You are on page 1of 26

ACM-1D V3.

0x USERS GUIDE
BFP002130000 BPF002140000 BPF002150000

On Test Alarm

Fct

U/I/

-1-

ACM-1D

CONTENTS
1 2 3 PREAMBLE .........................................................................................3 PRESENTATION .................................................................................3 CHARACTERISTICS ...........................................................................4 3.1 INPUT SPECIFICATIONS .......................................................................... 4 3.2 EMC ................................................................................................... 4 3.3 ENVIRONMENTAL CONDITIONS ................................................................ 4 3.4 MECHANICAL SPECIFICATIONS ................................................................ 4 3.5 EQUIPMENT SAFETY .............................................................................. 4 3.6 PROTECTION ........................................................................................ 4 INPUTS/OUTPUTS ..............................................................................5 4.1 ANALOG INPUTS .................................................................................... 5 4.2 ANALOG OUPUT .................................................................................... 5 4.3 DIGITAL INPUTS .................................................................................... 5 4.4 DIGITAL OUTPUTS ................................................................................. 5 CHARGING MODES ............................................................................7 5.1 DIRECT MODE ....................................................................................... 7 5.2 TEMPERATURE COMPENSATION MODE (FLOATING) .................................... 7 5.3 TEMPERATURE COMPENSATION (FLOATING) + BOOST CHARGE MODE .......... 8 5.4 2-RATE MODE ....................................................................................... 9 BATTERY TEST ................................................................................10 6.1 PRINCIPLE .......................................................................................... 10 6.2 SECURITY .......................................................................................... 10 6.3 HISTORY MANAGEMENT ........................................................................ 11 RECTIFIER MANAGEMENT ..............................................................12 ALARMS AND STATUS MANAGEMENT ..........................................12 8.1 ALARMS ............................................................................................. 12 8.2 STATUSES.......................................................................................... 13 FRONT PANEL ..................................................................................14 9.1 LEDS ............................................................................................... 14 9.2 DISPLAY ............................................................................................. 14 9.3 COMMANDS ........................................................................................ 16

7 8

10 INSTALLATION RECOMMENDATION..............................................17 11 MAINTENANCE .................................................................................18 12 COMMUNICATION ............................................................................19 12.1 PIN ASSIGNMENT OF RS232 CONNECTOR (RJ45) ................................... 19 12.2 COMMUNICATION SETTING ................................................................... 19 12.3 PROTOCOL ......................................................................................... 19 12.4 READING THE SYSTEM STATUS .............................................................. 20 12.5 CONFIGURATION COMMANDS ................................................................ 23 13 APPENDIX .........................................................................................24 13.1 ACM1D REAR CONNECTOR.................................................................. 24 13.2 SAFT POWER SYSTEMS SUBSIDIARIES....................................... 25

-2-

PREAMBLE

Declaration of conformance : registered with reference : SQ/DF/DEC99002


This equipment has been designed to meet the requirements of the European Directives applicable to the product concerned, i.e. Directive on Electromagnetic Compatibility (EMC) N89/336/EEC of 03-05-89 amended by directives N 92/31/EEC of 28-04-92 and N 93/68/EEC of 22-07-93 and Low Voltage Directive N 73/23/EEC of 19-03-73 amended by Directive N 93/68/EEC of 22-07-93. Therefore it has the mark. This equipment is designed to be used in an industrial or residential environment.

PRESENTATION

The ACM1D module is a flexible battery and rectifier controller powered on a 24 VDC, 48VDC or 60 VDC Bus. It can manage : up to 10 rectifiers. 2 relays (battery branch and load). 2 shunts (battery current, load or rectifiers current). Main features are : Control of the rectifiers output voltage to charge VRLA or open batteries with 4 charging modes available (configurable) : Direct mode : no battery management with a fixed voltage level. Floating with temperature compensation and charging current limitation Floating with temperature compensation + high-rate level (with charging current limitation). 2 rate mode without temperature compensation (with charging current limitation). Note : high-rate modes can be triggered manually or periodically. Control of a battery relay for deep discharge protection. Control of an auxiliary relay for non-essential load disconnection (battery life expander). Alarm detection and reporting on 5 possible digital outputs. Periodical and/or manual battery test to estimate the capacity.

