Professional Documents
Culture Documents
Laboratory Ventilation Systems Getting the Best Bang for the Buck
This report focuses on what type of ventilation system can yield the most favorable life cycle cost for a chemical laboratory with fume hoods. In many situations it's not possible to provide a one size fits all answer because of the many individual variables involved. Laboratory activities extend from basic chemistry instruction in teaching labs to advanced research. Laboratory rooms vary in size and involve an endless array of furnishings and equipment. All of these factors impact the type of ventilation system that will be most appropriate, as well as result in the lowest life cycle cost. This report is intended as a guide to selecting the type of ventilation system that is likely to attain the lowest life cycle cost for a specific type of laboratory and thus get the best bang for the buck.
Page 1 of 10
100 90 80 70 60 50 40 30 20 10 0
CAV-1
CAV-2
LAF-1
LAF-2 VAV
OC UN
OC UN
OC UN
OC UN
OC UN
Figure 1. Comparative Energy Consumption Characteristics for Laboratory Ventilation Systems During the OC (Occupied) and UN (Unoccupied) Times of the Day.
1.
Low Air Flow fume hoods typically consume about 60% of the airflow of conventional CAV fume hoods. However, the concept of LAF fume hoods is relatively new and has not yet received wide acceptance within the industry, nor have they established a history of satisfactory implementation and performance. Page 2 of 10
Table 1 lists the advantages and disadvantages of each type of system and provides general guidance for the type of system most suited for different types of laboratory facilities. All of the ventilation systems listed in Table 1 can be designed and controlled to meet the ventilation system functions listed above. The major differences lie in the cost effectiveness and suitability of each ventilation system for the specific application. The commentary that follows provides details on the recommendations listed in Table 1. Later in this document there are guidelines for determining the actual potential energy consumption for the different types of ventilation systems.
2.
In rooms having only one or two small fume hoods a room general exhaust may also be required to attain sufficient total room exhaust airflow for this purpose.
3.
Chemical laboratory rooms normally are required to be negatively pressurized to prevent room air from migrating out to non-laboratory areas. In some instances laboratory rooms require positive pressurization to prevent contamination from adjoining spaces. In such instances, an entry vestibule can be provided and maintained at a negative static pressure to prevent undesired transfer of laboratory room air to nonlaboratory areas and vice-versa. Siemens Industry, Inc. Document No. 149-980
Page 3 of 10
Table 1. Recommended Ventilation System Types for Various Chemistry Laboratory Applications. Type of Facility
1. Small Testing and Analysis Facility: Private laboratory or a small laboratory within a medical or commercial enterprise. 2. Small College: Undergraduate Chemistry Teaching Laboratory 3. Large College or University: Large Undergraduate and Graduate Chemistry Teaching Laboratories 4. University Research Laboratories
Laboratory Function
Provides testing and analytical services for environmental, medical, and other specialty purposes.
Usage Pattern
Mainly involves repetitive testing in a prescribed manner. No research or experimentation is conducted. Work is performed during routine workday hours. Rigidly scheduled usage periods. The lab may not be utilized for extended periods such as a summer semester. Rigidly scheduled usage periods. Some labs may not be use for summer semesters.
Provides basic chemistry instruction. No highly toxic or dangerous chemicals are present. Provides basic and higher level chemistry instruction. Limited use of toxic or dangerous chemicals. High-level research by esteemed researchers and graduate students.
CAV 2-Position CAV 1-Position with a fume hood exhaust shut-down 4 provision CAV 2-Position Possibly with a fume hood exhaust shut-down provision4 VAV
Does not follow a specific usage schedule. Occupancy and use ranges from intensive to sporadic and on any day and time. Most testing is done in a prescribed manner with no research of experimentation. Work is performed during a routine business day. Labs generally occupied according to a regular schedule but schedule variations frequently occur. Labs generally occupied according to a set schedule, but schedule variations can occasionally occur. Labs generally occupied according to a set schedule, but frequent variations are likely.
VAV LAF
5.
Conducts testing and analytical services on evidence and for regulatory compliance purposes. Advanced research under high security conditions. Research conducted by top-level scientists. Quality control and product development testing and research. Various levels of testing, product development and research for a wide array of purposes.
6.
7.
Small/Mid-Size Commercial and Industrial Firms Large Commercial and Industrial Firms
8.
NFPA 45 states: "The hood shall provide containment of the possible hazards and protection for personnel at all times when chemicals are present in the hood." Thus, if all chemicals are removed from a fume hood its exhaust system is not required to remain operating. Unless the fume hood exhaust system is also required to maintain the required laboratory room ventilation rate and negative pressurization, the fume hood exhaust system could be shut down when the laboratory room is unoccupied.
Page 4 of 10
additional energy savings to justify its increased cost. However, a VAV system may be beneficial in very large teaching laboratories because it can lower the overall room sound level when the fume hood sashes are not fully open. LAF type systems may not result in the lowest life cycle cost due to their significantly higher initial cost and the extra care that the fume hood users must exercise.
2. Small College
Undergraduate chemistry teaching laboratories typically operate for only a limited amount of hours throughout the year. For this reason, a CAV 2Position type of system is ideally suited for this application. A VAV or LAF system would probably not achieve sufficient additional energy savings to justify their higher cost. Also, because of their modest size, small colleges generally do not have high-level facility personnel who can maximize the potential of a sophisticated VAV system or ensure an LAF system is functioning properly. As an alternative, a simple CAV 1-Position system might be appropriate if the fume hood exhaust can be equipped with a shutdown provision. (See note 4 in Table 1.)
