You are on page 1of 22

LIST OF ELECTRICAL STANDARD SPECIFICATIONS 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Codes for electrical equipment Preparation of electrical documents Incoming substations Departmental substations

Medium voltage distribution boards Power transformers Power control centres, motor control centres Large motors Small motors Starters Variable speed drives Erection, cabling, earthing connections, lightning protection Production and distribution of auxiliary voltages Electrical cabinets and marshalling cabinets Instrumentation Process Control System : equipment and configuration Process Control System: application software and integration Lighting and power outlets Electrical devices for to mechanical equipment Earthing grid Process Control System : basic functional objects Visible Cut-off Switches Incoming transformers

Key codes : Substation, Electrical room, Switchroom, Power, Technical floor, Pressurisation, Air-conditioning, Lighting, Fire detection, Earthing, Cabling. F E D C

B A 0
Rev

18/10/05 28/05/03 19/09/02


Date

General revision Approval by CTEC Document edition


Scope of revision

S. DECANTER R. STRAUB R. STRAUB


Issued

M. MAHAUX M. MAHAUX M. MAHAUX


Approved CTI

R. MEINHARDT
R. MEINHARDT
Approved CTEC

LAFARGE CENTRE TECHNIQUE INTER-UNITES LIsle dAbeau Parc de Chesnes B.P. 70 F-38291 ST QUENTIN-FALLAVIER Cedex Phone : + 33 474 82 16 16 / Fax + 33 474 94 30 07 ASIA TECHNICAL CENTRE Level 3,Wisma Lafarge N 2 Jalan Kilang 46050 PETALING JAYA SELANGOR DARUL EHSAN MY-MALAYSIA Phone : + 603 77874800 / Fax : + 603 77874890 Reproduction & usage strictly forbidden without Lafarge th explicite agreement (Law March 11 , 1957)

LAFARGE CENTRE TECHNIQUE EUROPE CENTRALE Gumpendorfer Strasse 19-21, A-1060 WIEN, Postfach 264 Phone : + 43 1 811 42 0 / + 43 1 811 42 44 09

ELECTRICAL STANDARD SPECIFICATION

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

1/22

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

2/22

CONTENT

1.

GENERAL POINTS ......................................................................................................................4


1.1. 1.2. 1.3. 1.4.

1.5. 2.

APPLICABILITY.....................................................................................................................4 ASSOCIATED SPECIFICATIONS .........................................................................................4 APPLICABLE STANDARDS ..................................................................................................4 LOCAL CONDITIONS............................................................................................................4 GLOSSARY...........................................................................................................................4

CIVIL WORKS..............................................................................................................................6 GENERAL DESIGN...............................................................................................................6 2.2. FINISHING ASPECTS AND PAINTING .................................................................................6 2.3. DOORS .................................................................................................................................7 2.3.1. Common requirements ...................................................................................................7 2.3.2. Electrical rooms, staff access door..................................................................................7 2.3.3. Electrical rooms, door for emergency exit and equipment bringing in..............................7 2.3.4. Transformer rooms, staff access and equipment bringing in doors .................................8
2.1.

3. 4.

TECHNICAL FLOOR....................................................................................................................8 AIR-CONDITIONING AND PRESSURISATION ...........................................................................9 4.1. 4.2. 4.3. AIR-CONDITIONING .............................................................................................................9 PRESSURISATION .............................................................................................................10 POWER SUPPLY ................................................................................................................10 LIGHTING............................................................................................................................11 FIRE DETECTION...............................................................................................................11 CONTROL AND SAFETY DEVICES ...................................................................................12 EARTHING ..........................................................................................................................12 CABLING.............................................................................................................................12 SAFETY EQUIPMENT.........................................................................................................12

5.

LIGHTING AND FIRE DETECTION............................................................................................11 5.1.


5.2.

6.

GENERAL ELECTRICAL CONTRACTOR.................................................................................12


6.1.

6.2. 6.3.
6.4.

7. 8. 9.

