System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing

System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L Iso 7m E R 1.00E+00 0.00E+00 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

mm mm kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

3.51E-03 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

3.71E+02 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.375 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

9.52E+00 fcright

1.90E-01 rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V 0.672 Vr 1 Vf 0.753

Stress factors for right span V 0.707

Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) =

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL BPI Fcant Hi D

47 m/s 2 1

8000 N 2.3 m 0.2 m

Right Connection ISO 6.5 m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05

m4

N/m2 N/m2

2.61E-03 m

2.45

1.10E+01 Hz 2.21E-01

0 Vright1 = 0.67239 Vright2 = 0 Vright3 =

0 0.707149 0

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

0 0.752694 0 0

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

0 0.791316 0 0

0 0 0 0 0

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

0 0 0 0 0

Stress factors for right span Vr 1 Vf 0.791

5.51E+03

= 5.11E+03 N

0.00E+00 F1_right =

0.00E+00

5.29E+02 Fc_right =

4.91E+02 N

1.03E+03 Fw_right =

9.53E+02 N

0.00E+00 Fw1_right =

0.00E+00 N

6555.02 Fm_right =

6086.804 N

3.97E+07 m_right = YES Rightcheck

3.60E+07 N/m2 YES

1.84E+03 Fd_right

1.80E+03

1.56E+03 Fscf_right = 1.52E+03 (please add also dropper SCF force if value is defined)

FW2 = FW2/2 = Fd_left = Fd_right =

3.71E+02 1.86E+02 1.84E+03 1.80E+03

Fd = FW/2 + Fd_left + Fd_right 3.83E+03 N check2= OK

System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L Iso 6.7 m E R 1.00E+00 0.00E+00 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 N/m2 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

m m kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

2.95E-03 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

1.05E+03 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.375 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

1.04E+01 fcright

2.08E-01 rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V 0.692935 Vr Vf 1 0.775522

Stress factors for right span V 0.64632527

Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) =

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL CB Fcant Hi D

47 m/s 2 1

10000 N 4.2 m 0.31 m

Right Connection ISO 7.4 m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05 kA

m4

N/m2 N/m2

4.39E-03 m

2.45

8.52E+00 Hz 1.70E-01

0 Vright1 = 0.692935 Vright2 = 0 Vright3 =

0 0.646325 0

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

0 0.775522 0 0

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

0 0.723734 0 0

0 0 0 0 0

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

0 0 0 0 0

Stress factors for right span Vr 1 Vf 0.7237338

5.27E+03

= 5.82E+03 N

0.00E+00 F1_right =

0.00E+00

5.06E+02 Fc_right =

5.59E+02 N

9.82E+02 Fw_right =

1.09E+03 N

0.00E+00 Fw1_right =

0.00E+00 N

6274.09 Fm_right =

6929.592 N

3.75E+07 m_right = YES Rightcheck

4.27E+07 N/m2 YES

1.82E+03 Fd_right

1.87E+03

1.53E+03 Fscf_right = 1.58E+03 (please add also dropper SCF force if value is defined)

1.56E+02

FW2 = FW2/2 = Fd_left = Fd_right =

1.05E+03 5.26E+02 1.82E+03 1.87E+03

Fd = FW/2 + Fd_left + Fd_right 4.22E+03 N check2= OK

System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L BPI 1.85 m E R 1.00E+00 0.00E+00 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 N/m2 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

m m kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

1.71E-05 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

6.50E+02 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.375 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

1.36E+02 fcright

2.73E+00 rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V 1 Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) Vr Vf 1 1.840196

Stress factors for right span V 1

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL CB Fcant Hi D

47 m/s 2 1

3434 N 3.5 m 0.23 m

Right Connection ISO 1.98 m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05 kA

m4

N/m2 N/m2

2.25E-05 m

2.45

1.19E+02 Hz 2.38E+00

0 Vright1 = 0 Vright2 = 1 Vright3 =

0 0 1

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

0 0 0 0

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

0 0 0 0

0 1.840196 0 0 0

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

2.7 0 0 0 0

Stress factors for right span Vr 1 Vf 2.7

1.46E+03

= 1.56E+03 N

0.00E+00 F1_right =

0.00E+00

1.40E+02 Fc_right =

1.50E+02 N

2.71E+02 Fw_right =

2.90E+02 N

0.00E+00 Fw1_right =

0.00E+00 N

1732.398 Fm_right =

1854.134 N

4.13E+06 m_right = YES Rightcheck

4.73E+06 N/m2 YES

1.19E+03 Fd_right

1.87E+03

1.00E+03 Fscf_right = 1.58E+03 (please add also dropper SCF force if value is defined)

1.02E+02

FW2 = FW2/2 = Fd_left = Fd_right =

6.50E+02 3.25E+02 1.19E+03 1.87E+03

Fd = FW/2 + Fd_left + Fd_right 3.39E+03 N check2= OK

System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L NA 0m E R 1.00E+00 1.11E+01 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 N/m2 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

m m kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

0.00E+00 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

8.11E+02 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.375 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

#DIV/0! #DIV/0!

fcright

rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V #DIV/0! Vr 1 Vf #DIV/0!