-3-

3 3.1

CHARACTERISTICS Input Specifications

Nominal voltage Normal operating range: 18 - 75 VDC. Nominal current 0.15 Amp DC @ 48 volts.DC Board under dangerous voltage (for 60 volts DC applications).

3.2 EMC
Emission Immunity standard EN 50081-1 (Generic standard) standard EN 50082-2 (Generic standard)

3.3

Environmental Conditions
: : -30C to +80C -20C to +70C

Temperature range shipping and storage operating Relative humidity shipping and storage operating Altitude 1000 m maximum.

: :

10 to 95% 20 to 95%

3.4

Mechanical Specifications

Dimensions Height : 3 U (261.7 mm) Width : 9 TE (60.1 mm) Depth : 225 mm Weight : < 0.5 kg Degree of protection : level 2 Rear connector : DIN41612 96 pins.
On Test Alarm
SAFT

Fct

U/I/T/

RS232

ACM-1D

9 TE

225 mm +/-0.4

3.5

Equipment safety

Complies with IEC 950 (3rd edition).

3.6

Protection

Input fuse on minus polarity.

-4-

100 +/-0.3

3U

INPUTS/OUTPUTS

The ACM1D provides on the rear connector (96 pins) : - 5 analog inputs for measurements. - 1 analog output to control the rectifiers voltage. - 16 digital inputs - 9 digital outputs Note : The pinout of the rear connector is given in the appendix.

4.1 Analog inputs


DC bus voltage : Measurement range is from 18V to 75V Battery voltage Measurement range is from 18V to 75V Load or rectifier current Current is measured from a shunt sensor. The range is 0..50mV (shunt value is configurable). Battery current Measurement is done from a shunt sensor. The range is -50..20mV (shunt value is configurable). Note : positive millivolts means the battery in under charge. Temperature sensor The sensor probe is a LM335 type. It proportionally converts temperature (K) into voltage (10mV/K). The measurement range is 2.5V..3.33V (-23C...60C)

4.2 Analog ouput


1 analog output is available to control the DC bus voltage. The analog output varies from 0 to 10Vdc (referenced to the DC minus).

4.3

Digital Inputs

The digital inputs are used to detect the rectifiers position and control the system status. 5 inputs are dedicated to rectifiers detection (Rect1..Rect5). 5 inputs can be configured as rectifiers detection or spare inputs (Rect6/Spare8..Rect10/Spare4) 1 input is dedicated to feed back from the battery fuse (FuseBatt) 1 input is dedicated to feed back from the distribution fuses (FuseLoad). 1 input is dedicated to mains failure detection (MainsFail). 3 inputs are spares (Spare1 to Spare3)

Input is either connected to the DC- or is open. The logic to manage the inputs is configurable (individually for each input).

4.4

Digital outputs

The ACM1D provides 9 digital outputs : 1 output dedicated to the management of the battery LVD relay. Output characteristic is : Open drain. 100V/300mA
-5-

1 output dedicated to the management of the non essential load LVD relay. Output characteristic is : Open drain. 100V/300mA 1 output dedicated to the Mains failure alarm reporting. Output characteristic is : Open collector. 100V/10mA 1 output dedicated to the Urgent alarm reporting. Output characteristic is : Open collector. 100V/10mA 1 output dedicated to the Non Urgent alarm reporting. Output characteristic is : Open collector. 100V/10mA 2 spare outputs for alarm reporting (or fan management, .) Output characteristic is : Open collector. 100V/10mA These outputs are labelled Output1/Output3 on the rear connector. 2 spare outputs Output characteristic is : Current generator (5mA/10Vmax) These outputs are labelled RemoteOff/Output2 on the rear connector. Note : Usually the remoteOff output is used to shutdown the rectifiers on alarm conditions.

Important : The outputs characteristics described here deal with the ACM1D only. They may be different on the system or the subracks terminals.

-6-

CHARGING MODES

The ACM1D provides 4 different charging modes :

5.1

Direct mode

In this mode, regulation is performed to reach an user-defined level. There is no current limit and no temperature compensation.

5.2

Temperature compensation mode (floating)

The DC bus voltage depends on the temperature. The compensation curve has the following equation :

V/cell = K1 + K2 t + K3 t2
K1/K2/K3 coefficients are configurable parameters.

