Technical Information Sheet KP1

MULTISTAGE PROTECTION for HIGH DENSITY MDF MODULES


Eart hing The protectors must be referenced to earth using an earthing strip (as photographed). Suitable earthing strips are available from Novaris. Specifications
Single pair KRONE LSA-PLUS module protector Protection modes: Transverse & common modes Connection type: Description: *

Introduction Modern digital switching systems are highly susceptible to transient voltage disturbances. The traditional protection offered by shunt-connected gas-filled arresters is no longer a suitable form of protection for these switches.
Novaris MDF module protectors feature dual stage protection providing lower let through voltages that provide a safe working environment for sensitive digital equipment.

Series. Plugs directly into KRONE LSA* PLUS disconnect blocks (earthing strip required)

Maximum working voltage: KP1-7V5: 7.5 V KP1-18: 18 V KP1-68: 68 V KP1-75: 75 V KP1-200: 200 V Working temperature: Working humidity: 0 90% Current rating: Bandwidth: 350mA > 20MHz 10kA per mode (8/20us) -40 85C

Peak surge handling:

O p erat io n Novaris single pair protectors are dual stage overvoltage protection modules designed for the protection of PSTN equipment and low voltage control circuits, against transient overvoltages caused by lightning, induced impulses and other voltage surges.
Each protection module contains a circuit that has primary protection provided by a gas-filled arrester and secondary protection provided by clamping diodes. The two stages are balanced by series impedance that has been designed to minimise the let-through voltage and maximise the life of the protector. KP1 protection modules are virtually maintenance free as they are designed to fail-safe. The PCB tracks between the line side terminals and gas arrester primary protection act as fuses, causing the line to open circuit in the event of a surge exceeding the capacity of the primary arrester. This failure mode is preferred to an open-circuit arrester that gives no indication of failure. If such a failure occurs, service is interrupted giving a positive indication of a fault condition.

Let-through voltage for 5kV 10/700us pulse: KP1-7V5: 10 V KP1-18: 23 V KP1-68: 75 V KP1-75: 85 V KP1-200: 220 V Standards compliance: ITU (CCITT) IX K17 AS1768-1991 cat. A, B BS6651 cat C CP33-1996 cat. A, B IEC61643-21 UL497B N2530 In-line resistance: 8.2 ohms

Options
Cat No. KP1-7V5 KP1-18 KP1-68 KP1-75 KP1-200 Maximum Working Voltage 7.5V 18V 68V 75V 200V

Specify earthing strips upon ordering if required

* KRONE LSA-Plus is a trademark of Krone GmbH, Germany

Novaris Pty Ltd


72 Browns Road, Kingston, TAS. 7050 AUSTRALIA Copyright 2001 Novaris Technologies E-mail: sales@novaris.com.au ABN: 33 065 427 232 TEL: +61 3 6229 7233 FAX: +61 3 6229 9245