CFD ANALYSIS OF WIND DRIVEN NATURAL CROSS VENTILATION FOR A GENERIC ISOLATED BUILDING
N.S. Venkatesh Kumar1, Prof. K. Hema Chandra Reddy2
1

(Research Scholar, Department of Mechanical Engg., JNTUA, Anantapuram, A.P., India) 2 (Registrar, JNTUA, Anantapuram, Andhra Pradesh, India)

ABSTRACT Natural ventilation, which provides occupants with good indoor air quality and a high level of thermal comfort with reduced energy costs, has been drawing importance in sustainable strategy in building designs. This investigation used computational fluid dynamics (CFD) models to study the ventilation properties for a room with different opening configurations. The 3D steady RANS equations are solved in combination with the shear-stress transport (SST) k- model. The inlet wind velocity profile is defined according to the logarithmic law in accordance with urban climate. Ground surface roughness is considered for the analysis. The flow around a building captured the circulating bubbles upstream and downstream of the building, and the steady flow pressure coefficient has the same trend as the experimental ones. Air momentum transport seems to be carried mainly by convection and hardly by turbulent diffusion for cross ventilation. Keywords: computational fluid dynamics, ventilation, velocity profile, flow pattern, cross ventilation 1. INTRODUCTION Natural ventilation, which provides occupants with good indoor air quality and a high level of thermal comfort with reduced energy costs, has been drawing importance in sustainable strategy in building designs and is thus attracting considerable interests from designers [1] & [2]. Wind and buoyancy are the driving forces for natural ventilation. Wind pressure differences along the faade and differences between indoor and outdoor temperatures create a natural air exchange between indoor and outdoor air. The ventilation rate depends on the strength and direction of these forces and the resistance of the flow path. Prediction of ventilations rates is difficult as these physical processes are complex. Hence, it is challenging to control natural ventilation in order to obtain the required indoor environment conditions.
200

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

The configurations of building rooms and especially the location of inlet and outlet openings in relation to dominant wind direction at the site have major effects on the ventilation rates in buildings. Studies identified that locating Inlet openings near high-pressure surfaces of a building and exit openings at low-pressure ones produces higher flow rates through windows. Accordingly, an understanding of air flow around the building is necessary to design well-ventilated residences. External flows around buildings are very complicated involving severe pressure gradients, streamline curvature, swirl, separation and reattachment together with the resulting effects of enhancing and suppression of turbulence. Empirical models, experimental measurements and computational fluid dynamics (CFD) simulations are the three approaches available to study natural ventilation. The empirical models, as reviewed by [3], are often developed from analytical solutions and experimental data. Although the models are very useful for natural ventilation design, they could not provide sufficient information on natural ventilation and may not be so accurate. It has been proven that the experimental measurements are effective as a tool to obtain realistic information about natural ventilation [4]. The measurements are not only very expensive but also time consuming. Added to this, the data may not be in great enough detail for understanding the mechanism of natural ventilation. CFD has a number of clear advantages compared with the other approaches: (1) as opposed to most experimental techniques including Particle Image Velocimetry (PIV) , CFD provides field data as regards whole-flow, i.e. data on the relevant parameters in every point of the computational domain; (2) CFD avoids the sometimes incompatible similarity requirements in reduced-scale testing because simulations can be performed at full scale; and (3) CFD allows full control over the boundary conditions and easily and efficiently allows parametric studies to be performed[5]. CFD models are currently most popular and particularly suited for studying indoor air quality and natural ventilation, as these are difficult to be predicted using other models. For the above reasons, many studies on evaluating and optimizing the natural ventilation potential of buildings have employed CFD. In view of above factors, the present work is aimed to employ computational fluid dynamics to determine the distribution of steady, three-dimensional and turbulent in-room and external flow field of an isolated generic building. Although the effects of neighboring buildings can be significant, only an isolated room is considered for the present work to test the basic natural ventilation rules as affected by relative opening location and different sizes. The CFD simulations are carried out using ANSYS-CFX, CFD software. The two-equation SST turbulence model is used. 2. CFD SIMULATIONS Computational settings and parameters for the reference case are outlined and accordingly the results for this case are presented. Later on, these settings and parameters will be systematically modified for the parametric study. 2.1. Computational domain and grid The dimensions of the generic isolate building and computational domain were chosen from [5]. The buildings had dimensions W x D x H = 100 x 100 x 80 mm and thickness of the walls is 2 mm (reduced scale) corresponding to full-scale dimensions W x D x H = 20 x 20 x 16 m. Computational domain dimensions are calculated as width WD = W +10H, height HD = H + 5H and upstream and downstream length of 3H and 15H .The resulting dimensions of the domain were W x D x H = 0.9 x 1.54 x 0.48 m (reduced scale), which corresponds to 180 x 308 x 96 m in full scale. The computational grid is made of unstructured mesh with Hexa-core, tetrahedral surface mesh and prismatic elements on building walls. The prismatic elements at wall boundaries of building are able