DOCUMENTS.............................................................................................................................13 GUARANTEE .............................................................................................................................13 DATA SHEET.............................................................................................................................13

10. TYPICAL DRAWINGS................................................................................................................15

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

3/22

1. GENERAL POINTS
1.1. APPLICABILITY
This specification is applicable to any departmental substation, i.e. any electrical room feeding and controlling a plant department. It is also applicable to the incoming substation feeding the departmental substations with some additional requirements mentioned in specification STD.002.U03.

1.2. ASSOCIATED SPECIFICATIONS


STD.002.U01: STD.002.U02: STD.002.U12: STD.002.U13: STD.002.U18 : STD.2.99.0.V98: Codes for Electrical Equipment Preparation of Electrical Documents Erection, cabling, earthing connections, lightning protection Production and distribution of auxiliary voltages Lighting and Power Outlets. Paintwork

1.3. APPLICABLE STANDARDS


Unless otherwise mentioned in the Site Specification, IEC standards shall be implemented for manufacturing and installing equipment and systems, and in particular: IEC 60903: Personal Protective Equipment.

1.4. LOCAL CONDITIONS


Local conditions are described in the site specification. Anyway, surrounding temperature considered in equipment dimensioning shall not be less than 40 C, with a daily average not less than 35 C, as required by IEC standards. The attention of the Supplier is drawn on the fact that a cement plant is a very dusty environment.

1.5. GLOSSARY
ACC CCR Department Auxiliary Control Centre. Central Control Room. Functionally linked sub-process stage for a given process stage and a given line (please refer to specification STD.002.U01, section 1.1). Examples are : Raw Mill 2, Kiln 1, Cement Mill C, Emergency Shut-Down of a given department initiated by pressing an emergency shut-down push button installed in this department or in the CCR. It initiates a quick shut-down of each sequence and trips the contactors and MV circuit breakers of all users of the department.

DESD

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

4/22

Electrical room

Room of a substation where electrical switchgear and electrical equipment are installed to be kept in clean and cool ambiance ; also called Switchroom. Motor Control Centre. ( LV switchboard controlling motors and 3-phase users ) Medium voltage (above 1000 V and not exceeding 36 kV) Medium voltage emergency shut-down (tripping the departmental MV switchboard) Power Control Centre. ( LV distribution switchboard feeding MCCs or other 3-phase users ) The Site Specification is a technical specification complementing the Electrical Standard Specifications and describing, for a given site, its particulars such as : Local conditions (climate, altitude, earthquakes, ) Voltages and frequency of power and control circuits Local regulations Technical requirements specific to the site Approved deviations from the Electrical Standard Specifications if required.

MCC

MV MVESD

PCC

Site Specification

Substation

Place where electrical equipment are concentrated, installed in electrical room(s)/switchroom(s) and transformer room(s). Room of a substation where electrical switchgear and electrical equipment are installed to be kept in clean and cool ambience ; also called Electrical Room . Room of a substation where power transformers are installed. Uninterruptible Power System. Variable Speed Drive.

Switchroom

Transformer room UPS VSD

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

5/22

2. CIVIL WORKS
B

2.1. GENERAL DESIGN


Generally speaking, departmental substations shall be designed in accordance with typical drawings included in section 10. When local conditions are suitable (not frequently flooded area), basic solution (drawing 2) will be preferred. If the site is subject to flooding alternative solution (drawing 3) will be chosen. Then the stairs shall be completed with adequate handrails. The electrical equipment shall be installed preferably along the walls, keeping 100 to 200 mm space for ventilation. For each modular switchboard (MV switchboard, MCC, marshalling boards, ), spare room shall be kept for future installation of at least one additional module. In particularly, civil works design: shall include reservations for the installation of a technical floor covering the whole Electrical Room (access airlock excluded). A free space of 3000 mm minimum shall be kept between this technical floor and the beams supporting the ceiling or the insulated ceiling. shall include cable trenches and reservations of any kind for cable routings (including embedded conduits and cable galleries). shall include supply and installation of transformers supporting rails and of frames for retaining leaking oil. shall include supplies and services listed in sections 2.2 and 2.3. shall include reservations for the installation, by others, of air-conditioning and pressurisation equipment detailed in section 4. Electrical rooms of different departments shall be segregated by fire resisting walls / floors and by 2 hours fire resisting doors. To avoid dust ingress electrical rooms shall not be equipped with windows nor with glass doors (that could be broken). Each oil-immersed transformer shall be segregated from other oil-immersed transformers by a fire-resisting wall, or better be installed in a separate room. Shall also be installed in the transformer room(s) equipment dissipating huge heat quantities (braking resistors, ...) or which are too large and not dust critical (fixed capacitor power factor correction banks, ...).

