Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

1
Cts im ndeB U3et Vls 9 rya M oSe - oc Q dnVD nRoX IVFC

Specifications
TECHNICAL SPECIFICATIONS
Cooling Heating Cooling Heating Colour Material Packing Height Width Depth Unit Height Width Depth mm mm mm mm mm mm kg kg mm Length Nr of Rows Fin Pitch Face Area mm m Nr of Passes mm 430 2 1.4 2 0.108 12 4 Hi-XSS (7) Fin type Treatment Symmetric waffle louvre Hydrophilic Sirocco fan 1 m/min m/min m/min m/min Quantity Steps Output (high) Drive W 10 Direct drive R-410A Sound power (nominal) High Low High Low Type Diameter Gas Drain Type Diameter Diameter mm mm 12.7 I.D. 21.6, O.D. 27.2 Resin net with mold resistance Up and downwards Electronic expansion valve Microprocessor thermostat for cooling and heating PC board fuse Fan motor thermal protector mm 6.35 Flare connection 12.7 dBA 50 50 6.7 5.2 6.7 5.2 1 step motor 10 1 7.4 5.8 7.4 5.8 1 301 584 753 230 502 652 17 18 >250 430 2 1.4 2 0.108 12 kW kW kW kW
FXDQ20M9V3B FXDQ25M9V3B

1-1

Capacity

2.2 2.5 0.050 0.050 Non painted Galvanised steel

2.8 3.2 0.050 0.050

1
1

Power Input (50Hz) Casing Dimensions

301 584 753 230 502 652 17 18

Weight

Unit Packed Unit

Required Ceiling Void Heat Exchanger Dimensions

Nr of Stages Empty Tubeplate Hole Tube type Fin Fan Cooling Heating Fan Type Quantity High Low High Low Motor

Refrigerant Sound level

Name Cooling

Cooling Heating Piping connections

Sound Pressure Sound Pressure Liquid (OD)

dBA dBA dBA dBA

37 32 37 32 Flare connection

37 32 37 32 6.35

Air Filter Air direction control Refrigerant control Temperature control Safety devices

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

1
1-1
Notes

Specifications
TECHNICAL SPECIFICATIONS
FXDQ20M9V3B FXDQ25M9V3B

Nominal cooling capacities are based on : indoor temperature : 27CDB, 19CWB, outdoor temperature : 35CDB, equivalent refrigerant piping : 8m, level difference : 0m. Nominal heating capacities are based on : indoor temperature : 20CDB, outdoor temperature : 7CDB, 6CWB, equivalent refrigerant piping : 8m, level difference : 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

3 1
1

1-2 ELECTRICAL SPECIFICATIONS (50HZ)


Power Supply Name Phase Frequency Voltage Current Minimum circuit amps (MCA) Full load amps (FLA) Voltage range Notes Minimum Maximum Hz V A

FXDQ20M9V3B

FXDQ25M9V3B

V1 1~ 50 230 0.2 16 0.1 -10% +10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA < 4 x FLA Next lower standard fuse rating minimum 16A Select wire size based on the MCA Instead of a fuse, use a circuit breaker 50 230 0.2 16 0.1

Maximum fuse amps (MFA) A A V V

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

Safety device settings

1
2

FXDQ20M9 FAN MOTOR THERMAL PROTECTOR PC BOARD FUSE C OFF:1358, (ON:8715) 250V 10A

FXDQ25M9

3TW25511-3

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

Options

FXDQ20M9 WIRING ADAPTER (HOUR METER) (1) EKRP1B2

FXDQ25M9 3TW25779-1D

3 1
3

NOTE

Fixing box = KRP1A90

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

Control systems

Individual control systems


FXDQ20M9 FXDQ25M9 BRC1D52 BRC4C62 BRC4C64 BRC2A51 BRC3A61 WIRED REMOTE CONTROL INFRARED REMOTE CONTROL SIMPLIFIED REMOTE CONTROL REMOTE CONTROL FOR HOTEL USE

1
4

Heat pump Cooling only

Centralised control systems


FXDQ20M9 CENTRALISED REMOTE CONTROL UNIFIED ON/OFF CONTROL SCHEDULE TIMER DCS302C51 DCS301B51 DST301B51 FXDQ25M9

Others
FXDQ20M9 WIRING ADAPTER WIRING ADAPTER FOR ELECTRICAL APPENDICES (1) WIRING ADAPTER FOR ELECTRICAL APPENDICES (2) REMOTE SENSOR ELECTRICAL BOX WITH EARTH TERMINAL (3 BLOCKS) ELECTRICAL BOX WITH EARTH TERMINAL (2 BLOCKS) NOISE FILTER (FOR ELECTROMAGNETIC INTERFACE USE ONLY) EXTERNAL CONTROL ADAPTER FOR OUTDOOR UNITS (INSTALLATION ON INDOOR UNIT) KRP1B61 KRP2A51 KRP4A51 KRCS01-1 KJB311A KJB212A KEK26-1A DTA104A61 3TW25779-1D FXDQ25M9

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

5
5-1

Capacity tables
Cooling capacity tables
Indoor air temperature 19.0WB 27.0DB TC SHC 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.2 1.8 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 2.8 2.1 TC: Total capacity;kW SHC: Sensible capacity;kW 20.0WB 28.0DB 22.0WB 30.0DB 24.0WB 32.0DB

FXDQ-M9
Nominal capacity 2.2 Outdoor air temp. CDB 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0

3
SHC 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 TC 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 18.0WB 26.0DB SHC 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 TC 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 TC 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.4 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 SHC 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 TC 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 SHC 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 2.3 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 2.0 2.0

