You are on page 1of 9

Proceedings of Forum 2001

Solar Energy: The Power to Choose


April 21-25, 2001 Washington, DC

SIMULATION OF AN AIR-COOLED SOLAR-ASSISTED


ABSORPTION AIR CONDITIONING SYSTEM

*
Luis H. Alva and Jorge E. González .
Department of Mechanical Engineering
University of Puerto Rico – Mayaguez
Mayagüez, PR 00681-9045 USA

ABSTRACT. incorporates in a single unit the heat rejection and the


This paper investigates the technical feasibility of absorption system components. This work builds on prior
using a compact, air-cooled, solar-assisted, absorption air work by Tongu et al. [2] who proposed the option of air
conditioning system in Puerto Rico and similar regions. cooling, although not in combination with a solar energy
Computer simulations were conducted to evaluate the application. For the proposed system, air is used to cool
system’s performance when subjected to dynamic cooling the condenser and absorber of the absorption machine.
loads. Within the computer model, heat and mass The effects of using an air cooling process instead of
balances are conducted on each component of the system, water cooling are investigated in detail through computer
including the solar collectors, thermal storage tank, the simulations. Figure 1 shows the layout for the installation
air-cooled condenser, and the air-cooled absorber. of a 10.5 kW, air-cooled, absorption chiller in a typical
Guidance on component design and insight into the office building.
effects of such operating factors as ambient air
temperature were gained from exercising the simulation DESCRIPTION OF PRESENT WORK.
model. Comparisons are made with an absorption air The solar-assisted absorption system simulated in this
conditioning system that uses a cooling tower instead of work is represented in the schematic diagram of Fig. 2.
air-cooled components. The particular absorption system An arrangement of solar collectors in two parallel banks
of study is one that uses lithium bromide and water as the connected in serial is considered because it provides
absorbent and refrigerant, respectively. The heat input to higher temperature values than all the collectors mounted
the absorption system generator is provided by an array of in one parallel bank (Meza [1]).
flat plate collectors that are coupled to a thermal storage
tank. Systems having nominal cooling capacities of 10.5,
14, and 17.5 kW were considered. Useful information
about the number of collectors needed, storage tank
volume and efficiency of the overall system is presented.

INTRODUCTION.
The technical feasibility of solar absorption air
conditioning has already been proven for tropical climates
through the successful installation of a pilot system in the
city of Cabo Rojo, Puerto Rico (Meza et al. [1]). Typical
buildings in tropical islands are small requiring cooling
loads in the ranges of 10.5 and 35 kW, so the absorption
machines needed to fit this cooling loads must be smaller.
For this size of cooling load, the cooling tower commonly Figure 1: Conceptual layout for a 10.5 kW, compact air
used in the water cooled absorption machine is too large cooled, solar air conditioning installation.
and faces installation problems. As an alternative, a
technical feasibility study for an air cooling and compact As can be noted from Fig. 2, an air cooling system is
solar absorption system is presented in this paper. A considered to remove the waste heat from the condenser
compact air cooling absorption system is one that and the absorber of the absorption machine. The thermal