2.2. FINISHING ASPECTS AND PAINTING


The Supplier shall:
B

Install a thermal insulation under the ceiling of the whole substation if this ceiling is just under a roof. In the electrical room this insulation shall be covered with panels made of a soundabsorbing material.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

6/22

Materials used shall be non flammable and shall be certified by the National Fire Protection Association ( NFPA ). Fill in any hole or space through which the dust could penetrate, in order to make the pressurisation system efficient. Paint all the substation internal walls with a semi-glossy paint of light shade. Paint the concrete slab of the transformers room and of the airlock with a glossy paint of similar shade specially designed for concrete surfaces.

2.3. DOORS 2.3.1. Common requirements


Doors shall be made of steel painted according to specification STD.2.99.0.V.98 or of anodized aluminium. Their design and installation shall meet the principles developed in typical drawings of section 10. A common key (pass key) shall make people able to open any door of any substation on the site (Master Key system). Locks shall be of dust resisting type. Alternatively, mechanical locks can be replaced by electrical locks controlled by a common access badge. If this solution is chosen the Supplier shall also supply a workstation for controlling this access system and equipment necessary for making personal access badges.

2.3.2. Electrical rooms, staff access door


Staff will access the electrical room (clean area) through an airlock in order to limit dust ingress. This airlock will be, if possible, oriented towards the main building for facilitating staff circulation. Both airlock doors will be of local standard size, but not less than 2.10 m high and 0.90 m broad. These doors shall open towards outside and shall be equipped with antipanic bars at inside. They shall be equipped with seals to prevent dust ingress and with automatic door closers. The outside door frame shall border the door on its 4 sides, including a bottom section that will keep between the ground and the door a free space of 30 mm minimum to avoid that small stones could block the door. This outside door shall be equipped with a lock. A mat or a grate shall be inserted into the airlock slab, in order to keep the electrical room clean.

2.3.3. Electrical rooms, door for emergency exit and equipment bringing in
Except in small electrical rooms, a second door shall be installed at the other end of this area to facilitate staff evacuation in case of hazard, and also for bringing in the equipment.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

7/22

This door shall be identical to the inside door of the airlock here above mentioned but, in order to bring in the equipment easily, it shall be surrounded with metallic panels fixed by bolts or by locks. The passage shall be 2.80 m high and 1.20 m broad when panels are removed. This door shall not be equipped at outdoors side with any handle or lock entry so that entering in this area will be by the airlock only (but at indoors side with a panic bar). This door being a single barrier to dust ingress (the airlock is a double barrier), it shall be really dust tight. As it will be used in case of urgency only, thin silicon seals can be used, easy to be broken in case of emergency. The door frame shall border the door on its 4 sides, including a bottom section that will keep between the ground and the door a free space of 30 mm minimum to avoid that a small stone could block the door. For small electrical rooms, staff entry and equipment bringing in will be by the same access; this single access will be an airlock with both doors surrounded with metallic panels as explained here above.

Note :

2.3.4. Transformer rooms, staff access and equipment bringing in doors


The transformer rooms shall be equipped with staff access doors identical to these ones described here above. These doors shall be surrounded with metallic panels removable to bring in equipment. Dimensions of these panels will depend upon equipment dimensions but when panels are removed the passage shall not be less than 2.80 m high and 1.20 m broad. These doors shall be equipped with louvres for circulation of cooling air. In principle, access to medium voltage and low voltage bushings of each transformer is interlocked with the position of the MV cubicle earthing isolator and with the position of the LV circuit breaker. If such interlock does not exist, the transformer room shall be equipped with a door locked when the MV earthing isolator is not closed or the LV circuit breaker not open.

