Content
Content
1 About this document 1.1 1.2 1.3 2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target group . . . . . . . . . . . . . . . . . . . . . . . . . . Symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4 4 4
For your safety 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 Authorised personnel . . . . . . . . . . . . . . . Appropriate use . . . . . . . . . . . . . . . . . . . Warning about misuse . . . . . . . . . . . . . . General safety instructions . . . . . . . . . . . Safety approval markings and safety tips CE conformity . . . . . . . . . . . . . . . . . . . . SIL conformity . . . . . . . . . . . . . . . . . . . . Safety instructions for Ex areas . . . . . . . Manufacturer declaration for zone 2 . . . . Environmental instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. .. .. .. .. .. .. .. .. .. 5 5 5 5 6 6 6 6 6 7
Product description 3.1 3.2 3.3 3.4 Conguration . . . . . . . Principle of operation . Operation . . . . . . . . . Storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 8 .. 9 . . 10 . . 10
Connecting to power supply 5.1 5.2 5.3 Preparing the connection . . . . . . . . . . . . . . . . . 17 Connection procedure . . . . . . . . . . . . . . . . . . . 17 Wiring plan, single chamber housing. . . . . . . . . 18
Maintenance and fault rectication 7.1 7.2 7.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Remove interferences . . . . . . . . . . . . . . . . . . . 24 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . 25
29223-EN-080227
Content
Supplementary documentation
Information: Supplementary documents appropriate to the ordered version come with the delivery. You can nd them listed in chapter "Product description".
Instructions manuals for accessories and replacement parts
29223-EN-080227
Tip: To ensure reliable setup and operation of your VEGASWING 61, we oer accessories and replacement parts. The associated documents are:
l
List The dot set in front indicates a list with no implied sequence. Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure.
29223-EN-080227
29223-EN-080227
During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations.
2.6 CE conformity
VEGASWING 61 is in CE conformity with EMC (89/336/EWG), fulls NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EG). Conformity has been judged according to the following standards:
l
EMC: - Emission EN 61326/A1: 1998 (class B) - Susceptibility EN 61326: 1997/A1:1998 LVD: EN 61010-1: 1993
29223-EN-080227
this operating instructions manual the manufacturer declaration 24612 (download under "www.vega.com")
VEGASWING 61 - contactless electronic switch
29223-EN-080227
VEGASWING 61 - contactless electronic switch
Product description
3 Product description
3.1 Conguration
Scope of delivery
VEGASWING 61 point level sensor Documentation - this operating instructions manual - Safety Manual "Functional safety according to IEC 61508 or IEC 61511 (SIL)" - Supplementary instructions manual "Plug connector for level sensors" (optional) - Ex-specic "Safety instructions" (with Ex-versions) - if necessary, further certicates
Components
Housing cover Housing with electronics process tting with tuning fork
Fig. 1 2 3
1: VEGASWING 61 with plastic housing Housing cover Housing with electronics Process tting
Type label
The type label contains the most important data for identication and use of the instrument:
l l l l
29223-EN-080227
Product description
With the serial number, it is possible to show the delivery data of the instrument via "www.vega.com", "VEGA Tools" and "serial number search". In addition to the type label outside on the instrument, the serial number is also available inside the instrument.
VEGASWING 61 is a point level sensor with tuning fork for level detection. It is designed for industrial use in all areas of process technology and can be used in liquids. Typical applications are overll and dry run protection. With a tuning fork of only 40 mm length, VEGASWING 61 can be also mounted, e.g. in pipelines from DN 25. The small tuning fork allows use in vessels, tanks and pipes. Thanks to its simple and robust measuring system, VEGASWING 61 is virtually unaected by the chemical and physical properties of the liquid. It functions even under dicult conditions such as turbulence, air bubbles, foam generation, buildup, strong external vibration or changing products.
Fault monitoring
The electronics module of VEGASWING 61 continuously monitors via frequency evaluation the following criteria:
l l l
Strong corrosion or damage on the tuning fork loss of vibration Line break to the piezo drive
If a malfunction is detected or in case of power failure, the electronics takes on a dened switching condition, i.e. the contactless electronic switch opens (safe condition).
Functional principle
The tuning fork is piezoelectrically energised and vibrates at its mechanical resonance frequency of approx. 1200 Hz. The piezos are xed mechanically and are hence not subject to temperature shock limitations. The frequency changes when the tuning fork is covered by the medium. This change is detected by the integrated oscillator and converted into a switching command.