5. Government Agencies
Government agency laboratories are found at the federal, state, provincial and local level. This includes crime labs and regulatory agencies that test for compliance with stack emissions, wastewater discharge and other environmental related factors. These types of facilities mainly employ lab technicians who conduct repetitive testing during a fixed daily occupancy schedule. Fume hoods are usually modest in size (6-feet wide units) and the technicians may be at their fume wood for most of the day. A simple CAV 1-Position system will waste too much energy during unoccupied periods and may cause too much ventilation related sound in large laboratories. Therefore, these applications generally favor the CAV 2-Position system even though a VAV or LAF 2-Position system may also be a good fit. These types of laboratory applications are likely to require a thorough life cycle analysis to determine the most applicable type of system.
Page 5 of 10
6. Government Research
Government research laboratories include federally funded or federally sponsored research facilities. These labs tend to be very large facilities and often employ high level scientific personnel who conduct advanced research on space, defense, medical, biological, and in nuclear related areas. The fume hood sizes can vary widely and some may be quite large or of a special design. The time and usage pattern of the labs can vary extensively. Because of these widely varying usage patterns coupled with government mandates to minimize energy usage, these applications are very well suited for VAV type systems. An LAF 2-Position system may also be applicable, but only if the researchers can be expected to follow a rigid fume hood safety regimen. A life cycle analysis may be needed to substantiate the most appropriate system.
Page 6 of 10
Benefits
Lowest first cost Easiest to design and implement Least impact on facility support personnel. Relatively low first cost Good potential for energy reduction Not overly difficult to design and implement Modest impact on support personnel Lower ventilation related sound Reduced energy consumption at all times Not overly difficult to design and implement
Limitations
High ventilation related sound Highest energy consumption
High ventilation related sound during occupancy Requires fairly rigid occupancy schedule to achieve energy savings Requires somewhat knowledgeable support personnel High fume hood first cost May not comply with face velocity requirements of local (state or provincial) governing body Requires close monitoring to ensure proper functionality is maintained Requires knowledgeable support personnel High fume hood first cost May not comply with face velocity requirements of local (state or provincial) governing body More involved system design and implementation Requires fairly rigid lab occupancy schedule to maximize energy savings Requires close monitoring to ensure proper functionality Requires competent support personnel Increased first cost Requires sophisticated system design effort and implementation System requires close monitoring to ensure maximum benefit Requires higher level support personnel
LAF - 2-Position
Lower ventilation related sound Significant reduction in energy consumption Not overly difficult to design and implement
VAV
Lower ventilation related sound Potential for lowest energy consumption Greatest usage flexibility
5
VAV Allows changing room ventilation and fume hood operational parameters as changes in laboratory usage occur.
Page 7 of 10
Page 8 of 10
Average Fume Hood & General Exhaust Cubic Feet per Minute (cfm) Calculation Procedure
The average annual fume hood cfm is the normal constant fume hood exhaust cfm. The average annual general exhaust cfm is the normal constant general exhaust cfm. Step 1: Determine the laboratory's weekly occupancy percentage by dividing the normal Occupied Hrs/Wk6 by 168. (For 8 A.M. to 5 P.M. weekdays this typically is about 33%.) Step 2: Determine the laboratory weekly unoccupancy percentage by subtracting the resultant of Step 1 from 100%.
Step 3: Determine the unoccupied cfm percentage by multiplying the resultant from Step 2 by 20%, which represents the allowable minimum fume hood exhaust airflow. Step 4: Add the two percentages from Steps 1 and 3. Step 5: Determine the average cfm by multiplying the fume hood's maximum exhaust cfm by the resultant of Step 4. The average annual general exhaust usage is determined by the following expression: [Occ G.E. cfm Occ Hrs/Wk + Unocc G.E. cfm Unocc Hrs/Wk] 168 Step 1: Determine the normal laboratory fume hood usage time percentage by dividing the likely actual weekly usage hours by 168. (For a VAV system this typically ranges from 10% to 20%.) Step 2: Determine the laboratory fume hood non-usage time percentage by subtracting the resultant from Step 1 from 100%. Step 3: Determine the unoccupied cfm percentage by multiplying the result from Step 2 by 20%, which represents the minimum fume hood exhaust airflow. Step 4: Add the two percentages from Steps 1 and 3. Step 5: Determine the average cfm by multiplying the fume hood's maximum exhaust cfm by the resultant of Step 4. The average annual general exhaust cfm is determined from the following expression: [Average Occ G.E. cfm Occ Hrs/Wk + Average Unocc G.E. cfm Unocc Hrs/Wk] 168
VAV
The weekly occupied hours are the total of each day's regular occupancy hours plus the additional daily occupied hours for transitioning into and out of the unoccupied period (typically 2 hours per day).
Page 9 of 10
When feasible, use the exhaust airflow from offices as part of the supply airflow for the laboratories. Be sure to right-size equipment and not oversize central heating and cooling equipment. Studies and practical experience have shown that in large laboratories with many fume hoods, about 30% to 70% of the hoods are either closed or only partially used at any time. This yields an overall VAV diversity factor of approximately 50%. Therefore, select equipment with part-load operation and variable conditions in mind. Rather than having one or two large chillers, they should be sized in incremental modules that will activate singly or in tandem to meet variable loads while operating at maximum efficiencies. Two chillers of unequal size can provide more flexibility in matching variable loads than one large one or two equal sized units. Air duct sizing is important in that ducts should be designed for low-pressure drops. Consider designing the ventilation system with slightly oversized ducts that can reduce pressure drops as well as efficiently handle future needs.
Product or company names mentioned herein may be the trademarks of their respective owners. 2009 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Printed in the USA Document No. 149-980 Page 10 of 10