ControlLogix Ethernet Communication Interface Module 3 avoid a potential hazard, and recognize the consequences of a potential hazard:
WARNING
!
ATTENTION
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
!
IMPORTANT
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
ATTENTION
ATTENTION
Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static-safe workstation. When not in use, store the equipment in appropriate static-safe packaging.
Door Label
MAC ID Label
AUI
10 BASET
1756-ENET
Side View
Front View
Power Supply
1756-A4 Chassis
20805-M
ControlLogix Ethernet Communication Interface Module 7 For information about installing these products, refer to the publications listed in this table.
Chassis Type Series B: 1756-A4, -A7, -A10, -A13, -A17 Chassis Installation Pub. No. 1756-IN080 Power Supply 1756-PA72/B 1756-PB72/B 1756-PA75/A 1756-PB75/A Power Supply Installation Pub. No. 1756-5.67 Pub. No. 1756-5.78
Chassis
Circuit Board
2 Slide the module into the chassis. Make sure the module backplane connector properly connects to the chassis backplane.
3 The module is properly installed when it is flush with the power supply or other installed modules.
IMPORTANT
If you are replacing an existing module with an identical one, and you want to resume identical system operation, you must install the new module in the same slot.
When you insert or remove the module while backplane power is on, or you connect or disconnect the communications connectors, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
9-Ctrl IN Ckt B 10-Data OUT Ckt B 11-Data OUT Ckt B 12-Data OUT Ckt B 13-Voltage Plus 14-Voltage Shield 15-Ctrl OUT Ckt B
WARNING
!
POWER
OR
POWER
OR
IMPORTANT
Connecting the module to the network via an Ethernet switch will reduce collisions and lost packets and increase network bandwidth. See the EtherNet/IP Performance and Application Guide, publication ENET-AP001, for more information.
If your application requires the module door to be closed, use one of these custom AUI connector cables available in two lengths: 2 meters (catalog number 1756-TC02), or 15 meters (catalog number 1756-TC15).
ON
ON POWER OFF
POWER OFF
20921-M
<www> ETHERNET
POWER
RXD
TXD
OK
If the Power Supply and OK indicators are not in the states described above refer to the following troubleshooting section.
Red
Unrecoverable fault.
This table describes the transmit (TXD) and receive (RXD) indicator display:
If this indicator TXD is Green Off RXD Green Off the module is Transmitting data Not active Receiving data Not active
WARNING
Specifications
Module Location Maximum Backplane Current Load Power Dissipation Operating Temperature Any slot in the ControlLogix chassis 900mA @ 5.1V dc 350mA @ 24V dc from I/O chassis backplane 13.3W maximum IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0 to 60C (32 to 140F) IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
Storage Temperature
40 to 85C (40 to 185F) Relative Humidity Shock IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing IEC 60068-2-27 (Test Ea, Unpackaged Shock): Operating 30g Non-operating 50g IEC 60068-2-6 (Test Fc, Operating): 5g @ 10-500Hz CISPR 11: Group 1, Class A IEC 61000-4-2: 6kV contact discharges 8kV air discharges IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz IEC 61000-4-4: 2kV at 5kHz on communications ports IEC 61000-4-5: +2kV line-earth (CM) on shielded ports IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Radiated RF Immunity
(1) (2)
For information on conductor routing, refer to publications 1770-4.1, Industrial Automation Wiring and Grounding Guidelines, and ENET-IN001, EtherNet/IP Media Planning and Installation Manual. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
IMPORTANT
This equipment is not resistant to sunlight or other sources of UV radiation. The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments. Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments. This equipment shall be used within its specified ratings defined by Allen-Bradley. Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
Allen-Bradley and ControlLogix are trademarks of Rockwell Automation. Ethernet is a trademark of Digital Equipment Corporation, Intel, and Xerox Corporation.
PN 957689-13
Copyright 2002 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.