Contents
External structure Basic features and interrupting operation Standards and certification Types and ordering information Type of circuit breakers Ratings Accessories Control circuit diagrams Dimensions Technical data 26 28 31 32 40 43 51 82 86 142
Susol VCB is full line-up new VCB which has the high interrupting capacity, large current(~50kA, ~4000A), and maximized compatibility with existing products through the dual phases and compact sized models.
Vacuum Circuit Breaker, VCB is installed in the medium voltage distribution lines to protect life and load equipment. In case of accidents such as over current, short circuit and ground fault current, VCB works by interrupting the circuit through the inner Vacuum Interrupter which is acted by signal from the outside separate relay. LSIS' Super Solution, Susol VCB responds. - customer needs for the breakers with high interrupting capacity and large current due to the integration and increase of the load capacity. - worldwide trend of diversification in the medium voltage distribution lines. - increase of the reliability for the temperature characteristics of circuit breakers. Premium-type products to improve convenience and reliability of medium voltage switchgear configuration. - full line-up modeling to the high interrupting capacity and large current. - main structure with high reliability application. - a variety of accessories and ability to maximize. Suitable for use as the main circuit breaker to protect key installations in the places such as device industry, power plants, high-rise buildings, large ships.
Interrupting current
8/12.5/20/25/31.5/40/50kA 20/25/31.5/40/50kA 12.5/25/31.5/40kA 25/31.5/40kA 25/31.5kA
Rated current
400/630/1250/2000/3150/4000A 630/1000/1250/2000/3150/4000A 630/1250/2000/2500/3150A 1250/2000/3150A 1250/2000/3150A
Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor). Strong structure for the temperature rise (Natural cooling system).
Convenience of switchgear configuration and a variety of
accessories.
CB compartment structure: Metal isolation structures to prevent the accident spread and ensure safety. And the convenience of switchgear building is extended by its module style. A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock, Temperature Sensor, MOC, TOC, Earthing S/W. Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
Type testing is complete for all models according to latest standard, IEC62271-100 (2008) [M2, E2 (List1 or 3), C2].
7.2kV (VL-06)
Rated short-time (for withstand current ): 3sec. Rated operating sequence: O-0.3s-CO-15s-CO Type test level: M2, E2 (List1), C2 Electrical and mechanical life: 30,000 operations 100% Compatibility - with existing fixed type breakers - with existing drawout type breakers Various cradle: E, F and G type A variety of control power - DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V - AC 48V, AC 100~130V, AC 220~250V A variety of accessories - Charge switch, UVT, Secondary trip Coil, Current trip coil, Trip Latch Checking S/W, Position S/W - Key-lock, Button lock, Button cover, Padlock, UVT, Time Delay Controller, Lifting hook, CTD TEST/SERVICE Automatic Position Indicator Standards and certification - IEC62271-100 (2008) [M2, C2, E2 (List1)] - Tested in enclosure - KERI type tested, V-check (KESCO) certification
Ur (kV) 7.2
<<
7.2/12/17.5kV (VL-06/12/17)
Rated short-time (to withstand current ): 3sec. 4sec* Rated operating sequence: O-0.3s-CO-15s-CO Type test level: M2, E2 (List3), C2 Electrical and mechanical life: 30,000 operations Compatibility with existing Pro-MEC breakers Various cradle: E, F, G and H type CB Compartment for MCSG available A variety of control power - DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V - AC 48V, AC 100~130V, AC 220~250V A variety of accessories - VCB part: Charge switch, UVT, Secondary trip coil, Latch checking switch, Position switch, Locking magnet, Plug interlock, Key lock, Button cover, Button padlock, Padlock (H type Door interlock), MOC - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck Operated Cell switch), Temperature sensor, Earthing switch & accessaries, Door, Door interlock, Door emergency button - Others: Racking in/out handle, UVT Time delay controller, CTD (Condensor Trip Device), Temperature module TEST/SERVICE Automatic Position Indicator Standards and certification - IEC62271-100 (2008) [M2, C2, E2 (List3)] - KEMA, KERI type tested, V-check (KESCO) certification
Note ) * Please contact us
7.2/12/17.5/24/36/40.5kV (VH-06/12/17/24/36/40)
Rated short-time (to withstand current ): 3sec. 4sec* Rated operating sequence: O-0.3s-CO-3min-CO Type test level: M2, E2 (List3), C2 Electrical and mechanical life: 20,000 operations Various cradle: K and H type CB Compartment for MCSG available A variety of control power - DC 48V, DC 110V, DC 125V, DC 220V - AC 48V, AC 110V, AC 220V A variety of accessories - VCB part: UVT, Secondary trip coil, Latch checking switch, Position switch, Locking magnet, Plug interlock, Key lock, Button cover, Button padlock, Padlock (H type Door interlock), MOC - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck Operated Cell switch), Temperature sensor, Ur Isc Ir Earthing switch & accessaries, Door, Door (kV) (kA) (A) interlock, Door emergency button 31.5 1250 7.2 2000 12 - Others: Racking in/out handle, Lifting hook, 3150 UVT Time delay controller, CTD (Condensor 40 1250 2000 Trip Device), Temperature module 3150 4000 Standards and certification 50 1250 - IEC62271-100 (2008) [M2, C2, E2 (List3)] 2000 2500 - KEMA, KERI type tested, V-check (KESCO) 3150 certification 4000
Note ) * Please contact us 17.5 50 1250 2000 2500 3150 2500 1250 2000 3150 1250 2000 3150 1200 2000 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150 1250 2000 3150
Ur (kV) 7.2
Isc (kA) 20
Ir (A) 630 1250 2000 630 1250 2000 630 1000 1250 2000 630 1000 1250 2000 630 1250 2000 630 1250 2000
24
25 31.5
40
25
27 36
25 25
12
20
31.5
25
40
17.5
20
40.5
25
25
31.5
Susol
VCB
Breaker
Insulation rod Lower terminal Shunt Vacuum interrupter Upper terminal Tulip contactor
Contacts
Vacuum Interrupter, VI
The vacuum rate within the VI is very high the contacts are made of special alloy (copper(approximately 5x10-5 Torr) and the spacing chromium) and the interior is completely sealed between fixed contact and movable contact to prevent loss of vacuum. is about 6~20mm, depending on the Therefore the wearing of the contacts can be voltage. minimized in the event of short-circuit and the
The contacts are in a structure that arc can arc energy by overvoltage or switching can be easily be extinguished and the surfaces of reduced effectively.
<<
Stego Tulip
Main circuit structure with high reliability
Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor) Strong structure for the temperature rise (Natural cooling system)
Tulip finger
Tulip spring
Plate star: Supporting Tulip for position maintaing and torsional flow prevention
10
<<
6/12/17.5/24/36/40kV...
(VH-06/12/17/24/36/40)
Drawout / natural cooling system Improved temperature characteristics and ensured high reliability
11
CB Compartment
Convenience in building switchgears
CB compartment structure: H type cradle Metal isolation structure to prevent the accident spread and ensure safety Convenience of switchgear building
7.2/12/17.5/24/36/40.5kV 20/25/31.5/40/50kA
Metal isolation structure to prevent the accident spread and ensure safety Convenience of operation by Truck - Drawable in the closed position of the switchgear door - Racking-in/out positions indicated mechanically Equipped with safety devices and accessories - Control power connected Interlock - Earthing S/W and interlock, MOC/TOC (ANSI) Convenience in building switchgears - Module assembly with CB compartment
12
<<
LV Compartment
PT Compartment
Key lock for Earthing S/W Locking Magnet for Earthing S/W Position S/W for Earthing S/W TM (Temperature Monitoring Unit)
13
Cradles
E, F, G and H type... Variety of the Cradles
E type
E type
Economic style cradle with the basic structure No safety shutter and bushing For MESG Applies VL type VCB
E type
F type
H type
14
<<
H type
Metal isolation structure to prevent the accident spread and ensure safety Convenience of operation by Truck - Drawable in the closed position of the switchgear door - Racking-in/out positions indicated mechanically - Control power connected Interlock Convenience in building switchgears - Module assembly with CB compartment - Assembly with CT/PT integrated compartment Applies VL/VH type VCB
F type
Safety shutter has been added to the cradle of type E No bushing For MESG Applies VL type VCB
G type
Premium style cradle with safety shutter and bushings For MESG Applies VL type VCB
VL type
VL type
VL, VH type
15
Convenience
Convenience in building switchgears
- Maximizing compatibility with existing products through the dualistic deployment of phases and compact models.
150 150 210
210
VCB rating
Ur (kV) 12 Isc (kA) 20/25 Ir (A) 630 1000 1250 630 1000 1250
17.5
20/25
150 150
210
210
VCB rating
Ur (kV) 12 17.5 Isc (kA) 20/25 20/25 Ir (A) 2000 2000
210
210
275
275
VCB rating
Ur (kV) 24 25.8 Isc (kA) 31.5/40 31.5/40 Ir (A) 2000 2000
16
<<
17
Accessories
A variety of accessories for VL-06
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor Closing coil Trip coil Counter Auxiliary contacts UVT coil Current trip coil Key lock Button padlock Button cover Position switch Lead wire
18
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle
Handle for Racking-in and out UVT time delay controller Condenser trip device
19
Accessories
A variety of accessories for VL-06/12/17
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor Closing coil Trip coil Counter Auxiliary contacts UVT coil Key lock Button padlock Button cover Position switch Handle for Racking-in/out UVT time delay controller Condenser trip device (CTD) MOC Padlock (H type Door Interlock) Locking magnet Plug Interlock
20
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle (H type)
TOC (Truck operated cell s/w) MOC (Mechanical operated cell s/w) Temperature sensor Door Door interlock Shutter padlock Emergency ON/OFF button Earthing switch & Accessary Key lock for Earthing switch Locking Magnet for Earthing switch Position s/w for Earthing switch TM (Temperature monitoring unit)
21
Accessories
A variety of accessories for VH-06/12/17/24/36/40
If accessories are attached to the breaker, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Breaker
Motor AC/DC coil rectifier Trip coil/Closing coil Secondary trip coil AC/DC UVT coil rectifier UVT coil Latch checking switch Auxiliary contact wire Key lock Button cover/Push bar Button padlock Position switch Locking magnet Plug interlock Door Interlock for withdrawable type Lifting hook Charge handle Racking in/out handle UVT Time delay controller CTD (Condenser trip device)
22
<<
If accessories are attached to the cradle, the function of the breaker is upgraded. Susol VCB provides a variety of accessories depending on the purpose.
Cradle (H type)
MOC (Mechanism operated cell switch) TOC (Truck operated cell switch) Shutter padlock Temperature sensor Door Emergency ON/OFF button Earthing switch & Accessaries Key lock for Earthing switch Locking magnet for Earthing switch Position switch for Earthing switch TM (Temperature monitoring unit)
23
IEC62271-100 (2002)
274
IEC62271-100 (2008)
274
268 260
268 260
130
130
116
104
116
104
72
66 36
72
66 36
15
9 3 10 30 60 100(sym) 100(asym)
15
9 3 10 30 60 100(sym) 100(asym)
Arc Energy: List 1 (100%) < List 2 (125%) < List 3 (134%)
E2 List1 E2 List3
E2 List2 E1
24
<<
M2, C2
IEC standards to verify the relibilty of the product allows to select the quality level for the product to be tested according to its real performance and practical usage. The highest quality level of M2, C2 has been applied to Susol VCB.
2000 operation test Sequence C-O C-O C-O O - CO - C Control Voltage 85% 100% 110% 100% Number of operations 500 500 500 250
M2
10,000 10,000 operations operations
M1
operations
2,000
operations
2,000
Pre-test (characteristics, isolation, and temperature) Pre-test (characteristics, isolation, and temperature) Confirmative tests after the completion of 2000 operations Confirmative tests after every 2000 operation Confirmative tests after the completion of 10,000 (Characteristics, isolation, temperature) operations (Characteristics, isolation, temperature)
C1, C2: Capacitive current breaking test is to verify the probability of restriking and C2 class is secured for all Susol VCB.
