You are on page 1of 27

DATA SHEET:

ACCC-Arlington
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-007) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 583.2 mm2 9.53 mm 71.3 mm2 29.90 mm 654.2 mm2 186.4 kN 153.8 kN 132 kg/km 1745 kg/km 1612.6 kg/km o 180 C o 1.61E-06 /C 1.87E-05 /oC 112.3 GPa 60.5 GPa

Imperial 1151.0 kcmil 0.375 in. 0.110 in2 1.177 in. 1.014 in2 41.9 kips 34.6 kips 89 lb/kft 1172.8 lb/kft 1083.8 lb/kft o 356 F o 8.94E-07 /F 1.04E-05 /oF 16.3 Msi 8.8 Msi

Metric Imperial 0.0480 ohm/km 0.0773 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0503 ohm/km 0.0809 ohm/mile 0.0599 ohm/km 0.0964 ohm/mile 0.0801 ohm/km 0.1290 ohm/mile 1213 @ 100C & 60 Hz 1830 @ 180C & 60 Hz 0.012 m 0.040 ft 0.243 ohm/km 0.391 ohm/mile 0.144 Mohm-km 0.089 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 600.4 sq. mm (1184.9 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-124-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Beaumont
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-007) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 723.9 mm2 9.53 mm 71.3 mm2 32.87 mm 794.8 mm2 194.4 kN 153.8 kN 132 kg/km 2136 kg/km 2003.6 kg/km o 180 C o 1.61E-06 /C 1.94E-05 /oC 112.3 GPa 59.4 GPa

Imperial 1428.6 kcmil 0.375 in. 0.110 in2 1.294 in. 1.232 in2 43.7 kips 34.6 kips 89 lb/kft 1435.6 lb/kft 1346.6 lb/kft o 356 F o 8.94E-07 /F 1.08E-05 /oF 16.3 Msi 8.6 Msi

Metric Imperial 0.0387 ohm/km 0.0623 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0411 ohm/km 0.0661 ohm/mile 0.0488 ohm/km 0.0785 ohm/mile 0.0650 ohm/km 0.1045 ohm/mile 1381 @ 100C & 60 Hz 2096 @ 180C & 60 Hz 0.013 m 0.043 ft 0.237 ohm/km 0.381 ohm/mile 0.139 Mohm-km 0.087 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 745.2 sq. mm (1470.6 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-127-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Bittern
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 801.4 mm2 8.76 mm 60.3 mm2 34.16 mm 861.3 mm2 175.3 kN 130.2 kN 113 kg/km 2331 kg/km 2217.4 kg/km o 180 C o 1.45E-06 /C 2.01E-05 /oC 116.0 GPa 58.5 GPa

Imperial 1581.6 kcmil 0.345 in. 0.093 in2 1.345 in. 1.335 in2 39.4 kips 29.3 kips 76 lb/kft 1566.3 lb/kft 1490.3 lb/kft o 356 F o 8.06E-07 /F 1.11E-05 /oF 16.8 Msi 8.5 Msi

Metric Imperial 0.0352 ohm/km 0.0566 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0375 ohm/km 0.0603 ohm/mile 0.0444 ohm/km 0.0714 ohm/mile 0.0589 ohm/km 0.0947 ohm/mile 1465 @ 100C & 60 Hz 2229 @ 180C & 60 Hz 0.014 m 0.045 ft 0.234 ohm/km 0.377 ohm/mile 0.138 Mohm-km 0.085 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 825 sq. mm (1628.1 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-108-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Bluebird
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-011) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 1388.7 mm2 10.54 mm 87.3 mm2 44.75 mm 1476.1 mm2 266.4 kN 188.3 kN 164 kg/km 4022 kg/km 3858.0 kg/km o 180 C o 1.61E-06 /C 2.06E-05 /oC 112.3 GPa 57.7 GPa

Imperial 2740.6 kcmil 0.415 in. 0.135 in2 1.762 in. 2.288 in2 59.9 kips 42.3 kips 110 lb/kft 2702.9 lb/kft 2592.9 lb/kft o 356 F o 8.94E-07 /F 1.14E-05 /oF 16.3 Msi 8.4 Msi

