AIRCONDITIONING SYSTEM DESIGN SUMMARY

Cooling Capacity

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Air On Coil
Latent
(KW)

Supply Air Fresh air


(lps)
(lps)

Air Offcoil

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

Check Figures
sqmt/K
lps/sqmt
W

System

CLASS ROOMS SOUTH 3RD FLOOR (CRS3F)


1

Assignment Lab (ASSIGL-2)

199.3

4.5

15

60

33.60

31.4

2.20

2503.0

24.0

17.1

13.6

12.9

5.9

12.6

Chilled Water FCU

Class Room (C-5)

51.5

4.5

15

28

8.20

7.2

1.00

568.0

23.9

17.3

13.5

12.8

6.3

11.0

Chilled Water FCU

Class Room (C-5)

51.5

4.5

15

28

8.20

7.2

1.00

568.0

23.9

17.3

13.5

12.8

6.3

11.0

Chilled Water FCU

Class Room (C-5)

51.5

4.5

15

28

8.20

7.2

1.00

568.0

23.9

17.3

13.5

12.8

6.3

11.0

Chilled Water FCU

Gents Toilet

52

4.5

15

0.0

Extract Air

Class Room (C-1)

51.1

4.5

15

28

7.6

6.6

1.00

521

23.9

17.3

13.4

12.8

6.7

10.2

Chilled Water FCU

Store

24.6

4.5

15

2.2

2.1

0.10

167

23.9

16.8

13.5

12.8

11.2

6.8

Chilled Water FCU

Leture Hall (LH-5)

130.5

4.5

15

60

18.5

16.3

2.20

1293

23.9

17.2

13.4

12.8

7.1

9.9

Chilled Water FCU

Corridor-1

84

4.5

15

10

Additional Spece (AS-2)

51

4.5

15

6.10

6.0

0.10

489.0

24.0

16.9

13.7

13.1

8.4

9.6

Chilled Water FCU

11

Hardware Lab

103

4.5

22

15

30

17.70

16.3

1.40

1285.0

24.0

17.1

13.5

12.8

5.8

12.5

Chilled Water FCU

12

Assignment Lab (ASSIGL-1)

190.4

4.5

15

60

26.30

24.1

2.20

1925.0

24.0

17.2

13.6

13.0

7.2

10.1

Chilled Water FCU

13

Leture Hall (LH-1)

105

4.5

15

60

14.70

12.5

2.20

979.0

23.9

17.3

13.3

12.7

7.1

9.3

Chilled Water FCU

14

Additional Spece (AS-1)

51

4.5

15

5.00

4.8

0.20

388.0

23.9

17.0

13.7

13.1

10.2

7.6

Chilled Water FCU

15

Corridor-2

63

4.5

15

FAHU-2

400.0

Served by FAHU-2

Chilled Water FAHU

Served by FAHU-2
288.00

4300.0

Chilled Water FAHU


46.0

30.0

Chilled Water FAHU

LIBRARY AREA 3RD FLOOR (LI3F)


0.00

400.0

0.0

Extract Air

11.4

6.4

VRF

13.0

7.2

10.8

VRF

13.8

13.2

12.4

6.2

VRF

16.8

13.4

12.7

5.4

14.1

VRF

16.8

13.4

12.7

5.4

14.1

VRF

16

Gents Toilet

52

4.5

15

17

Quiet Room

16

4.5

15

1.40

1.3

0.10

103.0

23.9

17.1

13.6

12.9

18

Unknown Space (OF-B)

22.3

4.5

15

3.10

3.0

0.10

240.0

23.9

17.0

13.6

19

Unknown Space (OF-A)

22.3

4.5

15

1.80

1.7

0.10

138.0

23.9

17.2

20

Discussion Room

33.5

4.5

15

6.20

5.9

0.30

471.0

23.9

21

Discussion Room

33.5

4.5

15

6.20

5.9

0.30

471.0

23.9

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

Page 1 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

22

Library Area

198

4.5

15

20

29.20

27.9

1.30

23

Unknown Space

30.8

4.5

15

2.7

2.6

0.10

24

Corridor

82.5

4.5

15

15

FAHU-3

Supply Air Fresh air


(lps)
(lps)

Air Offcoil

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

2249.0

24.0

17.1

13.7

13.1

6.8

11.4

VRF

208

24

17.1

13.8

13.1

11.4

6.8

VRF

sqmt/K
lps/sqmt
W

Served by FAHU-3
155

2300

System

Chilled Water FAHU


46

30

Chilled Water FAHU

ASSIGNMENT LABS 3RD FLOOR (AL3F)


25

Ladies Toilet

52

4.5

15

0.0

Extract Air

26

Class Room (C-2)

51.5

4.5

15

28

7.9

6.9

1.00

549

23.9

17.3

13.5

12.9

6.5

10.7

Chilled Water FCU

27

Class Room (C-2)

