You are on page 1of 10

Technology Report June, 2003

Laboratory Ventilation Systems Getting the Best Bang for the Buck
This report focuses on what type of ventilation system can yield the most favorable life cycle cost for a chemical laboratory with fume hoods. In many situations it's not possible to provide a one size fits all answer because of the many individual variables involved. Laboratory activities extend from basic chemistry instruction in teaching labs to advanced research. Laboratory rooms vary in size and involve an endless array of furnishings and equipment. All of these factors impact the type of ventilation system that will be most appropriate, as well as result in the lowest life cycle cost. This report is intended as a guide to selecting the type of ventilation system that is likely to attain the lowest life cycle cost for a specific type of laboratory and thus get the best bang for the buck.

Constant Air Volume (CAV) 1Position


A CAV 1-Position ventilation system provides a constant ventilation airflow through a laboratory room and its fume hoods during both the occupied and unoccupied periods24 hours a day and 7 days a week. It is the simplest system to design and requires a limited amount of associated airflow controls. It also requires a minimum amount of knowledge and oversight by support (maintenance) personnel. However, the tradeoff for this simplicity is high-energy consumption since there is no provision for reducing ventilation airflow during times when the room is unoccupied or the fume hoods are not being used. However, in certain limited applications, the CAV 1-Position ventilation system can be the optimum type of system.

Ventilation System Characteristics


Laboratory ventilation standards require that a laboratory's ventilation system must remain functioning at all times when there are hazardous chemicals within the room or a fume hood. Under these situations, the laboratory room's ventilation system may only be fully shut down for short periods when necessary for testing, adjusting and servicing. At all other times some amount of ventilation airflow must be maintained. Thus, energy consumption becomes a significant expenditure. Figure 1 shows the relative energy consumption characteristics of the commonly applied types of laboratory ventilation systems during the room's occupied and unoccupied periods. An overview of each type of ventilation system follows. See Table 1 for the recommended ventilation system for various chemistry laboratory applications.

Constant Air Volume (CAV) 2Position


A CAV 2-Position ventilation system provides two levels of ventilation airflow through the laboratory room and its fume hoods. It provides a higher ventilation airflow rate when the laboratory room is occupied and a lower amount when the room is unoccupied. As with the basic CAV 1-Position system, it is not a very complex design and requires only a modest amount of associated airflow controls. It requires some supervision and knowledge by support personnel, and is often the optimum type of ventilation system for certain types of laboratories.

Siemens Industry, Inc. Document No. 149- 980

Page 1 of 10

100 90 80 70 60 50 40 30 20 10 0

CAV-1

CAV-2

LAF-1

LAF-2 VAV

OC UN

OC UN

OC UN

OC UN

OC UN

Figure 1. Comparative Energy Consumption Characteristics for Laboratory Ventilation Systems During the OC (Occupied) and UN (Unoccupied) Times of the Day.

Low Air Flow (LAF) 1 & 2-Position


LAF 1 & 2-Position ventilation systems are basically CAV systems that achieve a lower ventilation airflow in conjunction due to the use of Low Air Flow 1 chemical fume hoods. Like the CAV system, a LAF system can be implemented as a 1-Position or 2Position type of system. Since it is basically a CAV type of system, it is not overly difficult to design, but it does require some amount of associated airflow control to ensure proper and safe operation. Also, because it is critical to ensure that the proper level of airflow is maintained, LAF systems require significant vigilance by support personnel. Low Air Flow fume hoods generally have a considerably higher initial cost than conventional fume hoods, which is an important factor in considering the overall life cycle cost. As with the other types of systems, an LAF type of system can be an optimum choice in certain applications.

Variable Air Volume (VAV)


A VAV ventilation system is intended to provide just the right amount of airflow through a laboratory room and its fume hoods 24 hours a day and 7 days a week. It requires a careful ventilation system design and a sophisticated airflow control system. It also requires knowledgeable staff personnel to monitor and operate the VAV system. The major benefit of the VAV system is that it is the most energy efficient since it can reduce energy usage whenever a fume hood sash is not fully open. In other words, it has the potential to reduce energy consumption continually and not just when a laboratory room is unoccupied. VAV also provides much operational flexibility since fume hood face velocity and other ventilation parameters can be easily reset as needed. A VAV system can also achieve a lower ventilation related room sound level since it keeps the airflow at the minimal level. In many instances the VAV ventilation system is the optimum type of system due to the potential energy savings and operational flexibility.

