fitted with 1-3 cable clamps depending on the rating (to be ordered separately)
For bottom or top connection Through run type (1 cable feeds the right and left sections) It is mounted along the run, between 2 straight lengths
Fitted with splayed bars and a mounting plate. It is used for connection to a distribution panel. It can be mounted at either end of a component
I KV-KSR connector
The KV-KSR connector is fitted with a KV end length at one end and a KSA end length at the other. Due to its flexible design, it ensures direct connection from a feed run to a distribution run and reduces any risk caused by alignment faults
End cover
The end cover protects and isolates the ends of the conductors. It is mounted on the last length. Two products cover the entire KSR range: 400 and 800A.
D B
A C
8
Fixings
Used to fix the riser run to the structure of the building, directly or via an adjustable universal guide.
I Universal Guide
This bracket maintains the trunking in position at each floor. Two adjustable fixing straps are supplied to give a 30mm depth adjustment from the supporting wall.
Switch fuse and Fuse switch tap-offs 32A to 400A fuses 100 to 400A moulded case circuit breaker Standard KSA units with isolators and fuse carriers for 25 to 160A fuses
These fused tap-off units are designed to protect the tap-off by means of fuses (not supplied). They can be fitted with carriers for the following fuses:
I I
32 to 160A fused on-load tap-off unit, switch fuse on-load tap-off unit 250 to 400A fused off-load tap-off unit, fuse switch on-load tap-off unit
The unit is hooked onto the trunking, then automatically located in front of the tap-off outlet by moving it sideways The fixing brackets are then locked and the mobile power block plugged in, using an internal device
Used for instant connection of loads or secondary runs (for example, for low power distribution). The connectors and tap-off units conform to installation standards and regulations whatever type of neutral point connection is used (TT, IT, TNS or TNC).
I I I I I
They can be removed and moved whilst live, with no load The tap-off outlets are opened and closed automatically when units are plugged in or removed With the cover open, no live part can be accessed. Degree of protection IP2X Connectors and tap-off units are made in two versions Protected version, degree of protection IP54, suitable for most industrial and commercial applications
10
Accessories
To achieve the degree of protection, IP54, the following accessories are fitted to the riser.
Each tap-off outlet not being used, should be fitted with a sealed tap-off blanking plate Each junction between components should be fitted with a jointing sleeve to maintain the IP54 projection Various devices, for lead sealing in particular, can be used to complete the equipment of the KSR rising main.
11
12
Edgewise elbow
One model for each size of casing for turning to left or right
Flat elbow
Two models for each size of casing (one ascending, one descending). Flat and edgewise elbows can be manufactured upon request, with made to measure connection lengths, with multiple angles, with built-in fire barrier, etc. for the KSA components from the Canalis Busbar Trunking and Power Applications catalogue available upon request. Please contact 0870 608 8 608.
13
The types of load and their characteristics and floor locations The power source and its characteristics and location The structure of the premises (availability of fixing points for trunking) Any influences external to the installation site. (ambient temperature, dust, water, etc)
Polarity selection
3L + N + PE (IT-TT-TNS)
3L + PE (IT-TT-TNS)
3-pole distribution + N + PE (IT-TT-TNS) GKSA-GGD4GG trunking 3-pole + N + PE tap-offs possible, type 3-pole + PE or 3-pole + N + PE
3L + N + PE (IT-TT-TNS)
3-pole distribution + PEN (TNC) GKSA-GGED4GG trunking 3-pole + PEN tap-offs possible, type 3-pole + PEN (TNC) or 3-pole + N + PE (TNS).
3L + PE (IT-TT-TNS)
14
(1)
To enable it to be extended, prefabricated busbar trunking is generally protected to its nominal current Inc (or to its permissible current Iz if the K1 coefficient is applied according to the ambient temperature).
Calculate the standard nominal current In of the fuse so that : In Inc k1 Select the circuit breaker setting current Ir so that : Ib Ir Inc
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.
Note: Protecting trunking using a circuit breaker makes it possible to use the trunking at full capacity.
Determine the 3-phase short-circuit current, prospective lcc 3 (KA) at the start of the Canalis KSR Check the current limitation curve of the selected protective device, that this limits the peak current (kA) to a value below the permissible rated peak current of the KSR trunking. Limited current Canalis current
160
250
400
500
630
800
(1) By calculation or using graphs, pre-calculated tables, etc. Note: To obtain details of the Merlin Gerin circuit breaker range, please refer to the circuit breaker brochure available by phone from 0870 608 8 608 15
Tap-off units
The complete range of tap-off units for KSR are IP54 dust and damp proof range, for very dusty or damp environments.
KSEGG = IP54
Mounting position
230
21
120 - 150
A cable feed unit can be mounted at either end of a run, bottom or top 500 and 800A feed unit
Bottom (right hand) mounting (fig. A) Top (left hand) mounting (fig. B)
A
All types of neutral system. Connected by means of cable lugs. Switchboard feed may be connected via cable or busbar interconnector.