*
Author to whom correspondence should be addressed.
performance of the proposed system as a function of DESCRIPTION OF AN AIR-COOLED
ambient temperature and variable cooling load is obtained ABSORPTION MACHINE.
through a mathematical and computational simulation. Referring to Fig. 2, a diluted lithium bromide
solution is created in the absorber. This diluted solution is
pumped to the generator, gaining heat as it passes through
FAN 8 a liquid-to-liquid heat exchanger. Within the generator,
4 the diluted solution is heated by the hot water supplied
from the solar collector loop. A portion of the water is
1 3 boiled out of solution. The water vapor flows to the
FAN condenser, and the resulting, more-concentrated lithium
bromide solution flows back to the absorber, losing heat
as it passes through the same liquid-to-liquid heat
5 exchanger. The boiled-off vapor is air cooled as it passes
2 through the condenser coil. The two-phase refrigerant is
then throttled to a lower pressure and temperature before
7 entering the evaporator. In the evaporator, the refrigerant
6 gains heat from the chilled water loop that provides the
space cooling and dehumidification. After leaving the
evaporator as a vapor, the refrigerant flows back to the
• (1) solar collectors. (2) storage tank. (3) aux energy absorber. In the absorber, the concentrated solution from
source. (4) condenser. (5) generator.(6) heat the generator is air-cooled sufficiently enough to cause
exchanger. (7) absorber. (8) evaporator. the refrigerant vapor to be absorbed into solution. The
Figure 2:Air-Cooled Solar absorption System. resulting diluted solution is thermally pumped to the
generator, thus completing the cycle.
The optimal solar energy gain in the collectors is first
evaluated by comparing the following options: The computer simulation models how heat is
removed from the absorber and condenser by air cooling.
- A mass flow rate for the collectors of 0.024 The heat transfer in the absorber and condenser can
kg/m2s. This mass flow rate was obtained significantly influence the performance of the overall
experimentally by González and Khan [3] and is absorption cycle. A brief description of the details
a typical value for forced-circulation systems as considered in the simulation for the condenser and the
specified in the ASHRAE Standard 93 [4]. absorber is given below.
- Constant temperature increases between input
and output of collectors (Melendez [5]). Air-cooled Condenser.
- Maximum temperature increases between input The condenser is an air-cooled compact, finned-tube
and output of collectors. heat exchanger. The type of surface selected is a finned
- Maximum useful energy gain from the circular tubes, surface 8.0-3/8T (Kays and London [7]),
collectors. the surface geometric characteristics are:
With the optimized collectors, the thermal
performance of the proposed system is investigated under - Tube outside diameter = 0.0102 m.
dynamic cooling loads that are representative for a small - Fin pitch = 315 per meter.
office building in Ponce, Puerto Rico. The cooling loads - Flow passage hydraulic diameter = 0.00363 m.
are calculated using the CLTD method (Krieder & Rabl - Fin thickness = 0.00033 m.
[6]) and are supplied to the simulation program. - Free-flow area / frontal area, σ = 0.534
- Heat transfer area / total volume, α = 179 m2/m2
Finally, results are presented for cooling loads of - Fin area / total area = 0.913 .
10.5, 14, and 17.5 kW. For each case, the principal
parameters of operation are determined: number of solar The heat transfer from a bank of circular finned tubes
collectors, storage tank capacity, operating temperatures in cross flow is considered here and the number of tubes
for the air-cooled absorption machine, solar collector for the heat exchanger is calculated in the simulation
efficiency, and coefficient of performance (COP). program. The finned-tube rows are staggered in the
direction of the fluid velocity (see Fig. 3). The
superheated vapor comes from the generator into the
condenser tubes and is condensed as the heat is removed
in the tube bank by the cross-flow air. A similar flow