201

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

to provide fine mesh for capturing boundary layer. The geometry and mesh is generated using ICEM CFD, meshing software.

Fig.1: Surface mesh for domain (tetrahedral)

Fig.2: Volume mesh on central plane

Fig.3: Dense mesh around

2.2. Boundary conditions The inlet boundary conditions used in the simulations were based on the measured incident vertical profiles of mean wind speed and turbulence intensity. The inlet wind velocity profile is defined according to the logarithmic law with Y0 = 0.025 mm (Eq. 1), where 0.3627[m s^-1] is the ABL friction velocity, the von Karman constant (0.42) and y the height coordinate. Expression incorporated in CFX ; (0.3627[m s^-1]/0.42)*ln((y+0.000025[m])/0.000025[m]) (1)

For the ground surface, the no-slip wall functions with roughness height of 0.28 mm are chosen. No-slip wall functions are also used at the building surfaces, but with zero roughness height. Zero static pressure is applied at the outlet plane. Free-slip wall functions are used at the remaining
202

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

domain surfaces. The computational domain with boundary condition and velocity profile at inlet is as shown below.

Fig.4: Applied boundary conditions

Fig.5: velocity profile at inlet

2.3. Solver settings The 3D steady RANS equations were solved in combination with the shear-stress transport (SST) k- model. Advection scheme adapted for solving momentum governing equations is High resolution and for turbulence equations first order scheme. The convergence criteria are taken as 10-6. 3. RESULTS AND DISCUSSION CFD simulations of wind driven natural cross ventilation for generic isolated building are carried out using ANSYS CFX, CFD software. The results presented here are for three cases named as case I, case II and Case III. Case I refers to cross ventilation with equal area of inlet and exit openings, both are situated at center of wall. Case II is with larger opening and small inlet area and situated same as in Case I. The third one represents for equal inlet and exit opening areas and inlet is situated at bottom center and top center of front and rear wall. The pressure and velocity distributions are shown by contour plots and velocity vectors. 3.1. Case I The velocity vector field and pressure contours in the vertical center plane are presented below. Main features of the flow simulated are the standing vortex upstream of the building, the contraction and expansion of the indoor flow, the recirculation zone behind the room and the separation zone on the roof. External flow features resembles that of square block.

Fig 6: central plane vertical


203

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

Fig 7: pressure distribution in CPV The velocity vector field shows the inlet velocity profile which varies with the height and ground surface roughness which accounts the nature of surroundings. The results are thus expected to be varying in accordance with building height and surrounding ground roughness.

Fig: 8 Velocity vector in CPV around the building and in room The below figures show velocity vector field, velocity and pressure contour in the horizontal plane at height of 0.04 m. It can be seen that only the area spanned by the cylindrical stream tube is actually ventilated. The ventilated zones are generally referred as active and non-ventilated as calm or dead zone. The blue color zone represents the dead zone. The red color in pressure contour represents stagnation flow field which is located at top of front wall and on two sides of opening.

