You are on page 1of 47

TECHNICAL DATA

& SERVICE MANUAL


®

INDOOR UNIT: AW52AL


AW64AL

SPLIT SYSTEM AIR CONDITIONER


Model No. Product Code No.
AW52AL 387030095
AW64AL 387030096

0.8180.463.0 07/05
IMPORTANT! • Ground the unit following local electrical codes.
Please read before installation • The Yellow/Green wire cannot be used for any connection
different from the ground connection.
This air conditioning system meets strict safety and operating • Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard.
standards.
• Do not allow wiring to touch the refrigerant tubing, compressor,
For the installer or service person, it is important to install or
or any moving parts of the fan.
service the system so that it operates safely and efficiently.
• Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes. When transporting
• Pay close attention to all warning and caution notices given in Be careful when picking up and moving the indoor and outdoor
this manual. units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
•The unit must be supplied with a dedicated electrical line.
the air conditioner can cut your fingers.

WARNING
This symbol refers to a hazard or unsafe practice which can result When installing...
in severe personal injury or death. ... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

CAUTION ... In a room


Properly insulate any tubing run inside a room to prevent
This symbol refers to a hazard or unsafe practice which can result
"sweating", which can cause dripping and water damage to walls
in personal injury or product or property damage. and floors.

... In moist or uneven locations


Use a raised concrete base to provide a solid level foundation for
If necessary, get help the outdoor unit.
These instructions are all you need for most installation sites and This prevents damage and abnormal vibrations.
maintenance conditions.
If you require help for a special problem, contact our sale/service ... In area with strong winds
outlet or your certified dealer for additional instructions. Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
In case of improper installation
The manufacturer shall in no way be responsible for improper ... In a snowy area (for heat pump-type systems)
installation or maintenance service, including failure to follow the Install the outdoor unit on a raised platform that is higher than
instructions in this document. drifting snow. Provide snow vents.

SPECIAL PRECAUTIONS
When connecting refrigerant tubing
• During installation, connect before the refrigerant system and • Keep all tubing runs as short as possible.
then the wiring one; proceed in the reverse orden when removing • Use the flare method for connecting tubing.
the units. • Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
WARNING When wiring • Check carefully for leaks before starting the test run.

ELECTRICAL SHOCK CAN CAUSE SEVERE NOTE:


PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, Depending on the system type, liquid and gas lines may be either
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT narrow or wide. Therefore, to avoid confusion, the refrigerant
TO WIRE THIS SYSTEM. tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked, to ensure the grounding. When servicing
• Highly dangerous electrical voltages are used in this system. • Turn the power OFF at the main power board before opening
Carefully refer to the wiring diagram and these instructions when the unit to check or repair electrical parts and wiring.
wiring. • Keep your fingers and clothing away from any moving parts.
Improper connections and inadequate grounding can cause • Clean up the site after the work, remembering to check that no
accidental injury and death. metal scraps or bits of wiring have been left inside the unit being
serviced.
• Ventilate the room during the installation or testng the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

2
Table of Contents
Page

1. SPECIFICATIONS 4
1-1 Unit specifications 4
1-2 Major Component specifications 6
1-3 Other Component specifications 8

2. DIMENSIONAL DATA 9

3. SOUND LEVEL CHARACTERISTICS 10


3-1 Sound pressure levels 10

4. ELECTRICAL DATA 11
4-1 Electric Wiring Diagrams 11

5. CONTROL SYSTEM 12
5-1 Electronic control 12
5-2 Legend 13
5-3 PCB 14
5-4 General Functions 15
5-5 Cooling Mode 18
5-6 Heating Mode 21
5-7 Automatic Cooling or Heating 26
5-8 Dry Mode 28
5-9 Protections 29
5-10 Timer 34
5-11 Forced Operation 35
5-12 Sleep Mode 36
5-13 Air Filter 38
5-14 Self Test 39
5-15 Unit indicators and controls 43
5-16 System Diagnostics 44

6. TROUBLESHOOTING 45

3
1. SPECIFICATIONS
1-1 Unit Specifications
AW52AL

Power source 220 - 240V ~ 50Hz

Voltage rating 230V - 50 Hz

Performance Cooling Heating


Capacity See catalogue with the requested matching
Air circulation (High) m³/h 930

Features
Controls/Temperature controls Microprocessor/ I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours
Fan speed 3 and Auto
Airflow direction Horizontal Manual
Vertical Auto
Air Filter Washable, Anti-Mold
Power noise level High/Med./Low dB-A 56 / 53 / 50
Refrigerant tubing connections Flare type
Refrigerant Narrow tube mm(in.) 6,35 (1/4)
tube diameter Wide tube mm(in.) 12,7 (1/2)
Refrigerant R410A