Temperature compensation
2,4 2,35

V/cell

2,3

2,25 2,2 2,15 -10

10

20

30

40

50

t (C) 60

The temperature range for compensation can also be configured (0C/32F to 45C/113F in the above example). In this mode, the charging current is limited to an user-defined level.

-7-

5.3

Temperature compensation (floating) + boost charge mode

This mode is identical to the previous one with an additionnal boost charge mode.
temp. compensation + boost charge

2,4 2,35

V/cell

2,3 2,25 2,2 2,15 -10

10

20

30

40

50 t (C) 60

The boost charge voltage level is fixed (not temperature compensated) and programmable. Conditions to enter the boost charge mode are : Return of the mains supply At regular interval (can be inhibited) Manually with the local keyboard or through the communication protocol

Conditions to quit the boost charge mode are : Battery charging current below a programmable threshold. Manual release by the keyboard or the communication link. Time-out (programmable) : abnormal condition with alarm. Mains failure Abnormal conditions : Disconnection of the battery (Fuse blown, .), loss of a sensor.

A charging current limit is applied in floating and boost charge mode (2 different programmable values).

-8-

5.4

2-rate mode

In this mode, the ACM1D has 2 fixed voltage levels : Float level (low rate : programmable). Boost level (high rate : programmable).
2 rates mode
2,5 2,4 V/cell 2,3 2,2 2,1 2 -15 -5 5 15 25 Temp (C) 35 45 55 65

Conditions to enter in boost charge mode are : Return of the mains supply At regular interval (can be inhibited) Manually by the keyboard or through the communication protocol

Conditions to exit the boost charge mode are : Battery charging current below a programmable threshold. Manual release by the keyboard or the communication link. Time-out (programmable) : abnormal condition. Mains failure Abnormal conditions : Disconnection of the battery (Fuse blown, .), loss of a sensor.

-9-

6 6.1

BATTERY TEST Principle

The ACM1D can perform a battery test at regular intervals. Such a test can also be manually triggered. During a battery test, the ACM1D decreases the DC bus voltage so that the battery discharges at a constant current (configurable). The test will stop when the voltage has decreased of a pre-defined value (since the beginning of the test). The duration of the test (from the beginning to the test end) is compared to a nominal duration. The result is stored in the history and an alarm is raised if the battery test failed (test duration is too short).

Vbatt

DVT

test 1 and 2 start

test1 end

test2 end

time

Conditions to enter the battery test mode are : Periodically (can be inhibited) Manually triggered from the communication protocol or the keyboard. Conditions to exit from the battery test mode are : Battery voltage dropped of the pre-defined value (test performed to the end). In this case, the battery test duration is kept in the history. Test is manually stopped (local keyboard or communication protocol). Mains failure occured during the test : test is aborted. Current flowing in the load is is too low to continue the battery test. The test is aborted. Battery is disconnected from the DC bus (fuse blown, LVD open) : The test is aborted. Regulation gets out of limits (2V..8V) : test is aborted.

6.2

Security

When a periodical battery test must be launched, some conditions are checked. If conditions are not met, the test is post-poned by 24 hours. The conditions are : Load current is high enough to start a battery test. Battery is connected (fuse is OK, LVD is closed). No mains failure. Sensors are not faulty. Battery charging current is not too high (below an user-defined level).
- 10 -

6.3

History management

The history is stored in the non-volatile memory. Recorded information is : Duration of last test. Duration of previous test. Duration of longest test. Number of tests completed to the end. Number of tests delayed. Number of tests aborted. All this data can be retrieved from the communication protocol. The history test can be flushed.

- 11 -

RECTIFIER MANAGEMENT

The ACM1D provides a plug and play functionnality for the rectifiers detection. Rectifiers are sensed from the Rect1 to Rect5 inputs (and Rect6 to Rect10 if configured as rectifier inputs). The ACM1D dynamically stores the maximum of rectifiers detected in the non-volatile memory. Therefore : If a new rectifier is inserted in the system (in a free slot), it will be automatically taken into account in the stored configuration. If one ore more rectifiers are removed from the system, the ACM1D will compare this configuration to the maximum configuration and raise the 1 rectifier failed and more than 1 rectifier failed alarms. The user has the ability to freeze this new configuration so that the actual rectifiers configuration is stored as the maximum configuration (thus clearing the rectifiers failed alarms). The rectifiers configuration is persistent after a power-down of the ACM1D.