Metric Imperial 0.0203 ohm/km 0.0326 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0240 ohm/km 0.0387 ohm/mile 0.0278 ohm/km 0.0447 ohm/mile 0.0356 ohm/km 0.0573 ohm/mile 2010 @ 100C & 60 Hz 3130 @ 180C & 60 Hz 0.018 m 0.058 ft 0.214 ohm/km 0.345 ohm/mile 0.125 Mohm-km 0.077 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1429.6 sq. mm (2821.2 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-115-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Chukar
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-010) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 1135.8 mm2 10.03 mm 79.1 mm2 40.74 mm 1215.5 mm2 234.4 kN 170.6 kN 147 kg/km 3303 kg/km 3155.3 kg/km o 180 C o 1.61E-06 /C 2.03E-05 /oC 112.3 GPa 58.0 GPa

Imperial 2241.5 kcmil 0.395 in. 0.123 in2 1.604 in. 1.884 in2 52.7 kips 38.4 kips 99 lb/kft 2219.6 lb/kft 2120.6 lb/kft o 356 F o 8.94E-07 /F 1.13E-05 /oF 16.3 Msi 8.4 Msi

Metric Imperial 0.0247 ohm/km 0.0398 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0277 ohm/km 0.0445 ohm/mile 0.0324 ohm/km 0.0521 ohm/mile 0.0423 ohm/km 0.0681 ohm/mile 1808 @ 100C & 60 Hz 2785 @ 180C & 60 Hz 0.016 m 0.053 ft 0.221 ohm/km 0.356 ohm/mile 0.129 Mohm-km 0.080 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1169.2 sq. mm (2307.5 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-114-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Corpus Christi
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 558.9 mm2 8.76 mm 60.3 mm2 29.11 mm 618.9 mm2 161.5 kN 130.2 kN 113 kg/km 1656 kg/km 1543.3 kg/km o 180 C o 1.45E-06 /C 1.90E-05 /oC 116.0 GPa 60.2 GPa

Imperial 1103.0 kcmil 0.345 in. 0.093 in2 1.146 in. 0.959 in2 36.3 kips 29.3 kips 76 lb/kft 1113.2 lb/kft 1037.2 lb/kft o 356 F o 8.06E-07 /F 1.06E-05 /oF 16.8 Msi 8.7 Msi

Metric Imperial 0.0501 ohm/km 0.0806 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0524 ohm/km 0.0843 ohm/mile 0.0624 ohm/km 0.1005 ohm/mile 0.0836 ohm/km 0.1345 ohm/mile 1179 @ 100C & 60 Hz 1777 @ 180C & 60 Hz 0.012 m 0.039 ft 0.245 ohm/km 0.395 ohm/mile 0.145 Mohm-km 0.090 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 575.4 sq. mm (1135.4 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-123-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Curlew
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-011) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 523.4 mm2 10.54 mm 87.3 mm2 28.96 mm 610.5 mm2 218.0 kN 188.3 kN 164 kg/km 1610 kg/km 1446.2 kg/km o 180 C o 1.61E-06 /C 1.75E-05 /oC 112.3 GPa 62.5 GPa

Imperial 1033.0 kcmil 0.415 in. 0.135 in2 1.140 in. 0.946 in2 49.0 kips 42.3 kips 110 lb/kft 1082.0 lb/kft 972.0 lb/kft o 356 F o 8.94E-07 /F 9.75E-06 /oF 16.3 Msi 9.1 Msi

Metric Imperial 0.0536 ohm/km 0.0862 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0558 ohm/km 0.0898 ohm/mile 0.0664 ohm/km 0.1069 ohm/mile 0.0887 ohm/km 0.1428 ohm/mile 1142 @ 100C & 60 Hz 1722 @ 180C & 60 Hz 0.012 m 0.039 ft 0.245 ohm/km 0.394 ohm/mile 0.145 Mohm-km 0.090 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 538.8 sq. mm (1063.4 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-132-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Dallas
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-009) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 909.5 mm2 9.78 mm 75.1 mm2 36.88 mm 984.3 mm2 213.1 kN 162.1 kN 143 kg/km 2670 kg/km 2527.2 kg/km o 180 C o 1.61E-06 /C 1.99E-05 /oC 112.3 GPa 58.6 GPa

