Professional Documents
Culture Documents
X
1X 2
X
X 1X 2
1X 2
TRANSITION ANGLE: <-15 TRANSITION ANGLE: <-15 TRANSITION ANGLE: <-15 TRANSITION ANGLE: <-15
X
2
Rectangular Duct: x = Circular Duct: x = Duct Diameter
2 H x W
H + W
P.O. Box 6358 Santa Rosa, CA 95406 TEL 800-AIRFLOW Fax 707-526-9970 www.airmonitor.com
AIR MONITOR
POWER DI VI SI ON
CA Station
Combustion Airflow Measurement Station
Proven solutions for a tough industry
AIR MONITOR
POWER DI VI SI ON
CA Station
How It Works
The CA Station is also ideally suited to measure SA entering
each burner level of a partitioned windbox, SA being taken
out of a windbox to supply multiple OFA ports, at the ducted
inlet of FD fans, and bulk SA entering each windbox of a
corner fired unit.
The Need for Combustion Airflow Measurement
The objectives in the power industry today are twofold; to
lower emissions, and increase plant performance. Precise
measurement of combustion airflow and fuel rates positively
contributes to achieving those objectives, by providing the
information needed to optimize stoichiometric ratios and
facilitate more complete, stable combustion. Usable
measurements cannot be obtained from existing devices such
as venturis, foils, jamb tubes, etc., or instrumentation such
as thermal anemometers due to limited available straight duct
runs, low flow rates, proximity to modulating control dampers,
broad turndown range, and high concentrations of airborne
particulate (flyash).
Air Monitor Powers ruggedly constructed Combustion Air
(CA) Station, with both integral airflow processing cell and
Fechheimer-Pitot measurement technology, is engineered to
meet the challenging operating conditions of the typical power
plant while providing mass flow measurement of PA, SA, and
OFA within an accuracy of 2-3% of actual airflow.
While the main functions of primary air are to first dry and
then pneumatically convey the pulverized coal from the mill
to the individual burners, it also determines coal particle
velocity at the burner exit, influencing the flame position
relative to the burner tip and impacting flame stability, both
key factors in achieving optimized burner performance.
Accurate PA measurement obtained with a CA Station can
contribute to reducing NO
x
and CO, improving flame stability,
avoidance of coal pipe layout, minimizing LOI/UBC, reducing
waterwall corrosion, and increasing combustion efficiency.
Log-Tchebycheff Sensor Locat i on. A high concentration
of total and static pressure sensors positioned according to
the log-Tchebycheff rule sense the multiple and varying flow
components that constitute the airstream's velocity profile.
The log-Tchebycheff's perimeter weighted sensor pattern is
utilized to minimize the positive error (measurements greater
than actual) caused by the failure to account for slower
velocities at the duct wall when using traditional equal area
sensor locations. Spacing of total pressure sensors is per
the table below. Since the static pressure across the station
is relatively uniform, a lesser number of static pressure
sensors are utilized to minimize unrecovered pressure drop.
Fechhei mer Pi t ot Fl ow Measur ement. The CA Station
operates on the Fechheimer-Pitot derivative of the multi-point,
self-averaging Pitot principle to measure the total and static
pressure components of airflow. Total pressure sensing ports
with patented (U.S. Patent No. 4,559,835) chamfered
entrances, and Fechheimer pairs of offset static pressure
sensing ports combine to minimize the effect of directional
airflow. When located downstream of honeycomb airflow
processing cell, the Fechheimer Pitot method is extremely
effective at accurately measuring airflow in limited straight
duct runs.
Ai rf l ow Processi ng. To assure extremely high levels of
measuring accuracy (3% of actual flow) under extreme
conditions caused by turbulent, rotating, and multi-directional
airflows normally present near fan inlets, discharge ducts,
and directly downstream from duct elbows, transitions, etc.,
the CA Station uses open, parallel cell, honeycomb panels to
"process" the air into straightened flow just prior to the total
pressure measurement plane. These honeycomb panels
sharply reduce the need for long, straight runs of duct before
and after the station to obtain accurate flow measurement.
Negl i gi bl e Ai r f l ow Resi st ance. The CA Station airflow
measuring station is designed to function while producing a
minimum of resistance to airflow, due to the unique
honeycomb air straightener-equalizer section having a free
area of 96.6%. The unique, non-restrictive characteristic of
the CA Station is seen in the Resistance vs. Airflow Velocity
graph below. The values indicated are total resistance and
do not include any allowances for static regain (a potential
20% reduction to the values).
Denotes CA Station location
Duct / Station
Configuration
Rectangular
Circular
Quantity of Sensing Points
25 or more points, maximum 6" or 8" apart,
depending on duct size.
12 to 30 points, along 2 or 3 diameters.
Construction Features
Combustion Airflow Measurement Station
Specifications
Minimum Installation Requirements
Welded 3/16"
Carbon Steel Casing
90 Connection Flanges
12" Depth
24 ga. Carbon Steel
Airflow Straightener
Offset Fechheimer Static
Pressure Sensing Probe
Total Pressure Sensing Manifold
Conf i gurat i ons.
Rectangular, Circular, and Custom
Accuracy.
2-3% of actual flow
Operat i ng Temperat ures.
Continuous operation to 800F
Connect i on Fi t t i ngs.
1/2" FPT, Type 316 stainless steel
Stat i c and Total Pressure Sensi ng Mani f ol ds.