1.

Low Air Flow fume hoods typically consume about 60% of the airflow of conventional CAV fume hoods. However, the concept of LAF fume hoods is relatively new and has not yet received wide acceptance within the industry, nor have they established a history of satisfactory implementation and performance. Page 2 of 10

Siemens Industry, Inc. Document No. 149-980

Ventilation System Functions


Regardless of the type of ventilation system they must all fulfill five requirements: 1. Maintain necessary fume hood exhaust airflow. 2. Provide sufficient room makeup airflow to balance off the fume hood exhaust and other exhausts. 3. Maintain sufficient total room exhaust airflow to achieve the room's minimum ventilation rate in air changes per hour 2 . 4. Maintain enough total room exhaust airflow to allow sufficient supply airflow for maintaining the room ambient temperature and humidity2. 5. Maintain the required differential between the room's supply airflow and total room exhaust airflow to attain the required negative or positive static pressurization 3 relationship between the room and adjacent areas.

Table 1 lists the advantages and disadvantages of each type of system and provides general guidance for the type of system most suited for different types of laboratory facilities. All of the ventilation systems listed in Table 1 can be designed and controlled to meet the ventilation system functions listed above. The major differences lie in the cost effectiveness and suitability of each ventilation system for the specific application. The commentary that follows provides details on the recommendations listed in Table 1. Later in this document there are guidelines for determining the actual potential energy consumption for the different types of ventilation systems.

2.

In rooms having only one or two small fume hoods a room general exhaust may also be required to attain sufficient total room exhaust airflow for this purpose.

3.

Chemical laboratory rooms normally are required to be negatively pressurized to prevent room air from migrating out to non-laboratory areas. In some instances laboratory rooms require positive pressurization to prevent contamination from adjoining spaces. In such instances, an entry vestibule can be provided and maintained at a negative static pressure to prevent undesired transfer of laboratory room air to nonlaboratory areas and vice-versa. Siemens Industry, Inc. Document No. 149-980

Page 3 of 10

Table 1. Recommended Ventilation System Types for Various Chemistry Laboratory Applications. Type of Facility
1. Small Testing and Analysis Facility: Private laboratory or a small laboratory within a medical or commercial enterprise. 2. Small College: Undergraduate Chemistry Teaching Laboratory 3. Large College or University: Large Undergraduate and Graduate Chemistry Teaching Laboratories 4. University Research Laboratories

Laboratory Function
Provides testing and analytical services for environmental, medical, and other specialty purposes.

Usage Pattern
Mainly involves repetitive testing in a prescribed manner. No research or experimentation is conducted. Work is performed during routine workday hours. Rigidly scheduled usage periods. The lab may not be utilized for extended periods such as a summer semester. Rigidly scheduled usage periods. Some labs may not be use for summer semesters.

Ventilation System Recommendation


CAV 1-Position Possibly with a fume hood exhaust shut4 down provision CAV (2-Position)

Provides basic chemistry instruction. No highly toxic or dangerous chemicals are present. Provides basic and higher level chemistry instruction. Limited use of toxic or dangerous chemicals. High-level research by esteemed researchers and graduate students.

CAV 2-Position CAV 1-Position with a fume hood exhaust shut-down 4 provision CAV 2-Position Possibly with a fume hood exhaust shut-down provision4 VAV

Does not follow a specific usage schedule. Occupancy and use ranges from intensive to sporadic and on any day and time. Most testing is done in a prescribed manner with no research of experimentation. Work is performed during a routine business day. Labs generally occupied according to a regular schedule but schedule variations frequently occur. Labs generally occupied according to a set schedule, but schedule variations can occasionally occur. Labs generally occupied according to a set schedule, but frequent variations are likely.

VAV LAF

5.

Government Agencies: Crime Laboratories Regulatory Agencies

Conducts testing and analytical services on evidence and for regulatory compliance purposes. Advanced research under high security conditions. Research conducted by top-level scientists. Quality control and product development testing and research. Various levels of testing, product development and research for a wide array of purposes.

CAV -2-Position VAV LAF - 2-Position VAV LAF - 2-Position

6.

Government Research High Tech Defense Space Research

7.

Small/Mid-Size Commercial and Industrial Firms Large Commercial and Industrial Firms

CAV -2-Position LAF - 2-Position VAV LAF - 2-Position

8.

