Professional Documents
Culture Documents
CHAPTER-15
LT SWITCHGEAR
SNO.
1.
2.
3.
4.
5.
6.
7.
8.
LT SWITCHGEAR 15.2
A typical bus bar arrangement of LT switch is shown in fig-14. There are 02 sources of
3d power supply, one no. from transformer #1 & other from transformer #2. The 3d
supply terminals of transformers are connected to incoming terminals individual breakers
i.e Tr#1 to Q1 and Tr #2 to Q3 through Aluminum/copper strips, 3 core cables. If
aluminum or copper strips are used than these strips housed in a duct. Called bus duct, the
out going terminals of the breakers are connected to the horizontal bus bars of their
individual section. Called section A & B. By switching On the breaker Q1 & Q3 the
power supply can be fed to section-A and B respectively. The buss bar (Horizontal) of
section-A&B extended upto their extreme end of their section. To connected the bus
section-A&B a switch issued called bus coupler Q2. These type of bus bar arrangement
called single bus, sectionalized bus bar arrangement.
There are number of sets of vertical dropper bus bars in each section which are connected
to each phase of the horizontal main bus bars. The size of vertical bus bars is smaller
than the main bus bares as connected load to each set of vertical bus bars is less than
main bus bar.
The power supply tapped from these vertical bus bars for outgoing feeders.
If any source of supply fails, the power supply to that section can be fed from other
source of supply by switch on the bus coupler Q2.
A green colour bus bar in lower portion of switch R runs through out the MCC/PCC
called earthing bus bar which is connected to a external earthing pit/grid with a
MS/GIstrip.
(SNO-110)
TOPIC: CHANGE OVER SCHEME.
Change over means to feed both the section A & B from one source if these sections
earlier fed from individual source or to feed the individual section from own source if
earlier both the section fed from one source.
There are 02 types of change over schemes.
LT SWITCHGEAR 15.3
1.
2.
Local/Remote switch This switch is used whether breaker to be closed from local or
remote.
2.
3.
4.
LT SWITCHGEAR 15.4
5.
B-(I/L) defect relay). It is energized by synchronized. Check relay it defects the I/L to
close the breaker in case of live change over condition for I/Cs breaker closing.
i)
ii)
iii)
A)
Any other Incomer tripped/off due to any reason e.g tripping of upstream breaker.
B)
C)
The voltage of that bus less than 30% i.e no voltage in that bus this condition is
monitored by relay U/V-6 or U/V-4 as the case may be
Example: Suppose up stream of Incomer #1 switch Off. The voltage at Incomer #1 and
at corresponding bus will become zero. It is monitored by relay U/V-1 and U/K4. The
relay U/V-1 will give the tripping command to Incomer #1. The auto closing circuit will
check Incomer #1 is Off Yes.
Bus-A No fault Yes
Bus-B Voltage 780% - Yes
Bus-A Voltage , 30% - Yes
If all the condition fulfilled the bus coupler will close an auto mode.
The tripping circuit almost same for incomers and bus coupler except under voltage trip,
this command is generated by U/V-1 & U/V-2 incase of under voltage for I/C-1 & I/C-2
and up-stream trip.
LT SWITCHGEAR 15.5
(SNO-111)
TOPIC: CONTROL AND AUX.SUPPLY BUS LAYOUT.
In PCC/MCC the breakers and electromagnetic contractor type feeders used to fed
the power supply to the bus bars, motors or to other external loads. To switch On/Off
these breakers and contractors reliable control supply is needed. In case of breaker 02
nos 220 VDC needed, 01 for tripping circuit of the breaker and one for closing circuit and
spring charging motor. In breakers the tripping and closing achieved by energizing 02
nos electromagnetic coils 01 for tripping and other for closing which release the spring
mechanism by attracting a plunger as the case may be.
In case of contact feeder ( for motor) a mov AC supply is used to energize the
contact electromagnetic coil which attract a plunger. The 3 poles of contact mechanically
coupled with this plunger. These 3 poles make through the 3 supply to the motors. To
meet these requirements different type of supply bus bards are also provided throughout
the MCC/PCC and run along horizontal bus bar but in a isolated compartment. The
power supply to these bus bars fed from reliable sources e.g mov DC battery bank, 1 d
AC source.
The purpose of these bus bars are (ref. Fig no.15)
1.
2.
3.
4.
MOV DC bus bar for tapping the tripping supply of the breakers.
MODC bus bar for tapping the closing and spring charging motor supply.
MOV AC bus bar for tapping the contactor feeders control supply in service position.
MOVAC bus for space heater in PCC/MCC Panels and test control supply for contactor
feeders in test position.
SWITCHING OF LOADS
Switching equipment must clearly be suitable for switching normal and when required abnormal conditions
of the circuit in which it is situated. All circuits consist of series/parallel arrangements of resistance,
reactance and capacitance and during switching these components will produce resonances of different
forms. The switching equipment must therefore be capable of safety withstanding these resonant
LT SWITCHGEAR 15.6
conditions during the switching operation.
encountered.
Shunt Capacitor Bank switching: When switching a shunt capacitor bank the load is purely
capacitive. The source side of the circuit breaker will include bus bar capacitance to earth, this
being small compared with the load capacitance and series reactance. The energy stored in the
load capacitor is discharged to the bus bar shunt capacitance and series inductance to cause a high
frequency oscillation. Large currents will flow across the opening contact gap and damage to are
control devices may occur.
2.
Overhead Line and Cable Switching: Both overhead line and cable switching conditions present
problems similar to those of capacitor switching.
