HEAT LOAD ESTIMATE

Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF ORTHODONTICS

Date : 23/01/2010

Floor lvl

SECOND

Total Area in sqft

1399.68

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

18195.84

DP

Grs./ lb

DB

WB F

RH%

Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqft Sun gain

Factor

TD

Btu / hr
Summer

Outdoor air details

Solar heat gain through glass


North
East

11

0.56

0.00

11

0.56

0.00

South

119.4

13

0.56

869.23

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

Fresh air

Fresh air

cfm

change

909.792
ESHF

0.79

ADP Deh. RiseDeh. Cfm

56

15.84

4086

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

( 1- BF)* ( RM DB - ADP)

East

23

0.44

0.00 Deh cfm

ERSH / 1.08 * temp rise

South

442.2

21

0.44

West

4085.93 Supply cfmERSH / 1.08 * DESIRED Td

17

0.44

North East

16

0.44

0.00

0 Outlet Td ERSH / 1.08 * De hum CFM

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

1399.68

16

0.48

10749.54

Floor

1399.68

16

0.48

10749.54

Partition

16

0.40

0.00

All glass

21

1.10

0.00

50

280

Internal heat gain


People
Equipment kw

2.96 3410

14000.00
1.00

10093.60

Lights watts

1200

3.41

1.25

Subtotal

5115.00
55662.84
2783.14

Safety factor 5%

Room sensible heat

58445.99

SA duct gain 2.5%

1461.15

SA fan gain 5%

2922.30

Fresh Air

3 ####

2.4

1.08

7074.54

Reheat
Effective room sensible heat

69903.98

Latent heat
People

50

270

13500.00

Subtotal

13500.00
675.00

Safety factor 5%

Room latent heat

14175.00

Fresh Air

3 ####

2.4

0.68

4454.34

Effective room latent heat

18629.34

Effective room total heat

88533.32

Outdoor Air Heat


Fresh Air Sens

909.79

20 0.88

1.08

17293.33

Fresh air lat

909.79

73 0.88

0.68

39742.63

RA gain

RA fan gain
Grand Total

Tons TR

145569.27

12.13

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS )Date : 23/01/2010


Floor lvl

Ground Floor
P G CLINIC

Total Area in sqft

1049.76

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

13646.88

DB

WB F

RH%

DP

Grs./ lb

Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqft Sun gain

Factor

TD

Btu / hr
Summer

Outdoor air details

Solar heat gain through glass


North
East

Fresh air Fresh air

11

0.56

0.00

11

0.56

0.00

South

89.55

13

0.56

651.92

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

cfm

change

682.344
ESHF

0.82

ADP Deh. RiseDeh. Cfm

56

15.84

2793

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

( 1- BF)* ( RM DB - ADP)