Type 316 stainless steel, welded construction
Ai rf l ow St rai ght ener.
1" hexagonal, parallel cell straightener, 3" deep,
24 ga. (.024") thick carbon steel
Casi ng and Fl anges.
3/16" carbon steel, continuous welded seams
Casing depth is 12"
Speci al Const ruct i on Opt i ons.
Sensing Manifold Cleanouts
Inlet Bell Mouth
Multi-point Temperature Measurement
Alternate Materials of Construction
Integral Control Damper
Optional Manifold Cleanouts
DAMPERS
BRANCH DUCT
BELLMOUTH / FAN INLET
CONVERGING
DUCTS
REDUCING TRANSITION EXPANDING TRANSITION UNVANED ELBOW ELBOW
VANED
125-495 (04-09)
P.O. Box 6358 Santa Rosa, CA 95406 P: 800-AIRFLOW F: 707-526-9970
www.airmonitor.com amcsales@airmonitor.com
Ai r Moni tor Power' s Product Fami l i es of Ai r & Coal Fl ow Measurement Systems
IBAM
TM
Individual Burner Airflow Measurement
The IBAM
TM
Individual Burner Airflow Measurement probe is ideally suited for new or
retrofit applications where a reduction in plant emissions and improvement in efficiency
can be obtained through accurate measurement of burner secondary airflow. The IBAM
TM
probe has been designed to accurately measure in the particulate laden, high operating
temperature conditions found in burner air passages.
CEMS
TM
Continuous Emissions Monitoring System
Air Monitor Power's CEMS
TM
Continuous Emissions Monitoring Systems assist in
complying with the Clean Air Acts stringent emission measurement standards and the
requirements of 40 CFR 75. Air Monitor has assembled a cost effective integrated system
consisting of in-stack flow measurement equipment and companion instrumentation to
provide continuous, accurate, and reliable volumetric airflow monitoring of stacks and ducts
of any size and configuration.
CAMS
TM
Combustion Airflow Management Systems.
The CAMS
TM
Combustion Airflow Management System has been designed to reliably
and accurately measure airflow in combustion airflow applications. The CAMS
TM
contains
the microprocessor based instrumentation to measure the airflow and manage the AUTO-
purge. The AUTO-purge is a high pressure air blowback system that protects the duct
mounted flow measurement device from any degradation in performance due to the
presence of airborne particulate (flyash).
Engineering & Testing Services. Air Monitor Power offers complete engineering and testing to analyze air and coal
delivery systems. Air Monitor Powers field testing services use 3D airflow traversing and Pf-FLO coal flow measurement
systems for the highest possible accuracy. To ensure cost effective and accurate solutions, Air Monitor Power has full scale
physical flow modeling capability and in house Computational Fluid Dynamics (CFD). CFD analysis is used to analyze flow
profiles and design/redesign ductwork to improve overall performance. Full scale model fabrication and certified wind tunnel
testing is used to develop application specific products that will measure accurately where no standard flow measurement can.
Pf-FLO
TM
Pulverized Fuel Flow Management
The Pf-FLO
TM
system performs continuous and accurate fuel flow measurement in
pulverized coal fired combustion applications, providing boiler operators with the real-time
data needed to balance coal mass distribution between burners. Balanced fuel improves
combustion efficiency and lowers emissions while reducing in-furnace slagging, coal layout,
fuel slagging, and coal pipe fires.
VOLU-probe/SS
TM
Stainless Steel Airflow Traverse Probes.
Multi-point, self-averaging, Pitot-Fechheimer airflow traverse probes with integral airflow
direction correcting design. Constructed of Type 316 stainless steel and available in
externally and internally mounted versions for harsh, corrosive or high temperature
applications such as fume hood, laboratory exhaust, pharmaceutical, and clean room
production and dirty industrial process applications.
AIR MONITOR
POWER DI VI SI ON
CAMS
Combustion Airf low Management System
Proven sol uti ons for a tough i ndustry
The Air Monitor Power CAMS
TM
Combustion Airflow
Management System is designed to fulfill the need for a
reliable and accurate means of flow measurement in
combustion airflow applications. Combined into a single
engineered package are the CAMM
TM
Combustion Airflow
Management Module containing the microprocessor based
instrumentation to measure the airflow and manage the purge
cycle, and AUTO-purge to protect against any degradation in
performance of the duct mounted measurement device(s) due
to the presence of airborne particulate.
Product Descri pti on
CAMS Combustion Airf low Management System
TM
CAMM
TM
Performance Speci fi cati on
Accuracy. 0.1% of Natural Span, including non-linearity,
hysteresis, and non-repeatability.
Stabi l i ty. 0.5% of Natural Span for six months.
Temperature Effect. Zero. None; corrected by AUTO-zero.
Span. 0.015% of Full Span/F.
Mounti ng Posi ti on Effect. None; corrected by AUTO-zero.
Transducer Response Ti me. 0.5 second to reach 98% of a
step change.
Power Consumpti on. 35VA at 24VAC, 20VA at 24VDC,
and 42VA at 120VAC.
CAMM
TM
Functi onal Speci fi cati on
Di gi tal Output. Form "A" dry contacts (maintained) for
AUTO-purge activation and acknowledgment.
Di gi tal Inputs. External dry contact closure for AUTO-purge
external start and purge interrupt commands.