Imperial 1794.9 kcmil 0.385 in. 0.116 in2 1.452 in. 1.526 in2 47.9 kips 36.4 kips 96 lb/kft 1794.5 lb/kft 1698.5 lb/kft o 356 F o 8.94E-07 /F 1.11E-05 /oF 16.3 Msi 8.5 Msi

Metric Imperial 0.0309 ohm/km 0.0497 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0339 ohm/km 0.0546 ohm/mile 0.0398 ohm/km 0.0640 ohm/mile 0.0520 ohm/km 0.0837 ohm/mile 1585 @ 100C & 60 Hz 2430 @ 180C & 60 Hz 0.015 m 0.048 ft 0.228 ohm/km 0.367 ohm/mile 0.134 Mohm-km 0.083 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 936.3 sq. mm (1847.7 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-129-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Dove
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-005) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 361.6 mm2 7.75 mm 47.1 mm2 23.55 mm 408.6 mm2 122.3 kN 101.7 kN 86 kg/km 1083 kg/km 996.5 kg/km o 180 C o 1.61E-06 /C 1.85E-05 /oC 112.3 GPa 60.9 GPa

Imperial 713.5 kcmil 0.305 in. 0.073 in2 0.927 in. 0.633 in2 27.5 kips 22.9 kips 58 lb/kft 727.7 lb/kft 669.7 lb/kft o 356 F o 8.94E-07 /F 1.03E-05 /oF 16.3 Msi 8.8 Msi

Metric Imperial 0.0771 ohm/km 0.1240 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0792 ohm/km 0.1274 ohm/mile 0.0947 ohm/km 0.1524 ohm/mile 0.1273 ohm/km 0.2049 ohm/mile 902 @ 100C & 60 Hz 1346 @ 180C & 60 Hz 0.010 m 0.031 ft 0.261 ohm/km 0.420 ohm/mile 0.155 Mohm-km 0.097 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 372.2 sq. mm (734.5 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-090-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Drake
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-007) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 519.7 mm2 9.53 mm 71.3 mm2 28.14 mm 590.6 mm2 183.3 kN 153.8 kN 132 kg/km 1565 kg/km 1432.6 kg/km o 180 C o 1.61E-06 /C 1.83E-05 /oC 112.3 GPa 61.2 GPa

Imperial 1025.6 kcmil 0.375 in. 0.110 in2 1.108 in. 0.916 in2 41.2 kips 34.6 kips 89 lb/kft 1051.8 lb/kft 962.8 lb/kft o 356 F o 8.94E-07 /F 1.02E-05 /oF 16.3 Msi 8.9 Msi

Metric Imperial 0.0536 ohm/km 0.0863 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0554 ohm/km 0.0892 ohm/mile 0.0662 ohm/km 0.1065 ohm/mile 0.0888 ohm/km 0.1428 ohm/mile 1134 @ 100C & 60 Hz 1706 @ 180C & 60 Hz 0.011 m 0.038 ft 0.247 ohm/km 0.398 ohm/mile 0.147 Mohm-km 0.091 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 535 sq. mm (1055.8 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-097-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATASHEET:

ACCCEl Paso
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature GMR (estimated) Inductive Reactance Capacitive Reactance
3

Metric 684.0 mm2 8.76 mm 2 60.3 mm 31.80 mm 2 744.0 mm 168.6 kN 130.2 kN 113 kg/km 2001 kg/km 1888.2 kg/km o 180 C o 1.45E-06 /C o 1.96E-05 /C 116.0 GPa 59.2 GPa

Imperial 1349.9 kcmil 0.345 in. 0.093 in2 1.252 in. 1.153 in2 37.9 kips 29.3 kips 76 lb/kft 1345.0 lb/kft 1269.0 lb/kft o 356 F o 8.06E-07 /F o 1.09E-05 /F 16.8 Msi 8.6 Msi