Stress factors for right span V #DIV/0!

Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) =

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL LA Fcant Hi D

47 m/s 2 1

3434 N 2.87 m 0.35 m

Right Connection NA 0m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05 kA

m4

N/m2 N/m2

0.00E+00 m

2.45

#DIV/0! Hz #DIV/0!

#DIV/0! Vright1 = #DIV/0! Vright2 = #DIV/0! Vright3 =

#DIV/0! #DIV/0! #DIV/0!

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

#DIV/0! #DIV/0! #DIV/0! #DIV/0!

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

#DIV/0! #DIV/0! #DIV/0! #DIV/0!

#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

Stress factors for right span Vr 1 Vf #DIV/0!

0.00E+00

= 0.00E+00 N

1.04E+03 F1_right =

0.00E+00

0.00E+00 Fc_right =

0.00E+00 N

0.00E+00 Fw_right =

0.00E+00 N

4.99E+02 Fw1_right =

0.00E+00 N

1.54E+03 Fm_right =

0.00E+00 N

#DIV/0! m_right = #DIV/0! Rightcheck

#DIV/0! N/m2 #DIV/0!

1.54E+03 Fd_right

0.00E+00

1.04E+03 Fscf_right = #DIV/0! (please add also dropper SCF force if value is defined)

1.06E+02

FW2 = FW2/2 = Fd_left = Fd_right =

8.11E+02 4.06E+02 1.54E+03 0.00E+00

Fd = FW/2 + Fd_left + Fd_right 1.94E+03 N check2= OK

System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L CB 7.4 m R E 1.00E+00 0.00E+00 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 N/m2 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

m m kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

4.39E-03 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

7.24E+02 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.625 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

8.52E+00 fcright

1.70E-01 rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V 0.646325 Vr Vf 1 0.723734

Stress factors for right span V 0.52915403

Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) =

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL CB Fcant Hi D

47 m/s 2 1

10000 N 2.56 m 0.35 m

Right Connection ISO 9.5 m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05 kA

m4

N/m2 N/m2

1.19E-02 m

2.45

5.17E+00 Hz 1.03E-01

0 Vright1 = 0.646325 Vright2 = 0 Vright3 =

0 0.529154 0

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

0 0.723734 0 0

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

0 0.593544 0 0

0 0 0 0 0

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

0 0 0 0 0

Stress factors for right span Vr 1 Vf 0.5935435

5.82E+03

= 7.47E+03 N

0.00E+00 F1_right =

0.00E+00

5.59E+02 Fc_right =

7.18E+02 N

1.09E+03 Fw_right =

1.39E+03 N

0.00E+00 Fw1_right =

0.00E+00 N

6929.592 Fm_right =

8896.098 N

4.27E+07 m_right = YES Rightcheck

5.76E+07 N/m2 YES

3.12E+03 Fd_right

1.97E+03

2.63E+03 Fscf_right = 1.66E+03 (please add also dropper SCF force if value is defined)

2.69E+02

FW2 = FW2/2 = Fd_left = Fd_right =

7.24E+02 3.62E+02 3.12E+03 1.97E+03

Fd = FW/2 + Fd_left + Fd_right 5.46E+03 N check2= OK

System Parameters System Voltage System Frequency Symmetrical Short Circuit Fault Current Three Phase automatic reclosing System x/r ratio Phase to Phase Spacing Size of Rigid Bus Dropper Conductor type Height of equipment bus above ground Equipment connection details Connected Equipment Span Lenth Connection on main equipment Connection on other end equip. No. of spans Dropper Lenth No. of subconductor in Dropper (Ns)

f Ik "FALSE" x/r am

2.20E+02 kV 5.00E+01 Hz 5.00E+04 A 3.00E+01 4.00E+00 m 4.00E+00 inch "ACSR BER" 5.90E+00 m

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Heqpt

Left Connection L NA 0m R E 1.00E+00 1.11E+01 1.00E+00

Right Connection

(l)