29223-EN-080227
VEGASWING 61 - contactless electronic switch
Product description
Supply
VEGASWING 61 is a compact instrument, i.e. it can be operated without external evaluation system. The integrated electronics evaluates the level signal and outputs a switching signal. With this switching signal, a connected device can be operated directly (e.g. a warning system, a PLC, a pump etc.). The data for voltage supply are specied in chapter "Technical data".
3.3 Operation
The switching condition of VEGASWING 61 with plastic housing can be checked when the housing is closed (signal lamp). In the basic adjustment, products with a density > 0.7 g/ cm (0.025 lbs/in) can be detected. The instrument can be adapted if products with lower density should be measured. On the electronics module you will nd the following indicating and adjustment elements:
l l l
Signal lamp for indication of the switching condition (green/ red) DIL switch for sensitivity adjustment Mode adjustment for selection of the switching condition (A/B)
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180. The packaging of standard instruments consists of environment-friendly, recyclable cardboard. In addition, the sensor is provided with a protective cover of ABS. For special versions PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Transport
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device. The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Transport inspection
29223-EN-080227
10
Product description
Storage
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside. Unless otherwise indicated, the packages must be stored only under the following conditions:
l l l l l
Not in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature see "Supplement Technical data - Ambient conditions" Relative humidity 20 85 %
l l
29223-EN-080227
VEGASWING 61 - contactless electronic switch
11
Mounting
4 Mounting
4.1 General instructions
Switching point
In general, VEGASWING 61 can be installed in any position. The instrument simply has be mounted in such a way that the tuning fork is at the height of the desired switching point. The tuning fork has lateral markings (notches) that indicate the switching point with vertical mounting. The switching point refers to water with the basic setting of the sensitivity switch 0.7 g/cm (0.025 lbs/in). When mounting VEGASWING 61, make sure that this marking is at the height of the requested switching point. Keep in mind that the switching point of the instrument is shifted if the medium has a density other than water - water 1 g/cm (0.036 lbs/in). For products < 0.7 g/cm (0.025 lbs/in) and > 0.5 g/cm (0.018 lbs/in) the density switch must be set to 0.5 g/cm. Keep in mind that foams with a density > 0.45 g/cm (0.016 lbs/ in) are detected by the sensor. This can cause faulty switchings particulary when used as dry run protection system.
2 1 3
Fig. 1 2 3 4
2: Vertical mounting Switching point approx. 13 mm (0.51 in) Switching point with lower density Switching point with higher density Switching point approx. 27 mm (1.06 in)
29223-EN-080227
12
Mounting
2 1
Fig. 4: Horizontal installation (recommended installation position, especially for adhesive products) 1 Switching point 2 Marking with screwed version on top, with ange versions directed to the ange holes
With ange versions, the fork is directed as follows to the ange holes.
Moisture
29223-EN-080227
Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland. You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water
13
Mounting
can thus drain o. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels.
Transport
Do not hold VEGASWING 61 on the tuning fork. Particularly with ange or tube versions, the tuning fork can be damaged just by the weight of the instrument. Transport coated instruments very carefully and avoid touching the tuning fork. Remove the protective cover just before mounting.
Pressure/Vacuum
The process tting must be sealed if there is gauge or low pressure in the vessel. Before use, check if the seal material is resistant against the measured product and the process temperature. The max. permissible pressure is specied in chapter "Technical data" or on the type label of the sensor.
Handling
The vibrating level switch is a measuring instrument and must be treated accordingly. Bending the vibrating element will destroy the instrument. Warning: The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing. Use the hexagon above the thread for screwing in.
29223-EN-080227
14
Mounting
VEGASWING 61 has a dened thread starting point. This means that every VEGASWING 61 is in the same fork position after being screwed in. Remove therefore the supplied seal from the thread of VEGASWING 61. This seal is not required when using a welded socket with O-ring in front. Keep in mind that this welded socket is not suitable for coated instrument versions. Screw VEGASWING 61 completely into the welded socket. The later position can be determined already before welding. Mark the appropriate position of the welded socket. Before welding, unscrew VEGASWING 61 and remove the rubber ring from the welded socket. The welded socket has a marking (notch). Weld the socket with the notch facing upward, or in case of pipelines, aligned with the direction of ow.