2
configuration was proposed by Tongu et al. [2] for their Specific characteristics of the finned-tube heat
air cooled machine. exchanger are:
- Heat exchanger effectiveness: 0.7
The characteristics of the finned-tube heat exchanger - NTU (Number of Transfer Units): 1.21
are: - Number of tubes: 524, 582, 640 (for 10.5, 14,
and 17.5 kW).
- Heat exchanger effectiveness: 0.76 - Outside tube diameter: 0.0102 m.
- NTU (Number of Transfer Units): 1.48 - Air-side heat transfer coefficient: 0.0516
- Number of tubes: 150, 175, 199 (for 10.5, 14, kW/m2*C.
and 17.5 kW).
- Outside tube diameter: 0.0102 m. DESCRIPTION OF SIMULATION.
- Air-side heat transfer coefficient: 0.14 kW/m2*C. The simulation scheme used here is a modified
version of the one presented by Hernández [8]. That
simulation is for a coupled system consisting of solar
CONDENSER collectors, a non-stratified storage tank and a single effect
absorption machine which used a cooling tower for
condenser and absorber heat rejection. The refrigerant
considered is a lithium bromide – water solution.
Air Modifications made to this prior model included replacing
the cooling tower used to remove heat from the condenser
Flow and the absorber with air cooling systems and to include
optimal flow control strategies in the collectors. In the
simulation, the tilted radiation is estimated hourly and
monthly for a location in Puerto Rico using the Perez
model (Perez et al. [9]). The southern city of Ponce
(latitude 18.2o, longitude 67.1o) was considered in the
Tube Bank
analysis. A variable cooling load for a typical building
Figure 3: Air-cooled Condenser. application is considered for the hours from 8:00 to 17:00.
Available data for temperature, the horizontal total
The final dimensions for the condenser were obtained radiation, and relative humidity are used (Hernández [8]).
with a simulation code through the Sha’s iterative scheme
given in Kays and London [7] using constant air The general sequential steps of the program are
temperature increases as controlling variable. This presented in Fig. 4.
resulted in:
- 0.366m x 0.366m x 0.229m for the 10.5 kW The input data for the program is:
case. - Cooling load.
- 0.427m x 0.427m x 0.229m for the 14 kW case. - Location in Puerto Rico.
- 0.488m x 0.488m x 0.229m for the 17.5 kW - Month.
case. - Load application hours.
- Solar collector characteristics. (Collector size
Air-cooled Absorber. 1.9812 m x 1.2192 m; selective absorber
A similar air-cooled compact, finned-tube heat material ).
exchanger used for the condenser is considered here for - Solar radiation data.
the absorber with the same finned circular tubes, surface - Design conditions for the absorber.
8.0-3/8T (Kays and London, 1984). The number of tubes
for the heat exchanger is calculated in the simulation The output data is:
program in order to satisfy the absorber heat transfer. In - Number of collectors.
this case, the concentrated solution comes into contact - Storage tank volume and temperatures.
with the absorber tubes and is air cooled. Vapor from the - Mass flow rates, temperatures and pressures for
evaporator is supplied over the cooled concentrated the absorption cycle.
solution and is eventually absorbed. The resulting - COP.
dimensions for the absorber were: - Collector efficiency.
- 1.07m x 1.07m x 0.27 for the 10.5 kW case. - Solar fraction.
- 1.07m x 1.07m x 0.31 for the 14 kW case. - Overall efficiency.
- 1.07m x 1.07m x 0.34 for the 17.5 kW case.

3
The second case considers a fixed temperature
increase between the collector inlet and outlet, and a
Input Data variable collector mass flow rate in the range from 0.01
and 0.09 kg/s. This approach was first suggested by
Melendez [5] using a flow range between 0.038 to 0.08
kg/s. The temperature increases considered here were 3
and 4 oC. Increases of less than 3 oC require mass flow
Hourly Cooling rates that are too small at the hours of lowest insolation.
Load Calculation For temperature increases of more than 4 oC, smaller
quantities of energy are obtained from the collector when
compared with the other cases.

Absorp. Machine For the third case, a maximum temperature increase


Design Condition. was obtained between input and output while the collector
mass flow rate was made variable. The maximum
increase was always obtained with the minimum mass
flow rate from the range considered.

Absorp. Machine Off- In the fourth case, the maximum useful energy gain
Design Conditions from the collectors was achieved by varying the collector
mass flow rate accordingly.

