Genesis Range

Numerical
Overcurrent & Earthfault MJT 314
Protection

Cutout Details Description Features


The MJT 314 over current relay combines the power and Protection
flexibility of microprocessor technology with decades of • IDMTL / DTL phase fault overcurrent stage ( 50 / 51 )
experience in the field of protection. A wide range of protection • IDMTL / DTL earth fault overcurrent stage ( 50N /51N)
elements and characteristics are supplemented by advance • Dual DC transient free highsets for phase fault & earth fault
features such as metering, fault recorder and communication. • Numerical, true RMS measurement
• Six characteristics
MJT 314 offers inverse time and definite time over current
MODULAR CASES: SIZES 6 protection for phase fault and earth fault with communication. Control
SIZE 6 CASE The relay has the following output contacts
A B C Design
• Common Trip and Alarm 2 N/O
155 151 130.5 The MJT Protection unit consists of the following modules within
its dimensions. • Protection Healthy 1 N/C
• Input Module • Starter operated 1 C/O
Note:
• Power Supply and Output Relay module • Phase fault operated 1 N/O
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line • Measuring Module & communication interface • Earth fault operated 1 N/O
3. Maximum depth of equipment inside panel : 200mm • Front Fascia • P/F highset1 operated 1 N/O
• Group Change module • E/F highset1 operated 1 N/O
Ordering Information • P/F highset2 operated 1 N/O
The current inputs can be configured for operation with either
• Auxiliary Supply range • E/F highset2 operated 1 N/O
1A or 5A ratings. Appropriate connections are required on the
• Communication protocol – IEC 60870 – 5 – 103 (or)
relay terminal blocks.
MODBUS RTU
The four modules viz. Input, Power supply Measuring and group
Qualification change modules are plugged into the Front fascia which houses
ISO 9001-2000 switches, LEDs and LCD display for the human machine interface.
All PCB s are well protected from one another and from external
environment with best shielding for better electromagnetic
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment,
compatibility and housed in the enclosed chassis, which is with-
which may differ slightly from that described and illustrated in this publication.
drawable from the outer case.
The draw-out case is provided with the required CT shorting
HOSUR WORKS BANGALORE WORKS contacts.
#98, Sipcot Industrial Complex, #17/3 Arakere,
Hosur 635 126, India. Bannerghatta Road,
Tel: +91 4344 401600/01/02 Bangalore-560 076, India. Applications
FACT/MJT 314/07-06/Rev 0
Fax: +91 4344 276397 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642 • Distribution feeders
Email: blrworks@easunreyrolle.net • Transmission lines
SWITCHGEAR WORKS AUTOMATION DIVISION EXPORTS DIVISION • AC machines
Ernavur, “Ashirwad”, #25, 29th Main, #17/3 Arakere, • Capacitor banks
Chennai-600 057, India. 4th B Cross, BTM Layout 2nd Stage, Bannerghatta Road,
Tel: +91 44 25733715/358 Bangalore-560 076, India. Bangalore-560 076, India. • Transformers
Fax: +91 44 25733468 Tel: +91 80 26685496/51311405 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: switchgear@easunreyrolle.net Fax: +91 80 26685446 Email: exports@easunreyrolle.net
Email: smabp@easunreyrolle.net