Adhesive products
In case of horizontal mounting in adhesive and viscous products, the surfaces of the tuning fork should be vertical in order to reduce buildup on the tuning fork. On the screwed version you will nd a marking on the hexagon. With this, you can check the position of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can still be turned by approx. half a turn. This is sucient to reach the recommended installation position. With ange versions, the fork is directed to the ange holes.
29223-EN-080227
When used in adhesive and viscous products, the tuning fork should protrude into the vessel to avoid buildup. For that reason, sockets for anges and mounting bosses should be avoided when mounting horizontally.
15
Mounting
Inowing medium
If VEGASWING 61 is mounted in the lling stream, unwanted false measurement signals can be generated. For this reason, mount VEGASWING 61 at a position in the vessel where no disturbances, e.g. from lling openings, agitators, etc., can occur. To minimise ow resistance caused by the tuning fork, VEGASWING 61 should be mounted in such a way that the surfaces of the blades are parallel to the product movement.
Flows
29223-EN-080227
16
In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units. Connect the power supply according to the following diagrams. Oscillator SWE60C is designed in protection class 1. To maintain this protection class, it is absolutely necessary that the ground conductor be connected to the internal ground terminal. Take note of the general installation regulations. As a rule, connect VEGASWING 61 to vessel ground (PA), or in case of plastic vessels, to the next ground potential. On the side of the housing there is a ground terminal between the cable entries. This connection serves to drain o electrostatic charges. In Ex applications, the installation regulations for hazardous areas must be given priority. The data for voltage supply are specied in chapter "Technical data".
VEGASWING 61 is connected with standard cable with round cross section. An outer cable diameter of 5 9 mm (0.2 0.35 in) ensures the seal eect of the cable gland. If cable with a dierent diameter or wire cross section is used, exchange the seal or use an appropriate cable connection. In hazardous areas, only use approved cable connections for VEGASWING 61.
With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present. Proceed as follows:
17
1 2 3
Unscrew the housing cover Loosen compression nut of the cable entry Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) insulation from the ends of the individual wires Insert the cable into the sensor through the cable entry Open the terminals with a screwdriver Insert the wire ends into the open terminals according to the wiring plan Tighten the terminals with a screwdriver Check the hold of the wires in the terminals by lightly pulling on them Tighten the compression nut of the cable entry. The seal ring must completely encircle the cable
4 5 6 7 8 9
1
Fig. 1 2 3 4
8: Material versions, single chamber housing Plastic (not with EEx d) Aluminium Stainless steel (not with EEx d) Filter element for pressure compensation (not with EEx d)
29223-EN-080227
18
1
0,5 g / cm3 0,7 g / cm3
2 3 4
1 2
Fig. 1 2 3 4 5
9: Electronics and connection compartment, single chamber housing Control lamp DIL switch for mode adjustment DIL switch for switching point adaptation Ground terminal Connection terminals
Wiring plan
We recommend connecting VEGASWING 61 in such a way that the switching circuit is open when there is a level signal, line break or failure (safe condition). The contactless electronic switch is always shown in nonoperative condition. Warning: The instrument must not be operated without an intermediately connected load, because the electronics would be destroyed if connected directly to the mains. It is not suitable for connection to low voltage PLC inputs. For direct control of relays, contactors, magnet valves, warning lights, horns etc. Domestic current is temporarily lowered below 1 mA after switching o the load so that contactors, whose holding current is lower than the constant domestic current of the electronics, are reliably switched o.
29223-EN-080227
19
When VEGASWING 61 is used as part of an overll protection system according to WHG, also note the regulations of the general type approval.
1 2
AC L1 N DC + - +
Fig. 10: Wiring plan, single chamber housing
29223-EN-080227
20
Set up
6 Set up
6.1 In general
The numbers in brackets refer to the following illustrations.
Function/Conguration
The switching condition of the electronics can be checked on the plastic housing with closed housing cover (control lamp). In the basic setting, products with a density > 0.7 g/cm (0.025 lbs/in) can be detected. For products with lower density, the switch must be set to > 0.5 g/cm (0.018 lbs/in). On the electronics module you will nd the following indicating and adjustment elements:
l l l
Signal lamp (1) DIL switch for mode adjustment - A/B (2) DIL switch for sensitivity adjustment (3)
Note: For test purposes, immerse the tuning fork of VEGASWING 61 always in liquids. Do not test the function of VEGASWING 61 with the hand. This can damage the sensor.