Metric Imperial 0.0409 ohm/km 0.0659 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0418 ohm/km 0.0672 ohm/mile 0.0500 ohm/km 0.0805 ohm/mile 0.0674 ohm/km 0.1084 ohm/mile 1353 @ 100C & 60 Hz 2038 @ 180C & 60 Hz 0.013 m 0.042 ft 0.239 ohm/km 0.385 ohm/mile 0.141 Mohm-km 0.088 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 704.1 sq. mm (1389.6 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 92.9 W/sq. ft (1000 W/sq. m) sun radiation 4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-126-D

www.ctcglobal.com

Date Produced:

4/30/2013

DATA SHEET:

ACCC-Falcon
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-011) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 1036.3 mm2 10.54 mm 87.3 mm2 39.24 mm 1123.2 mm2 246.4 kN 188.3 kN 164 kg/km 3043 kg/km 2879.6 kg/km o 180 C o 1.61E-06 /C 1.99E-05 /oC 112.3 GPa 58.7 GPa

Imperial 2045.1 kcmil 0.415 in. 0.135 in2 1.545 in. 1.741 in2 55.4 kips 42.3 kips 110 lb/kft 2045.3 lb/kft 1935.3 lb/kft o 356 F o 8.94E-07 /F 1.10E-05 /oF 16.3 Msi 8.5 Msi

Metric Imperial 0.0271 ohm/km 0.0436 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0298 ohm/km 0.0479 ohm/mile 0.0350 ohm/km 0.0563 ohm/mile 0.0459 ohm/km 0.0739 ohm/mile 1719 @ 100C & 60 Hz 2639 @ 180C & 60 Hz 0.016 m 0.052 ft 0.224 ohm/km 0.360 ohm/mile 0.131 Mohm-km 0.081 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1066.8 sq. mm (2105.2 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-131-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Fort Worth
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-007) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 658.9 mm2 9.53 mm 71.3 mm2 31.50 mm 729.9 mm2 190.8 kN 153.8 kN 132 kg/km 1952 kg/km 1819.6 kg/km o 180 C o 1.61E-06 /C 1.91E-05 /oC 112.3 GPa 59.9 GPa

Imperial 1300.4 kcmil 0.375 in. 0.110 in2 1.240 in. 1.131 in2 42.9 kips 34.6 kips 89 lb/kft 1311.9 lb/kft 1222.9 lb/kft o 356 F o 8.94E-07 /F 1.06E-05 /oF 16.3 Msi 8.7 Msi

Metric Imperial 0.0425 ohm/km 0.0684 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0448 ohm/km 0.0721 ohm/mile 0.0533 ohm/km 0.0858 ohm/mile 0.0712 ohm/km 0.1146 ohm/mile 1305 @ 100C & 60 Hz 1975 @ 180C & 60 Hz 0.013 m 0.042 ft 0.240 ohm/km 0.385 ohm/mile 0.141 Mohm-km 0.088 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 678.3 sq. mm (1338.6 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-125-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Galveston
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 512.5 mm2 8.76 mm 60.3 mm2 27.69 mm 572.5 mm2 158.8 kN 130.2 kN 113 kg/km 1525 kg/km 1412.2 kg/km o 180 C o 1.45E-06 /C 1.87E-05 /oC 116.0 GPa 60.7 GPa

Imperial 1011.3 kcmil 0.345 in. 0.093 in2 1.090 in. 0.887 in2 35.7 kips 29.3 kips 76 lb/kft 1025.1 lb/kft 949.1 lb/kft o 356 F o 8.06E-07 /F 1.04E-05 /oF 16.8 Msi 8.8 Msi

Metric Imperial 0.0544 ohm/km 0.0875 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0564 ohm/km 0.0907 ohm/mile 0.0674 ohm/km 0.1084 ohm/mile 0.0905 ohm/km 0.1456 ohm/mile 1119 @ 100C & 60 Hz 1681 @ 180C & 60 Hz 0.011 m 0.037 ft 0.249 ohm/km 0.401 ohm/mile 0.148 Mohm-km 0.092 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 527.5 sq. mm (1041.1 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-121-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Grosbeak
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-006) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 416.2 mm2 8.13 mm 51.9 mm2 25.15 mm 467.8 mm2 135.2 kN 112.0 kN 98 kg/km 1245 kg/km 1147.0 kg/km o 180 C o 1.61E-06 /C 1.87E-05 /oC 112.3 GPa 60.6 GPa