Calculation Constants Stress corresponding to the Yield point Gravitational Constant Young's Modulus of Elasticity for Tube (E) Rigid Bus Parameters Outer Diameter of tube Inner Diameter of tube Mass per unit lenth Wall thickness of the tube Wind force constants Factor for ref. wind speed (Ko) Risk Co-eff (K1) Terrain roughness co-eff Drag Co-eff (Cond.) Drag Co-eff (Insu.) Gust response factor for conductor Gust response factor for Insulator

Rp0.2 g E

1.70E+08 n/m2 9.81E+00 m/s2 6.89E+10 N/m2 Dropper Parameters Conductor diameter

Do Di M Sthk

1.14E-01 9.69E-02 7.70E+00 1.00E-02

m m kg/m m

Ko Ki K2 Cdc Cdi Gc Gi

1.38E+00 1.00E+00 1.00E+00 1.00E+00 1.20E+00 1.83E+00 1.92E+00

Calculation of Peak value of SC Current -1.00E-01

1.91E+00 Calculation of rigid bus parameters

Ip

Moment of inertia of Tube (j)

4.05E-06

Section modulus of tube(z)

7.09E-05 m3

Permissible stress in rigid Bus(.max) for normal conditions for SC conditions Factor for plasticity(q) = 1.39E+00 = = 1.70E+08 2.36E+08

Actual Deflection Left Deflection Right Deflection

0.00E+00 m

Calculation of design wind pressure(Pd) Design wind pressure (Pd) Design wind speed Vd = K1.K2.Vr = 3.42E+01 N/m2 = 3.42E+01 m/s 7.01E+02 N/m2

Vr = Vb/Ko =

Calculation of wind load on equipment housing (Fw2)

= Determination of load factors , , & based on support types

6.41E+02 N

These factors take into consideration the effect of type of busbar support on equipment in transmitting the dynamic forces onto supports.

Load factors for left span 0.625 Determination of natural frequency Left span fcleft Ratio of natural frequency & system frequency leftratio 0.73 2.45

Load factors for right span 0.375 0.73

Right span

= =

#DIV/0! #DIV/0!

fcright

rightratio =

Calculation of stress factors V , Vr & Vf in the rigid conductors

Vleft1 = Vleft2 = Vleft3 =

Vrleft1 = Vrleft2 = Vrleft3 =

Vfleft1 = Vfleft2 = Vfleft3 = Vfleft4 =

Vfleft5 = Vfleft6 = Vfleft7 = Vfleft8 = Vfleft9 =

Stress factors for left span V #DIV/0! Vr 1 Vf #DIV/0!

Stress factors for right span V #DIV/0!

Calculation of SCF & Total deflection force SCF between rigid bus (Fm3) =

SCF between droppers F1_left =

Gravitational load of rigid bus conductor (Fc)

Fc=m.g.l Wind load on rigid bus (Fw) Fw = Pd.Gc.Cdc.Do.L Wind load on droppers (Fw1) Fw1 = Pd.Gc.Cdc.Do.L.ns Total Effective force (Fm) Vector = sum of forces due to SCF, Wind & Dead Load. Total Force Calculation of stresses in rigid conductor (m)

Fc_left =

Fw_left =

Fw1_left =

Fm_left =

m_left = IN Limit (m < max) Calculation of deflection forces on equipment top due to LEFT/RIGHT connection Leftcheck

Fd = Vf.Vr..Fl

Fd_left

FSCF = Vf.Vr..(Fscf-tube + Fscf-dropper)

Fscf_left = (please add also dropper SCF force if v

Cantilever strength analysis for equipment supports Wind force on equipment insulator acting on insulator midpoint Fw" Equivalent wind force on equipment top Deflection force due to left connection Deflection force due to right connection Total deflection force on top Fw"/2 Fd(left) Fd(right) Fd = FW/2 + Fd_left + Fd_right Fd = Acceptance Fd < Fcant

Topographical Inputs Basic wind speed Terrain category Reliability Level Equipment under analysis Equipment Description Cantilever strenth Equipment Height Equipment Diameter

Vb Ter RL LA Fcant Hi D

47 m/s 2 1

10000 N 2.94 m 0.27 m

Right Connection NA 0m E R 1 0 1

Dropper Parameters Conductor diameter Uo = 1.256E-06

Dc

0.03504 m

1.35E+05 kA

m4

N/m2 N/m2

0.00E+00 m

2.45

#DIV/0! Hz #DIV/0!

#DIV/0! Vright1 = #DIV/0! Vright2 = #DIV/0! Vright3 =

#DIV/0! #DIV/0! #DIV/0!

1 Vrright1 = 1 Vrright2 = 1 Vrright3 =

1 1 1

#DIV/0! #DIV/0! #DIV/0! #DIV/0!