C1
C2
25
Back side
26
Back side
27
Manual operation
Manual Charge a) VL type: operate the charge handle 7-8 times as a fully stroke. b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and then charge will be complete with a click sound. - When the closing spring is charged fully "CHARGED" is displayed at the charge indicator. Manual closing a) Pressing the ON button the breaker is closed. b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and "DISCHARGED" at the charge indicator. Manual trip a) Pressing the OFF button the breaker is opened. b) "OFF" is displayed at Close/Trip indicator.
Electric operation
Electric charge The breaker is remotely closing with charging of closing spring. If the breaker trips the closing spring is automatically charged by gear motors. Electric closing Remote closing is operated by the closing coil. Electric trip Remote trip can be operated by the trip coil or UVT coil. Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the mechanism. Breaker is closed by closing coil and tripped by trip coil. These operations are repeated in VCB as shown in the below sequence chart.
Start closing Closing signal Control power ON Charging time of closing spring (VL type : 5 sec, VH type : 12 sec.)
Main contacts Closing coil Motor Closing spring Opening spring Trip coil
Closing time Opening time
28
The interruption of VCB is carried out by the vacuum interrupters. Interrupter contacts as a key part made of copper - chromium (CuCr) material with spiral shape have low contact wear characteristics and withstand voltage is excellent. Spiral contacts make the arc generated between the surfaces of contacts rotated around the surface of contact by the induced magnetic field generated due to the spiral contact structure, which results in preventing local heating, thereby corruption and interrupting instantaneously.
Fixed electrode
Fixed shield
Contacts
Bellows shield
Bellows
An example of oscillogram obtained through the interrupting test using LC resonant circuit
29
In case of using the flat contact any of the designs do not reflect on when contacts are opening the arc with high temperature is contracted and fixed in the center of the contacts,Which is called pinch effect. To prevent the effect two kinds of contact shapes are designed. One is Axial magnetic field which spreads the arc before its contraction, and the other is Radial magnetic field which permits the contraction of the arc but makes it rotated to disperse the energy. Because contracted arc is shaped like a cylinder it is called Contracted arc or columnar arc.
Arc voltage waveforms and arc image captured during arcing time
Spiral contact structure (Radial magnetic field), using the force (F = jB) generated by the interaction of the radial magnetic field caused by the current flowing through the arc between two contacts, disperse the arc energy evenly on the surface of contact by rotating the arc that is contracted by the pinch effect so as to minimize contact damage. The images show arc behavior during the arcing time of about 8ms by shooting with high-speed camera capable of shooting 10,000 frames per sec. (0.1ms/frame) by focusing on parts of the arcing time on the above graph and simultaneously measured arc voltage also represented to show arc state by section.
30
Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international testing laboratory and can be installed and applied at the environment and conditions in accordance with the standard. Standard - IEC 62271-1 (2007.10) High-voltage switchgear and controlgear - Part 1: Common specifications. - IEC 62271-100 (2008.04) High-voltage switchgear and controlgear - Part 2: Alternating-current circuit breakers. Test and certification Test report (KERI) Test report (KEMA)
31
VL
Basic model name VL Susol VCB
06
Rated voltage (kV) 06 7.2 P E F G
P
Version Fixed E type drawout F type drawout G type drawout
08
Interrupting current (kA) 08 13 8 12.5 B
A
Phase distance/Compatibility A Standard Compatible with existing breaker Note6)
04
Rated current (A) 04 06 400 630
VL-06E08A04
M1
C1
T1
SA1
U1
14 7
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V T0 T1 T2 T3 T4 T5 T6 T7 T8 T9
Trip coil voltage Without trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Current trip coil U0 U1 U2 U3 U4 U5 U6 U7 U8
UVT
Note5)
Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
Closing coil voltage C0 C1 C2 C3 C4 C5 C6 C7 Without closing coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V SA1
Connector and wire A type connector, 2a2b 1 3 SA3 SA5 Flame SA6 retardant SA7 A type connector, 6a6b
Note5)
SA2 Standard A type connector, 4a4b A type connector, 6a6b A type connector, 2a2b 4 A type connector, 4a4b 5
(Test: 1a1b, Service: 2b) Position S/W (Test: 2a, Service: 2a) Position S/W (Test: 1a1b, Service: 1a1b)
Note) 1. In the case of selecting accessories such as A1(Secondary C8 AC 200V~250V trip coil), A4(Position S/W 2a2a)and A7(Key lock), A147 is type name in the ordering. 2. Unable to select A1(Secondary Trip coil), U1~U8(UVT)and T9(Current trip coil) simultaneously. 3. A4(Position S/W 2a2a) and A5(Position S/W 2a2b) can not be selected simultaneously. 4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously. 5. Maximum number of Auxiliary Contacts available are 5a5b, 5a6b and 6a5b in the case of selecting A1(Secondary trip coil), U1~U8(UVT).
7 8 9 A B O
Key lock Button Padlock Button cover Lead wire User Plug (Part) Lead Wire special color (Blue)
CTD1 Condenser Trip Device (AC 110V) CTD2 Condenser Trip Device (AC 220V) UDC1 UVT Time Delay Controller (AC/DC 110V) UDC2 UVT Time Delay Controller (AC/DC 220V) UDC3 UVT Time Delay Controller (AC/DC 48V) CTU Coil Test Unit VC Vacuum Checker
TC1 5a6b
UVT 5a6b
LCS 6a5b
6. In case of using the existing old type cradle and replacing breaker only please order type B (Compatible with existing breaker). Compatibille busbars are required for fixed version. 7. If T9(CTC) is selected, in case of adding Secondary trip coil, CTC is also added.
32
Cradle
VCL
Basic model name Susol VCB VCL Cradle
06
Rated voltage (kV) 06 7.2 E F G
E
Version E type drawout F type drawout G type drawout
08
Interrupting current (kA) 08 13 8 12.5 B
A
Phase distance/Compatibility A Standard Compatible with existing cradle Note)
06
Rated current (A) 04 06 400 630
Note) In case of replacing the existing old type VCB with Susol VCB please order type B for cradle and A for breaker.
33
VL
Basic model name VL Susol VCB
06
Rated voltage (kV) 06 12 17 7.2 12 17.5 P E F G H
H
Version Fixed E type drawout (for MESG) F type drawout (for MESG)
20
Interrupting current (kA) 20 25 20 25
A
Phase distance/Compatibility A B F 150mm 210mm Compatible with existing breaker Note)
06
Rated current (A) 06 13 20 630 1250 2000
Note) Types of phase distance 1. Only 150mm for 7.2kV VCB 2. In case of 12 and 17.5kV VCB - 150 and 210mm for H type - 150 and 210mm for 630/1250A of P type - 210mm available for E and F type - 630A and 1250A for F (compatible with existing breaker)
VL-06H20A06
M1
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
C1
T1
Trip coil voltage T0 T1 T2 T3 T4 T5 T6 T7 T8 T9 Without trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Current trip coil
SB1
U1
UVT U0 U1 U2 U3 U4 U5 U6 U7 U8 Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
14 7
Note) 1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are C0 Without closing coil selected, A147 is the type name in the ordering. C1 DC 110V 2. Unable to select A1(Secondary trip coil), U1~U8(UVT) simultaneously. C2 DC 220V 3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), A5(Position S/W 2a2b)can not be selected simultaneously. C3 DC 125V 4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously. C4 DC 24V~30V 5. When A1 (Secondary Trip coil) is selected the maximum available auxiliary contacts are 9a9b. C5 DC 48V~60V 6. When A2(Secondary trip coil with TCS Contact) is C6 AC 48V selected the maximum available auxiliary contacts are 4a3b, 9a8b. C7 AC 100V~130V 7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available only for H type. C8 AC 200V~250V 8. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b. 9. A-type connector is applicable to P/E/F/G type and B-type connector to H type. 10. Lead wire special color (blue) is applicable to A-type connector. 11. Locking magnet can be applied only to H type VCB - breaker and cradle. 12. Locking magnet of H type breaker use the same control power supply as motor. 13. Flame retardant type blue wire is not available. 14. M0, C0 and T0 are selectable only for ordering Dummy VCB. Please contact us before ordering. 15. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil), U1~U8(UVT) cannot be selected simultaneously and the maximum auxiliary contact is 4a4b.
Connector and wire SA2 SA4 Standard SB2 SB4 SA6 Flame SA8 retardant SB6 B type connector, 4a4b A type connector, 10a10b B type connector, 4a4b B type connector, 10a10b A type connector, 4a4b A type connector, 4a4b A type connector, 10a10b 1 2 3 4 5 7 8 9 A Optional CTD1 Condenser Trip Device (AC 110V) CTD2 Condenser Trip Device (AC 220V) UDC1 UVT Time Delay Controller (AC/DC 110V) UDC2 UVT Time Delay Controller (AC/DC 220V) UDC3 UVT Time Delay Controller (AC/DC 48V) CTU Coil Test Unit VC Vacuum Checker B C D E F O V W
Other accessories Note) Secondary Trip coil Secondary Trip Coil with TCM Contact Position S/W (Test: 1a1b, Service: 2b) Position S/W (Test: 2a, Service: 2a) Position S/W (Test: 1a1b, Service: 1a1b) Key lock Button Padlock Button Cover Lead Wire User Plug (Part) Plug Interlock Padlock (H type Door Interlock) MOC (Mechanical Operating Cell S/W) Locking Magnet Lead Wire special color (Blue) CT operated coil 1A CT operated coil 5A
34
Cradle
VCL
Basic model name Susol VCB VCL Cradle
06
Rated voltage (kV) 06 12 17 7.2 12 17.5
20
Rated short time current (kA) 20 25 20 25
06
Rated current (A) 06 13 20 630 1250 2000
14 7
Version E F G H E type drawout (for MESG) F type drawout (for MESG) G type drawout (for MESG)
Other accessories (H type) ES (Earthing Switch) without option ES with position S/W (2a2b) ES with position S/W (6a6b) ES with Key lock ES with Locking magnet: DC 110V ES with Locking magnet: DC 220V ES with Locking magnet: DC 125V ES with Locking magnet: DC 24V ES with Locking magnet: DC 48V ES with Locking magnet: AC 48V ES with Locking magnet: AC 110V ES with Locking magnet: AC 220V Shutter padlock TOC (Truck Operating Cell S/W) MOC (Mechanical Operating Cell S/W) Door Door Interlock Door Emergency Push Button Temperature Monitoring Sensor H type Lead wire 4a4b M (Flame retardant wire) H type Lead wire 10a10b N (Flame retardant wire) H type Lead wire 4a4b O (Rated short time current) Optional TM Temperature Monitoring
Note) 1.These accessories for cradle and TM can be applied only to H type. 2. AJ and AK can not be selected without door (AH). 3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor). 4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker. 5. Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button Cover) for body of H-type. 6. When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.
C D E F G H J K L
35
LVB
06
40
12
1A
2B
BB6GT2
Connector and wire A type connector, 4a4b A type connector, 10a10b B type connector, 4a4b B type connector, 10a10b Dummy VCB
Version P E F G G Fixed E type drawout F type drawout G type drawout G/T type drawout (for MESG)+T2 L
Control voltage DC110V DC220V DC48V DC125V AC220V AC110V AC48V Dummy VCB B B1 B2 B6 C1 C2 C3 D1 D2 D3 E F G H J K
Other accessories Note) Position S/W(Test : 2a, Service : 2a) Position S/W(Test : 1a1b, Service : 1a1b) Position S/W(Test : 1a1b, Service : 2b) User s Plug(Part) Button Padlock(ON) Button Padlock(OFF) Button Padlock(ON,OFF) Button Cover(ON) Button Cover(OFF) Button Cover(ON OFF) Button Padlock(ON) + Button Cover(OFF) Button Padlock(OFF) + Button Cover(ON) Keylock Secondary Trip coil Flame retardant wire Latch checking S/W Dummy VCB(A type connector) Dummy VCB(B type connector) Padlock Tulip contact, Closed type T + Earthing S/W Interlock change UVT
Note) 1. H(Secondary trip coil) and V(UVT) can not be selected simultaneously. 2. B(Position S/W 2a2a), B1(Position S/W 2a2b) and B2(Position S/W 1a3b) can not be selected simultaneously. However, only B(Position S/W 2a2a) is available for G/T type(MCSG drawable type) 3. If V(UVT) is selected , additional K(Latch checking S/W) is not allowed. (Because if UVT is slected a latch checking S/W is included as standard for electrical interlocking ) 4. One out of T and T2 should be selected for G/T type(MCSG drawable type). T2 is the standard and T (Product before Earthing S/W interlock change) is suitable for compatibility with existing products. 5. In case of T(Tulip contact, closed type) 3150A is available only for open type housing . 6. Only G/T type is available for 12kV.
