Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1900072
dx9200s 1900072 9thcc:na BAS Rev:
10/04/00
logo:
DX-9200 BAS
left ft:
dx9200a.tif
purpose electrical equipment control Options
applications. Several models are available, Application
each supporting either room control or Configuration Options
Modules
discharge air applications. As a standalone
Sensor/Transmitter ranging
unit, or when integrated into a LON WORKS
High/Low limits
network, the controller has both the hardware Analog Inputs
Filter constants
and software flexibility to adapt to a variety of Square root
control requirements. The controller can
PID Loops
extend its input and output point capability by Remote reset logic
communicating with Input/Output (I/O) Control Blocks Operation modes
modules on an extension bus, and provides Control limits and alarms
monitoring and control of all connected points Sequencer and step control logic
at its built-in Light-Emitting Diode (LED) Source points for logic functions
Digital Inputs
display. Pulse counters
DX-9200 Averaging
LONWORKS Compatible Digital Controller Features Minimum or maximum select
Enthalpy, wet bulb, and dew point
• LONWORKS compatible network variable
Description interface using FTT10 transceiver
Input selector
Calculation Arithmetic calculator
The LONWORKS® Compatible DX-9200 Digital • integration into Metasys® Network via Blocks Compare logic
Controller is the ideal digital control solution network control module (NCM350) Line segment function
for Air Handling Unit (AHU) applications or Timer functions
distributed lighting and related general • GX-9100 Software Configuration Tool
Runtime counter
• realtime clock and time programs Totalizer and integrator
• extension bus for additional I/O points AND, OR, NOT
XT/XTM Extension Modules Logic Blocks State change detect
• built-in local LED display and control panel Set and reset of parameters
and XPx Expansion Modules • optional manual override switches Analog
The DX-9200 controller supports a line of High/Low ranging
• optional text and graphic display unit Outputs
extension and expansion modules for a wider Incremental with or without
(DT-9100)
and more flexible range of I/O options, as well feedback
Digital Outputs
as a manual override option on outputs. An To Order Duration adjust type
(DX Controller)
extension module (XT-9100 or XTM-905) On/Off logic, including pulse and
used with expansion modules (XP/XPx) Specify the code number from the following start/stop
provides various combinations of analog and selection chart. Digital Outputs
On/Off logic, including pulse and
digital (binary) I/O points. A system can have (XT/XTM
start/stop
up to eight extension modules connected to Modules)
XT Bus Configuration
the controller via the XT (RS485) extension Yearly holiday calendar
XT/XTM Modules Quantity Time Start/stop times for days of week
bus.
Maximum Number of Schedule and holidays
The extension and expansion modules may be 8
XT/XTMs per DX Blocks Optimal start/stop modules
mounted next to the controller on the same (2 modules available)
8 analog + 8 digital
DIN rail, or remotely at a distance of up to 1200 Maximum Number of I/Os
(binary),
meters (3900 feet) from the controller. for each XT/XTM
or 16 digital (binary)
See the XTM-105/XTM-905/XPx Extension Maximum Number of I/Os
64
and Expansion Modules catalog page for more from XT/XTMs per DX
information.
Point Configuration
Quantity
Point Type Characteristics
DX-9200 XT-9100 w/XPx XTM-905 w/XPx (a)
0-10 VDC (impedance 300K ohm)
Analog Inputs 8 6 6 0/4-20 mA DC (impedance 100 ohm)
RTD Ni1000 (JCI), A99 (JCI), and Pt1000 (DIN)
Digital (Binary) Inputs 8 4/8/16 4/8/16 Dry Contacts (potential free)
24 VAC Triacs (minimum 0.05 amperes [A], maximum 0.5A)
Digital (Binary) Outputs 6 4/8/16 3 to 4/8/16 XT/XTM only: Relay Contact (maximum 250 VAC 3A)
XTM only: relays with magnetically latched or electrically held operation
0-10 VDC (10 mA maximum) or
4 2 2
Analog Outputs 0/4-20 mA DC
4 0 0 0-10 VDC (10 mA maximum) only
(a) The specifications of this table only pertain to modules available in North America.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 03/01 Johnson Controls, Inc
1/2
Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1900072
Specifications
DX-9200 LonWorks® Compatible Digital Controller
LONWORKS Communication FTT10 transceiver
Power Requirements 24 VAC ± 15 %, 10 VA (@ 24 VAC), 50-60 Hz
0 to 40°C (32 to 100°F)
Ambient Operating Conditions
10 to 90% RH non-condensing
-20 to 70°C (0 to 160°F)
Ambient Storage Conditions
5 to 95% RH non-condensing
Controller with Cabinet Door Mounting Frame 164 x 200 x 114 mm (6.5 x 7.9 x 4.5 in.)
Dimensions
(H x W x D) 200 x 184 x 100 mm (7.9 x 7.3 x 3.9 in.)
Controller with Panel Mounting Base
Allow minimum of 160 mm (6.3 in.) depth for hinged door clearance.
Controller: 1.8 kg (4 lb 0 oz)
Shipping Weight Panel Mounting Base: 0.8 kg (1 lb 12 oz)
Cabinet Door Mounting Frame: 0.8 kg (1 lb 12 oz)
CE Directive 89/336/EEC EN50081-1, EN50082-1
Agency Listings
FCC Compliant (UL and CSA Listings Pending)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 03/01 Johnson Controls, Inc
2/2