51.5

4.5

15

28

7.9

6.9

1.00

549

23.9

17.3

13.5

12.9

6.5

10.7

Chilled Water FCU

28

Class Room (C-2)

51.5

4.5

15

28

7.9

6.9

1.00

549

23.9

17.3

13.5

12.9

6.5

10.7

Chilled Water FCU

29

Service Room (SER-1)

24.7

4.5

15

3.00

2.9

0.10

243.0

24.0

17.1

14.0

13.3

8.2

9.8

Chilled Water FCU

30

Assignment Lab (ASSL-2)

183

4.5

11

15

60

22.70

20.5

2.20

1625.0

23.9

17.1

13.4

12.7

8.1

8.9

Chilled Water FCU

31

Lecture Hall (LH-10)

122.5

4.5

15

60

19.20

16.9

2.30

1338.0

23.9

17.2

13.4

12.7

6.4

10.9

Chilled Water FCU

32

Service Room

16.2

4.5

15

2.3

2.2

0.10

179

23.9

17

13.8

13.1

7.0

11.0

Chilled Water FCU

33

Additional Space (ASP-1)

51

4.5

15

10

4.00

3.6

0.40

284.0

23.9

17.1

13.4

12.8

12.8

5.6

Chilled Water FCU

34

Store Room (ST-1)

24.9

4.5

15

5.60

5.5

0.10

446.0

24.1

16.9

13.7

13.1

4.4

17.9

Chilled Water FCU

35

Assignment Lab (ASSL-1)

183.1

4.5

11

15

60

25.00

22.7

2.30

1822.0

24.0

17.2

13.6

13.0

7.3

10.0

Chilled Water FCU

36

Assignment Lab (ASSL-1)

183.1

4.5

11

15

60

25.00

22.7

2.30

1822.0

24.0

17.2

13.6

13.0

7.3

10.0

Chilled Water FCU

37

Class Room (C-1)

51.1

4.5

15

28

8.50

1.10

590

23.9

17.3

13.5

12.9

6.0

11.5

Chilled Water FCU

38

Corridor

185

4.5

15

15

FAHU-1

400.0

Served by FAHU-1
550.00

8150.00

Chilled Water FAHU


46.00

30.00

Chilled Water FAHU

CLASS ROOMS EAST 3RD FLOOR (CRE3F)


39

Service Room

16.2

4.5

15

2.40

2.4

0.00

190.0

23.8

16.8

13.5

12.9

6.8

11.7

Chilled Water FCU

40

Award Leader (AWL-1)

25

4.5

15

3.20

2.9

0.30

228.0

23.9

17.1

13.4

12.7

7.8

9.1

Chilled Water FCU

41

Award Leader (AWL-1)

25

4.5

15

3.20

2.9

0.30

228.0

23.9

17.1

13.4

12.7

7.8

9.1

Chilled Water FCU

42

Award Leader (AWL-1)

25

4.5

15

3.20

2.9

0.30

228.0

23.9

17.1

13.4

12.7

7.8

9.1

Chilled Water FCU

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

Page 2 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

43

Award Leader (AL-1)

28.5

4.5

15

3.90

3.6

0.30

44

Class Room (C-3)

51.5

4.5

15

28

8.50

7.5

45

Class Room (C-3)

51.5

4.5

15

28

8.50

46

Class Room (C-4)

51.5

4.5

15

28

47

Lecture Hall (LH-1)

130

4.5

15

48

Lecture Hall (LH-1)

130

4.5

49

Corridor

103

4.5

Supply Air Fresh air


(lps)
(lps)

Air Offcoil

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

281.0

23.9

17.0

13.4

12.8

7.3

9.9

Chilled Water FCU

1.00

592.0

23.9

17.2

13.5

12.8

6.1

11.5

Chilled Water FCU

7.5

1.00

592.0

23.9

17.2

13.5

12.8

6.1

11.5

Chilled Water FCU

11.20

10.2

1.00

822.0

24.0

17.2

13.7

13.0

4.6

16.0

Chilled Water FCU

60

18.00

15.8

2.20

1248.0

23.9

17.2

13.4

12.8

7.2

9.6

Chilled Water FCU

15

60

18.00

15.8

2.20

1248.0

23.9

17.2

13.4

12.8

7.2

9.6

Chilled Water FCU

15

12

sqmt/K
lps/sqmt
W

Served by FAHU-1

System

Chilled Water FAHU

OFFICES CENTER 3RD FLOOR (OC3F)


