You are on page 1of 2

Low consumption Y-Pack Range

38

TCAEY-THAEY 2702160
Cooling capacity: 67161 kW - Heating capacity: 79175 kW

3 capacity steps ESEER up to 4.37 Wide range of accessories

TCAEQY 270 THAESY 2145

TCAEBY 2160

Air-cooled water chillers and reversible heat pumps with axial fans. Range with hermetic Scroll compressors and R410A refrigerant.
Construction features
Compressor: hermetic, rotary scroll compressor, complete with thermal protection and crankcase heater. 2 or 3 capacity steps depending on the models with high eciency at partial loads. Water side heat exchanger: stainless steel plate exchanger, complete with closed cell polyurethane foam rubber insulation and water ow dierential pressure switch. Air side heat exchanger: nned coil exchanger, with copper pipes and aluminium ns. Fan: electric axial fans with external rotor, equipped with internal thermal protection, protection grilles and proportional electronic device for continuous regulation of fan rotation speed (TCAEBY excluded). Control: microprocessor electronic control iDRHOSS compatible, with Adaptive Function Plus logic for connection with the main BMS on the market (MODBUS RTU, LON). Structure: load-bearing structure in galvanised and painted sheet steel with polyester powder coating. The unit is also complete with: - compressor and fan thermal overload switches.

Models

TCAEBY: standard unit designed for cooling only. TCAETY: high temperature/eciency unit designed for cooling only. TCAESY: silenced unit designed for cooling only. TCAEQY: supersilenced unit designed for cooling only. THAETY: heat pump unit. THAESY: silenced heat pump unit.

FACTORY FITTED ACCESSORIES

Versions

B - Standard version (TCAEBY). T - High temperature/eciency version with larger coil surface (TCAETY-THAETY). S - Silenced version complete with soundproofed compressor compartment, lower fan speed and larger coil surface (TCAESYTHAESY). Q - Supersilenced version complete with soundproofed compressor compartment, super-low fan speed and larger coil surface (TCAEQY).

PUMP with single or double pump, including an automatic pump in standby, complete with expansion tank, safety valve and water pressure gauge. The pumps are available in the low or high pressure versions. TANK&PUMP with built-in buer tank from 250 to 450 litres and single or double pump, complete with expansion tank, air bleed valves, safety valve and water pressure gauge. Desuperheater. 100% heat recovery. Electronic expansion valve. -10C condensation control (TCAEBY only). Power factor correction capacitors (cos > 0.91). Soft starter. Refrigerant circuit high and low pressure gauges. Metal lters or coil protection grilles. Copper/copper or copper/pre-painted aluminium coils. Digital input for double set-point 4-20 mA analogue input for shifting set-point. Evaporator antifreeze heater, buer tank, pumps and heat exchangers for heat recovery if present. Serial interface for connection with external BMS.

ACCESSORIES SUPPLIED LOOSE

Antivibration rubber mountings. Remote keyboard with display. Clock card GSM 900/1800 modem kit for remote unit management. RHOSS supervision software for unit monitoring and remote management. Rhoss sequencer for the integrated management of several water chillers.

Web code: C2Y1

COOLING ONLY

HEAT PUMP

OUTDOOR INSTALLATION

39

E.E.R. Absorbed power TCAETY-TCAESY-TCAEQY MODEL Nominal cooling capacity Nominal cooling capacity Nominal cooling capacity E.E.R. E.E.R. E.E.R. E.S.E.E.R. E.S.E.E.R.+ Absorbed power Absorbed power Absorbed power THAETY-THAESY MODEL Nominal heating capacity Nominal heating capacity C.O.P. C.O.P. Nominal cooling capacity Nominal cooling capacity Absorbed power Absorbed power E.E.R. (EN 14511:2004) (***) C.O.P. (EN 14511:2004) (***) TCAEY-THAEY MODEL Sound pressure level TCAEBY Sound pressure level TCAETY-THAETY Sound pressure level TCAESY-THAESY Sound pressure level TCAEQY Sound power level TCAEBY Sound power level TCAETY-THAETY Sound power level TCAESY-THAESY Sound power level TCAEQY Scroll/step compressor Circuits Electrical supply DIMENSIONS AND WEIGHTS L - Width version B L - Width version T - S - Q H - Height version B H - Height version T - S - Q P - Depth version B P - Depth version T - S - Q Weight TCAEBY Weight TCAETY-TCAESY-TCAEQY Weight THAETY-THAESY mm mm mm mm mm mm kg kg kg dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) no. no. V-ph-Hz kW kW kW kW kW kW kW kW kW kW kW kW kW