NFPA 45 states: "The hood shall provide containment of the possible hazards and protection for personnel at all times when chemicals are present in the hood." Thus, if all chemicals are removed from a fume hood its exhaust system is not required to remain operating. Unless the fume hood exhaust system is also required to maintain the required laboratory room ventilation rate and negative pressurization, the fume hood exhaust system could be shut down when the laboratory room is unoccupied.

Page 4 of 10

Siemens Industry, Inc. Document No. 149-980

1. Small Testing and Analysis Facility


These laboratories are often small commercial operations with only one or two laboratory rooms. Technicians or workers conduct routine and repetitive testing that can involve daylong use of the fume hoods. Generally, the fume hoods are limited in size (5- or 6-feet wide units) and the testing requires only small amounts of non-toxic chemicals. Such facilities are usually best served by a CAV 1Position system and the fume hood exhaust can sometimes include a shut down provision. (See note 4 in Table 1.) If the facility is larger, having several laboratory rooms, a CAV 2-Position system may be appropriate. VAV systems, which provide maximum benefit when fume hood sashes are closed, would probably not achieve the lowest life cycle cost since the fume hoods in these facilities may be in use for long periods of time and perhaps all day long. Also, since the facilities are small, they probably do not have any high-level support personnel who are needed to maximize a VAV system's potential or to ensure that an LAF system is properly functioning.

additional energy savings to justify its increased cost. However, a VAV system may be beneficial in very large teaching laboratories because it can lower the overall room sound level when the fume hood sashes are not fully open. LAF type systems may not result in the lowest life cycle cost due to their significantly higher initial cost and the extra care that the fume hood users must exercise.

4. University Research Laboratories


Large universities often have many smaller laboratories where research is conducted under contracts to private firms or under government grants. These laboratories do not operate according to a fixed schedule and the fume hoods are utilized at unpredictable times and for varying lengths of time. A simple CAV 1-Position system will waste far too much energy when the fume hoods are not being used. A CAV 2-Position system is also not a good fit since there is no predictable occupancy schedule. A VAV type of system is usually the best type of system for these applications. An LAF 1Position system is a possible alternative, but will probably not return as much energy savings as a VAV system.

2. Small College
Undergraduate chemistry teaching laboratories typically operate for only a limited amount of hours throughout the year. For this reason, a CAV 2Position type of system is ideally suited for this application. A VAV or LAF system would probably not achieve sufficient additional energy savings to justify their higher cost. Also, because of their modest size, small colleges generally do not have high-level facility personnel who can maximize the potential of a sophisticated VAV system or ensure an LAF system is functioning properly. As an alternative, a simple CAV 1-Position system might be appropriate if the fume hood exhaust can be equipped with a shutdown provision. (See note 4 in Table 1.)

5. Government Agencies
Government agency laboratories are found at the federal, state, provincial and local level. This includes crime labs and regulatory agencies that test for compliance with stack emissions, wastewater discharge and other environmental related factors. These types of facilities mainly employ lab technicians who conduct repetitive testing during a fixed daily occupancy schedule. Fume hoods are usually modest in size (6-feet wide units) and the technicians may be at their fume wood for most of the day. A simple CAV 1-Position system will waste too much energy during unoccupied periods and may cause too much ventilation related sound in large laboratories. Therefore, these applications generally favor the CAV 2-Position system even though a VAV or LAF 2-Position system may also be a good fit. These types of laboratory applications are likely to require a thorough life cycle analysis to determine the most applicable type of system.

3. Large College or University


Since larger academic teaching laboratories typically operate during a specific time during the day, they are excellent applications for a CAV 2-Position type of system. Also, if the lab will not be utilized for extended periods (such as a summer semester), additional savings might be attained if the fume hood exhaust can be shut down. (See note 4 in Table 1.) A simple CAV 1-Position system will likely waste too much energy during the unoccupied periods. A VAV type of system will usually not provide enough
Siemens Industry, Inc. Document No. 149-980

Page 5 of 10

6. Government Research
Government research laboratories include federally funded or federally sponsored research facilities. These labs tend to be very large facilities and often employ high level scientific personnel who conduct advanced research on space, defense, medical, biological, and in nuclear related areas. The fume hood sizes can vary widely and some may be quite large or of a special design. The time and usage pattern of the labs can vary extensively. Because of these widely varying usage patterns coupled with government mandates to minimize energy usage, these applications are very well suited for VAV type systems. An LAF 2-Position system may also be applicable, but only if the researchers can be expected to follow a rigid fume hood safety regimen. A life cycle analysis may be needed to substantiate the most appropriate system.