50

Deans Office, Day Room & Ensuit

104

4.5

15

20

13.90

12.6

1.30

1004.0

23.9

17.1

13.5

12.8

7.5

9.7

Chilled Water FCU

51

Board of Trustees

113

4.5

15

20

11.40

10.2

1.20

814.0

24.0

17.3

13.6

13.0

9.9

7.2

Chilled Water FCU

52

Secretariant

72.7

4.5

15

10

7.00

6.2

0.80

500.0

24.1

17.4

13.8

13.1

10.4

6.9

Chilled Water FCU

53

President's Office, Day Room & Ensuit

114

4.5

15

15

14.00

13.1

0.90

1044.0

23.9

17.0

13.5

12.9

8.1

9.2

Chilled Water FCU

CLASS ROOM East 2ND FLOOR (CRE2F)


54

Class Room 15

25

4.5

15

15

7.60

6.1

1.50

482.0

23.9

17.7

13.5

12.9

3.3

19.3

Chilled Water FCU

55

Class Room 15

25

4.5

15

15

7.60

6.1

1.50

482.0

23.9

17.7

13.5

12.9

3.3

19.3

Chilled Water FCU

56

Class Room 15

25

4.5

15

15

7.60

6.1

1.50

482.0

23.9

17.7

13.5

12.9

3.3

19.3

Chilled Water FCU

57

Classroom (C-3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

58

Classroom (C-3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

59

Class Room (C-3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

60

Classroom (C-4)

51.5

4.5

15

28

11.10

10.0

1.10

813.0

23.9

17.2

13.7

13.1

4.6

15.8

Chilled Water FCU

61

Lecture Hall (LEH-1)

130

4.5

15

60

17.30

15.1

2.20

1210.0

23.9

17.3

13.6

12.9

7.5

9.3

Chilled Water FCU

62

Lecture Hall (LEH-1)

130

4.5

15

60

17.30

15.1

2.20

1210.0

23.9

17.3

13.6

12.9

7.5

9.3

Chilled Water FCU

63

Corridor

162

4.5

15

15

Served by FAHU-1

Chilled Water FAHU

ASSIGNMENT LAB North 2nd FLOOR (AL2F)


64

Ladies Toilet

52

4.5

15

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

400.0

Page 3 of 11

0.0

Extract Air

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

65

Lecture Hall (LEH-1)

130

4.5

15

60

15.60

13.4

0.00

66

Store (STO-1)

24.7

4.5

15

2.00

2.0

67

Service Room (SER-1)

24.7

4.5

15

2.90

68

Assignment Lab (ASSL-2)

183

4.5

11

15

60

69

Lecture Hall (LH-10)

122.5

4.5

15

70

Service Room

16.2

4.5

71

Class Room-14

51

4.5

72

Store Room (ST-1)

24.9

73

Class Room-13

74

Supply Air Fresh air


(lps)
(lps)

Air Offcoil

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

1080.0

24.1

17.6

13.8

13.2

8.3

8.3

Chilled Water FCU

0.00

160.0

23.9

16.9

13.7

13.0

12.4

6.5

Chilled Water FCU

2.8

0.10

235.0

23.9

17.1

13.9

13.3

8.5

9.5

Chilled Water FCU

21.40

19.2

2.20

1570.0

24.1

17.5

13.9

13.3

8.6

8.6

Chilled Water FCU

60

18.70

16.5

2.20

1302.0

23.9

17.2

13.4

12.8

6.6

10.6

Chilled Water FCU

15

2.20

2.2

0.00

177.0

23.9

17.0

13.7

13.1

7.4

10.9

Chilled Water FCU

15

28

5.30

4.3

1.00

340.0

23.9

17.6

13.4

12.8

9.6

6.7

Chilled Water FCU

4.5

15

5.30

5.2

0.10

421.0

23.9

16.9

13.7

13.0

4.7

16.9

Chilled Water FCU

61.5

4.5

15

28

9.10

8.0

1.10

644.0

24.0

17.3

13.6

13.0

6.8

10.5

Chilled Water FCU

Class Room -12

58.15

4.5

15

28

8.20

7.2

1.00

576.0

24.0

17.4

13.6

13.0

7.1

9.9

Chilled Water FCU

75

Class Room -11

60.5

4.5

15

28

8.10

7.0

1.10

564.0

23.9

17.3

13.6

12.9

7.5

9.3

Chilled Water FCU

76

Store Room

24.9

4.5

15

2.40

2.3

0.10

191.0

23.9

17.0

13.8

13.2

10.4

7.7

Chilled Water FCU

77

Classroom (C-1)

51.1

4.5

15

28

8.40

1.10

601

24.3

17.7

14.1

13.5

6.1

11.8

Chilled Water FCU

78

Classroom (C-1)

51.1

4.5

15

28

8.40

1.10

601

24.3

17.7

14.1

13.5

6.1

11.8

Chilled Water FCU

79

Classroom (C-1)

51.1

4.5

15

28

8.40

1.10

601

24.3

17.7

14.1

13.5

6.1

11.8

Chilled Water FCU

80

Classroom (C-1)