2,65 25,5 270 70,4 70,4 67,0 2,98 2,98 2,70 4,32 4,99 23,6 23,6 24,8 270 79,0 79,0 3,36 3,36 69,4 69,4 23,5 23,5 3,44 4,26 270 53 50 48 46 82 76 74 72 2/3 1 400-3+N-50 270 2.650 3.150 1.700 1.520 1.210 1.210 685 745 810

2,69 28,0 280 79,5 79,5 75,0 2,99 2,99 2,85 4,37 5,06 26,6 26,6 26,3 280 86,0 86,0 3,44 3,44 77,7 77,7 25,0 25,0 3,49 4,34 280 53 51 49 47 82 77 75 73 2/2 1 400-3+N-50 280 2.650 3.150 1.700 1.520 1.210 1.210 725 765 830

2,56 32,4 290 88,0 88,0 82,5 2,90 2,90 2,62 4,35 5,04 30,3 30,3 31,5 290 96,0 96,0 3,29 3,29 85,2 85,2 29,2 29,2 3,30 4,17 290 53 51 49 47 82 77 75 73 2/3 1 400-3+N-500 290 2.650 3.150 1.700 1.520 1.210 1.210 870 910 975

2,69 35,7 2100 101,2 101,2 95,0 2,90 2,90 2,73 4,32 4,99 34,9 34,9 34,8 2100 111,0 111,0 3,34 3,34 99,3 99,3 33,2 33,2 3,32 4,22 2100 55 52 50 48 84 78 76 74 2/3 1 400-3+N-50 2100 3.150 3.150 1.700 1.520 1.210 1.210 945 980 1045

2,72 40,6 2115 114,5 108,0 101,0 2,93 2,67 2,34 4,37 5,07 39,1 40,4 43,2 2115 122,0 120,0 3,21 3,22 111,0 107,2 38,0 37,3 3,34 4,04 2115 61 55 52 49 90 84 81 78 2/3 1 400-3+N-50 2115 3.150 3.250 1.730 2.000 1.210 1.520 1.020 1.130 1.215

2,64 45,6 2130 126,0 119,0 108,0 2,91 2,67 2,30 4,31 4,96 43,3 44,6 47,0 2130 139,0 135,0 3,31 3,31 123,8 118,5 42,0 40,8 3,33 4,14 2130 61 55 52 49 90 84 81 78 2/2 1 400-3+N-50 2130 3.150 3.250 1.730 2.000 1.210 1.520 1.040 1.195 1.285

2,66 52,1 2145 143,0 136,0 125,0 2,90 2,63 2,32 4,29 4,94 49,3 51,7 53,9 2145 157,0 154,0 3,22 3,25 141,3 135,6 48,8 47,4 3,30 4,01 2145 61 56 53 50 90 85 82 79 2/3 1 400-3+N-50 2145 3.150 3.250 1.730 2.000 1.210 1.520 1.100 1.225 1.315

2,61 59,4 2160 161,0 151,0 2,90 2,60 2,20 4,26 4,91 58,1 62,6 2160 175,0 170,0 3,21 159,8 150,2 54,5 53,0 3,29 4,02 2160 62 56 53 50 91 85 82 79 2/2 1 400-3+N-50 2160 3.450 3.250 1.730 2.000 1.210 1.520 1.160 1.390 1.290 3,21 55,5

In the following conditions: Air: 35C - Water: 12/7C Air: 7C D.B. - 6C W.B.- Water: 40/45C. At 10 m from the unit in free eld (Q = 2), coil side. Total sound power level in dB(A) on the basis of measurements taken in accordance with UNI EN-ISO 9614. Weight refers to the non-accessorised unit when empty. ESEER (European Seasonal EER) - Average European seasonal eciency. ESEER with Adaptive Function Plus software. (***) Energy indices for THAETY versions, calculated in compliance with that envisaged by EN 14511: 2004 Standard, in the conditions prescribed by the Finance Act, Italian market. TCAESY-THAESY silenced versions. TCAEQY super-silenced versions.

TERMINAL UNITS

FAN COIL UNITS

SYSTEM ACCESSORIES

CONDENSING UNITS

EXP Polyvalent systems

INDUSTRIAL & PROCESS COOLING

WATER cooled CONDENSERLESS UNITS

WATER CHILLERS HEAT PUMPS

AIR cooled CENTRIFUGAL fans

138,2

WATER CHILLERS HEAT PUMPS

AIR cooled AXIAL fans

Nominal cooling capacity

kW

67,5

75,3

83,0

96,0

110,5

120,5

138,5

155,0

WATER CHILLERS HEAT PUMPS

TCAEBY MODEL

270

280

290

2100

2115

2130

2145

2160

You might also like