TECHNICAL GUIDE
DrywallGridSystem
SYNTHETIC STUCCO
GRID SYSTEM
Hanging and Framing
EIFS/Direct Applied Ceilings
TABLE OF CONTENTS
DrywallGridSystem
Performance
Code Compliance
DrywallGridSystem
Main Beams
Item #
HD8906
HD8906G90
Face
Profile Duty Fire
Length Dimension
Height Load Rated
144
1-1/2
Heavy
1-11/16
Yes
duty
Routs
51 routs
starting 2-1/4
from each end
(type F fixture
compatible)
Perspective
Cross Tees
Item #
XL8947P
XL8947PG90
Length
50"
Face
Profile Fire
Dimension Height Rated
1-1/2"
1-1/2"
Routs
Yes
8 routsstarting 10"
from each end (type
F fixture compatible)
2'
50"
50"
13.0
19.5
3'
4'
2'
XL8945P
XL8945PG90
48"
1-1/2"
1-1/2"
Yes
2 routs12" from
each end
(type F fixture
compatible)
XL7936G90
36"
1-1/2"
1-1/2"
No
none
XL8925
XL8925G90
26"
1-1/2"
1-1/2"
Yes
2 routs12" from
each end (type F
fixture compatible)
98.0
117.0
XL8926
XL8926G90
24"
1-1/2"
1-1/2"
Yes
3 routscenter rout
and 10" from each
end(type F fixture
compatible)
129.0
158.0
XL7918
14"
1-1/2"
1-1/2"
Yes
none (type F
fixture compatible)
71.5
107.0
3'
15.0
Perspective
4'
22.5
33.3
50.0
Wire Load
12 Gauge Wire Breaking Strength and Technical Data
12 Gauge Wire
Diameter .105"
Galvanized Steel
375 lbs.
Breaking Point
3 Turns in 3"
Per ASTM C 636
500 lbs. Pullout
Hanger Wire Hole
Note: Per ASTM C 1063
wires must be plumb and
straight
INSTALLATION RECOMMENDATIONS
DrywallGridSystem
Hanger Wire
Hanger Wire
Finish
Substrate
Main Beam
Wafer Screw
Cross Tee
Stop
Main Beam
Space
Main Beam
Wafer Head
Screw
Wall
Track
Expansion Joint
Isolated Corner
Control Joint
3/8'' Min.
Isolation From Wall
DrywallGridSystem
Insulated
Uninsulated
Vertical Brace
Hanger Wire
Main Beam
Main Beam
Cross Tee
Substrate
Fiberglass Mesh
Vent Strip
Control Joint
Hanger Wire
Wall
Hanger Wire
Cross Tee
Main Beam
Main Beam
Main Beam
Screw
Vent
Casing
Bead
Drainage
Substrate
Vent Strip
Substrate
Vertical
Brace
Substrate
Cross Tee
WIND LOAD
DrywallGridSystem
EIFS System Exterior Wind Load Ceiling Design for North America
Plenum
Height
(Ft - In)
0
6
***
6 1
10 3
****
10 4
15 0
****
15 1
20 0
****
Up Lift
Load
(MPH)
Up Lift
Load
(Lbs./Ft.2 )
Stud
Thickness
(Inch)
Stud
Gauge
(Ga. No.)
Sheathing
5/8 Drywall Sheet
Densglass Gold G-P
Main Runner
Spacing
(Inch)
Cross Tee
Spacing
(Inch)
Hanger Wire
Spacing
(Feet)
Cross Tee
Length
(Feet)
Compression
Post Spacing
(Feet)
Compression
Post Load
(Lbs.)