Higher energy values were obtained for the case of


Collect. Energy and maximum energy gain. The results were higher in 0.8%
Tank Temperature respect to the 0.024 kg/m2 s mass flow rate case, 3%
higher respect to the 4oC temperature increase case, 2.3%
higher respect to the 3oC temperature increase case, and
8% higher respect to the maximum temperature increase
case. The case considering the maximum increase of
Output Data temperature has the lowest performance, this is due to the
fact that higher collectors temperatures increase energy
losses.
Figure 4: General Program Flow Chart.
Figures 5 shows results for the evaluation of the
RESULTS. optimum mass flow rate through the collectors. Figure 5
Optimum Energy from the Solar Collectors. shows results for a typical bank of collectors consisting of
To obtain the largest quantity of energy from the 32 collectors. Comparable performance was predicted for
solar collectors, different alternatives where taken into the cases of a 0.024 kg/m2 s mass flow rate, a 4oC
account. The coupled system: collectors – storage tank – increase, a 3oC increase, and a maximum energy gain.
absorption machine was considered for the simulation.
The alternatives considered were: Total Heat from Collectors -17.5 kW-July

- A mass flow rate from the collectors, 0.024 120000


kg/m2s (González and Khan [3]). 100000
- Constant temperature increase between the input
Qut (kw)

80000
and output of the collectors.
60000
- Maximum temperature increase between the
40000
input and output of the collectors.
20000
- Maximum useful energy gain from the
0
collectors.
8 9 10 11 12 13 14 15 16 17

For the first case a mass flow rate for the collectors of Hour
0.024 kg/m2s (González and Khan [3]) was considered, 0.058 kg/s Delta 4 C Max. Qu Delta 3C
remaining constant for all the operational hours.
Figure 5: Total Energy from Collectors.

4
Optimum Solar Collectors and Storage Tank. to be 32. Using less collectors is predicted to yield a solar
The optimum number of collectors for the absorption fraction that is less than 100 percent at the hour of
system to meet was predicted for three dynamic cooling maximum radiation. Using more collectors than 32 does
loads using the simulation program. The three cooling not make a higher solar fraction at the hour of maximum
loads were based on peak demands of 10.5, 14, and 17.5 radiation. The design thus would be oversized.
kW.

Table 1 shows the mass flow rates and temperature Solar Fraction vs Num ber of Collectors
increases for the cases considered. Comparison between
cases shows the expected inverse relationship between 102

Solar Fraction
mass flow rate and temperature rise. For the four best 100
cases, the overall heat transfer, however, is virtually the 98
same. 96
94
92
Hour Co.M.FlowR. Max.Delta T Delta T 4 C Max. Qu Delta 3 C 30 31 32 33 34
mc Del.T mc Del.T mc Del.T mc Del.T mc Del.T Num ber of Collectors
(Kg/s) ( C) (Kg/s) ( C) (Kg/s) ( C) (Kg/s) ( C) (Kg/s) ( C)
8 0.058 1.1 0.01 5.69 0.015 4 0.09 0.72 0.02 3
9 0.058 2.25 0.01 11.65 0.032 4 0.09 1.46 0.043 3 Figure 6: Solar Fraction vs Collector Number for the
10 0.058 3.54 0.01 18.39 0.051 4 0.09 2.3 0.069 3 hour of maximum solar radiation in Ponce, and for the
11 0.058 4.18 0.01 22.21 0.061 4 0.09 2.72 0.082 3 17.5 kW cooling case.
12 0.058 4.69 0.01 25.36 0.069 4 0.09 3.05 0.09 3
13 0.058 4.35 0.01 23.88 0.063 4 0.09 2.83 0.085 3
14 0.058 3.22 0.01 17.92 0.047 4 0.09 2.09 0.063 3 The storage volume is calculated as a function of the
15 0.058 1.82 0.01 10.04 0.026 4 0.09 1.18 0.035 3 optimum number of collectors. The optimum storage
16 0.058 0.41 0.01 2.22 0.026 4 0.09 0.27 0.035 3 volume to collector area ratio for a static cooling load
17 0.058 0 0.01 0 0.026 4 0.09 0 0.035 3
condition was reported by Hernández [8]. The reported
value was 40.5 l/m2. For a dynamic cooling load, higher
values for the storage volume to collector area ratio were
Table 1 : Collector Mass Flow Rate and Delta Temp. for :
predicted to be needed to maximize the annual solar
0.58 kg/s, Max. Temp. Increase, 4oC Increase, Maximum
fraction, Fig. 7. The higher values obtained under a
Collector Energy and 3oC Increase.
dynamic cooling load can be explained as being due to the
delay in the peak loading. In the dynamic case, a smaller
cooling load is reflected at the hours of maximum solar
Table 2 shows the predicted optimum number of
radiation. More energy storage is needed to compensate in
collectors for the three cases. The optimum number of
the peak cooling load occurring at a time when the solar
collectors is the lowest number of collectors for which a
radiation is decreasing. Therefore, a higher storage tank
100 percent solar fraction is achieved at the hour of
volume is required. The value of 125 l/m2 is projected as
maximum solar radiation. For the case of Ponce, the hour
the optimum value for the 10.5, 14, and 17.5 kW cases.
is 12:00 in the month of July.
Figure 8 shows the collector efficiency, COP, and
k W O p tim u m
solar fraction for the air-cooled absorption system when
C o ll.N u m . subject to a dynamic cooling load. Similar results were
1 0 .5 1 9 found for the 10.5, 14, and 17.5 kW cases. The solar
1 4 2 5 fraction expresses the contribution of the solar energy to
1 7 .5 3 2 the total load in terms of the fractional reduction in the
amount of extra energy that must be supplied. The COP is
Table 2: Optimum Number of Collectors for Ponce, given by:
Puerto Rico (collector area 2.42 m2).
Q& evap
Figure 6 shows the solar fraction vs the number of COP =
collectors for the 17.5 kW cooling load case and Ponce Q& gen
location. The optimum number of collectors is predicted