ALARMS AND STATUS MANAGEMENT

The ACM1D internally manages 30 alarms and 2 statuses. The alarms and statuses can be reported : On the local display and the communication protocol. To the digital ouputs (except the Mains Fail output which is tied by hardware to the Mains Fail input). To the front panel red LED. The alarms reported on each output can be individually filtered out to allow a very flexible alarm signalling. The following filters are available : Filter for display Filter for ALM Urgent output Filter for ALM Non Urgent output Filter for Red LED output Filter for Spare Output 1 Filter for Spare Output 2 Filter for Spare Output 3 Filter for RemoteOff output

8.1

Alarms
1 rectifier failed More than 1 rectifier failed These 2 alarms are raised when some rectifiers are missing (compared to the maximum configuration detected by the ACM1D). Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 These alarms are raised when the input is detected as activated (according to the logic defined for each input).

Battery fuse Battery fuse is detected as blown (from FuseBatt input according to the logic of the input). Load fuse Load fuse is detected as blown (from FuseLoad input according to the logic of the input). Battery test failed The last battery test duration was below the threshold. High voltage
- 12 -

The DC bus voltage is over the defined threshold. Battery voltage low Battery voltage is below the battery disconnection threshold (LVD batt). Load cutoff voltage The DC bus voltage is below the non-essential load disconnection threshold. Battery voltage critical Battery voltage is below a programmable level. Temperature > temperature threshold 1 Temperature is over a programmable level. Temperature > temperature threshold 2 Temperature is over a programmabel level. Regulation error The regulation process does not control the output voltage. Mains fail Mains fail input is activated. High rate charge error A high rate charge has been stopped due to a time-out. Internal error (memory error) Internal non-volatile memory has been corrupted. Battery on discharge Battery current is over a programmable threshold (and the battery test is not in progress). Uload Open Ubatt Open Ibatt Open(+) Ibatt Open(-) Temp Open Iload Open Analog input fault detection.

8.2

Statuses
High rate charge in progress Battery test in progress

- 13 -

FRONT PANEL

9.1 LEDs
3 LEDs are provided on the front panel : Green LED (On) : ACM1D is powered (when flashing, ACM1D is in high-rate charging mode) Yellow LED (Test) : Battery test in progress. Red LED (Alarm) : User configurable

9.2
9.2.1

Display
1st line

The front panel buttons are used to change the displayed information. During start up display is : X.YZ (where X.YZ is the release identifier) and dots reflects start-up progress. Right Button will scroll the following information. Displayed information Battery Temperature Battery Current Battery voltage Load voltage Load Current Rectifier Current Test status (down counter) : Time left until next battery test. Display String TBxx.xC IBxx.xA VB xx.xV VL xx.xV IL xx.xA IR xx.xA No Test or xxxDxxH or xxHxxMxx If periodic battery test is disable. If test starts in more than 24 hours If test starts in less than 24 hours (+) means charging (-) means discharging 9.2.2 Comment

Left Button will scroll the following information. Displayed information Number of rectifiers modules installed. Number of Failed Modules Battery test status Display String Nb PM x Nb FM x No Test or Test OK or TestFail or Test Run No Batt or FT or FT+HR:FT or 9.2.3 Comment

Where x is the number of detected modules Where x is the number of failed modules. Battery has not been tested. Battery tested and result is correct. Battery tested and result is test failed. Battery test in progress.
No battery mode. Or Floating (Temp. Comp). Or Floating (Temp. Comp) + high-rate : presently Floating. Or - 14 -

Battery charging mode

FT+HR:HR or F+HR:F or FT+HR:HR BRel On or BRel Off or BRel FOn


or

Floating (Temp. Comp) + high-rate : presently High-rate. Or 2-rate mode : presently low rate (Floating). 2-rate mode : presently high rate. Battery relay is closed. Or Battery relay is open. Or Battery relay is forced closed. Or Battery relay is forced open.