Imperial 821.4 kcmil 0.320 in. 0.080 in2 0.990 in. 0.725 in2 30.4 kips 25.2 kips 66 lb/kft 836.9 lb/kft 770.9 lb/kft o 356 F o 8.94E-07 /F 1.04E-05 /oF 16.3 Msi 8.8 Msi

Metric Imperial 0.0672 ohm/km 0.1081 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0692 ohm/km 0.1114 ohm/mile 0.0829 ohm/km 0.1334 ohm/mile 0.1116 ohm/km 0.1796 ohm/mile 981 @ 100C & 60 Hz 1468 @ 180C & 60 Hz 0.010 m 0.033 ft 0.256 ohm/km 0.412 ohm/mile 0.152 Mohm-km 0.095 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 428.4 sq. mm (845.5 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-092-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Hawk
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-004) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 309.8 mm2 7.11 mm 39.7 mm2 21.79 mm 349.7 mm2 103.2 kN 85.7 kN 76 kg/km 930 kg/km 853.8 kg/km o 180 C o 1.61E-06 /C 1.85E-05 /oC 112.3 GPa 60.9 GPa

Imperial 611.3 kcmil 0.280 in. 0.062 in2 0.858 in. 0.542 in2 23.2 kips 19.3 kips 51 lb/kft 624.8 lb/kft 573.8 lb/kft o 356 F o 8.94E-07 /F 1.03E-05 /oF 16.3 Msi 8.8 Msi

Metric Imperial 0.0900 ohm/km 0.1448 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0923 ohm/km 0.1485 ohm/mile 0.1094 ohm/km 0.1760 ohm/mile 0.1452 ohm/km 0.2338 ohm/mile 823 @ 100C & 60 Hz 1231 @ 180C & 60 Hz 0.009 m 0.029 ft 0.267 ohm/km 0.429 ohm/mile 0.159 Mohm-km 0.099 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 318.9 sq. mm (629.3 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-088-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Houston
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-011) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 976.7 mm2 10.54 mm 87.3 mm2 38.25 mm 1063.7 mm2 243.3 kN 188.3 kN 164 kg/km 2878 kg/km 2714.1 kg/km o 180 C o 1.61E-06 /C 1.97E-05 /oC 112.3 GPa 59.0 GPa

Imperial 1927.4 kcmil 0.415 in. 0.135 in2 1.506 in. 1.649 in2 54.7 kips 42.3 kips 110 lb/kft 1934.1 lb/kft 1824.1 lb/kft o 356 F o 8.94E-07 /F 1.09E-05 /oF 16.3 Msi 8.6 Msi

Metric Imperial 0.0285 ohm/km 0.0459 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0317 ohm/km 0.0510 ohm/mile 0.0370 ohm/km 0.0596 ohm/mile 0.0483 ohm/km 0.0777 ohm/mile 1660 @ 100C & 60 Hz 2554 @ 180C & 60 Hz 0.015 m 0.050 ft 0.225 ohm/km 0.363 ohm/mile 0.132 Mohm-km 0.082 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1005.4 sq. mm (1984.1 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-130-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Irving
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 308.8 mm2 8.76 mm 60.3 mm2 22.40 mm 368.8 mm2 147.7 kN 130.2 kN 113 kg/km 965 kg/km 851.8 kg/km o 180 C o 1.45E-06 /C 1.67E-05 /oC 116.0 GPa 64.3 GPa

Imperial 609.5 kcmil 0.345 in. 0.093 in2 0.882 in. 0.572 in2 33.2 kips 29.3 kips 76 lb/kft 648.5 lb/kft 572.5 lb/kft o 356 F o 8.06E-07 /F 9.28E-06 /oF 16.8 Msi 9.3 Msi

Metric Imperial 0.0903 ohm/km 0.1454 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0926 ohm/km 0.1491 ohm/mile 0.1111 ohm/km 0.1788 ohm/mile 0.1499 ohm/km 0.2412 ohm/mile 820 @ 100C & 60 Hz 1222 @ 180C & 60 Hz 0.009 m 0.030 ft 0.264 ohm/km 0.424 ohm/mile 0.158 Mohm-km 0.098 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 317.9 sq. mm (627.4 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-119-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Lapwing
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-009) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 987.6 mm2 9.78 mm 75.1 mm2 38.20 mm 1062.6 mm2 217.5 kN 162.1 kN 143 kg/km 2887 kg/km 2743.7 kg/km o 180 C o 1.61E-06 /C 2.01E-05 /oC 112.3 GPa 58.3 GPa