1 2 3
29223-EN-080227
Fig. 1 2 3
11: Oscillator SWE60C - Contactless electronic switch Signal lamp (LED) DIL switch for mode adjustment DIL switch for sensitivity adjustment
21
With the mode adjustment (A/B) you can change the switching condition of the relay. You can set the required mode according to the "Function chart" (A - max. detection or overll protection, B - min. detection or dry run protection). With this DIL switch (3) you can set the switching point to liquids having a density between 0.5 and 0.7 g/cm (0.018 and 0.025 lbs/in). With the basic setting, liquids with a density of > 0.7 g/cm (0.025 lbs/in) can be detected. In liquids with lower density, you must set the switch to > 0.5 g/cm (0.018 lbs/ in). The specications for the position of the switching point relate to water - density value 1 g/cm (0.036 lbs/in). In products with a dierent density, the switching point will shift in the direction of the housing or tuning fork end depending on the density and type of installation. Keep in mind that foams with a density > 0.45 g/cm (0.016 lbs/ in) are detected by the sensor. This can cause faulty switchings particulary when used as dry run protection system.
Switching status
Control lamp
Green
Red
29223-EN-080227
Switch closed
Green
22
Set up
Switching status
Control lamp
Red
Switch open
ashes red
29223-EN-080227
VEGASWING 61 - contactless electronic switch
23
The operator of the system is responsible for taken suitable measures to remove interferences. VEGASWING 61 oers maximum reliability. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.:
l l l l
Fault clearance
The rst measure to be taken is to check the output signal. In many cases, the causes can be determined this way and the faults rectied. However, should these measures not be successful, call the VEGA service hotline in urgent cases under the phone no. +49 1805 858550. The hotline is available to you 7 days a week round-the-clock. Since we oer this service world-wide, the support is only available in the English language. The service is free of charge, only the standard telephone costs will be charged.
? VEGASWING 61 signals "covered" when the vibrating element is not submerged (overll protection) ? VEGASWING 61 signals "uncovered" when the vibrating element is submerged (dry run protection)
l
Press the mode switch (min./max.). If the instrument then changes the mode, the vibrating element may be covered with buildup or mechanically damaged. Should the switching function in the correct mode still be faulty, return the instrument for repair.
29223-EN-080227
24
Push the mode switch. If the instrument then does not change the mode, the oscillator may be defective. Exchange the oscillator. Check if there is buildup on the probe, and if so, remove it.
l
Mount the instrument at a location in the vessel where no dead zones or air bubbles can form.
l
Set the correct mode on the mode switch (max.: overll protection, min.: dry run protection). Wiring should be carried out according to the quiescent current principle. ? Signal lamp ashes red
l
Exchange instrument or return instrument for repair ? The signal lamp ashes alternately red and green
l
instrument defective
Depending on the failure reason and measures taken, the steps described in chapter "Set up" must be carried out again, if necessary.
29223-EN-080227
Print and ll out one form per instrument Clean the instrument and pack it damage-proof Attach the completed form and, if need be, also a safety data sheet outside on the packaging Please ask the agency serving you for the address of your return shipment. You can nd the respective agency on our website www.vega.com under: "Company - VEGA worldwide"
25
Dismounting
8 Dismounting
8.1 Dismounting steps
Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present.
8.2 Disposal
The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/ EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. Correct disposal avoids negative eects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return.