East

23

0.44

0.00 Deh cfm

ERSH / 1.08 * temp rise

South

421.2

21

0.44

West

3891.89 Supply cfm ERSH / 1.08 * DESIRED Td

17

0.44

North East

16

0.44

0.00

0 Outlet Td

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

1049.76

16

0.48

8062.16

Floor

1049.76

16

0.48

8062.16

Partition

16

0.40

0.00

All glass

21

1.10

0.00

25

280

Internal heat gain


People
Equipment kw

1.72 3410

7000.00
1.00

5865.20

ERSH / 1.08 * De hum CFM

Lights watts

960

3.41

1.25

Subtotal

4092.00
37625.33
1881.27

Safety factor 5%

Room sensible heat

39506.59

SA duct gain 2.5%

987.66

SA fan gain 5%

1975.33

Fresh Air

3 ####

2.4

1.08

5305.91

Reheat
Effective room sensible heat

47775.49

Latent heat
People

25

270

6750.00

Subtotal

6750.00
337.50

Safety factor 5%

Room latent heat

7087.50

Fresh Air

3 ####

2.4

0.68

3340.76

Effective room latent heat

10428.26

Effective room total heat

58203.75

Outdoor Air Heat


Fresh Air Sens

682.34

20 0.88

1.08

12969.99

Fresh air lat

682.34

73 0.88

0.68

29806.97

RA gain

RA fan gain
Grand Total

Tons TR

100980.71

8.42

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS


Date) : 23/01/2010
Floor lvl

Ground Floor
OPERATION THEATRE

Total Area in sqft

699.84

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

9097.92

DP

Grs./ lb Enthalpy

DB

WB F

RH%

Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqftSun gain

Factor Btu / hr

TD

Summer

Outdoor air details

Solar heat gain through glass


North
East

Fresh air Fresh air

11

0.56

0.00

29.85

11

0.56

183.88

South

59.7

13

0.56

434.62

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

cfm

change

454.896
ESHF

0.88

ADPDeh. RiseDeh. Cfm

56

15.84

2111

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

110.55

23

0.44

1118.77 Deh cfm

South

221.1

21

0.44

2042.96 Supply cfmERSH / 1.08 * DESIRED Td

West

East

17

0.44

North East

16

0.44

0.00

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

0 Outlet Td ERSH / 1.08 * De hum CFM

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

699.84

16

0.48

5374.77

Floor

699.84

16

0.48

5374.77

Partition

16

0.40

0.00

All glass

21

1.10

0.00

10

280

Internal heat gain


People
Equipment kw

2.48 3410

2800.00
1.00

( 1- BF)* ( RM DB - ADP)
ERSH / 1.08 * temp rise

8456.80

Lights watts

720

3.41

1.25

Subtotal

3069.00
28855.56
1442.78

Safety factor 5%

Room sensible heat

30298.34

SA duct gain 2.5%

757.46

SA fan gain 5%

1514.92

Fresh Air

3 ####

2.4

1.08

3537.27

Reheat
Effective room sensible heat

36107.99

Latent heat
People

10

270

2700.00

Subtotal

2700.00
135.00

Safety factor 5%

Room latent heat

2835.00

Fresh Air

3 ####

2.4

0.68

2227.17

Effective room latent heat

5062.17

Effective room total heat

41170.16

Outdoor Air Heat


Fresh Air Sens

454.90

20

0.88

1.08

8646.66

Fresh air lat

454.90

73

0.88

0.68

19871.31

RA gain

RA fan gain
Grand Total

Tons TR

69688.14

5.81

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS


Date
) : 23/01/2010
Floor lvl

Ground Floor
STERILISATION AREA

Total Area in sqft

58.38

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

758.94

DB

WB F

RH%

DP

Grs./ lb

Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqftSun gain

Factor Btu / hr

TD

Summer

Outdoor air details

Solar heat gain through glass

Fresh air Fresh air

North

11

0.56

0.00

East

11

0.56

0.00

South

13

0.56

0.00

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

cfm

change

37.947
ESHF

0.73

ADP Deh. RiseDeh. Cfm

56

15.84

161

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

( 1- BF)* ( RM DB - ADP)

East

23

0.44

0.00 Deh cfm

ERSH / 1.08 * temp rise

South

21

0.44

0.00 Supply cfmERSH / 1.08 * DESIRED Td

West

17

0.44

North East

16

0.44

0.00

0 Outlet Td ERSH / 1.08 * De hum CFM

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

58.38

16

0.48

448.36

Floor

58.38

16

0.48

448.36

Partition

16

0.40

0.00

All glass

21

1.10

0.00

280

Internal heat gain


People
Equipment kw

0.08 3410

840.00
1.00

272.80

Lights watts

40

3.41

1.25

Subtotal

170.50
2180.02
109.00

Safety factor 5%

Room sensible heat

2289.02

SA duct gain 2.5%

57.23

SA fan gain 5%

114.45

Fresh Air

3 37.95

2.4

1.08

295.08

Reheat
Effective room sensible heat

2755.77

Latent heat
People

270

810.00

Subtotal

810.00
40.50

Safety factor 5%

Room latent heat

850.50

Fresh Air

3 37.95

2.4

0.68

185.79

Effective room latent heat

1036.29

Effective room total heat

3792.06

Outdoor Air Heat


Fresh Air Sens

37.95

20

0.9

1.08

721.30

Fresh air lat

37.95

73

0.9

0.68

1657.65

RA gain

RA fan gain
Grand Total

Tons TR

6171.00

0.51

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF CONSERVATIVE DENTISTRY

Date : 23/01/2010

Floor lvl

THIRD (P.G CLINIC)