Anal og Outputs. Four outputs for flow, temperature,
absolute pressure, and special function individually
configurable via jumper for 0-5VDC, 0-10VDC or 4-20mADC.
Anal og Inputs. Dual inputs are field configurable via jumper
for 0-5VDC, 0-10VDC, or 4-20mADC. One is reserved for
temperature input; the other for use with optional special
function.
Network Communi cati on. Optional ModBus TCP/IP over
Ethernet.
AUTO-purge Management. The AUTO-purge cycle is
initiated via an external dry contact input, or via the CAMM
timer, with field selectable frequencies of 1 to 24 hours in 1
hour increments. A pair of CAMM dry contacts control the
AUTO-purge System, and third dry contact provides remote
purge activation acknowledgment.
Power Suppl y. Standard 24VAC (20-28VAC) or 24VDC
(20-40VDC), with automatic selection. Optional 120VAC
(100-132VAC) via external UL listed transformer.
Overpressure and Stati c Pressure Li mi t. 25 psig.
Low Pass Fi l trati on. Response time to reach 98% of a step
change is adjustable from 2.0 to 250.0 seconds.
Automati c Zeroi ng. Accuracy. Within 0.1% of calibrated
span. Frequency. Every 1 to 24 hours selectable on 1 hour
intervals.
Ci rcui t Protecti on. Power input is fused and reverse
polarity protected.
Span and Zero Adj ustment. Electronic adjustment via
keypad.
Di spl ay. Backlit, graphical LCD provides indication of up to
four process variables. Triple-size digits for main process
variable, standard size characters for the other process
variables.
Temperature Compensati on Sel ecti on. Push-button
selection of linearized or nonlinear input. Choice of
thermocouple (Type E, K, J , and T) or 100 ohm platinum
RTD temperature sensor type.
Pressure Compensati on. Absolute pressure (atmosphere
or duct static), up to 60"Hg.
Humi di ty Li mi ts. 0-95% RH, non-condensing.
Temperature Li mi ts. 20F to 180F Storage.
+40F to 140F Operating.
Speci al Funct i ons Power Cert i f i cat i on Rapi d Stop
Summed Flow 24VAC Standard Yes
Differential Flow 24VDC NIST Traceable No
120VAC
CAMM
TM
Constructi on Opti ons
Air Monitor Power's AUTO-purge is designed for applications
where the presence of airborne particulate might impair the
measurement accuracy of Air Monitor Power's Combustion
Air (CA) Station or VOLU-probe array. When activated by a
CAMM
TM
or distributed control system, a combination of fail-
safe valves are operated to introduce high pressure/high
volume air to the flow measuring device's sensing ports for a
short duration while simultaneously isolating the CAMM
TM
from
overpressurization. This periodic purging assists in
maintaining the sensing ports of the total and static pressure
manifolds in a clear, unobstructed condition.
Product Descri pti on
AUTO-purge
STANDARD CAPACITY
NEMA 4X Stainless Steel Enclosure
Vortex Cooler. Requires 80-100 psi air supply.
Rapid Stop
TM
Enclosure Heater. Requires 120VAC power supply.
Viewing Window
Power Capacity
24VAC Standard
24VDC Low Model SP
120VAC High Model HP
Opti onal Constructi on
Di mensi onal Speci fi cati ons
Brass and Copper Construction
40F to 140F.
71 . 1
0
cut r r
c
f
m
s
L
v
By using this method only particle velocity is measured, which in most instances
differs from and is slower than the transport air velocity in a two-phase flow. This
difference, or velocity slip, is a function of such factors as pipe configuration, specific
weight and size of particles.
Signal 1
Signal 2
Cross-correlation
Fig. 2.2: Velocity measurement principle: signals and
resulting cross-correlation function
2.2.3 Calculation of the Mass Flow
The mass flow is calculated from the density and the particulate velocity
measurement as follows:
Equation 5.
The Pf-FLO system is calibrated to a known mass flow of the mill or pipe by adjusting
the frequency density factor k
fd
in Equation 3, which in turn depends on the pipe
diameter. The factor k
fd
is kept constant for all pipes with the same diameter.
2.3 Pf-FLO Test Configuration
The 4.86 diameter test duct pipe has a cut-off frequency of approximately 1.4 GHz.
The standard microwave generating unit of the Pf-FLO system has been selected to
provide frequencies up to only a 1 GHz level required for the range of larger coal pipe
s
v
dt
dm
,
_
dt
dm
Velocity = L /
m
5.25 D
rod
sensor
0.87 D 1.0 D 0.75 D 0.75 D 1.0 D 0.87 D
,
_
dt
dm
sizes found in power plants. For the test runs conducted it was necessary to replace
the standard model generator with a similar model having an extended frequency
range of up to 2.0 GHz.
Corresponding to the smaller inner diameter of the test duct, the sensor antenna was
also scaled down in length. Distances between sensors and rods in the test runs
were the standard distances based on a pipe having a diameter D, as show in Figure
2.3.
Fig. 2.3: Arrangement of sensors and rods at individual measurement locations
The Pf-FLO system uses wear resistant Tungsten Carbide rods to keep the
propagation of the microwaves within the certain measurement zone of the pipe.