29223-EN-080227
26
Supplement
9 Supplement
9.1 Technical data
General data Material 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts - Process tting - thread Process tting - ange Process seal Tuning fork Extension tube: 21.3 mm (0.839 in) 316L, Hastelloy C4 (2.4602) 316L, 316L with Hastelloy C4 plated, 316L with ECTFE coated, 316L with PFA coated Klingersil C-4400 316L/Hastelloy C4 (2.4610) 316L, Hastelloy C4 (2.4610), 316L with ECTFE coating, 316L with PFA coating plastic PBT (Polyester) Aluminium die-casting AlSi10Mg, powdercoated - basis: Polyester 316L 316L NBR (stainless steel housing, investment casting), silicone (Aluminium/plastic housing, stainless steel housing, electro-polished) PMMA (Makrolon) 316L 316L 316L/glass See chapter "Dimensions" +51 mm (2 in) 0.8 4 kg (0.18 8.82 lbs)
Materials, non-wetted parts - Plastic housing Aluminium die-casting housing Stainless steel housing - precision casting Stainless steel housing, electropolished Seal between housing and housing cover
Light guide in housing cover Ground terminal Temperature adapter (optional) Gas-tight leadthrough (optional)
29223-EN-080227
27
Supplement
Ra 3 m (1.18-4 in) Ra < 0,8 m (3.15-5 in) Ra < 0,3 m (1.18-5 in) G A, G1 A NPT, 1 NPT DIN from DN 25, ANSI from 1" Bolting DN 40 PN 40, Tri-Clamp 1", TriClamp 1" PN 10, conus DN 25 PN 40, Tuchenhagen Varivent DN 50 PN 10 < 10-6 mbar l/s PN 64 Bolting DN 40 PN 40, Tri-Clamp 1", TriClamp 1" PN 10, conus DN 25 PN 40, Tuchenhagen Varivent DN 50 PN 10
Process ttings - Pipe thread, cylindrical (ISO 228 T1) American pipe thread, tapered Flanges hygienic ttings
Output variable Output Modes (adjustable) - A B Contactless electronic switch Max. detection or overow/overll protection Min. detection or dry run protection
Accuracy (similar to DIN EN 60770-1) Reference conditions and actuating variables according to DIN EN 61298-1 - Ambient temperature +18 +30 C (+64 +86 F) Relative humidity Air pressure Product temperature Product density Viscosity Superimposed pressure Sensor installation Density selection switch 45 75 % 860 1060 mbar/86 106 kPa (12.5 15.4 psi) +18 +30 C (+64 +86 F) 1 g/cm (0.036 lbs/in) (water) 1 mPa s
29223-EN-080227
28
Supplement
1 4
10 ( 25/64")
8 ( 5/16") 6 ( 15/64") 4 ( 5/32")
-10 (-25/64")
0 C (32 F) 50 C (122 F) 100 C (212 F) 150 C (302 F) 200 C (392 F) 250 C (482 F)
Fig. 1 2 3 4
25: Inuence of the process temperature on the switching point Shifting of the switching point in mm (in) Process temperature in C (F) Switching point at reference conditions (notch) Tuning fork
29223-EN-080227
VEGASWING 61 - contactless electronic switch
29
Supplement
1 6
10 ( 25/64")
8 ( 5/16") 6 ( 15/64") 4 ( 5/32")
4 3
-10 (-25/64")
0,6 (0,022) 0,8 (0,029) 1 (0,036) 1,2 (0,043) 1,4 (0,051) 1,6 (0,058) 1,8 (0,065) 2 (0,072) 2,2 (0,079) 2,4 (0,087)
Fig. 1 2 3 4 5 6
26: Inuence of the product density on the switching point Shifting of the switching point in mm (in) Product density in g/cm (lb/in) Switch position 0.5 g/cm (0.018 lb/in) Switch position 0.7 g/cm (0.025 lb/in) Switching point at reference conditions (notch) Tuning fork
29223-EN-080227
30
Supplement
1 4
10 ( 25/64")
8 ( 5/16") 6 ( 15/64") 4 ( 5/32")
-10 (-25/64")
12 (174,1) 25 (362,6) 38 (551,1) 51 (739,7) 64 (928,2)
Fig. 1 2 3 4
27: Inuence of the process pressure to the switching point Shifting of the switching point in mm (in) Process pressure in bar (psig) Switching point at reference conditions (notch) Tuning fork
Repeatability Hysteresis Switching delay Frequency Ambient conditions Ambient temperature on the housing Storage and transport temperature
0.1 mm (0.004 in) approx. 2 mm (0.08 in) with vertical installation approx. 500 ms (on/o) approx. 1200 Hz
Process conditions Measured value Process pressure Limit level of liquids -1 64 bar/-100 6400 kPa (-14.5 928 psig) depending on the process tting, e.g. ange (see following diagrams) -50 +150 C (-58 +302 F)