Imperial 1948.9 kcmil 0.385 in. 0.116 in2 1.504 in. 1.647 in2 48.9 kips 36.4 kips 96 lb/kft 1940.0 lb/kft 1844.0 lb/kft o 356 F o 8.94E-07 /F 1.12E-05 /oF 16.3 Msi 8.5 Msi

Metric Imperial 0.0285 ohm/km 0.0458 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0315 ohm/km 0.0507 ohm/mile 0.0370 ohm/km 0.0595 ohm/mile 0.0485 ohm/km 0.0780 ohm/mile 1660 @ 100C & 60 Hz 2547 @ 180C & 60 Hz 0.015 m 0.050 ft 0.226 ohm/km 0.363 ohm/mile 0.132 Mohm-km 0.082 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 1016.6 sq. mm (2006.3 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-111-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Laredo
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-004) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 268.5 mm2 7.11 mm 39.7 mm2 20.50 mm 308.5 mm2 101.0 kN 85.7 kN 76 kg/km 816 kg/km 740.1 kg/km o 180 C o 1.61E-06 /C 1.80E-05 /oC 112.3 GPa 61.8 GPa

Imperial 529.8 kcmil 0.280 in. 0.062 in2 0.807 in. 0.478 in2 22.7 kips 19.3 kips 51 lb/kft 548.4 lb/kft 497.4 lb/kft o 356 F o 8.94E-07 /F 9.99E-06 /oF 16.3 Msi 9.0 Msi

Metric Imperial 0.1038 ohm/km 0.1671 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.1064 ohm/km 0.1712 ohm/mile 0.1276 ohm/km 0.2053 ohm/mile 0.1721 ohm/km 0.2769 ohm/mile 747 @ 100C & 60 Hz 1109 @ 180C & 60 Hz 0.008 m 0.027 ft 0.271 ohm/km 0.436 ohm/mile 0.162 Mohm-km 0.101 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 276.4 sq. mm (545.4 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-118-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Linnet
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-003) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 218.1 mm2 5.97 mm 28.0 mm2 18.29 mm 245.9 mm2 72.5 kN 60.4 kN 54 kg/km 655 kg/km 601.3 kg/km o 180 C o 1.61E-06 /C 1.86E-05 /oC 112.3 GPa 60.8 GPa

Imperial 430.5 kcmil 0.235 in. 0.043 in2 0.720 in. 0.381 in2 16.3 kips 13.6 kips 36 lb/kft 440.1 lb/kft 404.1 lb/kft o 356 F o 8.94E-07 /F 1.03E-05 /oF 16.3 Msi 8.8 Msi

Metric Imperial 0.1277 ohm/km 0.2055 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.1307 ohm/km 0.2103 ohm/mile 0.1564 ohm/km 0.2517 ohm/mile 0.2104 ohm/km 0.3386 ohm/mile 654 @ 100C & 60 Hz 968 @ 180C & 60 Hz 0.007 m 0.024 ft 0.280 ohm/km 0.451 ohm/mile 0.167 Mohm-km 0.104 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 224.6 sq. mm (443.1 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-082-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Lubbock
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 458.0 mm2 8.76 mm 60.3 mm2 26.42 mm 518.0 mm2 156.1 kN 130.2 kN 113 kg/km 1375 kg/km 1262.2 kg/km o 180 C o 1.45E-06 /C 1.83E-05 /oC 116.0 GPa 61.4 GPa

Imperial 903.9 kcmil 0.345 in. 0.093 in2 1.040 in. 0.803 in2 35.1 kips 29.3 kips 76 lb/kft 924.3 lb/kft 848.3 lb/kft o 356 F o 8.06E-07 /F 1.02E-05 /oF 16.8 Msi 8.9 Msi