P1 P2 S T T2 V
36
Cradle
LCL
06
40
12
BCDT2
Version P E F G G Fixed E type drawout F type drawout G type drawout G/T type drawout (for MESG)+T2 D
Other accessories Note) Earthing Switch Note2) Earthing Switch Position S/W(ON/OFF) Earthing Switch Locking coil Tulip contact, Closed type Note1) T + Earthing S/W Interlock change Note1) T2 +Earthing S/W without Conductor ass y
Note2)
Note) 1. One out of T, T2 and T3 should be selected for G/T type(MCSG drawable type). T2 is the standard and T (Product before Earthing S/W interlock change) is suitable for compatibility with existing products. T3 is available only for 1250/2000A. 2. U1(Reduced height type) and B(Earthing S/W) can not be selected simultaneously.
37
VH
Basic model name VH Susol VCB
06
Rated voltage (kV) 06 12 17 20 25 36 40 7.2 12 17.5 24 25.8 36 40.5 P E F G H
H
Version Fixed E type drawout (for MESG) F type drawout (for MESG) G type drawout (for MESG) H type drawout (for MCSG)
50
Interrupting current (kA) 25 32 40 50
Note)
B
Phase distance/Compatibility A B D E 150mm 210mm 275mm 300mm
13
Rated current (A) 12 13 20 25 30 32 40 1200A 1250A 2000A 2500A 3000A 3150A 4000A
25 31.5 40 50
Note) 1. 25kA is for 24/36/40.5kV 2. 31.5kA is for 7.2/12/17.5/24/36/40.5kV 3. 40kA is for 7.2/12/17.5/24/36kV 4. 50kA is for 7.2/12/17.5kV
VH-06H50B32
M0 M1 M2 M3 M5 M6 M7 M8
M1
Motor control voltage Without motor DC 110V DC 220V DC 125V DC 48V AC 48V AC 110V AC 220V
C1
T0 T1 T2 T3 T5 T6 T7 T8 Closing coil voltage
T1
Trip coil voltage Without trip coil DC110V DC220V DC125V DC48V AC 48V AC 110V AC 220V
SB2
U0 U1 U2 U3 U5 U6 U7 U8 Connector and wire
U1
UVT Without UVT DC 110V DC 220V DC 125V DC 48V AC 48V AC 110V AC 220
14 7
Other accessories Note) 1 2 3 4 5 6 7 8 9 A Secondary Trip coil Secondary Trip Coil with TCM Contact Position S/W(Test: 1a1b, Service: 2b) Position S/W(Test: 2a, Service: 2a) Position S/W(Test: 1a1b, Service: 1a1b) Latch checking S/W Keylock Button Padlock Button Cover Lead Wire User Plug(Part) Plug Interlock Padlock(H type Door Interlock) MOC(Mechanical Operating Cell S/W) Locking Magnet ANSI type Charge interlock Lead wire special color(Blue)
Note) 1. If A1(Secondary trip coil), A4(Position S/W 2a2a), C1 DC 110V A7(Keylock)are selected, A147 is the type name in the C2 DC 220V ordering. 2. A1(Secondary trip coil), U1~U8(UVT) can not be selected C3 DC 125V simultaneously. 3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), C5 DC 48V A5(Position S/W 2a2b) can not be selected simultaneously. 4. A8 (Button Padlock) and A9 (Button Cover) can not be C6 AC 48V selected simultaneously. 5. AC (Plug interlock), AD (H type Door interlock), AE (MOC) C7 AC 110V and AF (Locking magnet) are available only for H type. C8 AC 220V 6. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b. 7. A-type connector is applicable to P/E/F/G type and B-type connector to H type. 8. Lead Wire Special Color(blue) is available only for A type connector and the flame retardant is not applicable to it. 9. Locking magnet can be applied only to H type VCB - breaker and cradle. 10. Locking magnet of H type breaker use the same control power supply as motor. 11. In case of selecting UVT A6 (Latch checking S/W) is not allowed. A6 (Latch checking S/W) is installed by default to make electrical interlock with UVT. 12. Lead wire is enclosed in the breaker in case of ordering fixed type or H type
C0
SA2 SA4 SB2 SB4 DA1 DB1 SA6 SA8 SB6 DA2 DB2 Flame retardant Standard
A type connector, 4a4b A type connector, 10a10b B type connector, 4a4b B type connector, 10a10b Dummy A type connector Dummy B type connector A type connector, 4a4b A type connector, 10a10b B type connector, 4a4b Dummy A type connector Dummy B type connector Optional
B C D E F G O
CTD1 Condenser Trip Device(AC 110V) CTD2 Condenser Trip Device(AC 220V) UDC1 UVT Time Delay Controller(AC/DC 110V) UDC2 UVT Time Delay Controller(AC/DC 220V) UDC3 UVT Time Delay Controller(AC/DC 48V) CTU Coil Test Unit VC Vacuum Checker
breaker without cradle, installed of cradle in case of ordering the breaker with cradle. If user plug is selected it will be enclosed in the breaker.
13. AG(ANSI type Charge interlock) is available only for H type and the cradle option AQ should be selected accordingly. 14. M0, C0 and T0 are selectable only for ordering Dummy VCB. Please contact us before ordering. 15. 7.2/12kV, 31.5/40kA are not applicable for H type
38
Cradle
VCL
Basic model name Susol VCB VCL Cradle
06
Rated voltage (kV) 06 12 17 20 25 36 40 7.2 12 17.5 24 25.8 36 40.5
25
Interrupting current (kA) 25 32 40 50 25 31.5 40 50
13
Rated current (A) 12 13 20 25 30 32 40 1200A 1250A 2000A 2500A 3000A 3150A 4000A
14 7
Version E F G H K E type drawout (for MESG) F type drawout (for MESG) G type drawout (for MESG) H type drawout (for MCSG) K type drawout (for MCSG)
Phase distance/Compatibility A B D E 150mm 210mm 275mm 300mm Rotated bushing F type (210mm) 1 2 4 5 6 7 8 A B
Other accessories (H type) ES (Earthing Switch) without option ES with Position S/W (2a2b) ES with Position S/W (6a6b) ES with Key lock ES with Locking magnet: DC 110V ES with Locking magnet: DC 220V ES with Locking magnet: DC 125V ES with Locking magnet: DC 48V ES with Locking magnet: AC 48V ES with Locking magnet: AC 110V ES with Locking magnet: AC 220V Shutter padlock TOC (Truck Operating Cell S/W) MOC (Mechanical Operating Cell S/W) Door Door Interlock Door Emergency Push Button Temperature Sensor H type Lead wire 4a4b M (Flame retardant wire) H type Lead wire 10a10b N (Flame retardant wire) H type Lead wire 4a4b O (Rated short time current) Q R 3 Position ANSI type Charge interlock Optional TM Temperature Monitoring
* Only K-type cradle is available for 4000A. * H-type (box type cradle) * K-type (open type cradle)
Note) 1. Cradle accessories and the option TM are available only for H type(MCSG drawable type) Exceptionally AR is available for E, F, G types and A1 for K type. (If A1 is selected, Position S/W 4a4b is included as standard) 2. AJ and AK can not be selected without door (AH). 3. TM (Temperature Monitoring) should be used with AL (Temperature Sensor). 4. H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker. 5. If AQ(ANSI type Charge interlock) is selected, the breaker option AG should be selected accordingly. 6. If the H type breaker options A8(Button Padlock) and A9(Button Cover) are slected, the cradle option AK(Door Emergency Push Button) is not available. 7. When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.
C D E F G H J K L
39
Note) 1. Ur = Rated voltage 2. Isc = Rated short-circuit current 3. Ir = Rated normal current 4. p = Phase distance 5. E,F and G types are cradles for MESG(Metal Enclosed Switchgear) and H type for MCSG(Metal Clad Switchgear) 6. For the partial replacement of 7.2kV 8/12.5kA VCB, in case of using the existing old type cradle and replacing breaker only, please order type B (Compatible with existing breaker). Compatibille busbars are required for fixed version. To replace VCB fully(breaker and cradle) please order type A for breaker and compatible cradle B.
40
7.2/12/17.5/24/36/40.5kV (VH-06/12/17/24/36/40)
Ur [V] Isc [kA] p=150 1250 31.5 2000 3150 1250 2000 40 3150 7.2 4000 1250 2000 50 2500 3150 4000 1250 31.5 2000 3150 1250 40 12 2000 3150 4000 1250 2000 50 2500 3150 4000 1250 17.5 50 2000 2500 3150 25 1250 2500 p=210 Ir[A] p=275 p=300 Type LVB-06-32L/12 LVB-06-32L/20 LVB-06-32L/30 LVB-06-40L/12 LVB-06-40L/20 LVB-06-40L/30 VH-0640D40 VH-0650B13 VH-0650B20 VH-0650D25 VH-0650D32 VH-0650D40 LVB-12G-32L/12-T2 LVB-12G-32L/20-T2 LVB-12G-32L/30-T2 LVB-12G-40L/12-T2 LVB-12G-40L/20-T2 LVB-12G-40L/30-T2 VH-1240D40 VH-1250B13 VH-1250B20 VH-1250D25 VH-1250D32 VH-1250D40 VH-1750B13 VH-1750B20 VH-1750D25 VH-1750D32 VH-2025D25 VH-2032B13 VCB Version P,E,F,G,G/T P,E,F,G,G/T P,E,F,G/T P,E,F,G,G/T P,E,F,G,G/T P,E,F,G/T P,H P,H P,H P,H P,H P,H G/T G/T G/T G/T G/T G/T P,H P,H P,H P,H P,H P,H P,H P,H P,H P,H P,H P,H VCL-20H32F13 VCL-20H32B20 P,H VCL-20H32F20 P,H P,H P,H P,H VCL-20H40F13 VCL-20H40B20 P,H VCL-20H40F20 P,H P,H P,H VCL-20H40D13 VCL-20H40D20 VCL-20H40D32 H H H H B B B B H H B B VCL-20H32D13 VCL-20H32D20 VCL-20H32D32 VCL-20H40B13 H H H H H B B B B B H H B B CRADLE Type LCL-06G-32D/12-T2 LCL-06G-32D/20-T2 LCL-06G-32D/30-T2 LCL-06G-40D/12-T2 LCL-06G-40D/20-T2 LCL-06G-40D/30-T2 VCL-06K40D40 VCL-06H50B13 VCL-06H50B20 VCL-06H50D25 VCL-06H50D32 VCL-06K50D40 LCL-12G-32D/12-T2 LCL-12G-32D/20-T2 LCL-12G-32D/30-T2 LCL-12G-40D/12-T2 LCL-12G-40D/20-T2 LCL-12G-40D/30-T2 VCL-12K40D40 VCL-12H50B13 VCL-12H50B20 VCL-12H50D25 VCL-12H50D32 VCL-12K50D40 VCL-17H50B13 VCL-17H50B20 VCL-17H50D25 VCL-17H50D32 VCL-24H25D25 VCL-20H32B13 Version P,E,F,G,G/T P,E,F,G,G/T P,E,F,G/T P,E,F,G,G/T P,E,F,G,G/T G/T K H H H H K G/T G/T G/T G/T G/T G/T K H H H H K H H H H H H A,B A,B A,B A,B A,B A,B B B B B B B A,B A,B A,B A,B A,B A,B B B B B B B B B B B B B Connector
41
Note) 1. Ur = Rated voltage 2. Isc = Rated short-circuit current 3. Ir = Rated normal current 4. p = Phase distance 5. H type is MCSG style drawable type with a box type cradle for CB compartment construction. 6. G/T types are MCSG style drawable types with a cradle for builting in the switchgear , not a box type. (K of VCL type name indicates 4000A) Example of G/T type : LVB-06G-32L/12-T2, LCL-06G-32D/12-T2 7. G/T types use LVB and LCL names. 8. E, F and G types provide cradles for MESG(Metal Enclosed Switchgear) and H, G/T types for MCSG(Metal Clad Switchgear). 9. H type is not applicable to 7.2/12kV, 31.5/40kA.