Vfright1 = Vfright2 = Vfright3 = Vfright4 =

#DIV/0! #DIV/0! #DIV/0! #DIV/0!

#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

Vfright5 = Vfright6 = Vfright7 = Vfright8 = Vfright9 =

#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

Stress factors for right span Vr 1 Vf #DIV/0!

0.00E+00

= 0.00E+00 N

1.04E+03 F1_right =

0.00E+00

0.00E+00 Fc_right =

0.00E+00 N

0.00E+00 Fw_right =

0.00E+00 N

4.99E+02 Fw1_right =

0.00E+00 N

1.54E+03 Fm_right =

0N

#DIV/0! m_right = #DIV/0! Rightcheck

#DIV/0! N/m2 #DIV/0!

1.54E+03 Fd_right

#DIV/0!

1.04E+03 Fscf_right = #DIV/0! (please add also dropper SCF force if value is defined)

1.06E+02

FW2 = FW2/2 = Fd_left = Fd_right =

6.41E+02 3.21E+02 1.54E+03 #DIV/0!

Fd = FW/2 + Fd_left + Fd_right 1.86E+03 N check2= OK

Varriables Value(Alstom) lc 3.8 ns 1 Fst 843.5419 F' 93.61594 Mc' 2.384368 r 2.001752 1 63.45501 Fes 0.1 T 0.567381 Tres 0.410754 Eeff 1.94E+10 N 2.67E-06 8.22E-01 Tk1 0.226952 end 126.91 -1.00175 m 180 x== 3.712906 Ftd1 2271.73

ela th
Cd Cf fed Ftd2 Ftd Ftdkg Ffd Ffdkg bh v1 v2 V3 Fv

0.003809 3.3E-05 1.755157 1.15 0.201843 180 2271.73 2271.73 231.6437 2786.15 284.0981 0.180566 0.201843 1.643041 2.702 0.292 11575.99 0.456471 36.4265 5.00101 3.166 6.134703 1.098 7267.554 1 Ve1 calculation 2.476833 1.187069 0.479269 37.1111 19.32491 19.07491 4.367483 0.520731

st pi
j V41 Ve1 Fpi.d1

V42 Ve2 Fpi.d2 Fpi.d Fpi.d.kg

6.134703 4.864 9832.03 9832.03 741.5871

4.867483

E S L As Cth Ik Uo Ls as ds Li Dg Ls Fst.kg mc ms nc Tk1 .4T Tk1/Tres aph amin md

6.20E+10 100000 3.8 0.000724 2.196 0.456 2.7E-19 50000 1.26E-06 2.5 0.25 0.03504 0 0 2.5 end 86.0757 21 2.187 (1-r) 1.5 2 1 0.226952 0.552526 4 3.388869 0

1.570796 1

123.5216 126.91 -1.00175

Ve2 Calculation 2.476833 1.187069 0.479269 0.520731 19.32491

19.07491 4.367483 4.867483

Varriables Value(Alstom) lc 3.8 ns 1 Fst 843.5419 F' 93.61594 Mc' 2.384368 r 2.001752 1 63.45501 Fes 0.1 T 0.567381 Tres 0.410754 Eeff 1.94E+10 N 2.67E-06 8.22E-01 Tk1 0.226952 end 126.91 -1.00175 m 180 x== 3.712906 Ftd1 2271.73

ela th
Cd Cf fed Ftd2 Ftd Ftdkg Ffd Ffdkg bh v1 v2 V3 Fv

0.003809 3.3E-05 1.755157 1.15 0.201843 180 2271.73 2271.73 231.6437 2786.15 284.0981 0.180566 0.201843 1.643041 2.702 0.292 11575.99 0.456471 36.4265 5.00101 3.166 6.134703 1.098 7267.554 1 Ve1 calculation 2.476833 1.187069 0.479269 37.1111 19.32491 19.07491 4.367483 0.520731

st pi
j V41 Ve1 Fpi.d1

V42 Ve2 Fpi.d2 Fpi.d Fpi.d.kg

6.134703 4.864 9832.03 9832.03 741.5871

4.867483

E S L As Cth Ik Uo Ls as ds Li Dg Ls Fst.kg mc ms nc Tk1 .4T Tk1/Tres aph amin md

6.20E+10 100000 3.8 0.000724 2.196 0.456 2.7E-19 50000 1.26E-06 2.5 0.25 0.03504 0 0 2.5 end 86.0757 21 2.187 (1-r) 1.5 2 1 0.226952 0.552526 4 3.388869 0

1.570796 1

123.5216 126.91 -1.00175

Ve2 Calculation 2.476833 1.187069 0.479269 0.520731 19.32491

19.07491 4.367483 4.867483