Battery Relay Status

BRel FOf Auxilliary (Load) Relay Status ARel On

Load relay is closed Or Load relay is open Or Load relay is forced closed Or Load relay is forced open

or
ARel Off

or
ARel FOn
Or

ARel FOf LCD Contrast 9.2.4 2nd line LCD CTRx

LCD contrast setting.

The 2nd line of the local display reports the active alarms raised (selected by the display filter). Note : if several alarms are raised, the message for each alarm is alternately displayed. ACM1D AL 1 RF AL > 1RF AL In 1 AL In 2 AL In 3 AL In 4 AL In 5 AL In 6 AL In 7 AL In 8 AL FusBT AL FusLD AL BTF AL RVH AL BVL AL VDE AL BVC AL Temp1 AL Temp2 AL Vctrl AL Main AL Boost Sys Fail BatDisch TB open IL open IB open If no alarm (that should be displayed according to the display filter). One rectifier failed More than 1 rectifiers failed Input 1 open (*:see note below) Input 2 open (*:see note below) Input 3 open (*:see note below) Input 4 open Input 5 open Input 6 open Input 7 open Input 8 open Battery Fuse failure Load Fuse failure Battery Test Fail Over voltage Battery low voltage (low voltage disconnection) Cut-off voltage (load disconnected) Battery voltage critical. Temperature greater than TC1 threshold Temperature greater than TC2 threshold Vctrl out of range (Regulation error) Mains failure High rate charge alarm (high rate charge too long) Internal error (memory fault). Battery on discharge. Temperature sensor error. Load current sensor error Battery current sensor error
- 15 -

UB open UL open

Battery voltage sensor error DC bus voltage sensor error

*Note : Texts displayed for Input 1, Input 2 and Input 3 are user configurable.

9.3

Commands

It is possible to execute some commands from the 2 front panel push buttons : Start/Stop a battery test. When the line reporting the battery test status is displayed, a long push (6 sec. approx.) on the 2 push buttons will display the following : Toggle Y N By pressing the Fct button it is possible to start or stop a battery test Start/Stop a boost charge When the line reporting the battery charging mode is displayed, a long push (6 sec. approx.) on the 2 push buttons will display the following : Toggle Y N By pressing the Fct button it is possible to start or stop a boost charge (if relevant for the current charging mode). Change the LCD contrast When the line reporting the LCD contrast is displayed, a long push (6 sec . approx.) on the 2 push buttons will display the following : Change Y N By pressing the Fct button it is possible to change the LCD contrast from 0 to 3

- 16 -

10 INSTALLATION RECOMMENDATION
The ACM1D module must be installed by qualified personnel. The module can be installed in a 19 or 23 inch standard rack and is held in by 1 front screw. In order to insure EMC The controller must be slotted in a 19 or 23 inch rack, and placed inside a metal cabinet. Input and output cables must be pressed against the metal surfaces of the cabinet and equipped with ferrite beads on the output of the rack. In order to insure electrical safety The rectifier must be placed inside a cabinet providing an electrical, mechanical and fireproof shelter. It is imperative to provide air admissions and outputs to ensure the module natural convection. User & maintenance personnel access must be limited to front panel and to the insulator of solder face.

Any work on the module must be carried out by qualified maintenance personnel who are fully acquainted with the specific hazards of electricity and able to take the necessary precautions. Non-authorized persons are absolutely prohibited from handling or working on the module in operation. This module generates high leakage current. The sub-assembly which receives the module must be equipped with a warning label, near the mains connection.

The module connections are made through a DIN41612 H96 connector in the rear panel. Check the suitability of the socket connector. This class I (IEC 950) device requires the grounding of the connector row 32. The board may only be connected on a TBTS circuit (in compliance with IEC 950). Internally, no output terminal block is connected to ground. When in operation, the positive polarity may be connected to ground.

- 17 -

11 MAINTENANCE
This device requires no special maintenance, and is not intended to be repaired on site. When shut down, and for several minutes after module disconnection, hazardous voltages may be present within the module. If the troubleshooting procedures fail to fix your problem, contact our customer service. Adding a power module If a power module is added in the rack, the ACM1D automatically recognises it and lists it in the configuration. Changing a failed power module If a failed power module is changed in the rack it must be replaced at the same position in the rack. Otherwise the system will detect a new module + a failed module in the rack and will raise an alarm. Caution : When removing an ACM1D from the sub-rack, the load and battery relays could be unsupplied so they could open (depending on the subracks configuration and relays driving logic). In this case, during an ACM1D exchange operation, it is necessary to by-pass the relays manually.