42
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VL-06 0804
7.2 400 50/60 8 8/3 100 2.5 * Isc (50Hz)/2.6 * Isc (60Hz) 3 20 60 O-0.3s-CO-15s-CO (V) (V)
VL-0613 06
630
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version Fixed Drawout Phase distance Weight Breaker (E, F, G type) Cradle (E, F, G type) Dimensions Breaker (E, F, G type) Cradle (E, F, G type) Standards (mm) (kg) (kg) 37 18, 25, 32 (sec) (sec)
AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V AC/DC 100~130V, AC/DC 200~250V, DC 125V, DC 24~30V, DC 48~60V, AC 48V 2a2b, 4a4b, 6a6b 0.04 0.06 M2 E2 (List1) C2 P type E, F, G type (for MESG) 130 37 19, 26, 33 Page 86~87 Page 87~88 IEC 62271-100 (2008), KS C 4611, JEC 2300/JIS C 4603, V-check (KESCO)
43
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class
Installation version *
Fixed Drawout
Dimensions
Standards
* H type is a box type cradle with CB compartment style structure. ** ( ) displays option of phase distance.
44
7.2/12kV (LVB-06/12)
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (Cycle) Ud (kV) Up (kV)
LVB-06-32,4012, 20, 32 *
7.2 1250 2000 3150 50/60 31.5, 40 31.5/3, 40/3 393, 499
LVB-12-32,4012, 20, 30 *
12 1250 2000 3150
31.5, 40 31.5/3, 40/3 393, 499 2.5 * Isc (50)/2.6 * Isc (60) 3
20 60 O-0.3s-CO-3min-CO
28 75
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version * Fixed Drawout Phase distance Weight Breaker (MESG, MCSG) Cradle (MESG, MCSG) Dimensions Breaker (MESG, MCSG) Cradle (MESG, MCSG) Standards (mm) (kg) (kg) 135, 160 55, 110 P type (sec) (sec) (V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b 0.04 0.06 M2 E2 (List1) C2 MCSG Cradle 150 164 110 165 117 210 220 155
E,F,G type (for MESG), MCSG Cradle 150 135, 160 63, 117 210 210, 220 135, 155 Page 113~116 Page 128~132 IEC 62271-100, KERI/KEMA, V-check(KESCO)
* MCSG style drawable type provide a cradle for builting in the switchgear, not a box type for CB compartment. Ordering type is LVB. Note) H type that is a box type cradle for enabling a CB compartment in MCSG is under development. Consult us for ordering.
45
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VH-065013/20/25/32
7.2 1250 2000 2500 3150
VH-125013/20/25/32
12 1250 2000 60 50 50/3 2500 3150
VH-175013/20/25/32
17.5 1250 2000 2500 3150
623
1515
20 60
38 95
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version Fixed Drawout Phase distance Weight Breaker (H type) Cradle (H, type) Dimensions Breaker (H type) Cradle (H, type) Standards (mm) (kg) (kg) 210 230 175 Page 117 Page 134 287 320 275 290 320 (sec) (sec) (V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b 0.04 0.06 M2 E2 (List3) C2 P type H type (for MCSG) 210 230 175 Page 117 Page 134 287 320 275 290 320 210 230 175 Page 117 Page 134 287 320 275 290 320
46
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (Cycle) Ud (kV) Up (kV)
VH-0640, 5040 **
7.2 4000 50/60 40, 50 40/3, 50/3 499, 623 2.5 * Isc (50)/2.6 * Isc (60) 3 20 60 O-0.3s-CO-3min-CO (V) (V)
VH-1240, 5040 **
12 4000
831, 1039
28 75
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version * Fixed Drawout Phase distance Weight Breaker (P type, H type) Cradle (K type) Dimensions Breaker (P type, H type) Cradle (K type) Standards (mm) (kg) (kg) (sec) (sec)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b 0.04 0.06 M2 E2 (List1) C2 P type H type (for MESG), with K type Cradle 275 270, 318 315 Page 119 Page 133 IEC 62271-100, KERI/KEMA, V-check(KESCO)
* K type cradle drawable type provide a cradle for builting in the switchgear, not a box type for CB compartment. Ordering type is LVB.
47
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VH-202525
2500
VH-203213/20/32
24/25.8 1250 2000 60 3150
VH-20 40 13/20/32
1250 2000 3150
25 25/3 1039/1117
31.5 31.5/3 1309/1407 2.6 * Isc (60Hz) 3 50 (65) Note1) 125 O-0.3s-CO-3min-CO
40 40/3 1662/1787
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version * Fixed Drawout Phase distance ** Weight Breaker (H type) Cradle (H type) Dimensions Breaker (H type) Cradle (H type) Standards
* H type is a box type cradle with CB compartment style structure. ** ( ) displays option of phase distance. Note) 1. Contact us.
(V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b
(sec) (sec)
48
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VH-362513/20/32
1250 2000 3150
VH-363213/20/32
36 1250 2000 50/60 3150
VH-364013/20/32
1250 2000 3150
25 25/3 1559
31.5 31.5/3 1964 2.5 * Isc (50Hz)/2.6 * Isc (60Hz) 3 70 (95) Note1) 170 O-0.3s-CO-3min-CO
40 40/3 2494
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version * Fixed Drawout Phase distance Weight Breaker (H type) Cradle (H type) Dimensions Breaker (H type) Cradle (H type) Standards
* H type is a box type cradle with CB compartment style structure. Note) 1. Contact us.
(V) (V)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b
(sec) (sec)
(mm) (kg) (kg) 400 700 Page 124 Page 140 490 750 Page 125 Page 141 400 700
300 490 750 Page 125 Page 141 400 700 Page 124 Page 140 490 750 Page 125 Page 141
49
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit current Rated short-time withstand current Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik/tk (kA/s) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV) 1250
VH-402513/20/32
40.5 2000 3150 50 25 25/4 1754 2.5 * Isc (50Hz) 3 95 180 O-0.3s-CO-3min-CO (V) (V) 1250
VH-403213/20/32
2000 3150
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contacts Rated opening time No-load closing time Type test class Mechanical Electrical Capacitive current switching Installation version Phase distance Weight Dimensions Standards Breaker (H type) Breaker (H type) Fixed (mm) (kg) 400 Page 126 (sec) (sec)
DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V DC 48V, DC 110V, DC 125V, DC 220V, AC 48V, AC 110V, AC 220V 4a4b, 10a10b 0.04 0.06 M2 20 Operations at 100% Isc C2 P type 300 490 Page 127 GB1984 400 Page 126 490 Page 127
50
Accessory
Supplied as Mounting Type Position Breaker (Internal) M CC TC A1 T9 Motor Closing Coil Trip Coil Secondary Trip Coil Current Trip Coil Auxiliary Contact 2a2b SA (SB) Auxiliary Contact 4a4b Auxiliary Contact 6a6b Auxiliary Contact 10a10b U A3 A4 A5 A6 C A7 A8 A9 AA AB AC AD AE AF AO Under Voltage Trip Coil Position S/W(Test: 1a1b, Service: 2b) Position S/W(Test: 2a, Service: 2a) Position S/W(Test: 1a1b, Service: 1a1b) Latch Checking Switch Counter Keylock Button Padlock Button cover Lead Wire: A/B type connector Plug/Terminal for Lead Wire Plug Interlock Padlock (Type H Door Interlock) MOC(Mechanical Operated Cell Switch Locking Magnet Lead Wire: A type connector Option (Special Color: Blue) Trip Coil Monitoring Contact Breaker (External) CTD1 CTD2 UDC1 UDC2 UDC3 CTU TM Condenser Trip Device(AC110V) Condenser Trip Device(AC220V) UVT Time Delay Controller(AD110V) UVT Time Delay Controller(AD220V) UVT Time Delay Controller(AD48V) Coil Test Unit Temperature Monitoring Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Attached at the factory 69 71 71 72 72 72 70 73 Option Attached at the factory 65 Accessory VL: 7.2kV 8/12.5kA Option Option Option Option Option Option Option Option Option Option Option Option Option Remarks VL: 20/25kA Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option VH Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory 59 60 60 60 61 61 62 63 64 65 65 66 66 67 68 Attached at the factory 58 Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory 53 54 55 56 57 page
* : Basic Installation
51
Accessory
Supplied as Mounting Type Position Cradle A1 A2 ES(Earthing Switch) without Option ES(Earthing Switch) with Position Switch(2a2b) A4 A5 A6 ES(Earthing Switch) with Position Switch(6a6b) ES(Earthing Switch) with Keylock ES(Earthing Switch) with Locking magnet: DC110V A7 ES(Earthing Switch) with Locking magnet: DC220V A8 ES(Earthing Switch) with Locking magnet: DC125V A9 ES(Earthing Switch) with Locking magnet: DC24V AA ES(Earthing Switch) with Locking magnet: DC48V AB ES(Earthing Switch) with Locking magnet: AC48V AC ES(Earthing Switch) with Locking magnet: AC110V AD AE AF AG AH AJ AK AL AM AN (Normal cable) Type H Lead Wire 4a4b) AO (Flame retardant cable) Door padlock Option Option Attached at the factory 80 Option Option Attached at the factory 80 ES(Earthing Switch) with Locking magnet: AC220V Shutter padlock TOC(Truck Operated Cell Switch) MOC(Mechanical Operated Cell Switch) Door Door Interlock Door Emergency Push Button Temperature Sensor Type H Lead Wire 4a4b (Normal cable) Type H Lead Wire 10a10b Option Option Attached at the factory 80 Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Option Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory Attached at the factory 76 76 77 77 78 78 79 80 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Attached at the factory 75 Option Option Option Option Attached at the factory Attached at the factory 75 75 Option Option Attached at the factory 74 Accessory VL: 7.2kV 8/12.5kA Remarks VL: 20/25kA Option Option VH Option Option Attached at the factory Attached at the factory 74 74 page
52
Motor: M
VL type
Motor
Charge the closing spring of a circuit breaker by the external power source. When the charging is complete, control power of the motor will be "OFF" by the built-in Limit S/W. Without the external power source, charge manually.
Gear
Main shaft
Motor
VL type Input voltage (Vn) Load current (A) Starting current (A) Charge time
Note) Rated operation and control voltage range, see page 57.
DC 24~ 30V
DC 48~ 60V
DC 110V
DC 125V
DC 220V
AC 48V
AC 100~ 130
AC 200~ 250V
0.5
0.5
VH type
Motor
VH Type Input voltage (Vn) Load current (A) Starting current (A) Charge time
Note) Rated operation and control voltage range, see page 57.
DC 48V
DC 110V
DC 125V
DC 220V
AC 48V
AC 110V
AC 220V
6 30
3 20
3 20
2.6 17
Less than 12 sec.
6 30
3 20
2.6 17
53
Accessory
Closing Coil: C
Installed inside of a breaker as standard
VL type
It is a control device which closes a circuit breaker, when applying voltage continuously or instantaneously over 200ms to the coil control terminals.
Closing coil
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W)
Note) Rated operation and control voltage range, see page 57.
