Direct Stroke Lightning Protection Calculation 400 / 220 / 33kV Indrapuram Substation
0 Rev.
27.11.12 Date
Description
PREPARED BY
Checked By
Approved By
S-3, 2nd Floor, Aditya Mega Mall, Indirapuram, Ghaziabad 201010, 7th floor Tower c Building No. 10 DLF Cyber city phase-II Gurgaon India
Western Uttar Pradesh Power Transmission Corporation Limited Megha Engineering and Infrastructure Limited
PROJECT :
DATE
VIK
27.11.12
DOCUMENT TITLE
SHEET SIZE
A4
As Built
TABLE OF CONTENTS
DESCRIPTION PURPOSE
SHEET NO. 2 2 2 3 4 6
Sheet No. 1 of 6
1.0
PURPOSE: The purpose of this calculation is to determine the height of Lightning Masts for 400/220/33 kV Indrapuram Substation.
2.0
3.0 3.1
SIZING CRITERIA: The height of Lightning Masts depend on the a) b) Height of the equipment to be protected. Area to be protected.
3.2 a) b)
Data for 400KV Switchyard: Height of Lightning mast Height of the livepart to be protected: h hx 40 m 10 m
All the heights has taken from the plinth level. 3.2 a) b) Data for 220KV Switchyard: Height of Lightning mast Height of the livepart to be protected: h hx 40 m 6m
All the heights has taken from the plinth level. 3.2 a) b) Data for 33KV Switchyard: Height of Lightning mast Height of the livepart to be protected: h hx 40 m 4m
All the heights has taken from the plinth level. SHEET NO. 2 OF 6
4.0 A
Formulae Used: Protective radius (rx) : 1 If , hx <= (2/3)h and h > 30m:-
rx = 1.5h 1
h x P 0.8h
rx = 1.5h 1
h x 0.8h
3 4 5
Co-efficient for the Lightning Mast Height Allowable distance between two LMs Allowable diagonal distance between two LMs Where ha= h - hx m
P S D
5.5/
m m m
7 x ha x P m 8 x ha x P m
Midway point protective Height (ho) and Midway Point Protective Distance (bx)
S h0 = h - 7 P
hx bx = 1.5ho 1 - 0.8h o hx bx = 1.5ho 1 - 0.8h o hx bx = 0.75ho 1 - h o
SHEET NO. 3 OF 6
400/220/33 KV Indrapuram Substation Substation Name 5.0 a) Calculation For LM1 Height of the LM Height to be protected
h hx
40 10
m m
Protective radius
rx = 1.5h 1 -
h x P 0.8h
Protective radius
rx = 1.5h 1
h x P 0.8h
Hence protection area of LM1 covers the 400 kV Substation area which have to be protected.
40 6
m m
Protective radius
rx = 1.5h 1 -
h x P 0.8h
Protective radius
rx = 1.5h 1
h x P 0.8h
Hence protection area of LM1 & LM2 covers the 220 kV Substation area which have to be protected.
c)
40 5
m m
Protective radius
rx = 1.5h 1 -
h x P 0.8h
Protective radius
rx = 1.5h 1
h x P 0.8h
Hence protection area of LM4 covers the 33 kV Substation area which have to be protected.
SHEET NO. 5 OF 6
Direct stroke lightning protection Calculations Document Name Table Document No.
S.No.
LM
Height of LM (m)
Protection area
1
2
3 4
40 40 40 40
6 5
42.4125 44.04375
400 kV Switchyard area 220 kV Switchyard area 220 kV Switchyard area 33 kV Switchyard area
Conclusion Hence from the above calculated protection area of LM1,LM2,LM3 and LM4 we can protect the indrapuram switch yard area from the direct lightning.
SHEET NO. 6 OF 6