Metric Imperial 0.0608 ohm/km 0.0979 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0628 ohm/km 0.1011 ohm/mile 0.0752 ohm/km 0.1210 ohm/mile 0.1012 ohm/km 0.1628 ohm/mile 1045 @ 100C & 60 Hz 1566 @ 180C & 60 Hz 0.011 m 0.035 ft 0.252 ohm/km 0.406 ohm/mile 0.150 Mohm-km 0.093 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 471.5 sq. mm (930.5 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-120-D

www.ctcglobal.com

Date Produced:

4/24/2012

DATA SHEET:

ACCC-Oriole
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-004) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 222.3 mm2 7.11 mm 39.7 mm2 18.82 mm 262.3 mm2 98.3 kN 85.7 kN 76 kg/km 689 kg/km 613.0 kg/km o 180 C o 1.61E-06 /C 1.72E-05 /oC 112.3 GPa 63.1 GPa

Imperial 438.6 kcmil 0.280 in. 0.062 in2 0.741 in. 0.407 in2 22.1 kips 19.3 kips 51 lb/kft 463.0 lb/kft 412.0 lb/kft o 356 F o 8.94E-07 /F 9.57E-06 /oF 16.3 Msi 9.1 Msi

Metric Imperial 0.1255 ohm/km 0.2019 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.1283 ohm/km 0.2065 ohm/mile 0.1535 ohm/km 0.2471 ohm/mile 0.2065 ohm/km 0.3324 ohm/mile 665 @ 100C & 60 Hz 986 @ 180C & 60 Hz 0.008 m 0.025 ft 0.277 ohm/km 0.446 ohm/mile 0.166 Mohm-km 0.103 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 228.8 sq. mm (451.5 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-086-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Pasadena
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-003) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 154.4 mm2 5.97 mm 28.0 mm2 15.65 mm 182.1 mm2 68.9 kN 60.4 kN 54 kg/km 478 kg/km 424.5 kg/km o 180 C o 1.61E-06 /C 1.72E-05 /oC 112.3 GPa 63.1 GPa

Imperial 304.7 kcmil 0.235 in. 0.043 in2 0.616 in. 0.282 in2 15.5 kips 13.6 kips 36 lb/kft 321.3 lb/kft 285.3 lb/kft o 356 F o 8.94E-07 /F 9.57E-06 /oF 16.3 Msi 9.1 Msi

Metric Imperial 0.1793 ohm/km 0.2885 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.1829 ohm/km 0.2944 ohm/mile 0.2197 ohm/km 0.3535 ohm/mile 0.2968 ohm/km 0.4776 ohm/mile 528 @ 100C & 60 Hz 778 @ 180C & 60 Hz 0.006 m 0.021 ft 0.291 ohm/km 0.468 ohm/mile 0.175 Mohm-km 0.109 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 158.9 sq. mm (313.6 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-116-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Plano
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-008) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 536.9 mm2 8.76 mm 60.3 mm2 28.63 mm 596.8 mm2 160.1 kN 130.2 kN 113 kg/km 1597 kg/km 1484.0 kg/km o 180 C o 1.45E-06 /C 1.89E-05 /oC 116.0 GPa 60.4 GPa

Imperial 1059.5 kcmil 0.345 in. 0.093 in2 1.127 in. 0.925 in2 36.0 kips 29.3 kips 76 lb/kft 1073.4 lb/kft 997.4 lb/kft o 356 F o 8.06E-07 /F 1.05E-05 /oF 16.8 Msi 8.8 Msi

Metric Imperial 0.0522 ohm/km 0.0840 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0544 ohm/km 0.0876 ohm/mile 0.0649 ohm/km 0.1045 ohm/mile 0.0870 ohm/km 0.1400 ohm/mile 1150 @ 100C & 60 Hz 1733 @ 180C & 60 Hz 0.012 m 0.038 ft 0.247 ohm/km 0.397 ohm/mile 0.146 Mohm-km 0.091 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 552.6 sq. mm (1090.6 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-122-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-San Antonio
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-009) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 747.4 mm2 9.78 mm 75.1 mm2 33.40 mm 822.2 mm2 204.2 kN 162.1 kN 143 kg/km 2211 kg/km 2068.6 kg/km o 180 C o 1.61E-06 /C 1.94E-05 /oC 112.3 GPa 59.5 GPa