DC 24~ 30V
DC 48~ 60V
DC 110V
DC 125V 200
DC 220V
AC 48V
AC 100~ 130
AC 200~ 250V
VH type
It is a control device which closes a circuit breaker, when applying voltage continuously about 45ms to the coil control terminals. Electrical pumping preventing circuit is built in.
Closing coil
VH Type Input voltage (Vn) Rated current (A) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
2.5
2.5
Note) Rated operation and control voltage range, see page 57.
54
Trip Coil: T
VL type
It is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 35ms to coil control terminals. When UVT coil is installed, its location is changed.
Trip coil
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W)
Note) Rated operation and control voltage range, see page 57.
DC 24~ 30V
DC 48~ 60V
DC 110V
DC 125V 200
DC 220V
AC 48V
AC 100~ 130
AC 200~ 250V
VH type
It is a control device which trips a circuit breaker, when applying voltage continuously or instantaneausly over 35ms to the coil control terminals.
Trip coil
VH Type Input voltage (Vn) Rated current (A) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
2.5
2.5
Note) Rated operation and control voltage range, see page 57.
55
Accessory
Secondary Trip Coil: A1
Installed inside of a breaker as an option
VL type
It is a control device which trips a circuit breaker doubly from the outside. If the trip coil (T ) fails, it can trip a circuit breaker safely. Trip coil: Install it at existing location. Secondary trip coil: Install it on the right side of the trip coil. It is not available with UVT coil when installing secondary trip coil.
VL type Input voltage (Vn) Power consumption (inrush, W) Power consumption (steady, W) DC 24~ 30V DC 48~ 60V 200 DC 110V DC 125V DC 220V AC 48V AC 100~ 130 AC 200~ 250V
VH type
It is a control device which trips a circuit breaker doubly from the outside. If the trip coil (T) fails, it can trip a circuit breaker safely. It is not available with UVT coil when installing secondary trip coil.
VH Type Input voltage (Vn) Rated current (A) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
2.5
2.5
56
Susol VCB Item VL: 7.2kV 8/12.5kA Motor AC DC Closing AC DC Trip AC DC Applied standards 85~110% 75~110% 85~110% 75~125% 60~125% 60~125% IEC62271-100 (2008) KSC4611 VL: 20/25kA 85~110% 85~110% 85~110% 85~110% 85~110% 70~110% IEC62271-100 (2008) VH 85~110% 85~110% 85~110% 85~110% 85~110% 70~110% IEC62271-100 (2008) Remarks
This trip coil uses the output of the CT as its control power source and is used with over current relay in combination. Two current trip coils are supplied. Coil burden is 90VA.(T9) Coil impedance(Z) is like below - 3A: 10 or less, Operating current AC 3A (T9) - 1A: 160 or less, Operating current AC 1A (AV) - 5A: 6 or less, Operating current is AC 5A (AW) CT must be installed at load side. If it is installed at bus side there is the danger of malfunction or damage to CT. Dont disconnect the control power connector on main power is live condition at service position. Otherwise there is the danger of malfunction or damage to CT.
* CT is recommended to use 15VA 5P10 and more.
VL type : AV, AW
Current Trip Coil
57
Accessory
Auxiliary Contact: SA
Installed inside of a breaker as an option
VL type
Auxiliary contact
It is a contact used to monitor ON/OFF status of a breaker from remote place. The auxiliary contacts supplied as standard configuration is 4a4b. 10a10b is also available on request. For 7.2kV 8/12.5kA VCB standard configuration is 2a2b. 4a4b and 6a6b are optional.
VH type
Auxiliary contact
VL/VH Type Item AC Contact 250V configuration DC 125V 30V 10 10 5 5 10 5 For all models 250V 125V Resistive load (A) 10 10 Inductive load (A) 5 5 Remarks
58
VL type
VH type
VL type
It is installed inside of a breaker to trip when the main power or control power voltage drops below certain value. Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT time delay controller. The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied. UVT and secondary trip coil will not be selected together.
VH type
1. UVT rated voltage and characteristic - Operating voltage range: Pick up 0.65~0.85Vn, Drop out 0.4~0.6Vn - Operating voltage ranges based on the minimum value of each rated voltage (Vn)
VL type Input voltage (Vn) DC 24~ 30V Power consumption (inrush, W) DC 48~ 60V 200 DC 110V DC 125V DC 220V AC 48V AC 100~ 130 AC 200~ 250V
VH Type Input voltage (Vn) Power consumption (inrush, W) DC 48V DC 110V DC 125V DC 220V 350 AC 48V AC 110V AC 220V
10
59
Accessory
Position Switch: A3, A4, A5
Installed inside of a breaker as an option
This switch is used to indicate the breaker position (SERVICE, TEST), and contact configuration is 2a2a or 2a2b.
Contact configuration
1 3 5 7 1 3 5 7 1 3 5 7
1a1b(TEST)
2b(SERVICE)
2a(TEST)
2a(SERVICE)
1a1b(TEST)
6 8 1a1b(SERVICE)
60
VH type
This switch works in conjunction with the mechanism of the breaker. It checks if the breaker is ready to be closed. When the mechanism is OFF and the closing spring is at charged status the switch becomes "ON", which means the mechanism is ready to be closed. If the latch is not in a proper position the switch prevents the breaker from closing. In case of VH type it is connected internally in series with the closing coil.
Counter: C
VL/VH type
It displays the total number of ON/OFF operations of a breaker.
61
Accessory
Keylock: A7
Installed inside of a breaker as an option
VL type
The key is to unlock the locking device first to close the breaker electrically and mechanically. *How to operate - It is not possible to pull out the key in the unlocked position, possible only in locked status. - Pushing "OFF" switch of a breaker turn the key counter-clockwise to the locked position and pull it out. - It is not possible to close the breaker electrically and mechanically in the locked position. - Insert the key and turn clockwise and then the breaker can be closed electrically and mechanically.
Keylock
VH type
*How to operate - It is not possible to pull out the key in the unlocked position, possible only in locked status. - Trip the breaker first and then turn the key counter-clockwise to the locked position and pull it out. - It is not possible to close the breaker electrically and mechanically in the locked position.
Keylock
62
Button Padlock: A8
VL type
It is to prevent manual operation of ON/OFF button due to users wrong handling. It is not possible to handle ON/OFF operation under the Button lock status.
* Key lock is not supplied.
Button Padlock
VH type
Button Padlock
63
Accessory
Button Cover: A9
Installed outside of a breaker as an option
VL type
It is a protection cover to prevent an accident due to unintended operation of ON/OFF button. Use the push-bar to operate the ON/OFF button.
* Push bar is not supplied.
Push Bar
Button Cover
VH type
64
Lead wire: AA
VL/VH type
Lead wire
It is to connect with the control circuit of a breaker from outside. (supply wire length: 2m) A type connector is supplied for P/E/F/G type of VL VCB. B type connector is supplied for P type of VH VCB. In case of H type breaker of VL and VH models the Lead wire is installed in the cradle when supplied.
A type connector
B type connector
Lead wire of A type connector Enclosed in the breaker Lead wire of A, B type connector Installed in the breaker
Note) The connectors for VH type are different by the ratings. Refer to page 41 and 42.
VL/VH type
A type connector
B type connector
It is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire) Type of connector is depends on the type of connector installed in the breaker- A or B.
65
Accessory
Plug interlock: AC
Installed inside of a breaker as an option
It checks if the control power connector on the cradle (H type) is connected with the connecting terminal of the breaker before the proceeding of draw-in or out. It is not allowed to seperate the control power connector from the breaker in the position of draw-in /out or SERVICE, but TEST position.
Door interlock
66
MOC
VH type
MOC
67
Accessory
Locking magnet: AF
Installed inside of a breaker as an option
VL type
It allows the drawing-in of the breaker in the TEST position under the condition that the control power connector on the cradle (H type) is connected with the connecting terminal of the breaker and the power is supplied. During the drawing-in or in the SERVICE position draw-in/out is allowed without supplying power.
* Control power rating is the same as that of a motor.
Locking magnet
VH type
Locking magnet
68
VL type
Device for monitoring the functions of the trip coils. Supplied as standard for VL model and optional for VH model. To monitor the trip coils connect its terminals with the trip coil monitoring relay as shown on the circuit diagram. - If the trip coil is normal: closed-circuit consisting - If the trip coil is damaged: open circuit 1) Terminals A5 and A6 monitor the trip coils in closed position of the breaker. 2) Terminal A6 and aux. contact terminal 34 monitor the trip coils in trip position of the breaker. Coil Test Unit is opional, which enable monitoring the coils by connecting in parallel with the trip coil operation switch.
VH type
69
Accessory
Coil Test Unit: CTU
Installed outside of a breaker as an option
When no current flows through the coil it gives the test current which does not cause the coil to operate to check whether the coil is disconnected or not. - If the test current flows normally: coil normal - If the test current does not flow through: coil disconnected As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected. Monitoring of the running coils is not possible. One test unit can monitor up to two coils. 1. Input voltage: AC/DC 75V~264V 2. Contact output 1) 2a contacts for Fail indication and 2a contacts for Alarm 2) 250Vac/10A Resistive, 30Vdc/10A Resistive 3. Disconnection test cycle is 12 seconds (Test LED blinks) 4. The default operation If Fail happens (coil disconnected), Fail LED turns on and the Fail contacts become short state. If Fail happens three times in series, Alarm LED turns on and the Alarm contacts become short state. In order to clear the Alarm status push up DIP switch on the front and then push down it (Off On Off)
Alarm 1 Shunt 1
24~250V (AC/DC)
Alarm 2 Shunt 2
CTU CTU Input voltage Input voltage (+) (+) 1 5 7 Coil test current 2
Fail (LED) Fail (RELAY) Alarm (LED) Alarm (RELAY)
Coil
Coil drive power(-)
70
Ratings
Ratings Model Rated input voltage (V) Frequency (Hz) Rated charge voltage (V) Charging time Trip possible time Range of Input voltage Condenser capacity ( F) Specification CB - T1 AC 100/110 50/60 140/155 Within 10sec. Within 30sec. 85%~110% 1,000 CB - T2 AC 200/220 50/60 280/310 Within 10sec. Within 30sec. 85%~110% 560
It gets a circuit breaker tripped electrically within regular time when control power supply is broken down and is used with Shunt coil, SHT. In case there is no DC power, It can be used as the rectifier which supplies DC power to a circuit breaker by rectifying AC power. Tripping within 30 seconds on the power failure is possible. However after that automatic trip circuit must be configured separately in the switchgear.
Terminal arrangement
External dimension
(Mounting hole)
Circuit diagram
71
Accessory
UVT Time delay: UDC
Installed outside of a breaker as an option
UVT time delay, UDC is to delay the trip signal from UVT. Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker even in the the momentary power failure. UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure. It can be installed on the cradle or inside of the switchgear. UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker. b contact is closed at normal state and a contact is closed at trip.
1. Characteristics
Rated voltage (Vn) DC (V) 48~60 100~130 200~250 AC (V) 48 100~130 200~250 0.65~0.85 Vn 0.4~0.65 Vn 200 Opration voltage range (V) Pick up Drop out Consumption (VA or W) Inrush Steady - state Time delay (ms)
0.5, 1, 1.5, 3
- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)
12 12 10
3. Wiring diagram
5
14 16
18(a)
UVT
18 19 20 a c b Signal for tripping DC48~60V AC48 5 7 0.5 1 1.5 3
[sec]
Instantaneous trip signal
72
Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed in H-type cradle. Temperature sensor can be installed up to three (R, S, T phase). Temperature Alarm Unit converts the temperatures detected from the senser in the cradle and displays the maximum value and can transmit it throug communication. If the input temperature is above standard it may cause alarm. Temperature Alarm Unit supports Modbus/RS485 communication and contact us Profibus-DP communication.