Unit size 20

25

2.8

TC 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

14.0WB 20.0DB

SHC 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

TC 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

16.0WB 23.0DB

1
5

3TW25772-1

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

5
5-2
Unit Size

Capacity tables
Heating capacity tables
Nominal capacity 2.5 Outdoor air temperature 16.0 kW 1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.8 2.8 2.8 1.9 1.9 2.1 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.6 3.6 3.6 18.0 kW 1.5 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.5 2.5 2.6 2.7 2.7 2.7 2.7 1.9 1.9 2.1 2.2 2.3 2.4 2.4 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.4 3.4 3.4 3.4 3.4 Indoor air temperature CDB 20.0 21.0 kW kW 1.5 1.5 1.5 1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 1.9 1.9 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.4 2.5 2.4 2.5 2.4 2.5 2.4 2.5 2.4 2.5 2.4 1.9 1.9 1.9 1.9 2.0 2.0 2.2 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 3.0 3.0 3.1 3.1 3.2 3.1 3.2 3.1 3.2 3.1 3.2 3.1 3.2 3.1 3.2 3.1 22.0 kW 1.5 1.5 1.6 1.7 1.8 1.9 1.9 1.9 2.0 2.1 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 1.9 1.9 2.0 2.2 2.3 2.4 2.4 2.5 2.6 2.7 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 24.0 kW 1.5 1.5 1.6 1.7 1.8 1.9 1.9 1.9 2.0 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 1.9 1.9 2.0 2.1 2.3 2.4 2.4 2.5 2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3TW25512-2A

FXDQ-M9
CDB -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 CWB -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1
5

20

25

3.2

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

6
6-1

Dimensional drawing & centre of gravity


Dimensional drawing

FXDQ-M9
(Suspension position)

3
Nr 1 2 3 4 5 6 7 8 Part name Liquid pipe connection ( 6.35) Gas pipe connection ( 12.7) Drain hole (o.d. 27.2 - i.d. 21.6) Transmission wiring port Power supply wiring port Service space Switch box Nameplate

1
6

(Suspension position)

300 or more

250 or more

3TW25774-1

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

Piping diagram

FXDQ-M9

1
7

Heat exchanger

Fan

Liquid pipe connection port

Filter

Electronic expansion valve

Filter Gas pipe connection port

Refrigerant flow Cooling Heating

Piping connection diameters Model FXDQ20,25M9 Gas 12.7 Liquid 6.4

3TW21175-1C

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

8
8-1
FXDQ-M9

Wiring diagram
Wiring diagram

3 1
8
Terminals for operation indicator indoor Fan operation Wiring adapters Note 4 input from outside Centralised remote control note 2 Wired remote control Compressor operation

Switch box

Switch box cover

A1P C1R F1U F2U HAP M1F Q1E R1T R2T, R3T

Printed circuit board Capacitor (Fan) Fuse (250V, 10A) Field fuse Light emitting diode (Service monitor-green) Motor (Fan) Earth leak detector Thermistor (Air) Thermistor (Refrigerant)

RyF1-3 Magnetic relay (Fan) T1R Transformer (220-240V/22V) X1M Terminal strip (Power) X2M Terminal strip (Control) Y1E Electronic expansion valve Optional parts J1EH Electric heater K1R Magnetic relay (J1EH) Wiring adapter

RyC, RyF Magnetic relay RyH Magnetic relay (J1EH) F1U, F2U Fuse (250V, 5A) X1A, X2A Connector (Wiring adapter) X1M Terminal strip Connector for optional parts X16A Connector (Wiring adapter) X18A Connector (Wiring adapter for electronical appendices)

L N

: Field wiring : Live : Neutral : Connector : Wire clamp : Protective earth (screw)

COLORS : BLK : Black BLU : Blue BRN: Brown ORG : Orange

PNK : Pink RED : Red WHT : White YLW : Yellow

NOTES

1 2 3 4

Use copper conductors only. When using a centralised remote control, see manual for connection to the unit. When installing the electric heater change the wiring for the heater circuit. The main power supply has to be supplied independently. When connecting the input wires from the outdoor unit 'forced off' or 'on/off' operation can be selected by the remote control. For more details see installation manual.

2TW23666-1E

VRV Systems Indoor Units

10

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

9
9-1

Sound data
Sound level data
Model FXDQ20M9 Sound pressure level - 230V H 37 L 32
Suction Unit Duct Microphone Discharge

FXDQ-M9
Measuring location Sound power level 50

1
9

FXDQ25M9

37

32

Location of microphone

50

NOTES

1 2 3 4 5

dBA = A-weighted sound pressure level (A-scale according to IEC). Reference acoustic pressure 0 dB = 20 Pa. These operating values were obtained using a power source of 230V/50Hz. These operating values were obtained in a dead room (conversion values). Noise values will vary depending on a range of factors such as the construction of the particular room in which the equipment is installed. Operating noise differs with operation and ambient conditions.

11

VRV Systems Indoor Units

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

9
9-2

Sound data
Sound pressure spectrum
3TW21467-1 FXDQ25M9 3TW21477-1

FXDQ20M9

3 1
9

Sound pressure level (dB)

Octave band frequency (Hz) Octave band frequency (Hz)

VRV Systems Indoor Units

Sound pressure level (dB)

12

Indoor Units CONCEALED CEILING UNIT (SMALL) FXDQ-M9V3B

9
9-2

Sound data
Sound pressure spectrum

1
9

13

VRV Systems Indoor Units