29223-EN-080227
31
Supplement
Process temperature (thread or ange temperature) with temperature adapter (option) - VEGASWING 61 of 316L/Hastelloy C4 VEGASWING 61 with ECTFE coating VEGASWING 61 with PFA coating
-50 +250 C (-58 +482 F) -50 +150 C (-58 +302 F) -50 +150 C (-58 +302 F)
2 3
70 C (158 F) 40 C (104 F)
-50 C (-58 F)
0 C (32 F)
1
50 C (122 F) 100 C (212 F) 150 C (302 F) 200 C (392 F) 250 C (482 F)
-40 C (-40 F)
Fig. 1 2 3
28: Ambient temperature - Process temperature Process temperature in C (F) Ambient temperature in C (F) Temperature range with temperature adapter
1
64 (928) 40 (580) 20 (290) -1 (-14,5) -50 C (-58 F) 0 C (32 F) 50 C (122 F) 100 C (212 F) 150 C (302 F) 200 C (392 F) 250 C (482 F)
Fig. 29: Process temperature - Process pressure with switch position 0.7 g/cm (mode switch) 1 Process pressure in bar (psig) 2 Process temperature in C (F)
29223-EN-080227
32
Supplement
1
64 (928) 40 (580) 20 (290) -1 (-14,5) -50 C (-58 F) 0 C (32 F) 50 C (122 F) 100 C (212 F) 150 C (302 F) 200 C (392 F) 250 C (482 F)
Fig. 30: Process temperature - Process pressure with switch position 0.5 g/cm (mode switch) 1 Process pressure in bar (psig) 2 Process temperature in C (F)
0.1 10,000 mPa s (requirement: with density 1) 0.7 2.5 g/cm (0.025 0.09 lbs/in); 0.5 2.5 g/cm (0.018 0.09 lbs/in) by switching over
Electromechanical data Cable entry/plug (dependent on the version) - Single chamber housing
l
1 x cable entry M20 x 1.5 (cable: 5 9 mm), 1 x blind stopper M20 x 1.5; attached 1 x cable entry M20 x 1.5 1 x cable entry NPT, 1 x blind stopper NPT, 1 x cable entry NPT 1 x plug M12 x 1; 1 x blind stopper M20 x 1.5
or:
l
or:
l
Screw terminals
29223-EN-080227
VEGASWING 61 - contactless electronic switch
33
Supplement
Adjustment elements Mode switch - A B Max. detection or overow/overll protection Min. detection or dry run protection 0.5 2.5 g/cm (0.018 0.9 oz/in) 0.7 2.5 g/cm (0.025 0.9 oz/in)
Voltage supply Supply voltage Domestic current requirement Load current - Min. Max. 20 253 V AC, 50/60 Hz, 20 253 V DC approx. 3 mA (via load circuit) 10 mA 400 mA (with I> 300 mA the ambient temperature can be max. 60 C/140 F) max. 4 A up to 40 ms (not WHG specied)
Electrical protective measures Protection Overvoltage category Protection class Approvals1) Overll protection according to WHG ATEX II 1G 1/2G, 2G EEx ia IIC T6 ATEX II 1/2G, 2G EEx d IIC T62) FM (NI) CL I, DIV 2, GP ABCD FM (XP) CL I, DIV 1, GP ABCD (DIP) CL II, III, DIV 1, GP EFG3) Ship approvals IP 66/IP 67 III I
29223-EN-080227
1) 2) 3)
Deviating data in Ex applications: see separate safety instructions. Only with Aluminium housing. Only with Aluminium housing.
34
Supplement
9.2 Dimensions
VEGASWING 61
~ 59 mm (2 21/64") 77 mm (3 1/32") ~ 69 mm (2 23/32")
~ 69 mm (2 23/32")
80 mm (3 5/32")
77 mm (3 1/32")
112 mm (4 13/32")
M20x1,5/ NPT
112 mm (4 13/32")
M20x1,5/ NPT
M20x1,5/ NPT
1
Fig. 1 2 3 4
117 mm (4 39/64")
31: Housing versions Plastic housing Stainless steel housing, electro-polished Stainless steel housing - precision casting Aluminium housing
29223-EN-080227
VEGASWING 61 - contactless electronic switch
35
Supplement
VEGASWING 61
18,5 mm (47/64")
53 mm (2 3/32")
55 mm (2 11/64")
57 mm (2 1/4")
36 mm (1 27/64")
19 mm (3/4")
34 mm (1 11/32")
53 mm 50 mm (2 3/32") (1 31/32")
178 mm (7 1/64")
Fig. 1 2 3 4 5 6 7
32: VEGASWING 61 Thread Tri-Clamp Cone DN 25 Bolting DN 40 Flange Gas-tight leadthrough Temperature adapter
29223-EN-080227
36
Supplement
9.4 Trademark
All brands used as well as trade and company names are property of their lawful proprietor/originator.
29223-EN-080227
VEGASWING 61 - contactless electronic switch
37
Supplement
29223-EN-080227
38
Supplement
29223-EN-080227
VEGASWING 61 - contactless electronic switch
39