TROUBLESHOOTING
6-1. When the power is not coming on
Start
Isn't the main fuse of the power cord open? (Model with fuse) NO Is the voltage of CN70 end on main PCB normal? YES Is the voltage of 2nd side of TRANS on main PCB normal? YES Is the input voltage of REG1 (7812) on main PCB normal? YES Is the output voltage of REG1 (7812) on main PCB normal (12V)? YES
Is the output voltage of REG2 (7805) on main PCB normal (5V)?
25
6. TROUBLESHOOTING TROUBLESHOOTING
6-2. When the display panel PCB is not working
Start
Is the output voltage of REG1 (7812) on main PCB normal (12V)? YES Is the output voltage of REG2 (7805) on main PCB normal (5V)? YES Is the CN50 connection on main PCB normal? YES Is the wire connected between CN50 and panel PCB on main PCB normal? YES Is the connection of panel PCB connector normal? YES Is the panel PCB LED connection and pattern connection normal? YES Normal/Check set
NO
NO
NO
NO
26
6. TROUBLESHOOTING TROUBLESHOOTING
6-3. When photosynthesis LED is not working
Start
Is the PBA panel normally operating? YES Is the Fresh Care Light key on PBA panel selected? YES
NO
Check panel operation (Power Cool operation) Refer to panel problem repair
NO
Is the connection of the CN50 (3, 4) wire of main PCB connector to the photosynthesis LED PCB normal?
NO Repair wire
YES Is the photosynthesis LED PBA normal? YES Normal/Recheck the set NO Replace photosynthesis PBA
27
6. TROUBLESHOOTING TROUBLESHOOTING
6-4. When the compressor is not working
1. The compressor does not operate when 5 minutes have not passed after satisfying the temperature. 2. The compressor does not operate during defrosting. 3. When the freezer sensor is not connected, it detects as low temperature and the compressor does not operate. (Except for forced operation.)
Start
NO
YES Is the output of MICOM #26 "High" (5V)? YES NO Is the #14 of IC04 "Low"? YES NO Is the COMP relay normal? Replace IC04/replace PCB NO
YES Is the contact of connector CN71 normal? (1,5) NO Completely insert connector/ check contact
YES Is the COMP assembly normal? YES Assemble wire and check connected condition NO Replace/repair COMP
28
6. TROUBLESHOOTING TROUBLESHOOTING
6-5. When the cooling fan is not working
When checking the cooling fan, do the checking with the forced operation selected. 1. When the COMP is turned off, the freezer cooling fan is maintained off. 2. Even when the COMP is turned on, it is always kept off when the freezer or refrigerator door is open.
Start
NO
YES Is the connection with COMP end (joint) normal? YES Isn't the door open? (Freezer or refrigerator) NO Close door NO Correct connected condition/check wire
29
TROUBLESHOOTING 6. TROUBLESHOOTING
6-6. When the refrigerator LED lamp is not working
Start
YES Is the contact condition of the LAMP/LED board soket connector normal? YES Is the contact part of the door switch normal? NO Repair door switch part NO
YES Is the connecting contact part of connector CN70 1, 7 normal? YES Assemble wire and recheck the connected condition NO Improve/repair connector contact
30
TROUBLESHOOTING 6. TROUBLESHOOTING
6-7. When the defrost is not working
1. When the defrost sensor is short and defective, the defrost does not work but the normal operation continues. (As the self diagnosis check item, it is checked when the power is turn off/on again.) 2. When the temperature fuse is disconnected, the heating gets disabled, making the temperature rise naturally and delaying the COMP OFF time according to defrost to cause temperature defect. 3. When the defrost sensor is open and defective, the heating does not end and disconnects the temperature fuse to maintain the COMP OFF condition. (As the self diagnosis check item, it is checked when the power is turn off/on again.)
Start
When you press the forced defrost key , does defrosting start? YES Is the power connected to the defrost heater? NO
YES Is it IC04 #13? YES NO Is the relay (R Y72, R Y71) normal? Refer to common relay R Y71 defrost heater R Y72 relay check YES Is the contact condition connector CN71 normal? YES Is the temperature fuse within the EVAP normal? YES Is the defrost heater disconnected? NO Check the wire assembly condition YES Replace EV AP assembly NO Replace temperature fuse NO Recheck the contact condition of connector CN71 NO Replace/repair IC03, IC06, replace PCB
31
TROUBLESHOOTING 6. TROUBLESHOOTING
6-7. When the defrost is not working
YES
Normal
Is the temperature of defrost temperature higher than the ending temperature? Measure applicable sensor resistance (Appendix table) YES Is the voltage of MICOM #9 entered higher than voltage of ending temperature? Measure applicable sensor resistance (Appendix table) YES Replace PCB
NO
NO
32
6. TROUBLESHOOTING TROUBLESHOOTING
6-8. In case of self diagnosis error
1) In case of freezer temperature sensor Error display
Start
Is the single product of fridge temperature sensor normal? YES Is the inserted condition of main PCB connector (CN50) normal? YES
NO
NO
Is the connecting wire between main PCB connector (CN50) and temperature sensor (water color) normal? Reference 12 Refer to temperature table YES Is the input voltage of MICOM PIN #10 normal? YES Replace PCB
NO
33
6. TROUBLESHOOTING TROUBLESHOOTING
2) In case of external sensor error (Applied to type with external sensor) Error display
Start
Is the single product of defrost sensor normal? YES Is the inserted condition of main PCB connector (CN50) normal? YES
NO
NO
Is the connecting wire between main PCB connector (CN50) and defrost sensor (water color) normal? Reference 12 Refer to temperature table
NO
Is the input voltage of MICOM PIN #9 normal? YES Replace main PCB
34