Note :

3. TECHNICAL FLOOR
A technical floor shall cover all the electrical room. It shall be designed for an even load of 1500 daN/sqm (15 kN/sqm) and a local load of 300 daN/sqm (3 kN/sqm) on a 25 mm by 25 mm area. It shall be made of modular panels (600 mm x 600 mm). Each panel shall be made of: a high density clipboard panel, at least 30 mm thick; a high pressure laminated surface; a PVC edge, or better aluminium, crimped around panel sides.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

8/22

Panels shall be non flammable and shall be certified by the National Fire Protection Association (NFPA) or at least comply with ASTM standards. Panels shall be supported on a steel structure made of adjustable jacks and mobile supporting steel sections. Each steel item shall be protected from rust by hot dip galvanisation. Jacks shall be fixed to the base ground by bolts or glue. Their length shall be so that technical floor finish surface be at not less than 600 mm above supporting concrete slab. When necessary, additional steel sections shall be installed for reinforcing panels placed in cantilever, in order to keep resistance to here above mentioned loads. Technical floor installation is explained in section 10, drawing 5. A suction disc for lifting technical floor panels shall also be supplied in each electrical room as specified in section 6.4. For a revamping, if it is not possible to install a technical floor, the electrical rooms ground shall be covered with a plastic material (tiles or bands) limiting dust emissions and reducing electrical shock hazards by insulating operators from the ground, or at least with insulating mats on front and back of each cabinet.

Note : B

4. AIR-CONDITIONING AND PRESSURISATION


B

4.1. AIR-CONDITIONING
Air-conditioning system for the electrical rooms shall be reliable and simple. Priority shall be given to reliability rather than to performance. In countries with a hot climate (when average day/night temperature exceeds 35 C during more than 7 days a year) double air-conditioners shall be used, one unit only being able to keep internal temperature under here after mentioned maximum temperature. Air-conditioning units will use water cooled condensers or be of the "split system" type with an air cooled condenser installed outdoors. Electrical equipment shall be protected IP55. Air-conditioning system shall be dimensioned to keep into the Electrical Room a temperature lower than or equal to 28 C . This requirement is for limiting the temperature inside the cabinets so that this average temperature over a period of 24 h does not exceed +35 C as required by standard IEC 60947-1. The air-conditioning power installed shall not be less than 100 W/m3 of room volume; it shall be sufficient to evacuate: the heat dissipated in the room, the heat flowing through the walls, ceiling, floor of the room, the heat of the air injected in the room by the pressurisation system.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04

9/22

If batteries of lead-acid type are installed in the electrical room the ambient temperature of this room shall be limited to 20 C . Indeed, a temperature of 28 C would reduce consid erably its lifetime: raising the temperature from 20 C to 30 C divides by 2 the lifetime of a lead-acid battery. An alternative solution could be to install the battery in a separate room kept at 20 C maximum as it is common in incoming substations for feeding the HV switchgear control circuits. A heating system shall also be installed, if necessary, to keep the temperature above 15 C. Cool air shall be distributed from upside. Back air shall flow under the technical floor, passing through this floor by louvres to be installed at the opposite corner of the room to the airconditioning unit. The Supplier will decide whether air distribution ducts should be installed for cool air. Please also refer to section 10, drawing 6.

4.2. PRESSURISATION
Pressurisation of the electrical rooms is to avoid or limit dust ingress. This system shall be capable of keeping into the room a 20 mm water column (200 Pa) overpressure with a minimum air flow equal to 2 times the room volume each hour. This capability will be demonstrated by submitting to the Owners approval appropriate technical data (fan curve) about proposed equipment. Pressurisation equipment shall be mounted through the wall with an access for maintenance from the outside. It shall include: a static filter with an easy access for maintenance, generously dimensioned to avoid maintenance intervals shorter than three months. This filter shall stop any sedimentable dust particle (size above 10m) and be of class EU4 (90 % weight efficiency). Self cleaning filters shall be proposed by the Supplier as an option; a low noise fan running at 1500 RPM at the maximum with a motor protected IP55; a fresh air inlet duct in the electrical room. The pressurisation system shall automatically be switched off in case of fire (please refer to section 5.2). Please also refer to section 10, drawing 7.