Fig: 9 Velocity vector in CPV around the building and in room


204

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

Fig: 10 Pressure vector in CPV around the building and in room

Fig: 10 Velocity contour in CPV around the building and in room

3.2. Case II The results presented are for cross ventilation with increased area for exit openings. Supply and exhaust window location are at the center of opposite walls. The below figures shows the air flow vector field velocity and pressure contours in the vertical center plane. The plan of the ventilated zone seems to have larger area at exit and looks resembles a trapezoid. Transport of air momentum seems to be carried mainly by convection and hardly by turbulent diffusion.

Fig: 10 Velocity vector in CPV around the building and in room

205

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

Fig: 11 Pressure contour in CPV around the building and in room

Fig: 12 Velocity contour in CPV around the building and in room

Fig: 13 Velocity vector field in the horizontal plane plane at height of 0.04 m

Fig: 14 Pressure contour in the horizontal at height of 0.04 m

3.3. Case III The results presented are for cross ventilation with equal inlet and exit openings. Inlet opening located at bottom ad outlet at top. The below figures shows the air flow vector field and pressure contours in the vertical center plane. There is an increased area of the calm zone at center of room as compared to Case I and fresh air is more attached towards the wall. The quality of air inside of room is decreased. The external flow features are same as that of other cases.

Fig: 15 Velocity vector in the vertical center plane


206

International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6359(Online) Volume 4, Issue 5, September - October (2013) IAEME

Fig: 16 Velocity contour in the vertical center plane 4. CONCLUSIONS The model for flow around a building captures the circulating bubbles upstream and downstream of the building, and the steady flow pressure coefficient has the same trend as the experimental ones. The two-equation turbulence model is a useful tool for predicting in-room flows. Cross ventilation is useful for ventilating the areas passed by the stream tube between inlet and exit openings, but outside the stream tube recirculation zones with no domination of fresh air. The low turbulence level is not enough to enhance momentum transfer from the stream tube to the otherwise stand still air outside the tube. Based on the locations of humans inside the room, the wind incidence angle can cause an increase in velocity magnitude and reduction of calm air zones inside the room. REFERENCES [1] Etheridge, D., Sandberg, M, Building ventilation: theory and measurement (New York: John Wiley and Sons, Chichester; 1996). [2] Allard, F,.Natural ventilation in buildings: a design handbook (UK: James & James, London, 1998). [3] Allocca, C, Single-sided natural ventilation: design analysis and general guidelines, M.Sc. Thesis, Department of Mechanical Engineering, Massachusetts Institute of Technology, Cambridge, MA. 2001. [4] Katayama T., Tsutsumi J., Ishii A., Full-scale measurements and wind tunnel tests on crossventilation (J. Wind Eng. Ind. Aerodyn. 1992, 41-44) 2553-2562. [5] Ramponi R, Blocken B., CFD simulation of cross-ventilation for a generic isolated building: impact of computational parameters, Building and Environment, 2012, 53, 34-48. [6] Tarun Singh Tanwar, Dharmendra Hariyani and Manish Dadhich, Flow Simulation (CFD) & Static Structural Analysis (FEA) of a Radial Turbine, International Journal of Mechanical Engineering & Technology (IJMET), Volume 3, Issue 3, 2012, pp. 252 - 269, ISSN Print: 0976 6340, ISSN Online: 0976 6359. [7] P.S. Jeyalaxmi and Dr.G.Kalivarathan, CFD Analysis of Flow Characteristics in a Gas Turbine- A Viable Approach to Predict the Turbulence, International Journal of Mechanical Engineering & Technology (IJMET), Volume 4, Issue 2, 2013, pp. 39 - 46, ISSN Print: 0976 6340, ISSN Online: 0976 6359.