Sales Offices
Mumbai Delhi Kolkata Numerical Overcurrent & Earthfault Protection - MJT314
Tel: +91 22 22022270/22855415 Tel: +91 11 25747321/25747322 Tel: +91 33 22848320
Fax: +91 22 22825703 Fax: +91 11 25747320 Fax: +91 33 22848326
Email: mumbai@easunreyrolle.net Email: delhi@easunreyrolle.net Email: kolkata@easunreyrolle.net
Bangalore Chennai Secunderabad
Tel: +91 80 26685496/51311405 Tel: +91 44 24346425/24347608 Telefax: +91 40 27817847
Fax: +91 22 26685446 Fax: +91 44 24346435 Email: hyderabad@easunreyrolle.net Corporate Office
Email: blroffice@easunreyrolle.net Email: chennai@easunreyrolle.net Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Bhopal Hosur 635 126 India. Tel: +91 4344 401600/01/02
Telefax: +91 755 2684221 Fax: +91 4344 276397
Email: bhopal@easunreyrolle.net www.easunreyrolle.com
Metering Wiring Diagram Technical Information • P/F highset1 operated 1 N/O
• True RMS measurements • E/F highset1 operated 1 N/O
• Currents-Ir,Iy,Ib,Ie • P/F highset2 operated 1 N/O
CT Input Rating 1A/5A
• E/F highset2 operated 1 N/O
Frequency 50Hz
User Interface Contact Rating
• Readable human machine interface with Backlit LCD display Auxiliary supply Carry continuously 5A AC rms or DC
• LED indications Nominal VAUX Operating Range VAUX Make & Carry 20A for 0.2sec
• Push buttons for viewing/editing the settings and resetting 30, 48, 110 V DC 24V to 135V DC Break Resistive 75W DC
110, 220 V DC 43V to 280V DC Inductive 50W DC
Communication 110 V AC @L/R≤40msec
• Data communication using IEC 60870-5-103 or MODBUS with a maximum of 300V DC
Digital (status) input
RTU Protocol Indication
Nominal Operating Range
• RS485 communication electrical terminals at rear Green LED Protection healthy
30 V DC 18-36 V DC
Orange LED Starter
For higher input voltage up to 250 V DC, external dropping
Other Features Red LED Trip
resistors will be supplied.
• Digital input for group changeover application Red LED (3mm) Submenu
• Two group settings Protection Settings 16x2 Alphanumeric LCD display for settings, readings and fault
• Storage of two fault records Phase Fault 0.05xIn to 2.5xIn ∆ 0.01 In data
• Internal real time clock Earth Fault 0.05xIn to 2.5xIn ∆ 0.01 In Burden
Highset1 Phase Fault 0.5xIn to 30xIn ∆ 0.5 In, off AC Current Input
• Suitable for flashing faults
Highset1 Earth Fault 0.5xIn to 30xIn ∆ 0.5 In, off 5 A Rating ≤0.4 VA
• Both 1A & 5A ratings in same relay
Highset2 Phase Fault 0.5xIn to 30xIn ∆ 0.5 In, off 1 A Rating ≤0.05 VA
• Wide range of current settings Highset2 Earth Fault 0.5xIn to 30xIn ∆ 0.5 In, off
Typical Wiring Diagram for MJT314 Auxiliary input
• Suitable for wide range of auxiliary Supply P/F Time Multiplier 0.025 to 1.6 ∆ 0.001 Quiescent (typical) 5 W (DC)
• Non volatile memory for trip indication E/F Time Multiplier 0.025 to 1.6 ∆ 0.001 12VA (AC)
• Low AC and DC burden P/F DTL 0 Secs to 20 Secs ∆ 0.01 Secs
• Self-monitoring facility E/F DTL 0 Secs to 20 Secs ∆ 0.01 Secs Environmental
P/F Highset1 DTL 0 Secs to 20 Secs ∆ 0.01 Secs Temperature IEC 60068-2-1/2
E/F Highset1 DTL 0 Secs to 20 Secs ∆ 0.01 Secs Operating range -10° C to +55°C
Highset2 Shaped Instantaneous Storage range -25° C to +70°C
Reset Time 0 to 60 Secs ∆ 1 sec Humidity IEC 60068-2-3
56 days at 40°C and 93%RH
Inverse Characteristics Transient Overvoltage IEC 60255-5
Operating time can be calculated as follows: 5KV, 1.2/50µs, 0.5J between all terminals and earth or between
k any two terminals without damage or flashover
t = ————— x Tm
I α Insulation IEC 60255-5
[ I [-1
S
2.0 KVrms for 1 min between all terminals and earth
where 2.0 KVrms for 1 min between independent circuits
1.0 KVrms for 1 min across normally open contacts
I=fault current
High frequency Disturbance IEC 60255-22-1 Class III
Is=current setting
2.5 KV Common (Longitudinal) mode
Tm=time multiplier
1.0 KV Series (Transverse) mode
SI3 - k = 0.14, α= 0.02 Electrostatic Discharge IEC 60255-22 -2 Class III
SI1 - k = 0.0613, α = 0.02 6 KV Contact Discharge
VI - k = 13.5, α= 1.0 8 KV Air Discharge
EI - k = 80.0, α= 2.0 Radio Frequency Interference IEC 60255-22-3 Class III
LTI - k = 120.0, α = 1.0 20 MHz to 1000 MHz, 10V/m
Fast Transient
Output contacts