Temperature Sensor
LED temperature display (): 10 ~150, Warning Display maximum value of temperatures
73
Accessory
Earthing Switch: A1
Built-in a cradle as an option
Earthing Switch
Circuit diagram
E1 E3 E5 E7 E9 E11 E13 E15 E17 E19 E21 E23
E2
E4
E6
E8
74
In case of using earthing switch it can be added for two types of interlocking. 1) Interlock to keep opening 2) Interlock to keep earthing
75
Accessory
Shutter padlock: AE
Built-in a cradle as an option
Shutter padlock
VL type
Circuit diagram
VH Type TOC
121 122 124 125 127 128 130 131
123
126
129
132
a Contact: 122-123, 125-126, 128-129, 131-132, b Contact: 121-123, 124-126, 127-129, 130-132
76
This auxiliary switch is used to indicate the Close/Trip of VCB. It is operated mechanically at the SERVICE position and installed in the bottom of a H type cradle and operated by the frame of a breaker. MOC is consisted of 4 cell switches with changeover contacts as below diagram.
VL type
Circuit diagram
102 101 105 104 108 107 111 110
MOC
103
106
109
112
VH Type a Contact: 101-103, 104-106, 107-109, 110-112, b Contact: 102-103, 105-106, 108-109, 111-112
Door: AH
Door
77
Accessory
Door Interlock: AJ
Built-in a cradle as an option
Door Interlock
It is used to enable the Close/Trip of the breaker manually from outside of the door installed to H type cradle during an emergency. Push the ON/OFF button by ON/OFF handle supplied seperately.
78
Temperature Sensor: AC
B C D
79
Accessory
Type H Cradle Lead Wire: AM~AO
Built-in a cradle as an option
Lead Wire
Door Padlock
Door Padlock
80
Auxiliary guide frame is provided in order to move safely 36/40.5kV breaker into the switchgear. It can be used in combination with the hand pallet which meets the requirement shown below.
If dimension A in Fig. 1 is less than 120mm B type pallet can be used. In case of more than 120mm C type must be applied.
550
Bottom
<Fig 1>
81
UVT 2 4* 6* 8*
TC1
TC
82
Auxiliary switch
VL-06
P
P
4a 4b 2b
TEST SERVICE
P
2a
6a(5a)
Note5)
6b(5b)
Note5)
A1 A5
1 3*
LS4 LS5 LS7 LS6
9
5 7*
13
A3
D1 22 24 26 28 40 (42) 34 36 38 50 52 54 (56)
11
Note1)
LS2
CS
LCS
M
23 35 1 3*
LS4 LS5 LS6 LS7
52a 25 37 5* 7* 39 51 53 55 57 27 29 41 43 2
52a
Note3) Note4)
A2
23 25 27 29 41 (43) 37 39 51 53 55 (57)
10
14
A4 N
D2
12
A6
Indicating Contact
A4 14 6 23 4
10
D2/12 2 8
25 24 34
37 36
39 38
A
A1
/42 /56
B
A3 A5 1 3 9 13 D1/11 5 7 22
LCS : Latch Checking Switch "ready to close" position of circuit breaker or preventing closing unless opening latch is properly reset
LS4, LS5 : Position s/w (close in TEST position) LS6, LS7 : Position s/w (close in SERVICE position)
(2a2b)
S/W No.
A2 A6
/43 /57
A4 14 1 3 A3 A5
/42 /56
10 9 D1/11 13
D2/12 2 4
6 5
23
25
27
29
37
39
51
53
A
A1 7
B
22 24 26 28 34 36 38 50 52
TEST : 1a1b TEST : 2a TEST : 1a1b SERVICE : 2b SERVICE : 2a SERVICE : 1a1b A3 A4 A5 Close at TEST position Close at TEST position Close at TEST position OPEN at TEST position Close at TEST position OPEN at TEST position OPEN at SERVICE position Close at SERVICE position Close at SERVICE position OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
14
/57
(4a4b)
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT) TC1 : Secondary Trip coil(SHT1) C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (a) 52b : Auxiliary switch (b) LS2 : Motor stop limit switch CS : Closing spring charged indication limit switch CTC : Current Trip Coil CTC1 : Secondary Current Trip Coil
2 D1/11
/42
4 13
/56
6 1 3 5
23
25
27
29
41
37
39
51
53
55
A
A1 7
B
22 24 26 28 40 34 36 38 50 52 54
D2/12
/43
/57
14 D1/11
/42
13
/56
Note) 1. LCS : Latch Checking Switch (Terminal No. 13, 14) 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) 1a1b at TEST position and 1a1b at SERVICE position are also available. Option (In case of 1a1b * marked contact is b - nomally close contact) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) 5. CTC - Current Trip Coil (Terminal No. A5, A6) CTC1 - Secondary Current Trip Coil (Terminal No. 11, 12) 6. Closing and Trip coils are one pulse system. (Exception : trip coil DC 110V and 220V) 7. In case of selecting UVT as an option TC1, CTC is not an option. 8. In case of using LCS/UVT/TC1 the maximum available of auxiliary contacts is 5a5b, 5a6b, 6a5b 9. CTC and CTC1 are options, which are used at the positions of TC and TC1, to be connected with current transformer of the switchgear. 10. Above circuit diagram is based on OFF status of VCB and closing spring is charged. 11. Please make sure that keep the direction of P, N on this circuit diagram.
TC1 5a6b
UVT 5a6b
LCS 6a5b
Auxiliary switch
Trip coil monitoring contact Secondary trip coil with TCM Contact
P
4a 4b
TEST SERVICE
VL-06/12/17
P P
Position switch Note2) <2a(TEST),2a(SERVICE)>
1 3 5 7 15
A1
Position switch <1a1b(TEST),1a1b(SERVICE)>
1
3*
LS4 LS5 LS7 LS6
13
A3
22 24 26 28 40 42 44 46 34 36 38 50 52 54 56 58 70 72 74 48 60
D1
11
A5
LS2
5 7*
CS
2 4* 6 8*
40 42 44 46
48 60
34 36 38 50 52 54 56 58 70 72 74
M
23 25 27 29 41 43 45 47 49 61 35 37 39 51 53 55 57 59 71 73 75 2
52a
52a
Note1)
CTC2
Note5)
2 4*
6* 5*
C LM
7*
UVT
8*
TC1
TC
Note3) Note4)
A2
23 25 27 29 41 43 45 47 49 37 39 51 53 55 57 59 71 73 75 61 2 4 6 8 16
10
14
N
Note4) Note4)
A4 N N
D2
12
A6
LET : Low Energy Trip Device(25mJ,100mJ) CS : Closing spring charged indication limit switch LS4, LS5 : Position S/W (TEST position) LS6, LS7 : Position S/W (SERVICE position)
S/W No.
TEST : 1a1b TEST : 2a TEST : 1a1b SERVICE : 2b SERVICE : 2a SERVICE : 1a1b A3 A4 A5 Close at TEST position Close at TEST position Close at TEST position OPEN at TEST position Close at TEST position OPEN at TEST position OPEN at SERVICE position Close at SERVICE position Close at SERVICE position OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT) TC1 : Secondary Trip coil(SHT1) C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (NO) 52b : Auxiliary switch (NC) LS2 : Motor stop limit switch CTC : Current Trip coil(3A) CTC1 : Secondary Current Trip coil(3A) CTC2 : Current Trip coil(1A,5A) CTC3 : Current Trip coil(1A,5A)
B type
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36 34 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36 34 61 60 49 48 47 46 45 44 43 42 53 52 51 50
12 11 D2 D1
Note) 1. CTC2 : Current Trip Coil(1A,5A) (Terminal NO : 13,14) 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) - TEST position 1a1b, SERVICE position 1a1b/2b are available. (* marked contact is b contact.) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) In case TC1 is selected and auxiliary switch is 10a10b, Some 'a' contact. (Terminal No.: 40,41) and 'b' contact(Terminal No.:54, 55) are not available. 5. Secondary Trip Coil Monitoring Contact (Terminal NO.:36) In case Secondary Trip Coil TCM Contact is selected and auxiliary switch is 9a8b, Some 'a' contact (Terminal No.: 40,41) and 'b' contact(Terminal No.:36, 37) are not available. 6. CTC - Current Trip Coil (Terminal No.: A5,A6) CTC1 - Secondary Current Trip Coil (Terminal No.: 11,12) CTC2 - Current Trip Coil (Terminal No.: 13,14) CTC3 - Current Trip Coil (Terminal No.: D1,D2) 7. LET - Low Energy Trip Device (Terminal No.: 13,14) 8. LM - Locking Magent (Terminal No.:15, 16), In case of B type connector is available 9. Close and Trip coil is One Pulse type, excluding Trip coil (DC110, 220V) 10. In above optional accessories, UVT,CTC and TC1 can not be selected simultaneously. 11. Above circuit diagram is based on "OFF" state of VCB and closing spring is charged. Option
75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50 10 9 16 15 14 13 8 7 6 5 4 3 2 1
12 11 D2 D1
A B C D
10
9 16 15 14 13
A B C D
83
4
2
Note3)
UVT
TC1
TC
84
Auxiliary switch Trip coil monitoring contact Note6)
P
P
Note2)
P
4a
TEST SERVICE
10a 4b
34 36 38 50 52 54 56 58 70 72 74 1 3 5 7
Position switch <2a(TEST),2a(SERVICE)>
10b
CS
15 22 24 26 28 40 42 44 46 48 60
CS
A1
Position switch <1a1b(TEST),1a1b(SERVICE)>
1
A3
D1
11
A5
LS2
LS3
Ya
Note5)
1 3*
LS4 LS5 LS7 LS6
7*
Yb 2
2 4* 6 8*
LM
Note1)
22 34 1 3 LS4 LS7 4
1 3*
LS4 LS5
5 1 24 5 LS5 6
5*
VH-06/12/17/24/36/40
LCS1 26 7 LS6 8 28 40 42 44 46 48 60 36 38 50 52 54 56 58 70 72 74
M
23 49 61 35 37 39 51 53 55 57 59 71 73 75 25 27 29 41 43 45 47 2
52b
30
82
52a
31
83
6'
C
4*
Note4)
LS1
6*
8*
A2
16 23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6 8
10
A4 N
D2
12
A6
B type connector
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36 34 53 52 51 50
12 11 D2 D1
10
9 16 15
A B C D
24 25 24 25 26 27 28 29 34 36 37
A
11 D1
12 D2
11 D1
12 D2
58 59 1 3 5 7
B
16 15 14 13 12 11 10 9
26 27 1 3 5 6 8
B
2 4
2 4 6 8
60 61 70 71 72 73 74 75
C
41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 39 38 37 36 34 61 60 49 48 47 46 45 44 43 42 75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50
12 11 D2 D1
28 29 34 36 37
A
10
9 16 15
LS3: Anti-close, anti-pumping limit switch : External terminal of VCB LCS1: Trip latch checking switch 52: Vacuum circuit breaker (preventing closing unless the trip latch is properly reset) M: Spring charging motor LS4, LS5: Position S/W (close in TEST position) TC: Trip coil LS6, LS7: Position S/W (close in SERVICE position) TC1: Secondary trip coil C: Close coil TEST : 1a1b TEST : 2a TEST : 1a1b Y: Anti-pump relay S/W SERVICE : 2b SERVICE : 2a SERVICE : 1a1b UVT: Under voltage trip No. A3 A4 A5 52a: Auxiliary switch (a) LS4 Close at TEST position Close at TEST position Close at TEST position 52b: Auxiliary switch (b) LS5 OPEN at TEST position Close at TEST position OPEN at TEST position LS1: Close interlock limit switch LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position (only withdrawable type) LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position LS2: Motor stop, close spring charged indication limit switch LM: Locking magnet (only withdrawable type)
7
A B C D
Note) 1. LCS1 : Latch Checking Switch 2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8) 1a1b at TEST position and 1a1b at SERVICE position are also available. (In case of 1a1b *marked contact is b - nomally open contact) 3. UVT - Under Voltage Trip (Terminal No. D1, D2) 4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12) 5. LM - Locking Magnet (Terminal No. 15, 16), Type H only withdrawable type. 6. Secondary Trip Coil monitoring contact (Terminal No. 36) b contact(36, 37) is not available if Trip Coil monitoring contact is applied to Secondary Trip Coil. 7. Above options TC1 and UVT can not be used simultaneously. 8. LS1(closing-interlock Limit-switch) is not available for fixed version 9. Above circuit diagram is based on OFF status of VCB and closing spring is charged. 10. Please make sure that keep the direction of P, N on this circuit diagram. Option
Compartment
6a P MOC TM
8(R+) 9(S+) 10(T+) 17 102 101 105 104 108 107 111 110 121 122 124 125 127 128 130 131
6b
Note2)
2a TOC
Note3) Note4)
2b
E1
E5
E3
E1
E5
E3
E2
E4
E4
LM
TM
TM
TM
12(R-)
12(S-)
12(T-)
: External terminals for auxiliary contacts and locking magnet LM : Locking magnet for earthing swtich MOC : Mechanism operated cell switch (for H type cradle) TOC : Truck operated cell switch (for H type cradle) TM : Temperature alarm (for H type cradle)
Note) 1. LM - If it is energized with the rated power the earthing switch can be closed or opened (for H type cradle) 2. MOC - This auxiliary switch is used to indicate the Close/Open of VCB (for H type cradle) It is composed of 4 cell switches with 4 changeover contacts. 3. TOC - This auxiliary switch is used to indicate the 'SERVICE' position of VCB (for H type cradle) It is composed of 4 cell switches with 4 changeover contacts. 4. TM - Temperature Alarm Unit displays the input temperature detected through the temperature sensor installed in H-type cradle. Temperature sensor can be installed in each phase and can be connected with the temperature module. 5. Please make sure that keep the direction of P, N on this circuit diagram.
