You are on page 1of 4

July/August 2009 $5.

00

The Voice of the On-Site Power Generating Industry

Load
Banking
Best Practices
BEST PRACTICES

Load Banking Best Practices


By Lyndon B. Risser, CEO, DynaTech Power

Photo 1: Load banking can verify system operation, commissioning and maintenance as well as certify system capacity. Here a load testing
mobile unit is used to test a portable generator.

B ecause real-world facility load is often


dispersed, unpredictable and random,
load bank testing is essential. Load banking
Since emergency generators must be sized
to accommodate the full startup load of a
facility, they are generally sized above the
avoid wet stacking (see Photo 2). With the
increasing awareness of exhaust pollution,
regular loadbanking is an important con-
is a technique used to determine maximum entity’s normal operating load if a load tribution on the generator owner’s part to
back-up power system performance and management system is not in place. minimize exhaust pollution in their com-
should be performed regularly. A load Generators are commonly sized as munities.
bank is a self-contained unit that applies much as 30 percent over the kW rating of Wet stacking is common when diesel en-
controlled load on a power system. It con- a facility to accommodate the surge of the gines operate for extended periods of time
sists of load elements with controls that building and equipment startup load. This with little or no load applied. To operate at
allow an operator to incrementally step situation creates a challenge with diesel peak efficiency, the engine must be able to
and vary the load. For total peace of mind, powered generators. Conditions such as provide the proper ratio of fuel and air and
load banking is the method of choice to wet stacking and carbon buildup in com- maintain the right temperature to burn that
verify system operation, commissioning bustion chambers, injector nozzles, piston fuel completely. EPA requirements have re-
and maintenance as well as certify system rings, turbo chargers, exhaust piping and sulted in dramatic improvements in engine
capacity (see Photo 1 above). silencers can develop. design while the use of electronic controls
Wet stacking is best described as un- has resulted in increased performance.
Why Load Bank Test? burned fuel that accumulates in diesel ex- Every client should require load bank
Load banking is a critical requirement haust. It can be detected by black seepage testing when commissioning an emergency
to ensure that generator owners enjoy the around exhaust connections or continuous power system to ensure proper installation,
full potential of their emergency backup black exhaust from the stack after warm adequate cooling at ambient temperature,
power equipment and that it will perform up. Exhaust gas temperature of 275 de- sufficient fuel delivery, and proper load
as expected when pressed into service. grees Fahrenheit must be maintained to transfer.
2 Reprinted with express permission from the July/August 2009 issue of Powerline magazine
BEST PRACTICES

The Loadbanking Process


1. Logistics are important. Be conscious of the load bank’s proximity to any-
thing that could be affected by heat. The heat leaving a load bank can de-
stroy plants, trees and discolor the paint on objects that are too close to or
in the direct path of exhaust air. It is also important that the load bank is
situated in free air space for adequate cooling.

2. The emergency switchgear should be disabled to avoid accidental transfer


to facility load.
Photo 2: Record temperature at turbo and
3. Ideally, the load bank should be connected to the load side of the generator
after turbo during load test.
breaker. When connecting the transfer switch, confirm that the cable size
is rated to carry the full amp load encountered between the transfer switch
The American Society of Heating, Re- and the generator breaker.
frigerating and Air-Conditioning Engineers
(ASHRAE)1 guideline 1-1996 defines com- 4. Cable rated to carry 100 percent of the rated load should be used to con-
missioning as “the process of ensuring nect the load bank to the generator. For every additional 100 feet of cable
that the systems are designed, installed, required, cable size should be increased to the next largest cable size.
functionally tested and capable of being
5. Notify the facility manager of start time and estimated completion time.
operated and maintained to perform in
conformity with the design intent…” 6. Verify that all cables point-to-point have secure termination, proper insula-
To test performance, load bank testing tion, and correct phasing. All cables should be color coded prior to installa-
should be performed annually (for a mini- tion to simplify verification.
mum of two hours) for standby applica-
tions. During weekly exercises, the engine 7. Start generator and allow a 5 to 10 minute warm-up period.
will not reach manufacturer’s recommend-
ed operating temperatures. The National 8. Apply load in steps allowing 15 to 30 minutes between steps.
Fire Protection Association (NFPA 110)2
9. Closely monitor the engine for leaks, oil pressure and temperature.
has established the standards for monthly
Be prepared to quickly remove load if
maintenance and operation for standby
problems arise.
generators that states, “Generators should
be exercised monthly at 30 percent of the 10. Block load (switch the existing load
nameplate rating or loaded to the minimum including last step by switching master
engine exhaust temperature recommended switch) each step to record the genera-
by the engine manufacturer.” tors ability to pickup the load in one
step (see Photo 3). Measure the exhaust
Planning temperature and compare to manufac-
Load banking can create unexpected turer recommendation for engine and Photo 3: Use the master switch to
results. In many cases, the engine has exhaust filter if installed. Recent emis- “block” load as you increase load.
not been tested to its capacity since the sions requirements call for the instal-
manufacturer’s testing at the factory. If lation of particulate filters creating the
regular load banking was not instituted as need to raise exhaust temperatures to 400-800 degrees Fahrenheit to meet
part of a preventive maintenance plan, then the manufacturer’s requirement for effective regeneration.
the older the engine, the greater the risk
of operational breakdown during testing. 11. Allow a 30-minute cool down period at the end of the test with no load.
As a surgeon would review the potential
consequences with his patient prior to an
operation, it is important that you review
the worst case events with your client prior The facility should be disconnected a blackout. Backup generators should be
to subjecting their facility to the potential from the generator while testing to prevent recommended where a blackout is not an
risks of generator failure during a test. Test overloading the generator. For this reason, option for the facility. Testing should be
results will reflect the level of neglect or life support and mission critical clients scheduled during the most favorable time
underutilization experienced by the power need to be advised of the load bank test, of the day, week and month when inter-
system. and staff must be notified in the event of ruption would be most manageable.
Reprinted with express permission from the July/August 2009 issue of Powerline magazine 3
BEST PRACTICES