16
General characteristics
Type of trunking Number of conductors Nominal rated current INC to 35 C
0
(1)
KSA-40
KSA-63
KSA-80
Between live conductor and PE Average resistance of loop (thermal stabilisation temp. 01) Average resistance of loop (1) (short-circuit conventional temp.) Average reactance loop Rb1phPE m/m m/m m/m 0.304 0.167 0.128
Rb2phPE
0.365
0.201
0.153
XbphPE
0.303
0.225
0.226
(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2
17
Conductor characteristics
Type of trunking Live conductors (per conductor) GE resistance, cold state (ambient temperature 20C) R1 average resistance at/nc (ambient temperature 35C) X1 average resistance at/nc and at rated frequency (Hz) Protective conductors Average resistance, cold state (ambient temperature 35C) m/m 0.105 0.061 0.061
Rboph(1)
KSA-40
KSA-63
KSA-80
m/m
0.142
0.074
0.045
Rb1ph(1)
m/m m/m
0.190
0.101
0.061
Xbph(1)
0.112
0.070
0.071
Other characteristics
Type of trunking Short-circuit withstand capacity Maximum thermal limit 12 t ph or N PE PEN Permissible rated peak current Degree of protection IP54 Voltage drop With accessories. Ipk kA kA kA kA 354x106 354x106 500x10
6
KSA-40
KSA-63
KSA-80
49.2x106
Composite voltage drop, hot state, expressed in V/100 m/A for 3 phase 50Hz current, with load distributed along the run. Where the load is concentrated at the end of a feed run, the voltage drops are twice the values indicated in the table. Cos f=1.0 V/100 m/A 0.01645 Cos f=0.9 V/100 m/A 0.01904 Cos f=0.8 V/100 m/A 0.01898 Cos f=0.7 V/100 m/A 0.01844 0.00875 0.01051 0.01063 0.01045 0.00528 0.00743 0.00792 0.00805
For a power factor For a power factor For a power factor For a power factor Destination of permissible current Iz for a busbar trunking system, according to ambient temperature Average ambient temperature C Factor f1
Derating or uprating factor to be applied to the rated current of the trunking where the average daily ambient temperature is other than 35C 15 1.11 20 1.08 25 1.06 30 1.03 35 1.00 40 0.97 45 0.94 50 0.91 55 0.87
(1) Conforming to international standard IEC 439-2 and European standard EN 60439.2
18
400
2000 2500
16 20 24 30 28 35
630
2000 2500
800
2000 2500
450
900 - 2300
Y= 450 - 1850
(1)
Bottom end feed 400 unit by cables Bottom end feed 800 (630) unit by cables End cover 400 800 (630)
22.000
Weight kg
1150 1150
20 30
Fire barrier
(2)
(1) When ordering, state the required length in mm (in multiples of 5 mm) after the reference. Example : KSA-40EF4B L = 1250 mm. (2) Order 1 KSA00ZA1 per riser base support length
19
50 50 50
All
Junction sleeve
400 630/800
400 630/800
400/630/800 All
(1)
(1) When ordering, state the required length in mm (in multiples of 5mm) after the reference. Example: KSA-80ES4A L=1250mm.
Bracket
KSA-50EZ3 KSA-80EZ3
0.330 0.400
20
(2)
Mounting
Unit reference
Weight kg
Bottom
KSA50AB452SW
30.00
KSA-50AB452
Switched end feed 800 unit by cables bottom End feed unit by cables top End feed unit by cables top Centre feed unit 500 (400) 800 (630) Flange feed unit 500 (400) 800 (630) 800 (630) 500 (400) isolator
Lugs 2 x 300mm2 OR Lugs 3 x 240mm2 Lugs/2 x 300mm2 M12 screws Lugs/3 x 300mm2 M12 screws Lugs/2 x 300 mm2 (M12 screw) Lugs/3 x 300 mm2 (M12 screw) Bars (M12 screw) Bars (4 x M10 screw)
Bottom
KSA80AB452SW
65.00
Top
KSA50AB462
22.00
Top
KSA80AB462
36.20
Along the run Along the run Bottom or top Bottom or top Bottom or top Bottom or top
KV-KS connector
KV0-50ER41001
(2)
Unit reference
Weight kg
Elbows
500 (400)
KSA-50LC40 KSA-50LP41
(1)
9.860 10.000 10.000 15.000 13.700 13.700 15.000 18.240 16.500 20.000
KSAGGLP41
Flat downwards (1) Tee 500 (400) 800 (630) Cross 500 (400) 800 (630) (1) IP54 achieved with sealing accessories. See page 20 Edgewise Edgewise Edgewise Edgewise
(2) Other run components IP54 as standard, common to versions of 3L+N+PE and 3L+PEN straight lengths.