51.1

4.5

15

28

8.40

1.10

601

24.3

17.7

14.1

13.5

6.1

11.8

Chilled Water FCU

81

Business Faculty Corridor

185

4.5

15

12

sqmt/K
lps/sqmt
W

Served by FAHU-1

System

Chilled Water FAHU

LIBRARY 2nD FLOOR (LI2F)


82

Library Area (L-1)

198

4.5

15

20

29.40

28.1

1.30

2263.0

23.9

17.0

13.6

12.9

6.7

11.4

VRF

83

Library Area (L-2)

289

15

40

34.00

31.5

2.50

2505.0

23.9

17.1

13.5

12.9

8.5

8.7

VRF

84

Gents Toilet

52

4.5

15

0.0

Extract Air

85

Quiet Room

27

4.5

15

3.10

2.9

0.20

239.0

23.9

17.0

13.8

13.1

8.7

8.9

VRF

86

Staff Office

34

4.5

15

4.90

4.6

0.30

377.0

24.1

17.2

13.9

13.2

6.9

11.1

VRF

87

Book Sorting and Repair

34

4.5

15

6.30

6.0

0.30

483.0

24.0

16.9

13.6

12.9

5.4

14.2

VRF

88

Discussion Room

33.5

4.5

15

6.30

6.1

0.20

489.0

24.0

17.0

13.7

13.0

5.3

14.6

VRF

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

300.0

Page 4 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

89

Corridor

40

4.5

15

Total (KW)

Sensible(K
W)

Air On Coil
Latent
(KW)

Supply Air Fresh air


(lps)
(lps)

DB
(deg
C)

WB
(deg
C)

Air Offcoil
DB
(Deg
C)

WB
(Deg
C)

Check Figures
sqmt/K
lps/sqmt
W

Served by FAHU-3

System

Chilled Water FAHU

MULTI PURPOSE HALL 2ND FLOOR (MH2F)


90

Multi purpose Hall+Store

860

15

1000

428.80

268.6

160.20

13027.0

4000.0

30.6

22.0

13.4

12.8

2.0

15.1

Chilled Water AHU

CLASS ROOM CENTER 2ND FLOOR (CRC2F)


91

Office Room

52.6

4.5

15

10

5.80

5.7

0.10

455.0

23.9

16.8

13.6

12.9

9.1

8.7

Chilled Water FCU

92

Office Room (C7)

53.5

4.5

15

10

6.10

5.7

0.40

458.0

23.9

17.1

13.6

13.0

8.8

8.6

Chilled Water FCU

93

Office Room (C8)

58.8

4.5

15

10

5.40

5.0

0.40

398.0

23.9

17.0

13.5

12.8

10.9

6.8

Chilled Water FCU

94

Office Room (C9)

61.2

4.5

11

15

10

6.60

6.2

0.40

498.0

23.9

17.1

13.6

12.9

9.3

8.1

Chilled Water FCU

95

Office Room (C10)

64

4.5

11

15

12

9.30

8.8

0.50

709.0

23.9

16.9

13.5

12.9

6.9

11.1

Chilled Water FCU

96

Corridor

75

4.5

15

10

Served by FAHU-2

Chilled Water FAHU

CLASS ROOMS SOUTH 2nD FLOOR (CRS2F)


97

Assignment Lab (ASSIGL-2)

199.3

4.5

15

60

32.70

30.5

2.20

2447.0

24.0

17.1

13.6

13.0

6.1

12.3

Chilled Water FCU

98

Class Room (C-5)

51.5

4.5

15

28

8.10

7.1

1.00

572.0

24.0

17.4

13.7

13.0

6.4

11.1

Chilled Water FCU

99

Class Room (C-5)

51.5

4.5

15

28

8.10

7.1

1.00

572.0

24.0

17.4

13.7

13.0

6.4

11.1

Chilled Water FCU

100

Class Room (C-5)

51.5

4.5

15

28

8.10

7.1

1.00

572.0

24.0

17.4

13.7

13.0

6.4

11.1

Chilled Water FCU

101

Gents Toilet

52

4.5

15

0.0

Extract Air

102

Class Room (C-1)

51.1

4.5

15

28

7.80

6.8

1.00

538.0

23.9

17.3

13.5

12.9

6.6

10.5

Chilled Water FCU

103

Store

24.6

4.5

15

2.00

2.0

0.00

159.0

24.0

17.1

13.9

13.2

12.3

6.5

Chilled Water FCU

104

Leture Hall (LH-5)

130.5

4.5

15

60

18.80

16.5

2.30

1333.0

23.9

17.3

13.6

13.0

6.9

10.2

Chilled Water FCU

105

Corridor-1

84

4.5

15

106

Class Room (AS-2)

51

4.5

15

28

8.80

7.8

1.00

625.0

23.9

17.2

13.5

12.9

5.8

12.3

Chilled Water FCU

107

Class Room (AS-3)

