Procedure of Seismic Design According to Saudi Building


Code 301
Posted by enjiner on June 14, 2013 Leave a Comment
SITE PARAMETER
(SECTION 9)
1. Seismic Ground Motion
Step 1: Determine ground motion spectral response acceleration
Ground motions acceleration are determined from Figure 9.4.1. These include:
SS : Earthquake spectral response acceleration at short periods
(figure 9.4.1 (b)~(i))
S1 : Earthquake spectral response acceleration at 1-second periods
(figure9.4.1 (j)~(q))
Step 2: Determine Site Class
Site Cl ass i s determi ned based on the site soi l properti es, it shal l be classifi ed as Site A, B, C ,D, E or F
i n accordance wi th Chapter 14.
Step 3: Determi ne Maximum considered earthquake spectral response acceleration
S
MS
= F
a
S
S
F
a
: Site coefficient based on site class (table 9.4.3a)
S
M1
= F
v
S
1
F
v
: Site coeffi cient based on si te class (table 9.4.3b)
Step 4: Determine Design Spectral Response Accel eration
S
DS
= S
MS
S
D1
= S
M1
2. Occupancy Importance Factor
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
An occupancy importance factor shall be assigned in each structure based on table 9.5. Occupancy
category is determined from table 1.6-1
3. Seismic Design Category
All building shall be classified to seismic design category based on their occupancy category (I) and
the design spectral response acceleration coefficients, S
DS
and S
D1
. Each bui lding shall be assigned to
the most severe seismic design category in accordance with Table 9.6.a or 9.6.b
*************
BUILDING PARAMETER
(SECTION 10)
1. Response Modification Coefficient, R
Response Modification Coefficient, R is determined
from Tabl e 10.2

2. Irregularities
Structures shall be classified as regular or irregular
based on Tabl e 10.3.2.1 (Plan structural irregularities) and Table 10.3.2.2. (Vertical structural
i rregulari ti es)
3. Seismic Load Effect and Combination
For Factored load combination 1.2D + 1.0L + 1.0E
E =Q
E
+0.2S
DS
D
For Factored load combination 0.9D + 1.0E
E =Q
E
0.2S
DS
D

4. Direction of Loading
Category A and B, the design seismic forces are permitted to be applied separately in each of two
orthogonal directions.
Category C and plan structural irregularity Type 5 (Table 10.3.2.1) shall be analyzed for seismic
forces using a three dimensional representation as 100% of the forces for one direction plus 30% of
the forces for the perpendicular direction.
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
5. Analysis Procedure
There are three permitted analytical procedures based on Table 10.6.1. These are
Index Forces Anal ysis 1.
Si mpli fied Anal ysis 2.
Equivalent Lateral Forces Analysis 3.
1. Index Forces Analysis
F
x
= 0.01
x
2. Simplified Analysis
F
x
=
x
3. Equivalent Lateral Forces
Step 1 : Determine the effective seismic weight of structures, W
W = Total dead load of structures +
In areas used for storage, a minimum 25% of the reduced floor live load 1.
The actual partition weight or minimum weight of 0.5 kN/m
2
where an al lowance for parti tion
l oad is i ncluded i n the floor l oad design
2.
Operating weight of permanent equipment 3.
Step 2 : Determined Fundamental Period, T
Approximate Fundamental Peri od
where C
t
and x are determined from Table 10.9.3.2
Fundamental Period
T = C
u
T
Where Cu is determined from Table 10.9.3.2.1

Step 3 : Determine seismic base shear, V
V =C
s
W
Where C
s
is the seismic response coefficient
C
s
=S
DS
/ (R/I)
C
s
shall not be greater than
C
s
=S
D1
/ T(R/I)
But shall not be less than
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
C
s
=0.044S
DS
I
Step 4 : Determine vertical distribution of seismic shear
F
x
=C
vx
V
C
vx
=w
x
h
x
k
/ w
i
h
x
k
k = 1 for the period 0.5 sec or less
2 for the period 2.5 sec or more
For period between 0.5 and 2.5 second, k shall be determined by linear interpolation
Example
A six story bui lding is to be constructed i n Gizan Soi l Type is SC (medium dense soil ). Each Story
height is 4 m. The plan area of the building is including overhang 700 m
2
. The first story slab i s
covering 60% of the total area. The structural system is an intermediate moment resisting concrete
frame
Compute the design base shear
Compute the l ateral force distributi on along the buildi ng
Hint, assume seismic weight as 14 kN/m2
Determine Seismic Ground Motion
Step 1
SS = 0.435 g
S1 = 0.124 g
Step 2
Site Class C
Step 3
S
MS
= F
a
S
S
= 1.2 x 0.435 = 0.52
S
M1
= F
v
S
1
= 1.68 x 0.124 = 0.21
Step 4
S
DS
= S
MS
= 0.52 = 0.35
S
D1
= S
M1
= 0.21 = 0.14
Occupancy Importance Factor, I =1
Seismic Design Category
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
Based on short period response accelerati on : C
Based on 1-second period response accelerati on : C
ResponseModification Factor, R =4
Seismic Load Effect and Combination
E =Q
E
0.2S
DS
D =1Q
E
0.07D
Factored Load Combination
1.27D + 1.0L + 1.0E
0.83D + 1.0E

Equivalent Lateral Forces
Step 1
W
1
= 60% x 700 x 14 = 5880 kN
W
2
= 700 x 14 = 9800 kN
W
3
= 700 x 14 = 9800 kN
W
4
= 700 x 14 = 9800 kN
W
5
= 700 x 14 = 9800 kN
W
6
= 700 x 14 = 9800 kN
W
total
= 54800 kN
Step 2
C
t
= 0.044
x = 0.9
T
a
=C
t
h
n
x
=0.044 x 24
0.9
=0.768 s
Step 3
C
s
=S
DS
/ (R/I) =0.35/ (4/1) =0.087
C
smax
=S
D1
/ T(R/I)=0.14 / 0.768(4/1)=0.045
C
smin
=0.044S
DS
I =0.044 x 0.35 x 1 =0.015
C
sused
= 0.045
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
V =C
s
W =0.045(54800) =2473.52 kN
Step 4
F
x
=C
vx
V
C
vx
=w
x
h
x
k
/ w
i
h
x
k
k =1.13
Floor Wi Hi(m) Wi Hi
k
Fi Fi (UBC)
1 5880 4 28331.1 59.54 109.74
2 9800 8 103646.6 217.81 365.80
3 9800 12 164167.2 344.99 548.70
4 9800 16 227508.7 478.10 731.60
5 9800 20 293034.1 615.80 914.51
6 9800 24 360354.0 757.27 1097.41
54880 1177042 2473.52 3767.76
You May Like
1. Paris is
Miley... a week ago HitFix.com
(sponsored)

2.
Fi led under -,..=\' -=..,\' / Civil Engineering
I am just an enjiner from desert for the worl d
Blog at WordPress.com. The Structure Theme.
Foll ow
About these ads
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...
Follow I am just an enjiner
Powered by WordPress.com
Procedure of Seismic Design According to Saudi Building Code 301 | I am just an enjiner
11/11/2013 http://enjiner.wordpress.com/2013/06/14/procedure-of-seismic-design-according-to-saudi-buildi...

You might also like