Imperial 1474.9 kcmil 0.385 in. 0.116 in2 1.315 in. 1.274 in2 45.9 kips 36.4 kips 96 lb/kft 1486.3 lb/kft 1390.3 lb/kft o 356 F o 8.94E-07 /F 1.08E-05 /oF 16.3 Msi 8.6 Msi

Metric Imperial 0.0375 ohm/km 0.0603 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.0387 ohm/km 0.0623 ohm/mile 0.0459 ohm/km 0.0738 ohm/mile 0.0609 ohm/km 0.0980 ohm/mile 1432 @ 100C & 60 Hz 2176 @ 180C & 60 Hz 0.013 m 0.044 ft 0.235 ohm/km 0.379 ohm/mile 0.139 Mohm-km 0.086 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 769.4 sq. mm (1518.3 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-128-D

www.ctcglobal.com

Date Produced:

4/23/2012

DATA SHEET:

ACCC-Waco
NOT RELEASED
For questions, please contact CTC Application Engineering Department: applicationsupport@ctccable.com Governing Units: Imperial Mechanical Specifications Nominal Aluminum Cross-sectional Area* Nominal Diameter of Composite Core (CTC Part Number 200-005) Nominal Cross-sectional Area of Core Overall Diameter of Conductor Nominal Cross-sectional Area of the Conductor Ultimate Tensile Strength of Conductor1,2 Rated Strength of Core - 313 ksi (2158 MPa) Core Nominal Mass per unit length Conductor Nominal Mass per unit length Aluminum Nominal Mass per unit length** Maximum Allowable Operating Temperature at Surface4 Coefficient of Linear Expansion Above Thermal Kneepoint Coefficient of Linear Expansion Below Thermal Kneepoint Final Modulus of Elasticity Above Thermal Kneepoint Final Modulus of Elasticity Below Thermal Kneepoint Electrical Specifications Nominal Resistivity of Aluminum at 20C, DC 63% IACS Temperature Coefficient of Resistance Frequency AC Nominal Resistance at 25C AC Nominal Resistance at 75C AC Nominal Resistance at 180C AC Current Rating at Given Temperature3 GMR (estimated) Inductive Reactance Capacitive Reactance

Metric 230.1 mm2 7.75 mm 47.1 mm2 19.56 mm 277.2 mm2 114.8 kN 101.7 kN 86 kg/km 721 kg/km 634.7 kg/km o 180 C o 1.61E-06 /C 1.67E-05 /oC 112.3 GPa 64.1 GPa

Imperial 454.0 kcmil 0.305 in. 0.073 in2 0.770 in. 0.430 in2 25.8 kips 22.9 kips 58 lb/kft 484.6 lb/kft 426.6 lb/kft o 356 F o 8.94E-07 /F 9.26E-06 /oF 16.3 Msi 9.3 Msi

Metric Imperial 0.1212 ohm/km 0.1951 ohm/mile 0.00404 0.00404 60 Hz 60 Hz 0.1240 ohm/km 0.1996 ohm/mile 0.1488 ohm/km 0.2395 ohm/mile 0.2009 ohm/km 0.3233 ohm/mile 683 @ 100C & 60 Hz 1012 @ 180C & 60 Hz 0.008 m 0.027 ft 0.274 ohm/km 0.440 ohm/mile 0.164 Mohm-km 0.102 Mohm-mile

*ACCC conductor is produced with 1350 O-tempered aluminum. The nominal H-19 Aluminum equivaelnt area is 236.8 sq. mm (467.4 kcmil) **ACCC Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 1) Based on 96% of the annealed aluminum minimum tensile strength given in ASTM B 609 and EN 50540. 2) Strength at ambient temperature 3) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp. 40C Ambient temperature, 96 W/sq. ft (1033 W/sq. m) sun radiation

4) Maximum continuous operating temperature of ACCC is 180C and a maximum emergency temperature of 200C (10,000 hours over the life of the conductor). The information contained herein is offered in good faith. The actual configuration of a given size may vary between conductor manufacturers and may result in slight variations in some of the indicated values.

F-730-117-D

www.ctcglobal.com

Date Produced:

4/23/2012