8. Large Commercial and Industrial Firms


Large business enterprises can have many laboratories and, in some instances, several laboratory buildings. Activities vary from routine quality control testing to a good deal of product development and advanced research activities. Such facilities are well suited for LAF 2-Position systems or VAV systems depending upon the extent of the work hazard. LAF systems may be applicable for more routine type of laboratory operations. However, more sophisticated control and monitoring systems associated with VAV allow greater operational flexibility along with automated data storage, which can be highly desirable for higher hazard laboratories. Table 2 provides a summary of the potential benefits and limitations of different laboratory ventilation systems.

7. Small/Mid-Sized Commercial and Industrial Firms


Generally, small firms use laboratories for quality control testing. Larger firms also do substantial quality control testing, but are more likely to also engage in product development experimentation and research. Quality control laboratories normally conduct routine testing on a set daily schedule. If there are several such laboratory rooms, a CAV 2-Position system or a LAF system may be most appropriate. VAV systems are well suited for research or product development activities and provide the best return when fume hood sashes can be kept closed for extended periods. If the research work is very intensive, a LAF 2-Position type of system may be the most advantageous.

Page 6 of 10

Siemens Industry, Inc. Document No. 149- 980

Table 2. Comparison of Ventilation System Characteristics. Ventilation System


CAV - 1-Position CAV - 2-Position LAF - 1-Position

Benefits
Lowest first cost Easiest to design and implement Least impact on facility support personnel. Relatively low first cost Good potential for energy reduction Not overly difficult to design and implement Modest impact on support personnel Lower ventilation related sound Reduced energy consumption at all times Not overly difficult to design and implement

Limitations
High ventilation related sound Highest energy consumption

High ventilation related sound during occupancy Requires fairly rigid occupancy schedule to achieve energy savings Requires somewhat knowledgeable support personnel High fume hood first cost May not comply with face velocity requirements of local (state or provincial) governing body Requires close monitoring to ensure proper functionality is maintained Requires knowledgeable support personnel High fume hood first cost May not comply with face velocity requirements of local (state or provincial) governing body More involved system design and implementation Requires fairly rigid lab occupancy schedule to maximize energy savings Requires close monitoring to ensure proper functionality Requires competent support personnel Increased first cost Requires sophisticated system design effort and implementation System requires close monitoring to ensure maximum benefit Requires higher level support personnel

LAF - 2-Position

Lower ventilation related sound Significant reduction in energy consumption Not overly difficult to design and implement

VAV

Lower ventilation related sound Potential for lowest energy consumption Greatest usage flexibility
5

VAV Allows changing room ventilation and fume hood operational parameters as changes in laboratory usage occur.

Siemens Industry, Inc. Document No. 149-980

Page 7 of 10

Life Cycle Cost Analysis


As previously stated, a life cycle cost analysis may be necessary to determine the most advantageous type of laboratory ventilation system in some situations. However, a particular type of system may still not be acceptable if the ventilation system's limitations (indicated in Table 2) are unacceptable. It should also be emphasized that although a particular type of system may seem to provide the most advantageous life cycle cost, it may not be the best solution for the intended application based upon other considerations. These include lack of system flexibility and expandability. You should also consider the availability of a facility support staff that can ensure proper ventilation system operation and the achievement of the anticipated energy savings. When determining a system's life cycle cost, the training of facility operating personnel is a valid consideration. More complicated systems (such as VAV) and more advanced equipment (such as LAF fume hoods) will incur additional costs to keep facility personnel trained on the operation, testing and monitoring of the systems and associated equipment.

Life Cycle Energy Cost


When compiling a system's life cycle cost, a key factor is the overall energy cost associated with each type of system over its useful life. To estimate the energy cost associated with a particular type of ventilation system, determine the average annual cfm using the following steps: 1. Determine each fume hood's average annual cubic feet per minute (cfm). If a laboratory room's general exhaust is present also determine the general exhaust average annual cfm by the procedure listed in Table 3. 2. Total the fume hood average annual cfm for all fume hoods that will be served by the ventilation system. If a general exhaust is present, also total each room's general exhaust average annual cfm and add it to the totalized fume hood average annual cubic feet per minute. This results in the total average annual laboratory cubic feet per minute. 3. Determine the annual energy cost by multiplying the total average annual laboratory cfm (from Step 2) by the facility's annual energy cost per cubic feet per minute. This typically ranges from $3 to $6 per cfm in the U.S.