Without the rods, the density measurement would be disturbed by reflected signals
caused by pipe bends, orifice plates, isolation valves, etc., located upstream and/or
downstream of the measurement zone. The optional fifth rod perpendicular to the
sensors and located at their midpoint provides an additional signal short cut for
depressing the propagation of 90 polarized H
11
modes.
Without knowing the actual mass frequency factor for the test pipe size, all channels
were initially set to
This factor was kept constant for all measurements in the test. The resulting units for
measured density () and mass flow are in arbitrary units [a.u.].
1
]
1
m Hz
a.u.
500
fd
k
2.4 The Test Medium
The test plant could not be used with black coal for safety reasons. Therefore, glass
spheres were used, with such properties as particle size, dielectric constant, and
electrostatic charging similar to pulverized coal.
Typically 85 % 95 % by weight of pulverized coal particles downstream of the mills
classifier are smaller than 90 m and 0.3 % or less are bigger than 225 m. The two
glass particle sizes of 66 m and 225 m used for this test represent the main
fraction and the biggest possible size fraction of particles in coal pipes.
The manufacturer of the glass beads specifies a glass density of 158.6 lb/ft and an
r
of 2.28 at visible light. The
r
may be slightly different for microwaves due to
dispersion.
The dielectric properties of milled coal and the glass spheres were tested in a
microwave resonator chamber. It was found that the frequency shift in this
measurement was dependent upon the dielectric properties on the bulk density of the
pulverized medium. By calculating the frequency shift per mass, the influence of the
sphere packing were eliminated. The results are displayed in Table 2.1.
Medium
Bulk density
[lbs/ft]
Frequency shift/
mass [MHz/lb]
Glass spheres 88.1 124.1
Black coal (Primero) 35.8 200.1
Black coal (Blumenthal) 35.8 193.9
Black coal (Knurrow) 41.8 193.5
Table 2.1: Bulk density and frequency shift for fixed-bed powder
of pulverized black coal and glass particles
The frequency shift at the same mass flow caused by glass is about 2/3 of the tested
coal. Therefore, the expected frequency shift for the mass flow measurement will
only be about 1/3 less for glass than for coal with the same mass. This ensures a
good comparability between the test data obtained with glass particles used as the
test medium versus that which would have been obtained had coal been able to be
used for the test medium.
The density for raw coal is between 78.0 and 81.8 lbs/ft. Taking this density into
account, glass particles of the same size are about two times heavier than coal
particles. The weight differential plus the shape of the particles, spherical for glass
and polyhedral for coal, give glass aerodynamic properties which result in a greater
velocity differential or slip between the airflow and the glass particles.
The electrostatic charging depends on particle collisions and particle conductivity.
The velocity measurement needs a certain amount of electrostatic charge to
correlate the sensor signals into a reliable time of flight measurement. Charging
signal strengths for both size glass beads and bead mixtures were sufficiently high to
obtain accurate time of flight measurements. Induced by the substantially greater
number of particle amount within the airflow, the signal strength of 66 m particles
was about five times higher than for the 225 m particles.
Gravimetric Particle Size Distribution
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 50 100 150 200 250 300
Particle size [m]
R
e
l
.
p
a
r
t
i
c
l
e
d
i
s
t
r
i
b
u
t
i
o
n
[
%
]
Fig. 2.4: Particle distribution as a function of particle size for the
50/50 mix of 66 m and 225 m particles
Beside the pure 66 m and 225 m particles, a 50/50 mix by weight was also tested.
Figure 2.4 shows the gravimetric distribution of particle sizes.
2.5 Feeder Calibration
To calibrate the feeder, glass beads were fed by the frequency controlled feeder into
a container for 30 seconds and their mass was weighed. This procedure was
repeated twice for each particle size in steps of 50 rpm from 0 to 350 rpm. The
average of both sets of measurements was used for the feeder calibration.
The repeatability of the feeder calibration was then tested by 10 individual
measurements with the 66 m particles at 150 rpm. They were all in the range of
t0.9 % by weight.
This was acceptable since the aim of the tests was not to examine the characteristics
of the screw feeder. And with all four sensor locations measuring physically the same
airflow/particle mixture, any scattering of the feeder is eliminated as a common
variable.
Feeder Calibration
0
.11
.22
.33
.44
.55
0 50 100 150 200 250 300 350 400
Feeder speed [rpm]
M
a
s
s
f
l
o
w
[
l
b
s
/
s
]
66 225 m
mix
225 m
66 m
Fig. 2.5: Mass flow versus feeder speed for different particle fractions
The mass flow of the feeder is shown in Figure 2.5 for the specific particle fractions.
The mass flow at a particular feeder speed depends on the particle size distribution.
The mix of the two size fractions has the tightest packing and thus shows the highest
mass flow. The 66 m and 225 m particles have different mass flows since for
particles <100 m, adhesion forces influence the flowability within the screw feeder.
3. Testing Procedure
The test runs have been made under the aspect of realistic airflow velocities and
particle concentrations.
Within the capacity of the fan, three velocity levels were chosen at 72 ft/s, 82 ft/s, and
92 ft/s, representing normal transport velocities in utility plants. With constant air
velocities the feeder speed was varied between 0 - 300 rpm in steps of 50 rpm.
Particle Concentration Range
0
0.006
0.013
0.019
0.025
0.031
0.037
0.044
0.050
0 50 100 150 200 250 300 350
Feeder speed [rpm]
C
o
n
c
e
n
t
r
a
t
i
o
n
[
l
b
s
/
f
t
]
Fig. 3.1: Range of pf-concentrations based on feeder mass flow and
transport air flow
The pf concentrations in utility plants usually range between 0.012 to 0.031 lbs/ft.