2 KV, 5/50 ns, 2.5 kHz repetitive IEC 60255-22-4 Class III
The relay has the following output contacts
Vibration (Sinusoidal) IEC 60255-21-1 Class I
• Common Trip and Alarm 2 N/O
Shock and Bump IEC 60255-21-2 Class I
• Protection Healthy 1 N/C
• Starter operated 1 C/O Mechanical Classification
• Phase fault operated 1 N/O Durability 106 operations
• Earth fault operated 1 N/O
Metering Wiring Diagram Technical Information • P/F highset1 operated 1 N/O
• True RMS measurements • E/F highset1 operated 1 N/O
• Currents-Ir,Iy,Ib,Ie • P/F highset2 operated 1 N/O
CT Input Rating 1A/5A
• E/F highset2 operated 1 N/O
Frequency 50Hz
User Interface Contact Rating
• Readable human machine interface with Backlit LCD display Auxiliary supply Carry continuously 5A AC rms or DC
• LED indications Nominal VAUX Operating Range VAUX Make & Carry 20A for 0.2sec
• Push buttons for viewing/editing the settings and resetting 30, 48, 110 V DC 24V to 135V DC Break Resistive 75W DC
110, 220 V DC 43V to 280V DC Inductive 50W DC
Communication 110 V AC @L/R≤40msec
• Data communication using IEC 60870-5-103 or MODBUS with a maximum of 300V DC
Digital (status) input
RTU Protocol Indication
Nominal Operating Range
• RS485 communication electrical terminals at rear Green LED Protection healthy
30 V DC 18-36 V DC
Orange LED Starter
For higher input voltage up to 250 V DC, external dropping
Other Features Red LED Trip
resistors will be supplied.
• Digital input for group changeover application Red LED (3mm) Submenu
• Two group settings Protection Settings 16x2 Alphanumeric LCD display for settings, readings and fault
• Storage of two fault records Phase Fault 0.05xIn to 2.5xIn ∆ 0.01 In data
• Internal real time clock Earth Fault 0.05xIn to 2.5xIn ∆ 0.01 In Burden
Highset1 Phase Fault 0.5xIn to 30xIn ∆ 0.5 In, off AC Current Input
• Suitable for flashing faults
Highset1 Earth Fault 0.5xIn to 30xIn ∆ 0.5 In, off 5 A Rating ≤0.4 VA
• Both 1A & 5A ratings in same relay
Highset2 Phase Fault 0.5xIn to 30xIn ∆ 0.5 In, off 1 A Rating ≤0.05 VA
• Wide range of current settings Highset2 Earth Fault 0.5xIn to 30xIn ∆ 0.5 In, off
Typical Wiring Diagram for MJT314 Auxiliary input
• Suitable for wide range of auxiliary Supply P/F Time Multiplier 0.025 to 1.6 ∆ 0.001 Quiescent (typical) 5 W (DC)
• Non volatile memory for trip indication E/F Time Multiplier 0.025 to 1.6 ∆ 0.001 12VA (AC)
• Low AC and DC burden P/F DTL 0 Secs to 20 Secs ∆ 0.01 Secs
• Self-monitoring facility E/F DTL 0 Secs to 20 Secs ∆ 0.01 Secs Environmental
P/F Highset1 DTL 0 Secs to 20 Secs ∆ 0.01 Secs Temperature IEC 60068-2-1/2
E/F Highset1 DTL 0 Secs to 20 Secs ∆ 0.01 Secs Operating range -10° C to +55°C
Highset2 Shaped Instantaneous Storage range -25° C to +70°C
Reset Time 0 to 60 Secs ∆ 1 sec Humidity IEC 60068-2-3
56 days at 40°C and 93%RH
Inverse Characteristics Transient Overvoltage IEC 60255-5
Operating time can be calculated as follows: 5KV, 1.2/50µs, 0.5J between all terminals and earth or between
k any two terminals without damage or flashover
t = ————— x Tm
I α Insulation IEC 60255-5
[ I [-1
S
2.0 KVrms for 1 min between all terminals and earth
where 2.0 KVrms for 1 min between independent circuits
1.0 KVrms for 1 min across normally open contacts
I=fault current
High frequency Disturbance IEC 60255-22-1 Class III
Is=current setting
2.5 KV Common (Longitudinal) mode
Tm=time multiplier
1.0 KV Series (Transverse) mode
SI3 - k = 0.14, α= 0.02 Electrostatic Discharge IEC 60255-22 -2 Class III
SI1 - k = 0.0613, α = 0.02 6 KV Contact Discharge
VI - k = 13.5, α= 1.0 8 KV Air Discharge
EI - k = 80.0, α= 2.0 Radio Frequency Interference IEC 60255-22-3 Class III
LTI - k = 120.0, α = 1.0 20 MHz to 1000 MHz, 10V/m
Fast Transient
Output contacts
2 KV, 5/50 ns, 2.5 kHz repetitive IEC 60255-22-4 Class III
The relay has the following output contacts
Vibration (Sinusoidal) IEC 60255-21-1 Class I
• Common Trip and Alarm 2 N/O
Shock and Bump IEC 60255-21-2 Class I
• Protection Healthy 1 N/C
• Starter operated 1 C/O Mechanical Classification
• Phase fault operated 1 N/O Durability 106 operations
• Earth fault operated 1 N/O
Genesis Range
Numerical
Overcurrent & Earthfault MJT 314
Protection