Option
* Above circuit diagram is based on the status that the earthing S/W is Open and the breaker is at Test or between Test and Service position. MOC indicates the Open of the breaker. If the breaker is Closed from Service, the contacts configuration is displayed on the contrary.
85
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Fixed (P type)
(Mounting hole)
86
VL-06
(Earthing hole)
87
Dimensions - VL type
7.2kV, 8/12.5kA, 400/630A
Withdrawable (F type cradle)
Racking in/out Stroke:150
VL-06
(Earthing hole)
88
VL-06/12/17
281
6(10)
89
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (F type unit, phase distance 150mm)
90
VL-06/12/17
46.8
96.5
91
Dimensions - VL type
7.2kV, 20/25kA, 2000A
Withdrawable (E type unit, phase distance 150mm)
92
VL-06/12/17
46.8
96.5
93
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Fixed (P type, phase distance 210mm)
670
311.5
613.5
302
670
94
310
650
46.8
96.5
VL-06/12/17
670
311.5
613.5
302
670
169.5 310
650
95
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (F type unit, phase distance 210mm)
96
VL-06/12/17
96.5
46.8
97
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (E type unit, phase distance 210mm)
98
VL-06/12/17
99
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (H cradle, phase distance 150mm)
317 323.4 42.3 M12 (DP:25) 150 150
550
(Mounting hole)
65
285
(Mounting hole)
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
550
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
TUBE
10.0
TUBE
Detail A
30
Detail A
See Detail A
Detail A
100
86.8
30
VL-06/12/17
550.4
(Mounting hole)
65
285
(Mounting hole)
20 68.3
TUBE
10.0
550
25 Detail A
30
See Detail A
Detail A
86.8
465
310
101
Dimensions - VL type
12/17.5kV, 20/25kA, 630/1250A
Withdrawable (H cradle, phase distance 150mm)
317 (For assembly of lifting hook and LV compartment mounting hole) 323.4 42.3 M12 (DP:25)
550
600
1120
400
400
400
212.5
65
285
150 150
258.7
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
550
(Mounting hole)
212.5
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
10.0
TUBE
TUBE
30
445
205
Detail A
Detail A
See Detail A
Detail A
102
43.4
30
VL-06/12/17
700
(Mounting hole)
210
(Mounting hole)
210
(Mounting hole)
65 285
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (2 sheets) <1250A>
700
(Mounting hole)
20 87.3
Connecting busbar method (with earthing switch) Busbar : 8t40 (1 sheet) <630A>
10.0
TUBE
TUBE
30
Detail A
Detail A
87.3 20 2-M8(DP:18)
See Detail A
Detail A
63.4
30
103
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (H cradle, phase distance 150mm)
317 323.4 42.3 25
150 150
550
(Mounting hole)
2-M12 (DP:25)
725
(Mounting hole)
(Mounting hole)
65 285
(Mounting hole)
20 68.3
TUBE
10.0
550
25 Detail A
30
See Detail A
Detail A
104
86.8
VL-06/12/17
(Mounting hole)
700
(Mounting hole)
(Mounting hole)
(Mounting hole)
20 87.3
TUBE
10.0
Detail A
25 30
700
87.3 20 2-M8(DP:18)
See Detail A
Detail A
127
105
Dimensions - VL type
7.2kV, 20/25kA, 630/1250A
Withdrawable (E type cradle)
(Mounting hole) Rating A B C 630A 6 55 95 1250A 10 60 90 Racking in/out Stroke:132 (Earthing hole)
106
VL-06/12/17
107
Dimensions - VL type
7.2kV, 20/25kA, 630/1250/2000A,
Withdrawable (G type cradle)
(Earthing hole) (Earthing hole) (Earthing hole)
Rating A
630A 6
1250A 10
2000A 20
108
VL-06/12/17
11.8
(Earthing hole)
139 210 270 440 340 295 50 210
87.2
6 860 1050 40
800
2-M6 TAP
11.8
326
720.2
109
Dimensions - VL type
12/17.5kV, 20/25kA, 630A
Withdrawable (Compatible with existing F cradle, phase distance 210mm)
164 70 2-M6 TAP
11.8
(Earthing hole)
210 270 440 340
(Mounting hole)
50 210
2-M6 TAP
11.8
(Earthing hole)
139 210 270 440 340
(Mounting hole)
87.2
800
860 1050
40
110
326.2
10 295 720.2
60 210
326.2
720.2
VL-06/12/17
(Earthing hole)
(Mounting hole)
(Earthing hole)
(Mounting hole)
111
Dimensions - VL type
12/17.5kV, 20/25kA, 2000A
Withdrawable (E cradle, phase distance 210mm)
Racking in/out Stroke:182
VL-06/12/17
(Earthing hole)
(Mounting hole)
(Earthing hole)
(Mounting hole)
112
LVB-06/12
40
271
1250A(E, F type)
4- 13
40 2000A(E, F type)
20 130 295 670 286.6 20 115.5 515 589 A type connector B type connector 400.6 547 117
468.5
1250A (G type)
2000A (G type)
125.5 478
130
670
295 286.6 115.5 515 A type connector B type connector 169.5 310 582.5 Used only for F and G types - 2 EA at both sides 670
320
670
113
689 15
130
702.5 705.5
295 319.1 115.5 501 A type connector B type connector 114.5 126 350.7 388.5 618 668
689
15
130
3 10 355.5 715.5
47
60
114
342.5
702.5
LVB-06/12
750.5
40 350 286.6 115.5 665 739 A type connector B type connector 463.6 597 104
125.5 620
436.5 507.5
750.5
360 286.6 115.5 665 680 A type connector B type connector 129 507.5 630 303.5 Used only for type - 2 EA at both sides 750.5 130
750.5
130
115
LVB-06/12
693 16.5
360 140.2 135.6 331.6 795.5 805.5 115.5 687 A type connector B type connector 321.7 450.6 624.7 674.4
693
16.5
795.5 805.5
130
360 140.2 135.6 331.6 115.5 687 A type connector B type connector
10 10 348.5 795.5
60
116
60
348.5
795.5
130
Dimensions - VH type
7.2/12/17.5kV, 50kA, 1250/2000A
Fixed (P type, phase distance 210mm)
VH-06/12/17/24/36/40
2-M12 (DP:25)
610
130
862.5
816
25
M12 (Earthing hole) 108 115.5 360 602 695 94 144 137
285
653 644
12
130
48
335
89
3.5
447 53 656
42
412
72
193.5
380
340
117
Dimensions - VH type
7.2/12/17.5kV, 50kA, 2500/3150A
Fixed (P type, phase distance 275mm)
4-M12 (DP:25)
79
50
750
130
862.5
50
285
12 725
844
130
869.5
400 447
Note) Dimensions in ( ) apply to 2500A
53
656
118
3.5 42
89 193.5 380
335
340
VH-06/12/17/24/36/40
44
134
147 341
119
Dimensions - VH type
24kV, 25kA, 2500A
Fixed (P type, phase distance 275mm)
287.5
M12 (Earthing hole) 110.5 115.5 786 864 118 174 142 853 850 12 857 445 Racking in/out Stroke:310 53 497 535 788 3.5 41.5 80 225 440 340
120
335
130
VH-06/12/17/24/36/40
2-M12 (DP:25)
(Mounting hole)
610
130
287.5
M12 (Earthing hole) 115.5 110.5 137 Racking in/out Stroke:310 445 3.5 41.5 80 225 440 497 535 53 788 340
118 174
653 652
12 857
335
130
121
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Fixed (P type, phase distance 275mm)
2-M12 (DP:25)
750
130
287.5
M12 (Earthing hole) 110.5 118 174 142 12 857 850 445 Racking in/out Stroke:310 53 788 3.5 41.5 497 535 80 225 440 340
115.5
853
122
335
130
VH-06/12/17/24/36/40
4-M12 (DP:25)
(Mounting hole)
750
130
287.5
M12 (Earthing hole) 110.5 118 174 142 12 857 850 445 Racking in/out Stroke:310 53 788
3.5 41.5
853
130
497 535
80 225 440
335
340
123
Dimensions - VH type
36kV, 25/31.5/40kA, 1250/2000A
Fixed (P type)
M12
(Mounting hole)
1042.5
294.1
551.5
220.1
8.5
124
8.5
VH-06/12/17/24/36/40
M12
(Mounting hole)
1042.5
551.5
294.1
220.1
8.5
8.5
125
Dimensions - VH type
40.5kV, 25/31.5kA, 1250/2000A
Fixed (P type)
300 300 157
247
50
M12
420 50
392
914 830
(Mounting hole)
136.5 107
130
1042.5
294.1
551.5
400
220.1
(Earthing hole)
1.5 115.5
500 837 207 157 570
866 944
830
136.5 107
1446
130
697.6
403
104
115.5
140
623.6
8.5
1015
126
8.5
463.6
487.4
52 65
955
400
VH-06/12/17/24/36/40
80
M12
420 80
914 830
(Mounting hole)
392
130
1042.5
551.5
400
294.1
(Earthing hole)
1.5 115.5 500 837 207 157 570
866 944
830
136.5 107
1446
130
697.6
403
623.6
104
8.5
1015
8.5
463.6
487.4
52 65
955
400
127
2- 14
4- 14
1250A
2000A
7- 12 (Mounting hole)
525
50
260
Rating A 1250A 10
410
2000A 20
210
150
150
2- 14
4- 14
1250A
2000A
7- 12 (Mounting hole)
525
50
260
150
150
Rating A
23.2 A 326.2
128
23.2 A 326.2
720.2
720.2
LVB-06/12
600 560
100
662
1250A:12t 2000A:25t
150
150
129
4-M12 DP25
675
50
210
210
7- 12 (Mounting hole)
265
Withdrawable (F cradle)
Only for 3 position type 50 80 50 50
130
LVB-06/12
(Earthing hole)
131
145
35
800 760
4- 14 (Mounting hole)
100
724
12
12
210
132
LVB-06/12
(Mounting hole)
133
Dimensions - VH type
7.2/12/17.5kV, 50kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
42.3 317 378.4 2-M12 (DP:25)
187
37.5
49
210
210
710
(Mounting hole)
25
450
1325
450
450
65
285
200
200
217
(Mounting hole)
84.3 60
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (1 sheet) <1250A>
84.3 60
212.5
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (2 sheets) <2000A>
12
12
30
12
212.5
TUBE
TUBE
See Detail A
Detail A
134
63.3
30
565
340
VH-06/12/17/24/36/40
(Mounting hole)
1325
450
450
212.5
60
300
210
230 264.5
(Mounting hole)
90.8
20
Connecting busbar method (with earthing switch) Busbar : 12t80 (2 sheets) <2500A >
90.8 100
20
Connecting busbar method (with earthing switch) Busbar : 12t100 (2 sheets) <3150A>
80
212.5
12
TUBE
12
30
TUBE
25
See Detail A
Detail A
49.4
25
30
25
25
25
25
565
340
135
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Withdrawable (H cradle, phase distance 210mm)
352 30 (Mounting hole) 4-M12 (For assembly of lifting hook and LV compartment mounting hole) 25 2-M12 (DP:25) 750 (Mounting hole) 500 558
970
800
895
500
210 210
1380
500
500
212.5
60
300
280
300
269.5
(Mounting hole)
85.8 60
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (1 sheet) <1250A>
85.8 60
20
Connecting busbar method (with earthing switch) Busbar : 12t60 (2 sheets) <2000A>
12
12
30
12
212.5
TUBE
TUBE
See Detail A
Detail A
136
49.4
30
625
340
VH-06/12/17/24/36/40
210 210
2-M12 (DP:25)
970 1302
239.5
800
895
750
1380
60
300
280
300
269.5
(Mounting hole)
212.5
500
500
137
Dimensions - VH type
24kV, 31.5/40kA, 1250/2000A
Withdrawable (H cradle, phase distance 275mm)
352 30 (Mounting hole)
4-M12 (For assembly of lifting hook and LV compartment mounting hole)
558
275
2-M12 (DP:25)
970
1000
895
275
25
500
1380
500
500
60
300
280
300
269.5
(Mounting hole)
85.8 60
20
Connecting busbar method (with earthing switch) <2500A> Busbar : 12t60 (2 sheets)
12
212.5
TUBE
30
212.5
See Detail A
Detail A
138
49.4
625
340
