¾¾ UL Listed
¾¾ SLC Loop-Powered & Sub-Addressable
¾¾ 4” Square or 2-Gang Electrical Box Mounting
¾¾ Flexible Programming
¾¾ Durable Construction
¾¾ Cost-Effective & Trouble-Free Installation
Description:
The IDC input of the AX-I/O is capable of being wired Class “A” • Supervised Initiating Device Circuit (IDC)
(Style D) or Class “B” (Style B) and can monitor a single contact
device or a group of devices. Contacts can be normally open • Class A (Style D) or Class B (Style B) Wiring
(N.O.) or normally closed (N.C.) ranging from heat detectors, • Independently Controlled Form-C Relay Contact
linear heat detectors, 4-wire conventional smoke detectors,
waterflow switches, tamper switches, manual pull stations, • AX Series Dynamix I/O Relationship Programming
switch input points for control, or any other supervised input • IDC Activation Status LED
requirement. Though the IDC input can monitor any number
of contact devices, it is not recommended not to mix alarm, • Optically Isolated Voltage Input
Product Data Sheet
supervisory, or security contacts on the same IDC module • Cost-Effective & Trouble-Free Installation
circuit.
Each AX-I/O incorporates an integral eight position programming DIP switch which allows for device addressing and wiring
classification definition. The module contains a red status LED which illuminates steady during active condition of the IDC
input.
NO
1 2 3 4 5 6 7 8
> 4V = High INPUT Form- C Relay Contact
OPTO
2
4
< 1V = Low
COM
8
16
32
24 VDC @ 1 Amp
64
or 30 VAC @ .5 Amp (resistive)
+
B A
SW1
N/O TB4
L2
From
Class “B” (Style B) Wiring
AX Series TB5
A/B+
SLC Loop TB1
A+
E
4.7K
O
- A- L 1/2 Watt
L1
A/B-
TB3
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice.
903-003 Rev. 1.1 Page 2 of 2