5
where Q& evap is the heat removal rate at evaporator in kW, Air Cooling Absorption System - Dynamic Cooling

Q& gen is the heat supply rate to generator in kW.


Load
and
120 1

Coll. Eff. - COP


Solar Fraction
100 0.8
80 0.6

(%)
Annual Solar Fraction vs Storage Volume per m2 of 60 0.4
Collector Area for Ponce 40 0.2
20 0
0 -0.2
105 8 9 10 11 12 13 14 15 16 17
100
Hour
Annual Solar Fraction

95
90
85 Solar Frac. Coll. Eff. COP
10.5kW
80
75
14kW Figure 9: Hourly solar fraction, COP and coll. efficiency–
70 17.5kW Month: July – Location Ponce, air cooling absorption
65 system under dynamic cooling load.
60
55 A comparison between both cases, water and air
50 cooled, indicates that annual solar fractions for Ponce
0 25 50 75 100 125 150 175 200 225 250
were found to be 67.9% for the case of water cooling
Liters/m2 (cooling tower), 71.8% for the case of air cooling and a
static cooling load, and around 76% for air cooling and a
dynamic cooling load as shown in Fig. 8. As can be seen
Figure 7: Annual solar fraction vs storage volume per from Fig. 9 and 10, values for COP looks similar,
collector area ratio, for location Ponce and dynamic however there are some differences. The solar fraction is
cooling load. higher for the case of air-cooling and dynamic cooling
load because the peak load is delayed. The lowest values
for the collector efficiency are for the cooling tower case
due to the lack of phase between cooling load and solar
Annual Solar Fraction radiation.

Similar results were found for the 10.5, 14, and 17.5
Annual Solar Fraction

80
kW cases, so the annual solar fraction is almost constant
75
when considered as a function of the cooling load.
(%)

70
65
Cooling Tower Absorption System
60
10.5 14 17.5 120 1
0.9
kW 100 0.8
Solar Fraction

Coll. Eff. - COP


0.7
80
0.6
Colling Tower Air C.-Static L. Air C.-Dynam. L.
60 0.5
0.4
Figure 8: Annual Solar Fraction. 40 0.3
0.2
20
0.1
Results of collector efficiency, COP and solar 0 0

fraction for the case of using a cooling tower are shown in 8 9 10 11 12 13 14 15 16 17

Hour
Fig. 9. Similar values were found for the 10.5, 14, and
17.5 kW cases. Solar Frac. Coll. Eff. COP

Figure 10: Hourly solar fraction, COP and coll.


efficiency– Month July – Location Ponce, for cooling
tower under static cooling load.