Figure 3.1 shows the range of the expected pf concentration based on the ratio of
feeder mass flow and the airflow during the tests.
Table 3.1 gives an overview of the different test runs: From the total number of 15
test runs there were six runs with the 66 m particles, six runs with the particle mix
and three runs with the 225 m particles.
Particle Size Test Numbers
66 m I,VI II,V III,IV
225 m I II III
66 - 225 m mix I,IV II,V III, VI
72 ft/s 82 ft/s 92 ft/s
Gas Velocity
Table 3.1: Test run number for each particle size
The following diagrams illustrate the data acquired for all test runs: Diagram
Figures 3.2 and 3.3 show density and velocity measurement, and Figure 3.4 shows
the resulting mass flow of the 66 225 m particles of Test Number V. Each feeder
step was kept constant for at least 15 minutes to get about 20 individual
measurements. From the last 15 measurements of each feeder step the average was
taken and plotted against the feeder mass flow in Figure 3.5.
0
6
12
18
24
30
36
42
48
54
61
1
3
:0
4
1
3
:1
2
1
3
:2
0
1
3
:2
9
1
3
:3
7
1
3
:
4
6
1
3
:
5
4
1
4
:
0
2
1
4
:
1
1
1
4
:
1
9
1
4
:
2
8
1
4
:
3
6
1
4
:
4
4
1
4
:
5
3
1
5
:
0
1
1
5
:
1
0
1
5
:
1
8
0
50
100
150
200
250
300
350
400
CH 0
CH 1
CH 2
CH 3
feeder
Densities 66 - 225 m, Test V
D
e
n
s
i
t
y
[
a
.
u
.
/
f
t
]
F
e
e
d
e
r
s
p
e
e
d
[
r
p
m
]
Fig. 3.2: Density measurement Fig. 3.3: Velocity measurement
0
500
1000
1500
2000
2500
3000
3500
4000
4500
1
3
:0
4
1
3
:1
1
1
3
:1
9
1
3
:
2
6
1
3
:
3
4
1
3
:4
1
1
3
:4
9
1
3
:5
7
1
4
:
0
4
1
4
:1
2
1
4
:1
9
1
4
:2
7
1
4
:
3
4
1
4
:
4
2
1
4
:4
9
1
4
:5
7
1
5
:0
5
1
5
:
1
2
1
5
:
2
0
0
50
100
150
200
250
300
350
CH 0
CH 1
CH 2
CH 3
feeder
M
a
s
s
f
l
o
w
[
a
.
u
.
/
s
]
Mass Flows 66 - 225 m, Test V
F
e
e
d
e
r
s
p
e
e
d
[
r
p
m
]
Fig. 3.4: Resulting mass flow and feeder signal Fig. 3.5: Mass flow of feeder versus Pf-FLO
0
16
33
49
66
82
98
1
3
:
0
4
1
3
:
1
1
1
3
:
1
9
1
3
:
2
6
1
3
:
3
4
1
3
:
4
1
1
3
:
4
9
1
3
:
5
7
1
4
:
0
4
1
4
:
1
2
1
4
:
1
9
1
4
:
2
7
1
4
:
3
4
1
4
:
4
2
1
4
:
4
9
1
4
:
5
7
1
5
:
0
5
1
5
:
1
2
1
5
:
2
0
CH 0
CH 1
CH 2
CH 3
Velocities 66 - 225 m, Test V
V
e
l
o
c
i
t
y
[
f
t
/
s
]
Mass Flow of Feeder vs.
Pf-FLO, 66 - 225 m, Test I - VI
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 198 397 595 793 992 1190 1389 1587
CH 0
CH 1
CH 2
CH 3
P
f
-
F
L
O
M
a
s
s
f
l
o
w
[
a
.
u
.
/
s
]
Feeder mass flow [lbs/hr]
All test runs have been plotted as displayed in Figure 3.5. As there is only a constant
factor between [a.u./s] and [g/s], a unified y-axis scaling was used to help evaluate
the influence of different particle sizes (see also Figure 4.8).
4. Results
4.1 Pf-FLO Measurement Accuracy
Figures 4.1 and 4.2 illustrate results only for the 50/50 particle mix. Results for other
particle fractions are listed in the tabulations in Sections 4.1.1 and 4.1.2.
Mass Flow of Feeder versus Pf-FLO; 66 - 225 m, Test I - VI
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 198 397 595 793 992 1190 1389 1587
Feeder mass flow [lbs/hr]
P
f
-
F
L
O
m
a
s
s
f
l
o
w
[
a
.
u
/
s
]
Channel 0
Channel 1
Channel 2
Channel 3
lin average
Standard deviation [a.u./s]: 158
Fig. 4.1: Evaluation of all test runs with 66 / 225 m particles
The diagram in Figure 4.1 shows the evaluated results for all measuring channels
versus the feeder mass flow. The mass flow signals of all channels were averaged
for each feeder step and one particle fraction, and a linear coefficient was determined
for it. With this coefficient the linear average was calculated as it can be seen in the
diagram, indicated with lin. average. Based on the linear average the standard
deviation was determined for each measuring channel as listed in Table 4.1.