Dimensions & Weight


Unit dimensions Height mm 295
Width mm 1060
Depth mm 210
Package dimensions Height mm 360
Width mm 1125
Depth mm 280
Weight Net kg 14
Shipping kg 17
Shipping volume m3 0,11
DATA SUBJECT TO CHANGE WITHOUT NOTICE

4
AW64AL

Power source 220 - 240V ~ 50Hz

Voltage rating 230V - 50 Hz

Performance Cooling Heating


Capacity See catalogue with the requested matching
Air circulation (High) m³/h 990

Features
Controls/Temperature controls Microprocessor/ I.C. thermostat
Control unit Wireless remote control unit
Timer ON/OFF 24 hours
Fan speed 3 and Auto
Airflow direction Horizontal Manual
Vertical Auto
Air Filter Washable, Anti-Mold
Power noise level High/Med./Low dB-A 58 / 55 / 53
Refrigerant tubing connections Flare type
Refrigerant Narrow tube mm(in.) 9,52 (3/8)
tube diameter Wide tube mm(in.) 15,88 (5/8)
Refrigerant R410A

Dimensions & Weight


Unit dimensions Height mm 295
Width mm 1060
Depth mm 210
Package dimensions Height mm 360
Width mm 1125
Depth mm 280
Weight Net kg 15
Shipping kg 18
Shipping volume m3 0,11
DATA SUBJECT TO CHANGE WITHOUT NOTICE

5
1-2 Major Component Specifications
AW52AL

Controller PCB
Part No. WNG
Controls Microprocessor
Control circuit fuse 250 V - 3,15 A

Remote Control Unit RC-7 (RC)

Fan & Fan Motor


Type Cross - flow
Q'ty ……. Dia. and lenght mm 1…. Ø 92
Fan motor model…Q'ty RPS18M-2…1
No. Of poles…rpm (230 V, Hi) 4…1200
Nominal output W 18
Coil resistance (Ambient temp. 20 °C ) Ω ---
---
---
---
---
Safety devices Type thermal protector
Operating temp. Open °C 110
Close automatic reclosing
Run capacitor µF 2
VAC 450

Flap Motor
Type Stepping motor
Model 24BYJ48
Rating DC 12 V
Coil resistance (Ambient temp. 20 °C ) Ω Each terminals (1-2, 1-3, 1-4, 1-5) 200 ± 7%

Heat Exch. Coil


Coil Aluminium plate fin / Copper tube
Rows 2
Fin pitch mm 1,2
face area 0,306
DATA SUBJECT TO CHANGE WITHOUT NOTICE

6
AW64AL

Controller PCB
Part No. WNG
Controls Microprocessor
Control circuit fuse 250 V - 3,15 A

Remote Control Unit RC-7 (RC)

Fan & Fan Motor


Type Cross - flow
Q'ty ……. Dia. and lenght mm 1…. Ø 92
Fan motor model…Q'ty RPS30G-2…1
No. Of poles…rpm (230 V, Hi) 4…1300
Nominal output W 26
Coil resistance (Ambient temp. 20 °C ) Ω ---
---
---
---
---
Safety devices Type thermal protector
Operating temp. Open °C 110
Close automatic reclosing
Run capacitor µF 2
VAC 450

Flap Motor
Type Stepping motor
Model 24BYJ48
Rating DC 12 V
Coil resistance (Ambient temp. 20 °C ) Ω Each terminals (1-2, 1-3, 1-4, 1-5) 200 ± 7%

Heat Exch. Coil


Coil Aluminium plate fin / Copper tube
Rows 2 + additional part
Fin pitch mm 1,2
face area 0,306
DATA SUBJECT TO CHANGE WITHOUT NOTICE

7
1-3 Other Component Specifications AW52AL
AW64AL

Thermistor ( Coil sensor ) NTC-THERMISTOR


Resistance ΚΩ 10 at 25 °C

Thermistor ( Room sensor ) NTC-THERMISTOR


Resistance ΚΩ 10 at 25 °C

8
2. DIMENSIONAL DATA

9
3. SOUND LEVEL CHARACTERISTICS

AW52AL AW64AL

10
4. ELECTRICAL DATA
4-1 Electric Wiring Diagrams

11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Via Varese, 90 - 21013 Gallarate - Va - Italy