Features
Unit model
Supply air volume :

2.69
2240
0.6222
Interior
0

Type of mounting :
Altitude :

m/h
m/s

Casing :

Single skin 10 mm

Insulation :

Foam 10 mm

Unit net price :

uros

Ex-works

FOB (goods not unloaded)

The drawing shows the service side.


Length :
Width :

General options :

740
1150

mm
mm

Height :
Weight :

370
85

mm
kg

Date :
Quotation n :
Unit reference :

21.11.2013

CIUPERCARIE
TARGOVISTE

Project :
WinPak
Version : 3.0.2 / 3.0.2

Client :
Page :

Transport
section 1

-2/4-

HP4

Length :

740

mm

Weight :

85

kg

( 2 ) Filter
Filter data
Type

Synthetic panel filter

Class

G2

Performance data
Air volume
2240
0.6222
APD
13
Final APD
100

m/h
m/s
Pa
Pa

Qty of filters
562 * 335

E_0011

( 3 ) Heating
Type
Material
Face velocity
Rows/Circuits
Fin spacing

Coil data
Water coil
Cu/Al
2.04
2/6
2.1

Conn. In/Out

m/s
mm

26x34/26x34

Performance data
Air volume
2240
0.6222
Air in
-15/-15.25
Air out
42.6/16.4
Total
44.384
capacity
APD
19

m/h
m/s
C
C
kW

Type
Glycol
In/Out
Flow
Velocity

Pa

WPD

m/h
m/s
C

Type
Glycol
In/Out

Fluid data
Water
0
80/60
1951
1.45
10

%
C
l/h
m/s
kPa

( 4 ) Cooling
Type
Material
Face velocity

Coil data
Water coil
Cu/Al
2.04

m/s

Rows/Circuits

4 / 12

Fin spacing
Conn. In/Out

2.1
mm
26x34 / 26x34

Performance data
Air volume
2240
0.6222
Air in
35 /
26.13
Air out
11.8 /
11.8
Total capacity
32.711
Sens. capacity
17.523
Condensation
24.26
APD
66

Fluid data
Water
0
7 / 12

%
C

Flow

5609

l/h

kW
kW
l/h
Pa

Velocity
WPD

2.08
46.4

m/s
kPa

( 5 ) Supply fan
Model :
Blades :

Fan data
2.69
Forward curved

Drive :
Selected speed :

Direct
3

Motor data
Power
Supply
voltage
Protection
Therm.
protec.
Abs.
current

0.96
kW
230V/1ph/50Hz

Performance data
Air volume
2240
0.6222

IP20
Klixon

Unit APD
ESP

98
151

Pa
Pa

Static pressure

249

Pa

4.22

m/h
m/s

Date :
Quotation n :
Unit reference :
Project :
WinPak
Version : 3.0.2 / 3.0.2

Client :
Page :

21.11.2013

CIUPERCARIE
TARGOVISTE
-3/4-

Date :
Quotation n :
Unit reference :

CIUPERCARIE
TARGOVISTE

Project :
WinPak
Version : 3.0.2 / 3.0.2

Sound levels
Frequencies
Lw fan
Lw radiated
Lw duct upstream
Lw duct downstream
Lp *

125 Hz
250 Hz
77.1 dB
70.9 dB
75.1 dB
66.4 dB
77.1 dB
70.9 dB
77.1 dB
70.9 dB
61.1 dB
52.4 dB
* Sound pressure calculated at 2 m distance (free field).

Client :
Page :

500 Hz
71.1 dB
64.6 dB
71.1 dB
71.1 dB
50.6 dB

1 kHz
66.0 dB
60.5 dB
66.0 dB
66.0 dB
46.5 dB

2 kHz
63.7 dB
56.7 dB
63.7 dB
63.7 dB
42.7 dB

21.11.2013

-4/4-

4 kHz
56.9 dB
47.9 dB
56.9 dB
56.9 dB
33.9 dB

Global
72.3 dB(A)
66.6 dB(A)
72.3 dB(A)
72.3 dB(A)
52.6 dB(A)