The repeatability of one channel for all tests and one particle size is exemplarily
displayed in Figure 4.2. For other measuring channels and particle fractions, see
tabulations in Section 4.1.2.
Repeatability of Channel 0; 66 225 m Particles, All Tests
0
500
100
1500
2000
2500
3000
3500
4000
4500
0 397 793
1190 1587
Feeder mass flow [lbs/hr]
P
f
-
F
L
O
m
a
s
s
f
l
o
w
[
a
.
u
.
/
s
]
Test No. I 72 ft/s
Test No. II 82 ft/s
Test No. III 92 ft/s
Test No. IV 72 ft/s
Test No. V 82 ft/s
Test No. VI 92 ft/s
(Standard Deviation: 3.3 %)
Fig. 4.2: Repeatability of channel 0 for 66 - 225 m particles
4.1.1 Absolute Deviation
The standard deviation of one particle fraction from the linear average of all channels
is listed in Table 4.1. The errors in % refer to the maximum mass flow determined at
300 rpm feeder speed.
Particle Size Channel Test No.
Number of
Measurements
Standard
Deviation
[a.u./s]
Max. Mass
Flow
[a.u./s]
Mean
Error
%
66 m CH0 - CH3 Test I - VI 144 109 2462 4.4%
225 m CH0 - CH3 Test I - III 72 132 3520 3.8%
66 - 225 m CH0 - CH3 Test I - VI 144 158 4000 3.9%
Table 4.1: Standard deviation and mean error for individual particle fractions
4.1.2 Repeatability
The relative deviation of one channel in all tests shows its repeatability. This includes
the scattering of the feeder but excludes systematic deviations from one channel in
comparison to the others. Results for each channel are listed in the Tables 4.2 to 4.4.
Standard Deviation
To Linear
Average
Channel Test No.
Number of
Measurements [a.u./s]
Mean
Error
%
CH 0 Test I - VI 36 75.1 3.1%
CH 1 Test I - VI 36 92.5 3.8%
CH 2 Test I - VI 36 93.4 3.8%
CH 3 Test I - VI 36 72.9 3.0%
The error in % refers to the maximum mass flow at 300 rpm: 2462 [a.u./s]
Table 4.2: Standard deviation of the individual channels with 66 m particles
Standard Deviation
To Linear
Average
Channel Test No.
Number of
Measurements [a.u./s]
Mean
Error
%
CH 0 Test I - III 18 132.3 3.8%
CH 1 Test I - III 18 65.0 1.8%
CH 2 Test I - III 18 151.9 4.3%
CH 3 Test I - III 18 111.7 3.2%
The error in % refers to the maximum mass flow at 300 rpm: 3520 [a.u./s]
Table 4.3: Standard deviation of the individual channels with 225 m particles
Standard Deviation
To Linear
Average
Channel Test No.
Number of
Measurements [a.u./s]
Mean
Error
%
CH 0 Test I - VI 36 131.7 3.3%
CH 1 Test I - VI 36 114.1 2.9%
CH 2 Test I - VI 36 163.9 4.1%
CH 3 Test I - VI 36 141.2 3.5%
The error in % refers to the maximum mass flow at 300 rpm: 4000 [a.u./s]
Table 4.4: Standard deviation of the individual channels with 66-225 m particle mix
4.2 Influence of the Particle Size
Another purpose of the tests was to quantify the influence of particle sizes. As the
225 m particles can only be found in smaller percentages in pulverized coal, it is a
practical fraction to resolve particle size dependent influences on density and velocity
measurement. The transferability of the results to the operating condition of coal fired
power plants have to be viewed in relation to the real particle size distributions in coal
pipes. In Section 4.2.3 the results out of the tests are evaluated.
4.2.1 Velocity Measurement
Measured Particle Velocities at Channel 0
0
16
33
49
66
82
98
72 ft/s gas velocity 82 ft/s gas velocity 92 ft/s gas velocity
P
a
r
t
i
c
l
e
v
e
l
o
c
i
t
y
[
f
t
/
s
]
225m
66m
66-225 m mix
Fig. 4.3 Averaged particle velocities at channel 0
The measurements with 225 m particles showed a difference of about 16.4 ft/s
between airflow and particle velocity. This is due to the change in the aerodynamic
properties which increase the slip between particles and gas. The weight of particles
changes proportional to D but the cross section only changes proportional to D.
The velocity of the 66 m particles, as well as the 50/50 mix, was found to be very
close to the airflow velocity. The reason can be found by comparing the electrostatic
signal strength. The electrostatic signal strength of the 225 m particles was found to
be significantly lower than for 66 m. But the particle number increases with the
relation of particle diameters to the power of three (see above). With a 50/50 particle
mixture by weight, the number of 66 m particles is about 28 times greater than for
the 225 m particles. The cross correlation method resolves the time shift of the
sensor signals by comparing their highest identity. If the signal strength of two time
shifts is of the same order, it might be possible to distinguish between the two
velocities. In case of the particle mix the signal strength of the 225 m particles was
below the noise signal level of the 66 m particles. Therefore, it is obvious that only
the velocity of the 66 m particles has been measured. The error in relation to the
realistic particle size distribution is estimated in Section 4.2.3.
