B 19 00 0 L21/31
Normal value at full load Lubricating Oil System Temp. after cooler (inlet filter) SAE 40 TI 21 PI 22 68-73 C 4.2-5.0 bar
Delay
Cut-off standstill
TAH 21 PAL 22 PSL 22 (PSL 22) (D) PDAH 21-22 PAL 25 PAL 23 LAL 28/LAH 28
80 C 3.5 bar 3.0 bar (2.5 bar) 1.5 bar 0.12 bar (H) 0.9 bar low/high level
Pressure drop across filter Prelubricating pressure Pressure inlet turbocharger Lub. oil level in base frame Pressure before filter Fuel Oil System Pressure after filter Leaking oil Temperature inlet engine MDO HFO Cooling Water System Press. LT system, inlet engine Press. HT system, inlet engine Temp. HT system, outlet engine MDO HFO
PI 21
4.5-5.5 bar
PI 40 PI 40
No No No
TI 40 TI 40
30-40C 110-140C
PI 01 PI 10 TI 12
Yes Yes No No No No
Temp. LT system, inlet engine Exhaust Gas and Charge Air Exh. gas temp. before TC Exh. gas temp. outlet cyl. Diff. between individual cyl. Exh. gas temp. after TC Ch. air press. after cooler Ch. air temp. after cooler Compressed Air System Press. inlet engine Speed Control System Engine speed elec.
TI 01
30-40C
TI 62 TI 60
480-530 C 350-450 C
No No No Yes No
TI 61 PI 31 TI 31
TAH 61
PI 70
7-9 bar
PAL 70
6.5 bar
15 sec
No
SI 90
1000 rpm
SAH 81 SSH 81 (SSH 81) (D) SAH 81 SSH 81 (SSH 81) (D)
1150 rpm 1130 rpm (1150 rpm) 1035 rpm 1017 rpm (1035 rpm)
SI 90
900 rpm
Turbocharger speed
SI 89
41000-54000 rpm
03.40
B 19 00 0 L21/31
Normal value at full load Turbocharger speed Alternator Winding temperature Miscellaneous Jet system failure Monitoring system failure Safety system failure Turning engaged Local indication Remote indication Common shutdown Monitoring sensor cable failure Safety sensor cable failure Start failure Stop signal Stop failure Engine run Ready to start SI 90 900/1000 rpm 24 VDC 15% 24 VDC 15% TI 98 100 C SI 89 41000-54000 rpm
Alarm set point and shutdown (autostop) set point SAH 89 (J)
Delay 3 sec
Cut-off standstill No
TAH 98
130 C
3 sec
No
switch switch switch Engaged (F) switch switch switch (F) switch switch switch (G) switch (F) switch 880 rpm (I) switch
Yes No No No
Yes No No No
30 sec
Yes
03.40
B 19 00 0 L21/31
G. Start Failure. If remote start is activated and the engine is in blocking or local mode or turning is engaged the alarm time delay is 2 sec. Start failure will be activated if revulutions are below 50 rpm within 5 sec. from start or revulutions are below 210 rpm 10 sec. from start. Start failure alarm will automatically be released after 30 sec. of activation. H. Alarm Hysterese. On all alarm points (except prelub. oil pressure) a hysterese of 0.5% of full scale are present. On prelub. oil pressure alarm the hysterese is 0.2%. I. Engine Run Signal. The engine run signal is activated when engine rpm >880 or lube oil pressure >3.0 bar or TC rpm >5000 rpm. If engine rpm is above 210 rpm but below 880 rpm within 30 sec. the engine run signal will be activated. J. Limits for Turbocharger Overspeed Alarm (SAH 89)
Engine type 5L21/31 6L21/31 7L21/31 8L21/31 9L21/31 900 rpm 52,600 52,600 44,700 44,700 37,300 1000 rpm 52,600 52,600 44,700 44,700 37,300
F. Start Interlock. The following signals are used for start interlock/ blocking: 1) 2) 3) 4) 5) 6) Turning must not be engaged Engine must not be running "Remote" must be activated No shutdowns must be activated. The prelub. oil pressure must be OK, 20 min. after stop. "Stop" signal must not be activated
03.40