51

4.5

22

15

28

9.40

8.4

1.00

675.0

23.9

17.2

13.5

12.9

5.4

13.2

Chilled Water FCU

108

Class Room (AS-3)

51

4.5

22

15

28

9.40

8.4

1.00

675.0

23.9

17.2

13.5

12.9

5.4

13.2

Chilled Water FCU

109

Assignment Lab (ASSIGL-1)

190.4

4.5

15

60

25.20

23.0

2.20

1842.0

23.9

17.1

13.5

12.9

7.6

9.7

Chilled Water FCU

110

Leture Hall (LH-1)

105

4.5

15

60

14.10

11.9

2.20

940.0

23.9

17.4

13.4

12.8

7.4

9.0

Chilled Water FCU

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

400.0

Served by FAHU-2

Page 5 of 11

Chilled Water FAHU

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

111

Class Room (AS-1)

51

4.5

15

28

7.20

6.2

1.00

112

Corridor-2

63

4.5

15

Supply Air Fresh air


(lps)
(lps)

501.0

Air Offcoil

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

23.9

17.4

13.6

13.0

Check Figures
sqmt/K
lps/sqmt
W

7.1

9.8

Served by FAHU-2

System

Chilled Water FCU


Chilled Water FAHU

CLASS ROOM Center 1st FLOOR (CRC1F)

113

Office Room

52.6

4.5

15

10

5.80

5.7

0.10

455.0

23.9

16.8

13.6

12.9

9.1

8.7

Chilled Water FCU

114

Office Room (C7)

53.5

4.5

15

10

6.10

5.7

0.40

458.0

23.9

17.1

13.6

13.0

8.8

8.6

Chilled Water FCU

115

Office Room (C8)

58.8

4.5

15

10

5.40

5.0

0.40

398.0

23.9

17.0

13.5

12.8

10.9

6.8

Chilled Water FCU

116

Office Room (C9)

61.2

4.5

11

15

10

6.60

6.2

0.40

498.0

23.9

17.1

13.6

12.9

9.3

8.1

Chilled Water FCU

117

Office Room (C10)

64

4.5

11

15

12

9.30

8.8

0.50

709.0

23.9

16.9

13.5

12.9

6.9

11.1

Chilled Water FCU

118

Corridor

75

4.5

15

10

Served by FAHU-2

Chilled Water FAHU

Class Rooms-East 1st Floor (CRE1F)


119

Class Room (C4)

51.5

4.5

15

28

11.10

10.0

1.10

813.0

23.9

17.2

13.7

13.1

4.6

15.8

Chilled Water FCU

120

Class Room (C3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

121

Class Room (C3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

122

Class Room (C3)

51.5

4.5

15

28

9.30

8.2

1.10

652.0

23.9

17.1

13.4

12.7

5.5

12.7

Chilled Water FCU

123

Class Room

25

4.5

15

15

4.60

3.6

1.00

289.0

23.8

17.7

13.4

12.9

5.4

11.6

Chilled Water FCU

124

Class Room

25

4.5

15

15

4.60

3.6

1.00

289.0

23.8

17.7

13.4

12.9

5.4

11.6

Chilled Water FCU

125

Service Room

25

4.5

15

4.20

4.2

0.00

336.0

23.9

16.8

13.6

12.9

6.0

13.4

Chilled Water FCU

126

Lecture Hall (LH-1)

130

4.5

15

60

17.30

15.1

2.20

1210.0

23.9

17.3

13.6

12.9

7.5

9.3

Chilled Water FCU

127

Lecture Hall (LH-1)

130

4.5

15

60

17.30

15.1

2.20

1210.0

23.9

17.3

13.6

12.9

7.5

9.3

Chilled Water FCU

128

Corridor

162

4.5

15

15

Served by FAHU-1

Chilled Water FAHU

Assignment Labs 1st Floor (AL1F)


129

Ladies Toilet

52

4.5

15

130

Class Room (C-2)

51.5

4.5

15

28

8.00

7.0

1.00

565.0

112.0

24.0

17.4

13.7

13.1

131

Class Room (C-2)

51.5

4.5

15

28

8.00

7.0

1.00

565.0

112.0

24.0

17.4

13.7

13.1

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

400.0

Page 6 of 11

0.0

Extract Air

6.4

11.0

Chilled Water FCU

6.4

11.0

Chilled Water FCU

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil
Supply Air Fresh air
(lps)
(lps)

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

132

Class Room (C-2)

51.5

4.5

15

28

8.00

7.0

1.00

565.0

133

Service Room (SER-1)

24.7

4.5

15

2.90

2.8

0.10

134

Assignment Lab (ASSL-2)

183

4.5

11

15

60

21.40

19.2

135

Lecture Hall (LH-10)

122.5

4.5

15

60

18.70

136

Service Room

16.2

4.5

15

137

Additional Space (ASP-1)

51

4.5

15

138

Store Room (ST-1)

25

4.5

139

Assignment Lab (ASSL-1)