4.3. POWER SUPPLY


Air-conditioning and pressurisation systems shall be fed from a single feeder from a lighting distribution board ; please refer to specification STD.002.U18 : Lighting and Power Outlets. The electrical cabinet protecting and controlling power supply to air conditioning and pressurisation equipment is included in this Supply.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 10/22

5. LIGHTING AND FIRE DETECTION


5.1. LIGHTING
Technical specification: substation lighting shall meet the clauses of specification STD.002.U18. Electrical Rooms shall be illuminated with fluorescent lamps (except for very high ceiling substations where it will be better to use high pressure sodium lamps). All these lighting fittings shall be controlled by a switch installed in the area access airlock. Emergency lighting blocks shall be installed inside this area above each access door and in the airlock. In large rooms, some additional emergency lighting blocks shall also be installed throughout the room to facilitate the exit. Transformer Rooms shall be illuminated with watertight fluorescent lamp fittings. These lighting fittings shall be controlled by switches installed close to each access door. Power outlets: at least two single-phase power outlets shall be installed in each electrical room and one in each transformer room.

5.2. FIRE DETECTION


B

Automatic fire detectors: ionisation fire detectors shall be installed: in the electrical rooms above technical floor; in the electrical rooms under technical floor, protected by a wiremesh cover; in the transformer rooms above transformers. The numbers of detectors shall be adapted to volumes to be monitored.

Non automatic fire detectors: 1 push button protected by a breaking glass (IP65) shall be installed close to the access doors to the transformer rooms. Annunciators: 1 red lamp flashing lamp (IP 65) and 1 amovible signal, 100dB at 1m Monitoring: all the detectors of each substation shall be connected to a common monitoring panel installed in the Central Control Room. Each substation will be a separate monitoring area on this panel. Integration in an existing fire detection system: if the plant is already equipped with a general fire detection system the present supply shall be integrated into the existing system and fires annunciated on the existing general fire monitoring panel in the CCR. The fire detection system shall automatically switch off the pressurisation fan in case of fire (please refer to section 4.2). Test: each detector shall be tested regularly in accordance with standards applicable on the site. Equipment required for performing periodic tests is included into the Supply.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 11/22

6. GENERAL ELECTRICAL CONTRACTOR


B

6.1. CONTROL AND SAFETY DEVICES


In addition to Supplies and Services related to the process described in other specifications, the General Electrical Contactor shall supply and install: 3 MV emergency Shut-Down push buttons (MVESD). These push buttons, of large size red mushroom type, shall be installed: 2 inside the electrical room, close to each door (access door and emergency exit door), 1 outdoors, close to the access doors to transformer rooms. Each of these push buttons shall trip the incomer of the MV switchboard installed in the electrical room, cause a Department Emergency Shut-Down (DESD) and be signalled in the CCR by an alarm message. The detail of these emergency shut-down circuits is given in specification STD.002.U13. A temperature switch initiating an alarm message in the Central Control Room informing the operator that the temperature in the electrical room is abnormally high. An alarm message in the Central Control Room informing the operator that the pressurisation fan is off (Warning alarm).

6.2. EARTHING
As required by specification STD.002.U12, the General Electrical Supplier has to earth the metallic structure supporting the technical floor. This shall be performed by connecting each third supporting jack to an insulated 16 sqmm copper cable. This cable shall in turn be connected at both ends to the plant earthing grid or to the main earthing conductor in 2 different points.

6.3. CABLING
Cables shall be installed in accordance with specification STD.002.U12 as well as with principles given in section 10 drawing 4. At the end of cabling any access into the departmental substation shall be filled in with fire resisting material as required by specification STD.002.U12. It is reminded that no cable should be installed directly on the ground. This is also valid for cables running under the technical floor.

Note :

6.4. SAFETY EQUIPMENT


The Supply shall include for each substation safety equipment required by applicable regulations. It shall include at least: Personal Protective Equipment: - 2 boxes with insulating gloves - 1 MV insulating stool / platform

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 12/22

- 1 voltage tester up to 22 kV - 1 MV rescue insulated stick perch. warning signs (in local language), suction disc for lifting technical floor panels; The Supply shall also include the fire extinguishers as required by applicable regulations, except if these extinguishers are part of the civil work contract or of a general fire protection contract.