Total Area in sqft

1166.4

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

15163.2

DB

WB F

RH%

DP

Grs./ lb

Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqft Sun gain

Factor

TD

Btu / hr
Summer

Outdoor air details

Solar heat gain through glass


North
East

Fresh air Fresh air

11

0.56

0.00

119.4

11

0.56

735.50

South

13

0.56

0.00

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

cfm

change

758.16
ESHF

0.83

ADP Deh. Rise Deh. Cfm

56

15.84

2998

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

582.6

23

0.44

5895.91 Deh cfm

South

21

0.44

West

East

0.00 Supply cfmERSH / 1.08 * DESIRED Td

17

0.44

North East

16

0.44

0.00

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

0 Outlet Td ERSH / 1.08 * De hum CFM

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

1166.4

16

0.48

8957.95

Floor

1166.4

16

0.48

8957.95

Partition

16

0.40

0.00

All glass

21

1.10

0.00

25

280

1.64

3410

Internal heat gain


People
Equipment kw

7000.00
1.00

( 1- BF)* ( RM DB - ADP)
ERSH / 1.08 * temp rise

5592.40

Lights watts

720

3.41

1.25

Subtotal

3069.00
40208.72
2010.44

Safety factor 5%

Room sensible heat

42219.16

SA duct gain 2.5%

1055.48

SA fan gain 5%

2110.96

Fresh Air

758.16

2.4

1.08

5895.45

Reheat
Effective room sensible heat

51281.04

Latent heat
People

25

270

6750.00

Subtotal

6750.00
337.50

Safety factor 5%

Room latent heat

7087.50

Fresh Air

758.16

2.4

0.68

3711.95

Effective room latent heat

10799.45

Effective room total heat

62080.50

Outdoor Air Heat


Fresh Air Sens

758.16

20

0.88

1.08

14411.11

Fresh air lat

758.16

73

0.88

0.68

33118.85

RA gain

RA fan gain
Grand Total

Tons TR

109610.46

9.13

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF CONSERVATIVE DENTISTRY

Date : 23/01/2010

Floor lvl

THIRD

Total Area in sqft

2099.52

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

27293.76

U G CLINIC

DB

WB F

RH%

DP

Grs./ lb Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqft Sun gain

44

Factor Btu / hr

TD

Summer

Outdoor air details

Solar heat gain through glass

Fresh airFresh air

North

11

0.56

0.00

East

11

0.56

0.00

South

179.1

13

0.56

1303.85

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

cfm

change

1364.7
ESHF

0.84

ADPDeh. Rise Deh. Cfm

56

15.84

6430 1.Plain Glass( cl E) has to be changed from .

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

( 1- BF)* ( RM DB - ADP)

East

23

0.44

0.00 Deh cfm

ERSH / 1.08 * temp rise

South

663.3

21

0.44

6128.89 Supply cfmERSH / 1.08 * DESIRED Td

West

17

0.44

0 Outlet Td ERSH / 1.08 * De hum CFM

North East

16

0.44

0.00

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

2099.52

16

0.48

16124.31

Floor

2099.52

16

0.48

16124.31

Partition

16

0.40

0.00

All glass

21

1.10

0.00

2.Light & Equipmnet load to be taken as pe


3.Roof facor,as normal building.
4.Roof factor to be filled when the Roof is e
5.Ceiling facor to be filled up in case of Floo
6.Floor facor when ,we have floor below th
7.The caliculation table only for large areas