Be aware of any local Environmental Protection regulations. For Load Bank Test Log
example, the New Jersey Department of Environmental Protec- Date 7.2.2009
tion (NJDEP) requires you to log onto their website (www.state. Customer Embarq
Job / Location Harrisburg, PA
nj.us/dep/aqpp/aqforecast) to check the air quality conditions and Brand Shindawa
forecasts BEFORE testing a generator to avoid heavy fines. Ambient Temperature F 78
Serial 247864 Parameters and Measurements
kW 100
Battery Voltage (running)13.5 1. Ideal operating temperature 165 - 190
Methods Hz 60 2. Ideal operating exhaust temperature @ turbo 600 - 1200
Hour reading at end 797 3. Increase load @ 5-10 min intervals
There are two methods for load banking generators: resistive Hour reading at start 801.5
testing and reactive testing, with resistive load banking being the Total test time 4 hrs 30 min
Water Temp
most common. The resistive method, which measures kW, but Time Volts Amps Hz Oil Psi
Temp F Exhaust F
kW %

not kVA at the rated power factor, is ideal for testing the engine 13:00
13:10
480
480
120
120
60.0
60.0
60
60
189
200
462
520
0
25
0%
25%
cooling system, exhaust system and the fuel delivery system. Reac- 13:20 484 119 59.9 52 200 630 52 52%
13:30 489 119 59.8 49 210 728 77 77%
tive testing is a generator specific kVA test typically performed at 14:00 487 119 59.5 49 210 842 101 101%
14:15 487 119 59.5 49 210 862 101 101%
the factory. 14:30 486 119 59.5 48 210 861 101 101%
14:45 486 119 59.5 48 210 861 101 101%
15:00 486 119 59.5 48 210 861 101 101%
Observations 15:15 486 119 59.5 48 210 861 101 101%
15:30 486 119 59.5 48 210 861 101 101%
1. If the exhaust has not cleared (smoke-free) during the test 15:45 486 119 59.5 48 210 861 101 101%
period, engine repair will be required. Extensive smoke is 16:00
16:15
486
486
119
119
59.5
59.5
48
48
210
210
861
861
101
101
101%
101%
most often caused by rings that have never seated properly, a 16:30 486 119 59.5 48 210 861 101 101%
16:45 486 119 59.5 48 210 861 101 101%
fuel pump that needs to be rebuilt or bad fuel. 17:00 484 119 59.5 48 210 780 77 77%
60.0
2. If the temperature is not within the manufacturer’s recom- 17:30 480
Technician Remarks:
120 48 200 538 0 0%

mended range, the cooling system may need to be flushed to 1. kW Output performance down from last test by 3%
remove any restriction, or there could be a faulty thermostat 2. Exhaust temerature within manufacturer's recommendations
3. Engine oil and temp performance within manufactures recommendations.
or defective water pump. 4. Recommend replacing air filter
3. If the oil pressure drops below the manufacturer’s recom-
mended range, the oil pump may need to be rebuilt or low
pressure may be an indication of excessive engine wear that
Photo 4: A sample load test report.
could signal the need for an engine overhaul.
References
Documentation 1
The American Society of Heating, Refrigerating and Air-Condi-
Ideally a digital recorder should be connected to chart frequen- tioning Engineers (ASHRAE) www.ashrae.org
cy, voltage and amperage, and document in one-second sampling. 2
The National Fire Protection Association (NFPA 110) Standard
This information should be downloaded to graph a detailed per- for emergency and standby power systems. www.nfpa.org
formance report. Engine oil pressure and temperature should be
documented at 25, 50, 75 and 100 percent of the nameplate rating About the author
of the generator (see Photo 4). Lyndon Risser is the CEO of DynaTech Power located in
Lebanon, PA. Their primary focus is “Delivering Power and Con-
Conclusion fidence” through the sale, service and rental of emergency power
Load bank testing should not be considered an option, but equipment. For information, visit www.dynagen.com. Contact Lyn-
rather a critical element of your emergency preparedness plan. If don at lyndon.risser@dynagen.com ■
you are the maintenance provider, consider it your responsibility
to recommend load banking to your client. As a generator owner,
make sure this is included as part of your annual maintenance
plan. There is no better way to have the peace of mind that you
are prepared when the lights go out!

4 Reprinted with express permission from the July/August 2009 issue of Powerline magazine

You might also like