183.1

4.5

140

Assignment Lab (ASSL-1)

183.1

141

CLASS ROOM (C-1)

142

Air Offcoil

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

112.0

24.0

17.4

13.7

13.1

6.4

11.0

Chilled Water FCU

235.0

4.0

23.9

17.1

13.9

13.3

8.5

9.5

Chilled Water FCU

2.20

1570.0

240.0

24.1

17.5

13.9

13.3

8.6

8.6

Chilled Water FCU

16.5

2.20

1302.0

240.0

23.9

17.2

13.4

12.8

6.6

10.6

Chilled Water FCU

2.20

2.0

0.20

177.0

4.0

23.9

17.0

13.7

13.1

7.4

10.9

Chilled Water FCU

10

3.40

3.0

0.40

237.0

40.0

23.9

17.2

13.5

12.9

15.0

4.6

Chilled Water FCU

15

5.70

5.7

0.00

457.0

4.0

23.9

16.8

13.6

12.9

4.4

18.3

Chilled Water FCU

11

15

60

25.80

23.6

2.20

1896.0

240.0

24.0

17.2

13.6

13.0

7.1

10.4

Chilled Water FCU

4.5

11

15

60

25.80

23.6

2.20

1896.0

240.0

24.0

17.2

13.6

13.0

7.1

10.4

Chilled Water FCU

51.1

4.5

15

28

8.40

1.10

601

112.0

24.3

17.7

14.1

13.5

6.1

11.8

Chilled Water FCU

Corridor

185

4.5

15

15

GL1F-AHU

1420.5

143

GYM Ladies

253

4.5

15

60

144

Gents Toilet

52

4.5

15

145

Lockers Changing (Ladies) -LCL-1

33.7

4.5

15

146

Ladies Toilet

52

4.5

15

147

Store Room(STO-1)

37

4.5

15

194

148

Corridor

86.5

4.5

15

149

Additional Space (ASP-2)

50.1

4.5

15

150

PLAY AREA

726

15

151

Plant Room

130.2

4.5

15

sqmt/K
lps/sqmt
W

Served by FAHU-1

System

Chilled Water FAHU

GYM LADIES 1ST FLOOR (GL1F)


283.3

184.9

98.40

31

12714

948

2482.00

240

25.2

19.2

13.1

12.6

5.0

9.0
9.8

Chilled Water AHU

9.1

Ectract Air

6.4

Chilled Water AHU

9.1

Ectract Air

5.3

Chilled Water AHU

697

32

8.1

Chilled Water AHU

376

32

7.5

Chilled Water AHU

150

97.3

7690.0

600.0

10.6

Chilled Water AHU

10

806

6.2

Chilled Water AHU

474
3

214

32

474

MEETING ROMMS & OFFICES 1ST FLOOR (MR1F)


152

Office (OF1)

81

4.5

11

15

10

12.30

11.7

0.60

934.0

40.0

23.5

16.6

13.1

12.5

6.6

11.5

VRF

153

Faculty Offcie

230

4.5

15

40

23.90

21.3

2.60

1715.0

160.0

23.3

16.8

13.0

12.4

9.6

7.5

VRF

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

Page 7 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil
Supply Air Fresh air
(lps)
(lps)

Air Offcoil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

154

DEANS OFFICE

55

4.5

11

15

7.00

6.5

0.50

513.0

155

Meeting Room (M)

51.1

4.5

15

12

6.10

5.3

0.80

156

Meeting Room (M1)

51

4.5

15

12

6.60

5.9

157

Meeting Room (M2)

56

4.5

15

14

7.40

6.5

158

Gent Toilet

52

4.5

15

159

Office (OF2)

38

4.5

11

15

10

6.60

6.0

0.60

482.0

40.0

23.7

17.0

13.3

12.7

160

Office (OF3)

46

4.5

11

15

6.10

5.6

0.50

449.0

32.0

23.7

16.9

13.3

161

Office (OF4)

57

4.5

11

15

10

8.50

7.9

0.60

631.0

40.0

23.6

16.9

13.3

162

Corridor

40

4.5

15

163

Unknown Space

28

4.5

15

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

32.0

23.4

16.5

12.8

12.2

7.9

9.3

VRF

425.0

48.0

23.5

17.0

13.1

12.5

8.4

8.3

VRF

0.70

470.0

48.0

23.5

16.9

13.1

12.5

7.7

9.2

VRF

0.90

526.0

56.0

23.6

17.1

13.3

12.7

7.6

9.4

VRF

0.0

Extract Air

5.8

12.7

VRF

12.7

7.5

9.8

VRF

12.7

6.7

11.1

VRF

sqmt/K
lps/sqmt
W

400.0

Served by FAHU-1

3.60

3.4

0.20

System

Chilled Water FAHU

272.0

20.0

23.6

16.8

13.3

12.7

7.8

9.7

5591

392

25.2

18.9

13.4

12.8

6.4

7.6

0.0

200.0

0.0

Extract Air

VRF

GYM & PLAY AREA GROUND FLOOR (GPGF)