- 18 -

12 COMMUNICATION 12.1 Pin assignment of RS232 connector (RJ45)and to RS232

1 8

4 : Gnd 5: Receive (of ACM1D) 6 : Transmit (of ACM1D)

Note : If the cable should be connected to a PC with a DSub9 connector, the wiring is as follows :

DSub9-5 DSub9-3 DSub9-2

RJ45-4 RJ45-5 RJ45-6

DSub9-5 DSub9-3 DSub9-2

12.2 Communication Setting


Baud rate: 9600 Baud Data length: 8 bit Parity: no parity Stop bit: 1 Flow control: none Local echo mode on terminal side. Insulation against all others ACM1D potentials: > 100V DC.

12.3 Protocol
Commands are based on 3 characters mnemonics. They allow you to know the status of the system (measurements, alarms, ..). read and set the system configuration. send some commands. The communication is in the Request/Response format with ASCII characters code. Requests delimiter is the Carriage Return (referred to as <CR> in the rest of the document). Backspaces are supported in the request. Response delimiter is the sequence <CR><LF><ACK> Note : <CR> ASCII code is 13. <LF> ASCII code is 10. <ACK> ASCII code is 6. 12.3.1 Read requests Read requests format is : ?<Mnemonic><CR> Or <Mnemonic><CR> Read response has the following format : <Mnemonic>:<value><CR><LF><ACK> Or (if multi-lines response) :
- 19 -

<Mnemonic>: <value-line1><CR><LF> <value-line2><CR><LF> . . . <value-lineN><CR><LF><ACK> 12.3.1.1 Write requests and Commands This part is not described in this manual. Configuration of an ACM1D should be done by using the dedicated PC software Win1d. Configuration requires proper access rights.

12.4 Reading the system status


12.4.1 Alarms : ALM Returns the list of active alarms (bitstring) : Example : Response : ALM Alarm[0..31] : 00000000000000000000000100000000 Displ[0..31] : 00000000000000000000001000000000 Status :0/0/4

1st line gives all the alarms raised. 2nd line gives all the alarms that should be displayed (according to the display filter) 3rd line gives a summarized status x/y/z with x : Number of urgent alarms raised. y : Number of non urgent alarms raised. z : Event counter : increments each time a status has changed.

Bit 0 : 1 rectifier failed 1 : More than 1 rectifier failed 2 : Input 1 3 : Input 2 4 : Battery fuse 5 : Load fuse 6 : Input 3 7 : Battery test failed 8 : High voltage 9 : Battery voltage low (disconnect threshold) 10 : Load cutoff voltage 11 : Battery voltage critical (BVC threshold) 12 : Temperature > temperature threshold 1 13 : Temperature > temperature threshold 2 14 : Regulation error(Vctrl) 15 : Mains fail 16 : High rate charge error 17 : Internal error (memory error) 18 : Input 8 19 : Input 7 20 : Input 6 21 : Input 5 22 : Input 4 23 : Battery on discharge 24 : Uload sensor fault 25 : Ubatt sensor fault 26 : Ibatt sensor fault (charge) 27 : Ibatt sensor fault (discharge) 28: Temp sensor fault 29 : ILoad sensor fault 30 : High rate charge in progress 31 : Battery test in progress
- 20 -

12.4.2 Digital outputs status : DOS Returns the status of the outputs (bitstring). Example : DOS DOS:000000011

0 (leftmost) 1 2 3 4 5 6 7 8 (rightmost)

: REMOTE OFF : Out 2 : ALM U : Alm NU : Alm MF : Out 3 : Out 1 : Battery LVD relay : Load LVD relay

12.4.3 Rectifiers status : RST Gives the list of currently present rectifiers and maximum detected. Example : RST Returned value : RST: Failed : 0 See[0..9] : 1111000000 Max[0..9] : 1111000000 See is the positions of rectifiers presently detected. Max is the positions of all rectifiers detected (maximum configuration) Failed is the number of faulty rectifiers. 12.4.4 Measurements DC bus Voltage : ULD ULD ULD:54.26V