Velocities of the 225 m Particles
0
16
33
49
66
82
98
72 ft/s gas velocity 82 ft/s gas velocity 92 ft/s gas velocity
v
e
l
o
c
i
t
y
[
f
t
/
s
]
CH0
CH1
CH2
CH3
Fig. 4.4: Acceleration along the test duct of the 225 m particles
In the tests which measured 225 m particles only, channel 3 was found to have
higher velocities than the other channels. This can be explained by the position of
this sensor pair located at the end of the horizontal test duct with the longest straight
run after a bend (see Figure 2.1). This leads to a certain acceleration, especially for
the bigger sized particles.
Influence of Mass Flow on Velocity of the Particle Mix
67
72
79
85
92
98
0 397 793 1190 1587
Feeder [lbs/hr]
v
e
l
o
c
i
t
y
[
f
t
/
s
]
CH 0
CH 1
CH 2
CH 3
Fig. 4.5: Influence of the mass flow on the velocity of the particle mix in Test IV-VI
Figure 4.5 shows the influence of the mass flow on particle velocity. This effect, here
illustrated for the particle mix, is obvious when the averaged velocity of each feeder
step is plotted over the mass flow as it is done in Figure 4.5. Each bundle of the four
channels represents one step of the airflow velocity.
The higher the airflow velocity the higher the influence from pf load in the pipe.
Channel 2 with the shortest distance from a bend seems to be affected most. It is
assumed that this effect is related to particle interaction between 66 m and 225 m
particles, the latter having significantly lower velocities.
4.2.2 Density Measurement
Densities 66 m Particles, Test V
0
6.1
18.3
24.4
30.5
36.6
42.7
1
3
:
3
2
1
3
:
4
1
1
3
:
5
0
1
3
:
5
8
1
4
:
0
7
1
4
:
1
6
1
4
:
2
5
1
4
:
3
4
1
4
:
4
2
1
4
:
5
1
1
5
:
0
0
1
5
:
0
9
1
5
:
1
8
1
5
:
2
7
1
5
:
3
6
1
5
:
4
5
1
5
:
5
4
0
50
100
150
200
250
300
350
400
CH 0
CH 1
CH 2
CH 3
feeder
D
e
n
s
i
t
y
[
a
.
u
.
/
f
t
]
F
e
e
d
e
r
s
p
e
e
d
[
r
p
m
]
Fig. 4.6: Density measurement with 66 m particles Test V.
Densities 225 m Particles, Test I
0
15.2
30.5
45.7
61.0
76.2
1
0
:
1
4
1
0
:
2
0
1
0
:
2
7
1
0
:
3
3
1
0
:
4
0
1
0
:
4
6
1
0
:
5
3
1
0
:
5
9
1
1
:
0
6
1
1
:
1
2
1
1
:
1
9
1
1
:
2
5
1
1
:
3
2
1
1
:
3
8
1
1
:
4
5
1
1
:
5
1
1
1
:
5
8
1
2
:
0
4
1
2
:
1
1
1
2
:
1
7
0
50
100
150
200
250
300
350
400
CH 0
CH 1
CH 2
CH 3
feeder
D
e
n
s
i
t
y
[
a
.
u
.
/
f
t
]
F
e
e
d
e
r
s
p
e
e
d
[
r
p
m
]
Fig. 4.7: Density measurement with 225 m particles Test I
The diagrams in Figures 4.6 and 4.7 show the particle size dependent scattering of
the densities in two test runs. The more extended scattering of the density signal for
66 m particles also increases with the load or particle numbers. With the 225 m
particles there was less scattering although the densities in Figure 4.7 were nearly
twice as high. The fluctuation quantity for the particle mix is higher than the one for
the 225 m, but less than the one for the 66 m particles and was also influenced by
the load (see Figure 3.4).
The scattering of measurement is proved to be realistic and relates to the density
fluctuations of the particle flow. The different behavior can be explained with the
mean free path between particle collisions. The 66 m particles have less particle-
wall collisions but more particle-particle collisions in a smaller volume. Local high
and low density concentrations do not average out within the pipe volume that has
been measured.
4.2.3 Mass flow measurement
Influence of the Particle Size
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 198 397 595 793 992 1190 1389 1587
Feeder mass flow [lb/hr]
P
f
-
F
L
O
m
a
s
s
f
l
o
w
[
a
.
u
.
/
s
]
lin average 66 m
lin average 200 m
lin average 66 - 200 m
2.885
2.734
2.356
Ratio ([a.u.] to [lbs]):
Fig. 4.8: Influence of the particle size on the Pf-FLO measurement
The diagram in Fig. 4.8 shows the ratio of arbitrary units [a.u./sec] to mass [g] taken
from the linear averages of the four measurement channels. This factor was found to
be a function of the used particle fraction. The temporarily applied arbitrary units to
frequency factor of 500 (see section 2.3) has to be divided by this ratio to get the
calibrated mass flow signal for each particle fraction. The resulting k
fd
is displayed in
Table 4.5.
Particle Fraction ratio [a.u./lbs] k
fd
[g/m kHz]
66 m particles 2.3562 26.7
225 m particles 2.7342 23.0
66-225 m particle mix 2.8854 21.8
Table 4.5: Ratio of arbitrary units to mass and the resulting
mass frequency factor k
fd
for each particle fraction
The deviation of 13.8 % between the 66 and 225 m particles can be regarded as
dependent on particle size. The deviation of the 66 225 m particle mix is due to
the deviation of the velocity measurement described in Section 4.2.1.