21
Reference
Reference
Weight kg
Twinbreak Switchfuse Twinbreak Switchfuse Twinbreak Switchfuse Twinbreak Switchfuse Twinbreak Switchfuse Fupact Fuseswitch Fupact Fuseswitch Fupact Fuseswitch
(2)
(2)
(2)
(2)
(2)
(2)
(2)
22
Tap-off units for Merlin Gerin Compact NS fixed circuit breaker complete
Fully assembled fitted with N frame MCCB and door interlocked rotary handle
Number of conductors Scheme
(1)
3L + N + PE TT TNS TT TNS
Trunking Tap-off
Tap-off scheme
Type of circuit breaker fitted NS100N/TM25D NS100N/TM63D NS100N/TM100D NS100N/TM125D NS160N/TM160D NS250N/TM200D NS250N/TM250D NS400N/STR23SE
Reference
Weight kg
Empty tap-off units for Merlin Gerin Compact NS fixed circuit breaker
Standard extendable rotary handle (not included)
Rating A Type of circuit breaker Reference Weight kg
NS100 (either) N,H,L NS160 (either) N,H,L NS250 (either) N,H,L NS400 (either) N,H,L
(1)
(2)
(1)
(2)
(1)
(2)
(1)
(3)
(1) Selection of moulded case circuit breaker, please refer to the Merlin Gerin circuit breaker brochure available from 0870 608 8 608 KSE-16DB411 (2) A standard extended rotary handle part No. 29338 needs to be fitted with the MCCB. (3) A standard extended rotary handle Part No. 32598 needs to be fitted with the MCCB.
23
Trunking riser lengths 400, 600 and 800A KSA-40VDGGG, KSA-63VDGGG, KSA-80VDGGG
a
250
250
146
Rating A
500 500
a 75 113
400/500 630/800
2000
2500 500
500
500
24
Trunking feeder lengths 400, 500, 630 and 800A KSA-40EDGGG, KSA-50EDGGG, KSA-63EDGGG, KSA-80EDGGG
750
1000
1000
1000
1000
250
250
1000
1000
1000
1000
750
5000
146
Rating A 400/500
a 75 113
630/800
120 - 150
(1)
630/800
25
Feed units for 400 and 800A trunking - KSA-GGBT402, KSA-GGAB4G2 KSA-GGBT402
A1 A
KSA-GGAB4G2
D1 D
Rating A
A1
400/500
B B-20
290 390
235 316
510 556
11
11
300
660 1000
177
C-20 C
Rating A
D1
600 680
770 850
406 556
230 310
175 236
300 300
150 190
KSA-50AB402SW
344
127 89
KSA-80AB402SW
409
147 91
11
1058 900
450
11
400
388 433
259 331
650 695 299 429
220 170
KSA-80ER4 290
260 210
11 40
37
143 N 80 80 80
20
166 N 80 80 80
40 72
16
26
Elbows, tee and cross for 400 to 800A trunking KSA-GGLP41 KSA-GGLC40
N 146 290
KSA-GGLP42
N
290 N 290
290
290
a 290
KSA-GGTC40
N 146
KSA-GGXC40
N
Rating A a 75 113
146
400/500 630/800
290
290 580
290
290
290
KSA-50EZ3
40 50 50 36
KSA-80EZ3
40 50 50 36
152 30
230
176
115
21
30
8x14
120-150
323
95 323
Dust and damp proof tap-off units with/without isolator for modular equipment KSE-05DAG KSE-10DAG
270
395
50 113* 183
190
100 40
70
52
28
176
8x14
Dust and damp proof tap-off units for Merlin Gerin circuit breakers KSE-16DBG11GG KSE-25DBG11GG KSE-40DBG11GG
147
197
207
257
275
325
465 590
780
Dust and damp proof tap-off units for fused switch disconnector KSE-03ST41 KSE-06ST41 KSE-12ST41 KSE-10ST41 KSE-16ST41
51 147 50 51 147 50 51 147 50
271
10
271
10
271
10
421
10
306
406
456 606
29
450
250
Feeder busbar
500
2500
Guide bracket
500
450
250
500
Feeder busbar
2000 500
3500
Guide bracket
505
Ground floor
30
450
Feeder busbar
500
2000
Guide bracket
450
250
500
Feeder busbar
2000 500
3500
Guide bracket
505
Ground floor
31
Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems. Its quality products, solutions and services are focused on the needs of both the commercial and industrial sectors.
Modicon is a world leader in high technology programmable controllers (PLCs) and motion control systems used in industrial automation. Its international catalogue includes PLCs, numerical controllers, terminals, software, multiple fieldbus and ethernet communication networks, and human machine interfaces (HMI).
Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltage electrical distribution equipment, systems and services are used extensively in residential and commercial applications.
Telemecanique is a UK market leader and world expert in industrial control and automation. It provides complete solutions, with its range of components, programmable logic controllers, variable speed drives and communications software. In addition, it offers power distribution through prefabricated busbar trunking.
South West Schneider Electric Ltd 190 Aztec West Park Avenue Almondsbury Bristol BS32 4TP
webmasterGB@schneider.co.uk
North West Schneider Electric Ltd 8 Brindley Road City Park Business Village Cornbrook Manchester M16 9HQ
webmasterGB@schneider.co.uk
Greater London Schneider Electric Ltd 2nd Floor 408 Strand London WC2R 0NE
webmasterGB@schneider.co.uk
http://www.schneider.co.uk
CAN 5226 JUN 2002