Cutout Details Description Features


The MJT 314 over current relay combines the power and Protection
flexibility of microprocessor technology with decades of • IDMTL / DTL phase fault overcurrent stage ( 50 / 51 )
experience in the field of protection. A wide range of protection • IDMTL / DTL earth fault overcurrent stage ( 50N /51N)
elements and characteristics are supplemented by advance • Dual DC transient free highsets for phase fault & earth fault
features such as metering, fault recorder and communication. • Numerical, true RMS measurement
• Six characteristics
MJT 314 offers inverse time and definite time over current
MODULAR CASES: SIZES 6 protection for phase fault and earth fault with communication. Control
SIZE 6 CASE The relay has the following output contacts
A B C Design
• Common Trip and Alarm 2 N/O
155 151 130.5 The MJT Protection unit consists of the following modules within
its dimensions. • Protection Healthy 1 N/C
• Input Module • Starter operated 1 C/O
Note:
• Power Supply and Output Relay module • Phase fault operated 1 N/O
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line • Measuring Module & communication interface • Earth fault operated 1 N/O
3. Maximum depth of equipment inside panel : 200mm • Front Fascia • P/F highset1 operated 1 N/O
• Group Change module • E/F highset1 operated 1 N/O
Ordering Information • P/F highset2 operated 1 N/O
The current inputs can be configured for operation with either
• Auxiliary Supply range • E/F highset2 operated 1 N/O
1A or 5A ratings. Appropriate connections are required on the
• Communication protocol – IEC 60870 – 5 – 103 (or)
relay terminal blocks.
MODBUS RTU
The four modules viz. Input, Power supply Measuring and group
Qualification change modules are plugged into the Front fascia which houses
ISO 9001-2000 switches, LEDs and LCD display for the human machine interface.
All PCB s are well protected from one another and from external
environment with best shielding for better electromagnetic
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment,
compatibility and housed in the enclosed chassis, which is with-
which may differ slightly from that described and illustrated in this publication.
drawable from the outer case.
The draw-out case is provided with the required CT shorting
HOSUR WORKS BANGALORE WORKS contacts.
#98, Sipcot Industrial Complex, #17/3 Arakere,
Hosur 635 126, India. Bannerghatta Road,
Tel: +91 4344 401600/01/02 Bangalore-560 076, India. Applications
FACT/MJT 314/07-06/Rev 0
Fax: +91 4344 276397 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642 • Distribution feeders
Email: blrworks@easunreyrolle.net • Transmission lines
SWITCHGEAR WORKS AUTOMATION DIVISION EXPORTS DIVISION • AC machines
Ernavur, “Ashirwad”, #25, 29th Main, #17/3 Arakere, • Capacitor banks
Chennai-600 057, India. 4th B Cross, BTM Layout 2nd Stage, Bannerghatta Road,
Tel: +91 44 25733715/358 Bangalore-560 076, India. Bangalore-560 076, India. • Transformers
Fax: +91 44 25733468 Tel: +91 80 26685496/51311405 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: switchgear@easunreyrolle.net Fax: +91 80 26685446 Email: exports@easunreyrolle.net
Email: smabp@easunreyrolle.net

Sales Offices
Mumbai Delhi Kolkata Numerical Overcurrent & Earthfault Protection - MJT314
Tel: +91 22 22022270/22855415 Tel: +91 11 25747321/25747322 Tel: +91 33 22848320
Fax: +91 22 22825703 Fax: +91 11 25747320 Fax: +91 33 22848326
Email: mumbai@easunreyrolle.net Email: delhi@easunreyrolle.net Email: kolkata@easunreyrolle.net
Bangalore Chennai Secunderabad
Tel: +91 80 26685496/51311405 Tel: +91 44 24346425/24347608 Telefax: +91 40 27817847
Fax: +91 22 26685446 Fax: +91 44 24346435 Email: hyderabad@easunreyrolle.net Corporate Office
Email: blroffice@easunreyrolle.net Email: chennai@easunreyrolle.net Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Bhopal Hosur 635 126 India. Tel: +91 4344 401600/01/02
Telefax: +91 755 2684221 Fax: +91 4344 276397
Email: bhopal@easunreyrolle.net www.easunreyrolle.com