Internal heat gain


People

50

280

14000.00

Equipment kw

7.08

3410

1.00

24142.80

Lights watts

2400

3.41

1.25

10230.00

Subtotal

88054.17
4402.71

Safety factor 5%

Room sensible heat

92456.88

SA duct gain 2.5%

2311.42

SA fan gain 5%

4622.84

Fresh Air

3 1364.69

2.4

1.08

10611.81

Reheat
Effective room sensible heat

110002.96

Latent heat
People

50

270

13500.00

Subtotal

13500.00
675.00

Safety factor 5%

Room latent heat


Fresh Air

14175.00
3 1364.69

2.4

0.68

6681.51

Effective room latent heat

20856.51

Effective room total heat

130859.47

Outdoor Air Heat


Fresh Air Sens 1364.69

20 0.88

1.08

25939.99

Fresh air lat

73 0.88

0.68

59613.94

1364.69

RA gain

RA fan gain
Grand Total

Tons TR

216413.40

18.03

ass( cl E) has to be changed from .56 to.1.0


Equipmnet load to be taken as per site conditions.
or,as normal building.
tor to be filled when the Roof is exposed.
acor to be filled up in case of Floor on top.
cor when ,we have floor below the Space to be airconditioend/\
culation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client

Medical College

City : KOTAYAM

Space used : DEPARTMENT OF ORTHODONTICS

Date : 23/01/2010

Floor lvl

SECOND

Total Area in sqft

1399.68

Latitude

8.29

Height ft

13

Suntime

16 :00

Volume cuft

18195.84

DB

WB F

RH%

DP

Grs./ lb

Enthalpy
Btu/lb

Item

Summer

95

80

52.5

188

44

Monsoon

85

80

80.65

212

44

Room

74

100

27.5

Diff

21

88

16.5

Area sqft Sun gain

Factor

Btu / hr

TD

Summer

Outdoor air details

Solar heat gain through glass


North
East

11

0.56

0.00

11

0.56

0.00

South

119.4

13

0.56

869.23

West

164

0.56

0.00

North East

11

0.56

0.00

North West

103

0.56

0.00

South East

11

0.56

0.00

South West

127

0.56

0.00

Fresh air

Fresh air

cfm

change

909.792
ESHF

0.79

ADP Deh. Rise Deh. Cfm

56

15.84

Solar heat gain through walls


North

19

0.44

0.00 Deh rise

( 1- BF)* ( RM DB - ADP)

East

23

0.44

0.00 Deh cfm

ERSH / 1.08 * temp rise

South

442.2

21

0.44

West

4085.93 Supply cfm ERSH / 1.08 * DESIRED Td

17

0.44

North East

16

0.44

0.00

0 Outlet Td

North West

11

0.44

0.00

South East

23

0.44

0.00

South West

19

0.36

0.00

Transmission gain through roof/ ceiling/partitions


Roof

0.48

0.00

Ceiling

1399.68

16

0.48

10749.54

Floor

1399.68

16

0.48

10749.54

Partition

16

0.40

0.00

All glass

21

1.10

0.00

50

280

2.96

3410

Internal heat gain


People
Equipment kw

14000.00
1.00

10093.60

ERSH / 1.08 * De hum CFM

4086 1.Plain Glass( cl E) has to be ch

2.Light & Equipmnet load to be


3.Roof facor,as normal building
4.Roof factor to be filled when
5.Ceiling facor to be filled up in
6.Floor facor when ,we have flo
7.The caliculation table only fo

Lights watts

1200

3.41

1.25

Subtotal

5115.00
55662.84
2783.14

Safety factor 5%

Room sensible heat

58445.99

SA duct gain 2.5%

1461.15

SA fan gain 5%

2922.30

Fresh Air

909.79

2.4

1.08

7074.54

Reheat
Effective room sensible heat

69903.98

Latent heat
People

50

270

13500.00

Subtotal

13500.00
675.00

Safety factor 5%

Room latent heat


Fresh Air

14175.00
3

909.79

2.4

0.68

4454.34

Effective room latent heat

18629.34

Effective room total heat

88533.32

Outdoor Air Heat


Fresh Air Sens 909.79

20

0.88

1.08

17293.33

Fresh air lat

73

0.88

0.68

39742.63

909.79

RA gain

RA fan gain
Grand Total

145569.27

Tons TR

12.13

1.Plain Glass( cl E) has to be changed from .56 to.1.0


2.Light & Equipmnet load to be taken as per site conditions.
3.Roof facor,as normal building.
4.Roof factor to be filled when the Roof is exposed.
5.Ceiling facor to be filled up in case of Floor on top.
6.Floor facor when ,we have floor below the Space to be airconditioend/\
7.The caliculation table only for large areas of Above 500 sq ft.