Example :

Battery voltage : UBA UBA UBA:53.76V

Example :

Load current : ILD ILD ILD:20.7A

Example :

Battery current : IBA IBA IBA:-12.4A

Example :

Battery temperature : TBA TBA TBA:20.5C

Example :

12.4.5 Timers : TCV Example : TCV

- 21 -

Response :

TCV: TIT:012D08H20M30S BIT:001D05H12M04S BCT:000D03H30M00S CNT:000D10H25M08S

TIT : time to the next battery test BIT : time to the next transition to high rate mode BCT : time elapsed since the high rate mode was started CNT : internal timer. 12.4.6 Regulation mode : MRB Returns the current charging mode applied : MRB:0 [No Batt] Or MRB:1 [FT] Or MRB:2 [FT+HR:FT] Or MRB:2 [FT+HR:HR] Or MRB:3 [F+HR:F] Or MRB:3 [F+HR:HR] : : : No battery mode Floating mode with temperature compensation. Floating (with temp. comp) + high rate : Present mode=floating Floating (with temp. comp) + high rate : Present mode=high rate 2-rate : Present mode=low rate 2-rate : Present mode=high rate

12.4.7 Battery test history : HBT Example (response) : HBT: PERFORM:2 DELAYED:1 ABORT :1 REF0:9:1:24 MAX0:9:1:24 PRE0:8:48:35 LAS0:9:1:24

PERFORM : DELAYED : ABORT : MAX : PRE : LAS :

Number of tests performed. Number of tests delayed. Number of tests aborted. Duration of longest battery test (Day:Hour:Min:Sec). Duration of previous battery test (Day:Hour:Min:Sec). Duration of last battery test (Day:Hour:Min:Sec).

12.4.8 Battery test in progress : TRN Returns 1 if a battey test is in progress. Example (response) : TRN:1 Or TRN:0 Or TRN:-1 (test is running) (no test in progress) (not applicable : no battery mode).

- 22 -

12.5 Configuration commands


Configuration commands are not described in this document. Use the Win1d Windows based software to change the configuration. Configuration parameters are : Number of battery cells. Shunt value. Shunt configuration (on the load or on rectifiers output) Input configuration for inputs Rect6/Spare8 to Rect10/Spare4 (rectifier input or spare input). Logic of digital inputs. Logic of digital outputs. Regulation mode. Current limits in float charge and high rate charge. Low rate voltage. Highrate voltage. Voltage level in No battery mode. Temperature compensation characteristics (slope, ..). Temperature bounds for compensation. High rate charge periodicity. Current to switch from high rate charge to float charge. High rate charge time-out. Voltage level to open the non essential load contactor. Voltage level to raise a Battery voltage critical alarm. Voltage level to open the battery LVD. Overvoltage alarm threshold. Hysteresis to close the battery and load relays. Logic to drive the battery and load relays. Alarms filters for the digital outputs and the display. Temperature thresholds to raise temperature alarm (2 thresholds). Battery test current. Battery test periodicity.

- 23 -

13 APPENDIX 13.1 ACM1D rear connector.


A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ALM MainsFail+ Output 3+ Output 1 + ALM Urgent+ ALM Non Urgent+ B GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND GND Spare Input 3 Rect8/Spare Input 6 Rect2 Rect5 Main Fail Input GND Spare Input 2 DCGND DC + (0V) GND GND C ALM MainsFailOutput 3 Output 1 ALM UrgentALM Non Urgent-

SH BatSH Load U Load U Bat TempBattery Relay

SH Bat+ SH Load+ U Load+ U Bat+ Temp+ Load Relay (Aux.)

Battery Fuse input Rect10/Spare Input 4 Rect7/Spare Input 7 Rect3 Rect1 Remote Off Output Spare Input 1 DCDC+ (0V) GND

Load Fuse Input Rect9/Spare Input 5 Rect6/Spare Input 8 Rect4 Vadjust Output 2 DCDC+ (0V) GND

GND is the ACM1D internal reference which is tied to the DC-.

