TS 02-000I Issue 0
MOTOR CAPACITORS
These Technical application notes try to facilitate to our customers and/or representatives, concrete answer to problems and doubts that can arise in the use of motor capacitors.
INDEX
Codification of motor capacitors according to DIN/VDE Selection of capacitance on motor capacitors Use of three phase motors in single phase networks
TS02000I.WPD
1/1
TS 02-010I Issue 0
H P F NT
2nd 3rd 4th 5th
CLIMATIC RANGE 1st digit Lower limit temperature Letter G H J K EC - 40 - 25 - 10 0 2nd digit Higher limit temperature1) Letter S R P M EC 70 75 85 100 F # 75 # 95 3rd digit Admissible limits of relative humidity (%)2) Letter Mean3) Max.4)
RELIABILITY 4th digit N of failures for 109 componentshour5) Letter M N P Q N 1000 3000 10000 30000 5th digit
Expected life5)
Letter S T U V
1)
Temperature measured on the surface of the capacitor In motor capacitors it is usual to use only the F range Yearly mean value Maximum value for a period non higher than to 30 days per year Pairs MS, NT, PU and QV give a failure rate (at the end of the expected life) lower than 3 % Example: NT, 300010-9 h-1 10000 h = 0.03 (3 %)
2)
3)
4)
5)
In the example HPF NT, meaning of the letters is then: H P F N T Lower limit temperature Higher limit temperature Limits of relative humidity Failure rate (at the end of expected life) Expected life - 25 EC 85 EC # 75 % Mean; # 95 % Max. #3% 10000 h
TS02010I.WPD
1/1
Selection of a permanent capacitor for a single phase motor implies the consideration of technical and economical aspects. As the winding of a single phase motor can be done in very different ways (division of the winding space between the main winding and the auxiliary winding, selection of the number of winding turns and sections of the winding, and so on), it is not possible to give universal rules to determine the capacitance and the working voltage of the capacitor for a certain power of the motor. It is then always necessary to apply the criteria established by the motor manufacturer. However, following it is exposed a calculation procedure with the only aim of being useful for a first evaluation and give an approximate idea of the values of the permanent capacitor: It is considered that in general, for each CV of power, a motor capacitor requires approximately a reactive power of 1 kvar. Power of the capacitor can be then determined from the following formula: QC = Where: QC = P = 1.35 P (kvar) Capacitor power in kvar Motor power in kW [1]
As the reactive power of the capacitor is being given by: QC = Where: UC = f = C = UC2 2 f C10-9 (kvar) Capacitor voltage in V Rated frequency in Hz Capacitance of the capacitor in F
Capacitance of the capacitor will be then given by: QC C = S)))))))))))))))Q UC2 2 f10-9
(F)
[2]
TS02011I.WPD
1/2
Voltage between terminals of the capacitor can be calculated from the current of the auxiliary winding of the motor: UC = S))))))))QQ 2 f C Where: IA = IA106 (V) [3]
Example: Motor of power P = 0.05 kW, with a current in the auxiliary winding of IA = 0.17 A First of all it is calculated the necessary power [1]: QC = 1.35 0.05 = 0.0675 kvar
immediately after, equations [2] and [3] are proposed 0.0675 C = S))))))))))))))))QQ UC2 2 5010-9 0.17106 UC = S)))))))))))))Q 2 50 C (V)
(F)
C = 1.4 F
UC = 397 V
TS02011I.WPD
2/2
TS 02-012I Issue 0
Remark:
The change of the connection terminal * of the capacitor allows to invert the turning sense of the motor.
Selection of the capacitor Approximate values of the capacitance on the required capacitor are indicated in the following table. Due to the crossing of the capacitor current through the winding of the motor, its working voltage is higher than the one of the network Network voltage (V) 220 V 110 V 380 V Capacitor C - 70 F/kW - 240 F/kW - 22 F/kW Capacitor voltage UC - 250 V - 125 V - 430 V
Output of the motor Values that can be expected from a three-phase motor connected to a single-phase network are those following: Starting torque: Maximum voltage: from the 25 to the 30% of the rated one from the 70 to the 80% of the rated power
REMARK:
If the starting torque is not enough, it can be improved by adding a motor start capacitor with a capacitance value of approximately two times the pointed. This capacitor must be dimensioned after having carried out test of real application test.
TS02012I.WPD