6
Finally, the overall efficiency is calculated using the between the cases in study. Figure 14
relationship suggested by Meza et al. (1998): shows the condenser pressure for air cooling and water
cooling. In general, higher values for the case of air
Qe cooling with respect to the water cooling case were found.
η oe = *100
IT * Ac Air Cooling and Water Cooling Temperatures
where:
43
Qe : evaporator heat in kJ/hr. 41
IT : hourly total radiation in kJ/hr*m2.

Temperature (C)
39
Ac : total collector area in m2. 37
35
33
31
Overall Efficiency for 13:00 hour
29
27
36.3 25
8 10 12 14 16
36.2
Hour
36.1
Cooling Tow er
(%)

36.0 Tamb Tcond(CT) Tabs(CT) Tcond(AC) Tabs(AC)


Air Cooling
35.9
35.8 Figure 12: Absorption Cycle Temperatures for Air
35.7 Cooling and Water Cooling.
13
Hour
Figure 15 shows the COP vs ambient temperature for
the air cooling absorption system. As can be noted the
Figure 11: Hourly overall efficiency. COP decreases as the ambient temperature increases.

In practical terms Qe is the useful cooling of the Figure 16 shows the COP for air cooling and water
conditioned space. The overall efficiency for the hour of cooling, and some higher value is noted for the case of air
maximum solar radiation (13:00 for Ponce) for the case of cooling in the earlier and later hours with respect to water
air cooling and water cooling (cooling tower) is shown in cooling. From 11:00 to 15:00 the air cooling COP
Fig. 11. As can be seen, values are almost the same for decreases due to the increase in the ambient temperature,
both cases. Similar results were found for the 10.5, 14, while the cooling tower one keeps almost constant.
and 17.5 kW cases.

Thermal Performance of the Absorption Air Cooling and Water Cooling Generator Temperatures
Machine.
The thermal performance of the proposed air-cooled
absorption machine was investigated in further detail and 90 33 Ambient Temperature (C)
32.5
Temperature (C)

similar results were found for all three cases. Results are 88 32
provided in Fig. 12 and 13. Hourly results are obtained in 86
31.5
31
the simulation program for the thermodynamic cycle of 30.5
84
the absorber. 30
82 29.5
29
Figure 12 shows the condenser and absorber 80 28.5
temperature for air cooling and water cooling absorption 8 10 12 14 16

machines and the ambient temperature for the working Hour


Tgen(CT) Tgen(AC) Tamb
hour cycle from 8:00 to 17:00. While the water cooling
values are steady the air-cooling values change as the air
temperature changes. Some difference is noted during the
Figure 13: Generator Temperatures.
early and late hours respect to the water cooling values.
Figure 13 shows values for the generator temperature for
air cooling and water cooling. Similar trends are noted

7
CONCLUSIONS.
Air Cooling and Water Cooling Pressures
This paper presents simulation results for the thermal
performance for a conceptual air cooled absorption air
8.30
conditioning system. Air cooled absorption machines
8.20 could have the great advantage of reducing maintenance
Pressure (KPa)

8.10 and cost when compared with conventional water cooled


ones for small cooling loads. The present paper focused
8.00
in dynamic cooling loads in the range of 10.5, 14, and
7.90 17.5 kW.
7.80
8 10 12 14 16 It was found that the maximum quantities of energy
Hour gained by the solar collectors were obtained when using
the maximum useful energy gain as control variable when
Pcond (CT) Pcond (AC)
compared with three other operational modes. The
constant collector mass flow rate case obtained values
Figure 14: Condenser Pressure. only 0.8% lower respect to the maximum useful energy
gain case. The other two cases showed larger differences
when compared with the case of maximum useful energy
gain.
COP vs Ambient Temperature