GPGF-AHU

734

114.9

79.4

164

TOILET LADIES

52

4.5

15

165

Lockers/Changing Ladies

48

4.5

15

3.0

234.0

20.0

4.9

Chilled Water AHU

166

Lockers/Changing Gents

54

4.5

15

5.4

424.0

20.0

7.9

Chilled Water AHU

167

Gents Toilet

52

4.5

15

200.0

0.0

Extract Air

168

Lockers Changing-1

8.8

Chilled Water AHU

60

4.5

15

6.7

35.50

529.5

32

169

Lockers Changing-2

170

Lobby & Corridor

218

4.5

15

15

13.2

1047.0

60.0

4.8

Chilled Water AHU

171

Store - SO-1

41

4.5

15

2.5

194.0

4.0

4.7

Chilled Water AHU

172

Gymnasium

189

4.5

15

40

29.7

2345.0

240.0

12.4

Chilled Water AHU

Chilled Water AHU

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

Page 8 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

173

Store

20

4.5

15

Total (KW)

Sensible(K
W)

Air On Coil
Latent
(KW)

4.5

Supply Air Fresh air


(lps)
(lps)

DB
(deg
C)

WB
(deg
C)

Air Offcoil
DB
(Deg
C)

WB
(Deg
C)

352.0

8.0

200.0

23.6

16.6

13.3

12.6

16092

2374

27.2

19.9

13.6

13

Check Figures
sqmt/K
lps/sqmt
W

System

17.6

Chilled Water AHU

6.4

#VALUE!

VRF (Fresh Air by


FAHU-3)

4.0

10.5

RECEPTION AND ENTRACE GROUND FLOOR (REGF)


174

RECEPTION AND ENTRANCE

506

15

50

79.60

76.4

3.20

DINING AREA GROUND FLOOR (DPGF)


DPGF-AHU-1

1528.8

380.1

263.1

117.00

175

Female Staff Dinign Room

204

4.5

11

15

80

30.8

2432.0

320.0

11.9

Chilled Water AHU

176

Store (S-02)

22.8

4.5

15

2.0

155.0

4.0

6.8

Chilled Water AHU

177

Gents Dining Area

675

4.5

11

15

230

76.1

6018.0

920.0

8.9

Chilled Water AHU

178

Ladies Dining Area

378

4.5

15

200

71.3

5637.0

800.0

14.9

Chilled Water AHU

179

Kitchen

149

4.5

11

15

30

19.3

1529.0

560.0

10.3

Chilled Water AHU

180

Ladies Toilet

50

4.5

15

1187.0

400.0

23.7

Extract Air

181

Gents Toilet

50

4.5

15

400.0

0.0

Extract Air

PRAYER HALLS GROUND FLOOR (DPGF)


DPGF-AHU-2

1097.2

192.5

182

Lift Lobby

14

4.5

15

183

Service Zone

89

4.5

15

184

Male Prayer Hall

225

4.5

185

Lobby near Male Prayer Hall

60

4.5

186

Male Toilet & Ablusion Areaa

28

187

Female Prayer Hall

188

43.40

2.70

216.0

28.0

15.4

Chilled Water AHU

10.3

812

9.1

Chilled Water AHU

15

100

21.4

1687.0

400.0

7.5

Chilled Water AHU

15

15

4.3

343.0

60.0

5.7

Chilled Water AHU

4.5

15

8.8

Extract Air

225

4.5

15

80

21.4

1688.0

320.0

7.5

Chilled Water AHU

Lobby near Female Pryer Hall

41

4.5

15

10

7.6

601.0

40.0

14.7

Chilled Water AHU

189

Female Toilet & Ablusion area

28

4.5

15

8.8

Extract Air

190

Nurses Section

86

4.5

15

7.0

554.0

32.0

6.4

Chilled Water AHU

191

Service Room

16.2

4.5

15

1.1

91.0

4.0

5.6

Chilled Water AHU

192

Gents Toilet

52

4.5

15

494.0

400.0

9.5

Extract Air

247.0

Page 9 of 11

18.3

13.2

12.5

9.2

988

247.0

25.5

5.7

10055

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

149.1

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

193

Corridor to Prayer Halls

233

4.5

15

25

Total (KW)

Sensible(K
W)

Air On Coil
Latent
(KW)

49.3

Supply Air Fresh air


(lps)
(lps)

3898.0

DB
(deg
C)

WB
(deg
C)

Air Offcoil
DB
(Deg
C)

WB
(Deg
C)

Check Figures
sqmt/K
lps/sqmt
W

100.0

16.7

System

Chilled Water AHU

EXTERNAL SER GRN FLOOR/Post Graduate Program/Research Study Center (EXGF)