- 24 -

13.2 SAFT POWER SYSTEMS SUBSIDIARIES


ARGENTINA / ARGENTINE GERMANY / ALLEMAGNE
SAFT ARGENTINA S.A Jose Leon Suarez 2244 PO Box 1440 1440 BUENOS AIRES Tel : + 54 11 4 686-1994 Fax: + 54 11 4 686 -0270 AEG SVS PSG GmbH Emil Siepmann Strasse 32 D59581 WAERSTEIN-BELECKE GERMANY Tel : + 49 2902 7630 Fax : + 49 2902 763 680

AUSTRALIA / AUSTRALIE
SAFT Australia Pty Ltd Unit 7, 20 Powers Road PO Box 883 SEVEN HILLS NSW 2147 Tel : + 61 2 9674 0700 Fax : + 61 2 9620 9990

HONG KONG / HONG KONG


SAFT Hong-Kong Ltd Unit 1106-9 Westin Centre 26 Hung to Road KWUN TONG KOWLOON HONG-KONG Tel : + 852 2796 9932 Fax : + 852 2798 0619

BRAZIL / BRESIL
SAFT Ltda AV. Forte do Leme, 215 Parque Industrial So Loureno 08340-010 SAO PAULO - SP Tel : + 55 11 6100-6301 Fax : + 55 11 6100-6363

ITALY / ITALIE
SAFT S.p.A Viale Cembrano, 11 Casella Postale 1283 16148 GENOVA Tel : + 39 0 10 37 47 911 Fax : + 39 0 10 38 62 73

CANADA / CANADA
SAFT Division 125 NANTUCKET Blvd SCARBOROUGH, ONTARIO M1P 2N8 Tel : + 1 416 757 51 51 Fax : + 1 416 752 45 14

KOREA / COREE
SAFT Korea Co Ltd #195-42, Anyang 7-Dong Manan-Ku, Anyang City KYUNGGI-DO Tel : + 82 343 41 1134 Fax : + 82 343 41 1139

FRANCE / FRANCE
SAFT POWER SYSTEMS Customer Service 10, rue Jean Perrin BP 359 37 173 CHAMBRAY LES TOURS Tel : +33 (0)2 47 80 88 96 Fax : +33 (0)2 47 80 88 38 e-mail : services.psf@saft.alcatel.fr

- 25 -

MALAYSIA / MALAISIE
SAFT Power Systems Sdn Bhd N37, Jalan 10/91 Taman Shamelin Perkasa Batu 3 1/2 Jalan Cheras 56100 KUALA LUMPUR Tel : + 60 3 985 29 96 Fax : + 60 3 984 49 95

SPAIN / ESPAGNE
SAFT Iberica SL Vitorialanda, 4-6 01010 VITORIA-GASTEIZ Tel : + 34 945 21 41 10 Fax : + 34 945 21 41 11

MEXICO / MEXIQUE
SAFT S.A. de CV Camos Eliseos N 385 Torre A Piso 11 Col. Polanco MEXICO D.F CP 11560 Tel : + 525 280 0619 Fax : + 525 280 3559

SWEDEN / SUEDE
SAFT AB PO BOX 4121 SE 171-04 SOLNA SWEDEN Tel : + 46 8 598 49750 Fax : + 46 8 598 49755

UNITED KINGDOM / ROYAUME UNI MIDDLE-EAST / MOYEN-ORIENT


SAFT M.E. Ltd PO Box 54307 3723 LIMASSOL CYPRUS Tel : + 357 53 40 637 Fax : + 357 57 48 492 SAFT Ltd Peregrine Road, HAINAULT, ILFORD Essex IG6 3XJ Tel : + 44 181 500 1211 Fax : + 44 181 500 9365

USA / ETATS-UNIS NETHERLANDS / PAYS BAS


SAFT B.V PO Box 82 1160 AB ZWANENBURG Tel : + 31 (0) 20 407 78 00 Fax : + 31 (0) 20 407 78 01 ALCAD INDUSTRIAL AND RAILWAY BATTERIES 73, Defco Park Road Wharton Brook Industrial Park NORTH HAVEN, CONNECTICUT 06473 Tel : + 1 203 234 83 33 Fax : + 1 203 234 82 55

SINGAPORE / SINGAPOUR
SAFT Power Systems Pte Ltd 54 Genting Lane Hiang Kie Complex II #03-01/03 - SINGAPORE 349562 Tel : + 65 846 5736 Fax : + 65 743 1037

- 26 -