7. DOCUMENTS
The Supplier shall supply following documents : Substation general lay-out Civil works guide drawing Cable routings lay-out Air conditioning and pressurisation systems: Air conditioning calculation note; Pressurisation system technical data; General lay-out; Electrical diagrams; Erection and maintenance leaflets. Lighting design documents Fire detection system design documents. These documents shall comply with the requirements of specification STD.002.U02, Preparation of Electrical Documents, except for leaflets and standard documents from the manufacturers.

8. GUARANTEE
Guarantee on equipment supplied shall cover a minimum period of 24 months after Provisional Acceptance, with a maximum of 30 months after the equipment has been delivered at site.

9. DATA SHEET
Values to be mentioned in boxes shaded and marked with sign the Owner or by the main Contractor.

are to be given by

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 13/22

CUSTOMER: PROJECT: DATA SHEET AIR-CONDITIONING / PRESSURISATION EQUIPMENT: Air-conditioning system 1 Equipment type 2 Manufacturer 3 Stand-by device 4 Electrical power 5 Full load cooling capacity 6 Air flow 7 Design with ducts, louvres, deflection grids 8 Condensation type 9 Water flow (if water cooling) 10 Humidity control system 11 Dimensions 12 Weight 13 Heater power (if required) Pressurisation system 14 Filter type 15 Filter cleaning system type 16 Dust storage system 17 Filter weight efficiency 18 Operpressure maintained to : 19 Air flow 20 Electrical power 21 Fan sound pressure 22 Dimensions 23 Weight 24 Deviations from this specification

SUPPLIER : PROJECT N : OFFER: DATE :

Yes/No kW kW Cum/h normal Yes/No l/h Yes/No mmxmmxmm kg kW

% mm H2O Cum/h normal kW DB(A) mmxmmxmm kg

Note : The Supplier is requested to fill in a data sheet for each type of equipment proposed and to return it with his proposal.

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 14/22

10. TYPICAL DRAWINGS


All free space dimensions indicated in the following drawings are minimum requirements.
D R A W IN G 1
11000 H o t a ir e x h a u s t

EC

EC

VS1

VS2

- s e e d e ta il 3 1500 s e e D e ta il 1 M a te ria l A cc e ss & S a fe ty D o o r

S U - E le c tric a l ro o m e x te n s io n 1700 MC MC MC MC MC MC MC MC MC MC

TF1 CP2 CP2

12000

e xte n s io n UP AC

AM DM

1500

E m b e d d e d P ip e s

AU

s e e D e ta il 1 Documentation Table C a b le tre n ch e s e x te n sio n

Pressurisation

DH

DH

DH

DH

DH

Cable trenches

Cable trenches

500 min.

s e e D e ta il 1 LT A B CP1

Cable trenches 800 m in . s e e D e ta il 6


W e ig h t kg) 340 870 2800 -

3300

TF3 800 m in . 800 min.

TF2 1500 800 m in . SU T ra n s fo rm e r ro o m se e D e ta il 1

- s e e d e ta il 2

A irlo c k

- s e e D e ta il 4 - s e e D e ta il 2 D e ta il 1 : A - S m o k e d e te c to r
T y p ic a l B o a rd s D im e n s io n s
Code MC AC A M /D M UP DH TF1 TF2 TF3 D e v ic e MCC ACC M a rs h a llin g B o a rd UPS M V S w itc h b o a rd 1 6 k V A a u x . T ra n s f. 1 0 0 0 k V A -T ra n s fo rm e r 2 0 0 0 kV A -T ra n s fo rm e r L e n g th (m m ) 1000 1200 1200 600 750 520 1850 2120 D e p th (m m ) 400 400 400 700 1220 342 1000 1180 W e ig h t kg ) 96 2300 3700 C ode CP1 CP2 VS1 VS2 EC LT AU D e vic e M V -C a p a c ito r L V - C a p a c ito r V S D - 400kW V S D - 1400kW W e ig h fe e d e r b o a rd L ig h tin g D istrib . B o a rd A ir-c o n d itio n in g s y s te m