VH-06/12/17/24/36/40
970
1000
895
275
1380
500
500
60
300
280
300
270
90.3 80
20
12
Connecting busbar method (with earthing switch) Busbar : 12t80 (2 sheets) <2500A>
90.3 100
20
12
Connecting busbar method (with earthing switch) Busbar : 12t100 (2 sheets) <3150A>
212.5
212.5
12
30
12
TUBE
TUBE
25
See Detail A
Detail A
49.4
25
30
25
25
25
25
625
340
139
Dimensions - VH type
36kV, 25/31.5/40kA, 1250/2000A
Withdrawable (H type cradle)
25 1194 466 14 300 300 296.5 201.5 40 12 15 1200 A 48 505
2200
1520
855
400
50.5
290
46
140.5
60
14
30 40
127.5 30
25 Remove both side of shrink tube for bolting busbar when using Cu PIPE
10 STS HEX M8X70 BOLT BUS BAR: 60 X 12t 19 53.5 8.5 Remove the plates for both sides when assembled in pannel 185 300 563 300
25
1194
140
104 604
66
203.8
120
56.12
1226.7
61
203.8
563
463
216.5
VH-06/12/17/24/36/40
2200
1520
855
400
50.5
290
46
1226.7
140.5
30 40 110 40
127.5
30
25 Remove both side of shrink tube for bolting busbar when using Cu PIPE
14
Using Cu PIPE(2ea) as right figure Detail A or Bending BUSBAR(28.5mm) <For connecting BUSBAR> See Detail A 28.5
25
1194
568
104 604
66
203.8
300
(Earthing hole)
120
56.12
61
203.8
563
463
221.5
141
Item
Rated voltage Rated normal current Rated frequency Rated short-circuit breaking current Rated short-time withstand current (3 sec) Rated short-circuit breaking capacity Rated short-circuit making current Rated breaking time Rated withstand voltage Power frequency (1 min) Impulse (1.250) Ur (kV) Ir (A) fr (Hz) Isc (kA) Ik (kA) (MVA) Ip (kA) (cycle) Ud (kV) Up (kV)
VL-25 16B 06
25.8 630 50/60 16 16 665/715 40/41.6 3 60 125 O-0.3s-CO-3min-CO (V) (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 200~250V 5a5b (sec) (sec) Mechanical Electrical Capacitive current switching 0.04 0.06 M1 E1 C1 (time) (time) Right Left 2,000 2,000 R type L type 210 95 IEC 62271-100
Rated operating sequence Control voltage Closing coil Trip coil Auxiliary contact Rated opening time No-load closing time Type test class
Lifetime *
Mechanical Electrical
Installation
Fixed
(mm) CB (kg)
142
P
9
P
D1
5a
22 24 26 28 40
Auxiliary switch
5b
36 38 50 52 54
A3
CLOSE POWER SOURCE
A5
TRIP POWER SOURCE
22
24
26
28
40
36
38 50
52
54
52a
M C
23
25
27
29
41
37
39
51 53
55
Note1)
UVT
D2
TC
A2
10
A4
Closing Spring Contact (Charge switch)
A6
N
A2 A4 A6 10 D2 A5 9
23 25 27 29 41
37 39 51 53 55
: External terminal of VCB 52 : Vacuum circuit breaker M : Spring charging motor TC : Trip coil(SHT)
C : Closing coil(CC) UVT : Under Voltage Trip 52a : Auxiliary switch (a) 52b : Auxiliary switch (b)
LS2 : Motor stop limit switch CS : Closing spring charged indication limit switch
B
D1 22
(5a5b)
Note) 1. UVT : Under Voltage Trip (No. D1, D2) Option * Closing and Trip coil : One Pulse type * This circuit diagram is based on 'OFF' status of CB and Closing spring is charged.
210
210
212.5
600 605
818 355.5
38.5
169 300
Ordering information VL
Basic model name e-VCB
25
Rated voltage (kV) 25 25.8 R L
R
Installation type On the right (Fixed type) On the left (Fixed type) 16
16
Breaking 16
B
Phase distance/Compatibility B 210mm
06
Rated current (A) 06 680
VL-2516B06
Motor control voltage M0 M1 M2 M3 M4 M5 M6 M7 M8 Without Motor DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V Closing coil voltage C0 C1 C2 C3 C4 C5 C6 C7 C8 Without Closing coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
M1
C1
T1
Aux. contact & wire ass'y SA5 A type connector, 5a5b
SA5
UVT U0 U1 U2 U3 U4 U5 U6 U7 U8
U1
AAB
Other accessories AA AB Lead Wire User Plug(Part)
Trip coil voltage T0 T1 T2 T3 T4 T5 T6 T7 T8 Without Trip coil DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
Without UVT DC 110V DC 220V DC 125V DC 24V~30V DC 48V~60V AC 48V AC 100V~130V AC 200V~250V
100
120
M10-DP 25
145
Dimension
210
210
143
Technical data
Electrical endurance by interrupting current
Number[ops.]
Interrupting current [kA] VI model LV2 at 7.2kV N : Operation numbers I : Interrupting current N : Operation numbers I : Interrupting current
Number[ops.]
Number[ops.]
Interrupting current [kA] VI model LV4 at 24kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV5 at 17.5kV N : Operation numbers I : Interrupting current
144
Number[ops.]
Interrupting current [kA] VI model LV8 at 17.5kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV7-P1 at 24kV N : Operation numbers I : Interrupting current
Number[ops.]
Interrupting current [kA] VI model LV8 at 36kV N : Operation numbers I : Interrupting current
Note) 1. Above graphs represent the characteristics of the electrical life of LS Susol VCB. 2. Life characteristics of each model in each rating represents the LOG-LOG graphs.
145
Technical data
If a standard circuit breaker is used in high temperature exceeding 40, you are advised to use it according to the current corrected for each level of ambient temperature in catalog. If used in conditions of high humidity, the dielectric strength or electric performance may be degraded.
It is highly recommended to use a dust cover or anti-humid agent if it is used in dusty and humid conditions. Excessive vibration may cause a trip breaker such as connection fault or flaw on mechanical parts.
If it is left ON or OFF for a long time, it is recommended to switch load current on a regular basis. It is recommend to put it in the sealed protection if corrosive gas is prevalent.
146
The circuit breaker is designed for use in standard use environment specified in Section 2. 1 of IEC62271-1. Concerning the special use environments as below the special use conditions are required to be considered, thus please contact us in advance. - where altitude and ambient temperature are out of standard use environment. - where a strong sea breeze blows - when usually used in a humid place - where a lot of steam or oil steam exists - where explosive, flammable and other harmful gases might permeate the breaker - In a dusty place - where abnormal vibration or shock exists - where a lot of ice and snow exist - other special conditions
170 125
Up [kV/1.2
50
147
Technical data
Special Use Environment
Altitude (m)
<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)
Correction parameter 2
1 0.95 0.9 0.85 0.8 0.75 0.7 0.65 0.6 0.55 0.5 1000
1500
2000
2500
3000
3500
4000
Altitude (m)
<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)
Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV (correction parameter 1 applied) - correction parameter at 2500m is 1.2 - criteria of withstand voltage by rated voltage: Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV - requirements withstand voltage criteria: Power Frequency Withstand Voltage (Ud) = 201.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage. Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level (correction parameter 2 applied) - correction parameter at 2500m is 0.825 - dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 280.825 = 23.1kV, Impulse Withstand Voltage (Up) = 750.825 = 62kV/1.250 Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.
148
Rated current (A) 20 4000 3150 2000 1250 630 4000 3150 2000 1250 630 25 4000 3150 2000 1250 630 30 4000 3150 2000 1250 630
Ambient temperature () 35 4000 3150 2000 1250 630 40 4000 3150 2000 1250 630 45 3843 3026 1922 1201 605 50 3679 2898 1840 1150 580 55 3508 2763 1754 1096 553 60 3328 2621 1664 1040 524
4500
4000A
4000 3500
3150A
3000 2500
2000A
2000 1500 1000 500 0
1250A
630A
20
25
30
35
40
45
50
55
60
Ambient temperature()
<Figure 3> Allowable load current by ambient temperature
149
Technical data
Comparison of GCB & VCB
In the system of medium voltage lines VCB uses a vacuum which is an eco friendly medium for arc extinguishing. It also offers excellent interrupting properties and ease of maintenance and has expanded the area to the scope of the GCB as the overlap increases.
Items Images
GCB
VCB
Comparison results
Remarks
VI
SF6 gas - Greenhouse gas that causes global warming. - The toxic gas generated by chemical reactions due to arc energy. - 5kgf/ high pressure required.
Vacuum - Green clean medium. - 510-5 Torr vacuum rate to maintain. VCB is better than GCB
- Periodic check and supplement the gas pressure required. - Automatic locking if gas pressure falls below the certain value. In the event of an accident while the gas valve is locked trip is disable and the load equipment can not be protected.
- Available until the product life. - Always keep trip-first feature. VCB is better than When an accident occurs the trip-first feature functions to protect the equipment. GCB
Rated voltage range (kV) 3.6~550 3.6~36 GCB is better than VCB
VCB has been increasing rapidly in the medium voltage systems. IEC62271-100 Annex M applied/ Interrupting performance verified.
Applicable rate of transient Low recovery voltage (RRRV) Development and trends Decline - Company M discontinued producing GCB. - Company A manufactures VCB in medium voltage GCB production factory. - GCB Maker S started the production of VCB. Increasing - Companies A and S have developed new VCBs. - Development trend that the voltage coverage of VCB expands. - VI increased coverage. (GIS, DAIS, SIS, etc.) High
150
For your safety, please read user's manual thoroughly before operating. Contact the nearest authorized service facility for examination, repair, or adjustment. Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
eng.lsis.biz
HEAD OFFICE
LS-ro 127 (Hogye-dong) dongan-gu Anyang-si Gyeonggi-do Korea Tel. (82-2)2034-4887, 4873, 4918, 4148 Fax. (82-2)2034-4648
CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea
LSIS Beijing Office Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: sunmj@lsis.com.cn
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
2013. 13