In the case of over head line there will be distributed capacitance between the phases and to earth
along the line, interspersed with distributed line inductance. The load current is again small and
its interruption is probable at the first available current zero. This will leave a charge on the line
which may result in a travelling wave propagating along the line to the far end where it will reflect
and return to the circuit breaker.
A further problem may occur when switch an over head line which is terminated at an unloaded
transformer. The combination of line capacitance and x-mer reactance then may cause high
frequency oscillations with phase to earth over voltages in excess of 3 pv. Over head line
switching regimes usually prohibit the switching of such circuits.
With cable switching the condition is similar to over head line switching except the capacitance
values significantly higher than those associated with the over head line will be encountered.
3.
Transformer Magnetizing Current Switching: We know that circuit breakers generally clear on
cessation of flow of current i.e at a natural zero current. When interrupting very low values of
current this may hot always be the case and the arc extinction mechanisms may force the arc to
extinguish before the current reaches its natural zero. This phenomenon is referred to as current
chopping, since the voltage appearing across the circuit is proportional to the rate of change of
current times and inductive of the circuit, very high voltages may occur as a result of current
chopping. This phenomenon occurs when switching low inductive currents, as for example may
occur when switching the magnetizing current of a x-mer. The transient voltage in fact oscillate at
a frequency determined by the x-mer magnetizing inductance and winding capacitance. The
oscillation will be damped by eddy and current hysterics losses in the x-mer. Over voltages of the
order of 3 P.V may be generated.
4.
Shunt Reactor Switching Shunt reactors are often used to compensate for the capacitance of
highly loaded lines. They may be frequently switched depending on the line loading regimes.
Shunt reactor switching presents overuse switching conditions for a circuit breaker and frequent
maintenance may be necessary.
5.
Series Reactor Switching: Series reactors are same times used to limit the short circuit fault
capacity between the two connected sections of a supply system should a fault occur on the circuit
side of the reactor this would cause a relatively high frequency transient on the reactor side of the
circuit breaker and a low frequency oscillation on the bus bar side. Thus circuit breakers for series
reactor switching duties need to be tested for these specific conditions.
6.
Disconnector Switching: Whilst disconnectors generally have only to switch the small capacitive
currents associated with a section of bus bar between the disconnector and circuit breaker, this can
cause certain problems. Firstly, the disconnector must be capable of satisfactorily switching the
LT SWITCHGEAR 15.7
maximum value of capacitive current likely to be encountered causing contact or dielectric
deterioration. Secondly contacts of a disconnector are generally slow in operation and when
switching very low values of capacitive current, very many re-ignitions may occur.
Disconnectors are also commonly used to transfer load (current from one bus bar to an adjacent
parallel connected bus bar. Under these conditions the disconnector may have to make and break
full load current with a voltage across its contacts equal to the impedance drop around the parallel
circuit. Whilst this may only be some tens of volts contact burning can result.
7.
Earth Switch/Switching: Since earth switches are only applied to a de-energised circuit they
should not under normal conditions, be required to make or break current. However, when an
over head line is taken out of service and where work is required on the line, it is necessary to
earth the line at both ends.
COURSE SR.NO.107
AIR CIRCUIT BREAKERS
The arc interruption in oil is due to the generation of hydrogen gas because of the decomposition of oil. No,
doubt, arc interruption properties of hydrogen are much superior to air, but air has several advantages as an
arc extinguishing medium as compared to oil. They are;
LT SWITCHGEAR 15.8
1.
Fire risk and maintenance associated with the use of oil are eliminated.
2.
Arcing products in air are generally completely removed whereas oil deteriorates with successive
breaking operation. Therefore, the expense of regular oil replacement is avoided.
3.
Heavy mechanical stresses set up by gas pressure and oil movement are absent.
4.
Relatively inferior arc extinguishing properties of air may be offset by using various principles of
arc control and operating air at high pressures.
This is why except for a certain medium range of voltages, ACBs are widely used for the low
voltage circuits as well as the highest transmission voltages.
Simple ACBs which do not incorporate any arc control devices are used for low voltages below
1KV. These breakers usually have two pairs
Of contacts per phase. The main pair of contact carries the current under normal operating
conditions and is made of copper. The additional pair actually becomes the arcing electrode as the
circuit breaker is opened and are made of carbon because the vaporization and distortion of the
contacts due to the heat of the arc are confined to these contacts and therefore, the material used
for the contacts should be non volatile. The main contacts separate while the arcing pair is still in
contact and the arc is therefore, initiated only when the arcing pair separate.
The principle of operation of these breakers is based on the high resistance method in which the
arc resistance is increased in time to such a high value that it forces the current to reach zero
without possibility of arc being restruck thereafter. The arc resistance may be increased due to
any of all the deionizing methods i.e cooling, lengthening and splitting of the arc.
ARC CHUTE AIR CIRCUIT BREAKERS:
In this case the arc is extinguished by lengthening and increasing the voltage gradient i.e power
loss of the arc. The arc discharge is moved upward by both thermal and electromagnetic effects
(as shown in figure). This is then driven into a chute consisting of splitters and baffles. The
splitters increase the length of the arc even further and the baffles give improved cooling. In this
breaker relatively high arc resistance is obtained near current zeros. This effect plays an important
role in obtaining high breaking capacity by modifying the circuit p.f near current zero such that the
voltage available to re-strike the arc is appreciably less than the peak value. A disadvantage of arc
principle is the inefficiency at low currents where the electromagnetic fields are weak. The chute
itself is not necessarily less efficient in its lengthening and de-ionizing
LT SWITCHGEAR 15.9
Action than at high currents, but the movement of the arc into the chute tends to become slower
and high speed interruption is less assured.