FA
s e e D e ta il 5

L e n g th (m m ) 1550 800 2100 5230 800 -

D e p th (m m ) 950 400 600 600 400 -

A cc e s so rie s

- In d o o rs L ig h tin g = 2 5 0 lu x - T e c h n . F lo o r (s e e D rw g .) - C a b le s a lw a ys to b e la id o n c a b le tra ys (s e e D rw g .) - E m e rg e n c y S h u t-d o w n P u s h -b u tto n - A ir c o n d itio n in g + P re s s u risa tio n

M V E m e rg e n c y S h u t D o w n p u s h b u tto n (M V E S D )

FA

F ire a la rm p u s h b u tto n

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 15/22

DRAWING 1 (Continued)

Detail 3: Screwed Plate extensions around door to ensure easy material access Detail 4: Door with Louvre for Transformer Room Detail 2: Door Standard Dimensions: 900*2100

2100

Anti- Panic Bar no key lock

Floor level 900 1200

2800

Outdoors Ground Level

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 16/22

DRAWING 1 (Continued) SECTION A-A

Thermal Insulation

Thermal Insulation

Airlock

Door Mat Side Walk

SECTION B-B

TF2 CP1

TF3

See Detail 5

See Detail 6

Detail 5
Rails Anchoring

Detail 6
frame for retaining leaking oil Seal

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 17/22

DRAWING 2 Basic Solution (General Case)

Thermal Insulation

MV Switch-Board

MCC

100

100

600

To be filled in after cables'installation

DRAWING 3 Alternative Solution (When there are risks of cable room's flooding)

MV Switch-Board

MCC

Side Walk

1000

600

To be filled in after cables'installation

DEPARTMENTAL SUBSTATIONS

Document

3000

3000

Page

Rev.

STD.002.U04 18/22

DRAWING 4

EC

EC

VS1

VS2

SU - Electrical room

Emergency lighting block Lighting fixtures

D C

extension MC
Embedded pipes

MC MC

MC MC

MC MC TF1 CP2 CP2

MC

MC

MC

Fire Alarm Detector

CEMENT PLANT SIDE

UP

AM AC DM

AU

DH

DH

DH

DH

DH

Fire Alarm Detector

Cable trench

Cable trench

Cable trench

LT

Emergency lighting block

CP1

TF2

TF3

SU - Transformer room

Lighting fixtures

Detail 1: Cable crossing to be made within 2 levels by means of cable bridge

Detail 2: MV - Cable tray

LV - Cable tray

Legend 3: Field bus cables to be installed in steel pipes unless they have a metal armor

Control Cable tray

DEPARTMENTAL SUBSTATIONS

Document

Cable trench

Page

Rev.

STD.002.U04 19/22

DRAWING 4 (Continued)

SECTION C-C
Embedded pipes from " Electrical Room " to "Production Area " (field)

Detail 7
900 150 200 200 200 150 Concrete Electrical Room Pipes end to be filled in after cables installation Electrical Room

600

300

See Detail 7 Control LV MV

1000

SECTION D-D

Plant

Sidewalk 600

Cable ladder

SECTION E-E

Plant

Pipes end to be filled in after cables installation

Sidewalk

DEPARTMENTAL SUBSTATIONS

Document

200

STD.002.U04 20/22

45

Page

Rev.

DRAWING 5

Fire Alarm Detector

600

600

30mm Thickness

Adjustable Jacks

16mm

600

Fire Alarm Detector

Wire mesh protection

Screwed or Stuck Base concrete

DEPARTMENTAL SUBSTATIONS

Document

600

Page

Rev.

STD.002.U04 21/22

DRAWING 6
Air Conditioning

Thermal Insulation
Cooled Air Flow

Air Condenser if no cooling water used (Split system)

DRAWING 7
Pressurisation

Fresh Air

Thermal Insulation

Outside Air Dust Filter

DEPARTMENTAL SUBSTATIONS

Document

Page

Rev.

STD.002.U04 22/22

You might also like