194

External Service Zone

206

4.5

15

15

22.40

21.5

0.90

1699.0

23.5

16.5

13.0

12.3

9.2

8.2

195

Post Graduate Program/Research


Study Center

288

4.5

11

15

30

44.00

42.1

1.90

3381.0

23.7

16.7

13.3

12.7

6.5

11.7

VRF (Fresh Air by


FAHU-2)

ADMIN OFFICE GROUND FLOOR (AOGF)


196

Asst Dean

54

4.5

11

15

10

9.20

8.6

0.60

678.0

23.4

16.5

12.9

12.2

5.9

12.6

197

IT Dept

123

4.5

21

15

14

13.50

12.6

0.90

998.0

23.5

16.6

13.0

12.4

9.1

8.1

198

Server Room

26.4

4.5

35

15

3.20

3.0

0.20

241.0

23.7

16.7

13.2

12.6

8.3

9.1

199

Main Control (Security)

27

4.5

21

15

3.80

3.7

0.10

296.0

23.4

16.5

13.1

12.4

7.1

11.0

200

Corporate ID

54

4.5

15

5.90

5.6

0.30

443.0

23.5

16.6

13.0

12.4

9.2

8.2

201

Center & Research

189

4.5

11

15

18

18.10

16.9

1.20

1342.0

23.5

16.6

13.0

12.4

10.4

7.1

202

Store-1

39.6

4.5

15

4.50

4.4

0.10

358.0

23.5

16.5

13.2

12.6

8.8

9.0

203

Store-2

38.7

4.5

15

4.60

4.5

0.10

358.0

23.4

16.3

12.9

12.2

8.4

9.3

204

Service Room - SR01

14.2

4.5

15

6.40

6.4

0.00

497.0

23.3

16.1

12.6

12.0

2.2

35.0

205

Ladies Toilet

40

4.5

15

315

7.9

Extract Air

206

Gents Toilet

40

4.5

15

315.0

7.9

Extract Air

207

Admin & Finance Dept

189

4.5

11

15

45

40.30

37.5

2.80

2983.0

23.6

16.7

13.1

12.5

4.7

15.8

208

Quality Assurance

108

4.5

11

15

12

18.80

18.0

0.80

1425.0

23.5

16.5

13.0

12.4

5.7

13.2

209

INT Audit & CRTL Dept

54

4.5

11

15

11

9.00

8.3

0.70

665.0

23.3

16.5

12.9

12.3

6.0

12.3

210

Waiting Area

81

4.5

11

15

20

16.00

14.7

1.30

1163.0

23.4

16.6

12.9

12.2

5.1

14.4

211

Corridor

177

4.5

15

15

15.20

11.3

3.90

794.0

25.2

18.0

12.4

11.4

11.6

4.5

2993.0

23.5

16.7

13.0

12.4

8.4

8.6

VRF (Fresh Air by


FAHU-3)

0.0

Extract Air

VRF (Fresh Air by


FAHU-3)

VRF (Fresh Air by


FAHU-3)

ADMISSION REGISTRATION GROUND FLOOR (ARGF)


212

ADMISSION REGISTRATION

350

4.5

11

15

60

213

TOILET LADIES & GENTS

50

4.5

15

214

Files storage - FS1

54

4.5

15

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

41.60

37.8

3.80

400.0
5.30

5.1

0.20

425.0

24.3

17.4

14.3

13.7

10.2

7.9

VRF (Fresh Air by


FAHU-3)
Page 10 of 11

AIRCONDITIONING SYSTEM DESIGN SUMMARY


Cooling Capacity

Air On Coil

SI NO:

Description

Area
(m2)

Height

Electrical
Equipment
(W/m2)

Lighting
Load
(W/m2)

Occupancy
(Nos of
people)

Total (KW)

Sensible(K
W)

Latent
(KW)

215

Admin & Reg off- AR1

30

4.5

11

15

4.70

4.4

0.30

216

Secretary

30

4.5

11

15

3.3

3.1

217

Admin/Reg off- AR2

20

4.5

11

15

2.60

2.4

Note:
1. Fresh Air for Rooms shall be served by the FAHUs at the rate of 4 lps/person based on the occupancy defined.
2. The Filled Cells indicate the rooms changed as per the revised Architectural Drawings issued on 18-07-13

Page 11 of 11

Supply Air Fresh air


(lps)
(lps)

Air Offcoil

Check Figures

DB
(deg
C)

WB
(deg
C)

DB
(Deg
C)

WB
(Deg
C)

365.0

24.2

17.4

14.2

13.5

6.4

12.2

0.20

248

24.2

17.4

14

13.3

9.1

8.3

0.20

198.0

24.3

17.4

14.1

13.4

7.7

9.9

sqmt/K
lps/sqmt
W

System

VRF (Fresh Air by


FAHU-3)