The results have to be compared with the real particle size distribution in a coal pipe
after classifier. These deviations have influence only on the absolute accuracy but
not on the relative accuracy between several pipes of one mill since a segregation of
particle fractions between several pipes is not probable.
The following calculations are linear estimations of the error in real particle size
distributions within the results of the tests: For an examplary particle distribution of
15% >90 m and 0.2 % >225 m it was assumed to have a discrete mixture out of
84.8 % 66 m particles, 15 % 145 m particles and 0.2 % 225 m particles. The
relation of the diameters was taken to interpolate the velocity of the 145 m particles
linear between the velocities of the 66 m and 225 m particles. Also the relation of
the diameters was taken to interpolate the deviation of density measurement for
145 m particles linear between the densities of the 66 and 225 m particles.
Deviation caused by Particle Size
0
20
40
60
80
100
120
100% 66 m 89.9% 66m
10.0% 145m
0.1% 225m
84.8% 66m
15.0% 145m
0.2% 225m
79.0% 66m
20.0% 145m
1.0% 225m
R
e
l
a
t
i
v
e
m
a
s
s
f
l
o
w
[
%
]
225 m
145 m
66 m
100.0 101.2 101.8 102.5
Fig. 4.9: Estimated deviation by modeled particle size distribution
The results of the estimation are shown in Figure 4.9. If the distribution changes from
column 2 to 3, the estimated error is about 0.6 % of the mass flow. The distribution of
the last column shows a 2.5 % error but this change in particle distribution is meant
to be quite unrealistic in an optimized milling process and will also influence the
combustion badly.
5. Abstract
A reference test at the pneumatic conveying test plant of the Lehrstuhl fr
Mechanische Verfahrenstechnik at the University of Halle- Wittenberg was
established to prove the accuracy of a flow measurement system for air-solid flows.
The test facility consists of a calibrated screw feeder, a pipe system with vertical and
horizontal elements, and the particle separation equipment. Glass beads were used
as a test medium whose physical properties are comparable to coal dust if taking into
account the measurement principle. In addition to the single sized test materials with
diameters of 66 m and 225 m, a 50/50 mixture by weight of both particle sizes was
used. The experimental matrix for the tests covered the usual operational range for
the throughput and the velocity in coal pipes of power plants.
In total, four measurement instruments were located at two locations in the upward
run and two locations in the horizontal run of the test pipe. From the measured
density and velocity signals of the particles the mass flow was calculated in each
case and compared with the calibrated feeder signal. The measuring error was
related to a single standard deviation.
As a result, the measured deviation from the feeder signal is < 4.5 %; this applies to
the entirety of all four measuring points and all particle fractions. For individual
sensors the deviation lies in the range between 1.8 % to 4.3 %, and is in this case
not significantly dependent on the used particle size.
In addition, investigations of the influence of the particle size were carried out. Within
the wide range of the used particle fractions, the density and velocity measurement
showed some size dependencies. However, the measured differences have only little
influence on the accuracy (< 0.6 %) since in utility plants the grading of coal dust
usually changes only in a comparable small range.
IBAM
TM
Individual Burner Airflow Measurement
Proven sol uti ons for a tough i ndustry
AIR MONITOR
POWER DI VI SI ON
IBAM
Performance Benefits
combination of fixed and/or adjustable inlet sleeve/disk
dampers, and in most installations the burners are equipped
with actuators to facilitate DCS controlled modulation of burner
SA airflow corresponding to varying fuel loads. Unfortunately
some low NO
x
burners come equipped with a non-calibrated
airflow sensing device and most others lack any means to
determine how much SA is entering the burner, resulting in
the need for extensive burner tuning targeted at meeting the
manufacturers NO
x
and CO emissions guarantees but not
repeatable or maintainable long term over varying load
conditions.
J ust as there are variances in fuel distribution to each burner,
multiple burners served by a common or partitioned wind box
can have substantial burner-to-burner imbalances in SA.
Accurate and repeatable measurement of individual burner
SA requires Air Monitor Powers IBAMs, airflow probes that
are economically feasible to retrofit into existing burners and
yet able to accommodate a variety of design challenges
the absence of any undisturbed cross section of airflow
passage; an installation location typically downstream of a
modulating inlet sleeve, disk or damper; a broad range of
boiler operating conditions; the presence of fly ash particulate
and 1200F operating temperatures; and for wall fired burners
the broad range of airflow pitch and yaw vectors produced by
the adjustable swirl angle blades.
The Need for Burner Airflow Measurement
The objectives in the power industry today are twofold; to
lower emissions, and increase plant performance. Precise
measurement of combustion airflow and fuel rates positively
contributes to achieving those objectives by providing the
information needed to optimize burner stoichiometric ratios
and facilitate more complete, stable combustion. As indicated
by the following chart, optimization of the key combustion
parameters of NO
x
, O
2
, LOI, CO, and boiler efficiency only
occurs within a narrow range of air-to-fuel ratios.
Traditional coal fired power plants lacked any means to
measure and control airflow into individual burners. New
burner designs prompted by Clean Air Act attainment levels
for NO
x
reduction are typically comprised of inner and outer
airflow barrels to introduce secondary air (SA) to the flame
ball, adjustable swirl angles blades in each barrel, a
O
2
Reduces NO
x
through furnace operation with less excess
air.