Page 8 of 10

Siemens Industry, Inc. Document No. 149- 980

Table 3. Laboratory Annual Cubic Feet per Minute. System Type


CAV 1 & LAF - 1

Average Fume Hood & General Exhaust Cubic Feet per Minute (cfm) Calculation Procedure
The average annual fume hood cfm is the normal constant fume hood exhaust cfm. The average annual general exhaust cfm is the normal constant general exhaust cfm. Step 1: Determine the laboratory's weekly occupancy percentage by dividing the normal Occupied Hrs/Wk6 by 168. (For 8 A.M. to 5 P.M. weekdays this typically is about 33%.) Step 2: Determine the laboratory weekly unoccupancy percentage by subtracting the resultant of Step 1 from 100%.

CAV 2 & LAF - 2

Step 3: Determine the unoccupied cfm percentage by multiplying the resultant from Step 2 by 20%, which represents the allowable minimum fume hood exhaust airflow. Step 4: Add the two percentages from Steps 1 and 3. Step 5: Determine the average cfm by multiplying the fume hood's maximum exhaust cfm by the resultant of Step 4. The average annual general exhaust usage is determined by the following expression: [Occ G.E. cfm Occ Hrs/Wk + Unocc G.E. cfm Unocc Hrs/Wk] 168 Step 1: Determine the normal laboratory fume hood usage time percentage by dividing the likely actual weekly usage hours by 168. (For a VAV system this typically ranges from 10% to 20%.) Step 2: Determine the laboratory fume hood non-usage time percentage by subtracting the resultant from Step 1 from 100%. Step 3: Determine the unoccupied cfm percentage by multiplying the result from Step 2 by 20%, which represents the minimum fume hood exhaust airflow. Step 4: Add the two percentages from Steps 1 and 3. Step 5: Determine the average cfm by multiplying the fume hood's maximum exhaust cfm by the resultant of Step 4. The average annual general exhaust cfm is determined from the following expression: [Average Occ G.E. cfm Occ Hrs/Wk + Average Unocc G.E. cfm Unocc Hrs/Wk] 168

VAV

The weekly occupied hours are the total of each day's regular occupancy hours plus the additional daily occupied hours for transitioning into and out of the unoccupied period (typically 2 hours per day).

Siemens Industry, Inc. Document No. 149-980

Page 9 of 10

Life Cycle Cost


The annual energy cost along with the respective ventilation system's initial cost, maintenance costs, training costs, and other operating factors are then used in determining the life cycle cost for the ventilation systems being compared. Normally a life cycle cost should cover at least 10 years and oftentimes a few years longer. A constant air volume (CAV) system will usually provide the optimum expenditure based upon a 2 to 4-year life cycle. A VAV system will likely have the lowest lifecycle cost based upon 5 or more years. Note that ventilation system operating factors can have a substantial effect on annual energy usage. For instance, maintaining unnecessarily narrow operating ranges for relative humidity results in consuming large amount of energy due to extra cooling and reheating. If only certain rooms require tight operational parameters, they should be on a separate HVAC system.

When feasible, use the exhaust airflow from offices as part of the supply airflow for the laboratories. Be sure to right-size equipment and not oversize central heating and cooling equipment. Studies and practical experience have shown that in large laboratories with many fume hoods, about 30% to 70% of the hoods are either closed or only partially used at any time. This yields an overall VAV diversity factor of approximately 50%. Therefore, select equipment with part-load operation and variable conditions in mind. Rather than having one or two large chillers, they should be sized in incremental modules that will activate singly or in tandem to meet variable loads while operating at maximum efficiencies. Two chillers of unequal size can provide more flexibility in matching variable loads than one large one or two equal sized units. Air duct sizing is important in that ducts should be designed for low-pressure drops. Consider designing the ventilation system with slightly oversized ducts that can reduce pressure drops as well as efficiently handle future needs.

Product or company names mentioned herein may be the trademarks of their respective owners. 2009 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Printed in the USA Document No. 149-980 Page 10 of 10

You might also like