The optimum value found for the storage volume to


0.775 collector area ratio for a dynamic cooling load was
0.77 achieved is 125 liter/m2. This value is higher respect to
0.765 the 40.5 liter/m2 value for static cooling load reported by
0.76
Hernández [8].
0.755
Very similar results were found for the collector
0.75 efficiency, the solar fraction and COP for air cooling and
25 26 27 28 29 30 31 32 33 34 35 36
water cooling cases especially at the hours with maximum
Ambient Temperature (C)
solar radiation for working hours from 8:00 to 17:00.

The results for the thermodynamic properties for the


air-cooled absorption cycle are very close to those for the
Figure 15: COP vs ambient temperature for air cooling. absorption cycle with cooling tower, specially at the hours
of higher solar radiation. Similar trends were found for
10.5, 14, and 17.5 kW cases.

COP The COP for the air cooled absorption machine


decreases as the ambient temperature increases.
0.7700

ACKNOWLEDGMENTS.
0.7650
This work was partially supported by the National
0.7600 Science Foundation under grant number STTR 9960710.
0.7550
REFERENCES.
0.7500
[1] Meza J.I., A. Y. Khan, and J. E. González, 1998,
“Experimental assessment of a solar-assisted air
0.7450 conditioning system for applications in the
8 9 10 11 12 13 14 15 16 17
Caribbean”, Proceedings of the Solar Engineering
H o ur
1998 Conference, pp. 149-154, New Mexico.
Air Cool. Col. Tow.

[2] Tongu S., Y. Makino, K. Ohnishi, and S.


Figure 16 : COP of the Absorption Cycle. Nakatsugawa, 1993, “Practical operating of small-
sized air-cooled double effect absorption chiller-
heater by using lithium bromide and aqueous”,

8
International Heat Pump Conference, ASME, AES- [8] Hernández H., 1997, “Analysis and Modeling of a
Vol. 31. Solar-Assisted Air Conditioning and
[3] González, J. E. and A. Y. Khan, “Solar-Assisted Dehumidification System for Applications in
Air Conditioning System for Applications in Puerto Rico”, M.S. Thesis, University of Puerto
Puerto Rico”, Final Report 96-311 of the Urban Rico – Mayagüez.
Consortium Energy Task Force.
[9] Pérez R. R., R. Seals, P. Ineichen, R. Stewart, and
[4] ASHRAE 93-1986, “Methods of testing to D. Menicucci, 1987, “A new simplified version of
determine the thermal performance of solar the Perez Diffuse IrradianceModel for tilted
collectors”, American Society of Heating surfaces”, Solar Energy, Vol.39,pp. 221-231.
Ventilating and Air Conditioning Engineers,
Atlanta, Georgia. [10]ASHRAE, 1993 ASHRAE Handbook –
Fundamentals, American Society of Heating
[5] Meléndez L, 2000, “Automation and Control of Ventilating and Air Conditioning Engineers,
Solar Air Conditioning Systems”, M.S. Thesis, Atlanta, Georgia.
University of Puerto Rico – Mayagüez.
[11]Hernández H., J.E. González, and A.Y. Khan,
[6] Kreider J.and A. Rabl, 1994, “Heating and Cooling 1997, “A parametric study of solar assisted air
of Buildings”, McGraw-Hill. conditioning and dehumidification systems
operating in the Caribbean region”, Proceedings of
[7] Kays W.M. and London, A.L, 1984,.”Compact the Solar Engineering 1997 Conference, pp. 327-
Heat Exchangers”, third Ed. McGraw-Hill Book 333, Washington, D.C.
Company. New York.

You might also like