15
30
45
60
90
120
140
172
15
30
45
60
90
120
140
172
*15
*30
*45
*60
*90
*120
*140
*172
**15
**30
**45
**60
**90
**120
**140
**172
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
0.576
2.304
5.18
9.22
20.7
36.8
50.09
75
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 STH
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
2 1/2 CSJ
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 5/8 CSW
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
3 1/2 CSJ
22
22
22
22
22
22
22
22
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
16
16
16
16
16
16
16
16
48
48
48
36
36
36
24
24
48
48
48
36
36
36
24
24
48
48
48
36
36
36
24
24
48
48
48
36
36
36
24
24
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
4 O.C.
4 O.C.
4 O.C.
3 O.C.
3 O.C.
2.5 O.C.
2.5 O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
3 O.C.
2.5 O.C.
2.5 O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
3 O.C.
2.5 O.C.
2.5 O.C.
2 O.C.
4 O.C.
4 O.C.
4 O.C.
3 O.C.
3 O.C.
2.5 O.C.
2.5 O.C.
2 O.C.
4
4
4
3
3
3
2
2
4
4
4
3
3
3
2
2
4
4
4
3
3
3
2
2
4
4
4
3
3
3
2
2
4
4
4
3
3
2.5
2.5
2
4
4
4
3
3
2.5
2.5
2
4
4
4
3
3
2.5
2.5
2
4
4
4
3
3
2.5
2.5
2
9.3
37
83
83
187
276
251
300
9.3
37
83
83
187
276
251
300
9.3
37
83
83
187
276
251
300
9.3
37
83
83
187
276
251
300
Ceiling System = HD8906G90 Main Beam 12 ft. / XL8945PG90 Cross Tee 4 ft. / XL7936G90 Cross Tee 3 ft. / XL8926G90 Cross Tee 2 ft. / #12 Ga. H.D.G. Hanger Wire
*
**
***
****
Note: IBC Section 1609 Table 1609.6.2.1 and ASCE 7 Figure 6-1. The Exterior Ceiling wind load designs we have shown were tested and approved for the
highest exposure category listed for the continental U.S. as shown in the IBC Section 1609 Wind Exposure Charts.
Control Joints
Control joints minimize cracking caused by stresses in the surface
material attached to a metal suspension system. Materials have
different rates of expansion and control joints are placed 35 to 50
apart to control bucking and cracking of surface. Control joints are
also used to minimize stresses in monolithic ceiling membrane that
occur at columns, access doors, light fixtures, inside and outside
corners and other unusual penetrations in ceilings.
Component
Combination
Expansion Joints
Ceiling expansion joints are installed to separate the metal
suspension system when expansion joints occur in buildings, ceiling
span is over 100 or when metal changes direction. Expansion joints
are required to separate a system in T, H, L and U or Circle shaped
buildings to eliminate cracking from expansion. Both expansion and
control joints look similar but perform different functions.
Maximum Load
in Lbs./Ft.2 at
Hanger Wire/
Cross Tee Spacing
36"/ 16"
L/240
L/360
HD8906/XL7936G90
(mains 36" O.C.)
21.77
14.51
HD8906/XL8926
(mains 24" O.C.)
26.13
21.77
DrywallGridSystem
For maximum wind speed of 172 MPH. For other wind speed designs, see page 6.
Fastner Attachment
by Other Contractor
Positive Attachment
Concrete Slab
3/4"
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.
10'- 3"
Vertical
Drop
Positive
Attachment
Hanger
Wire
4'O.C.
Main Beams
2' O.C.
5/8" Exterior
Water Resistant
Gypsum Board
NOTES:
(1) Wind Load Brace 2-1/2" 18 Gauge Steel 2' O.C
(2) From 0' to 6' 22 Gauge 2-1/2" Metal Studs Minimum
From 6' to 10'-3" 18 Gauge 2-1/2" Metal Studs Minimum
(3) From 10'- 4" to 15' 18 Gauge 2-1/2" Metal Studs
Minimum 16 Gauge CRC Mid Span
(4) From 15' to 20' 18 Gauge 2-1/2" Metal Studs Minimum
16 Gauge CRC 1/3 Points
(5) Item 3 and 4 above CRC Bracing Shown on Other
Drawings
(6) Main Beams 3' O.C. / Cross Tees 16" O.C.
(7) Positive Attachment Metal Studs Top and Bottom
(8) #12 Hanger Wire No Knots, as Shown Above
DrywallGridSystem
Length
Stud splice
6"
2' O.C.
Maximum
6"
Bracing Clip
Stud brace
(4) #10 - 16
Fasteners on
each side of
splice point
Minimum
#10 - 16
Screws
4-1/4" 4-1/4"
1" 3/4" 3/4" 1"
Power actuated
fastener
Steel stud
SPLICE DETAIL
(Use stud piece x12" long - same size and gauge
as main studs. Center over splice point.)
3-5/8
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ
362 - CSJ
Gauge
20
20
18
16
14
Gauge
4 - SCJ
4 - CSJ
4 - CSJ
20
18
16
4 - CSJ
14
Gauge
6 - CSJ
20
6 - CSJ
18
6 - CSJ
16
6 - CSJ
14
NOTES:
(1) Positive attach with #10 -16 screw - clip
to stud.
(2) Positive attach with Clip to Bar Joist with 2
.145 Dia. x 1/2 long.
(3) Screws: #10 - 16 TEKS/ 3 Buildex or equal.
(4) Power activated Fasteners: .145 Dia. x 1/2
long (X-DNI) Hilti pins.
(5) Clips: All Clips to be made of 50 KSI material.
Spans up to 70 use angle 2 x 5 x 12 gauge
x 0-4 long. Spans 72 x 120 use angle
2 x 5 x 10 gauge x 0-5 long. For studs up
to 4, use 3 flange in lieu of 5.
8
Gauge
8 - CSJ
18
8 - CSJ
18
8 - CSJ
8 - CSJ
8 - CSJ
16
14
16
(6)
(7)
(8)
(9)
DrywallGridSystem
LENGTH
STUD SPLICE
2' O.C.
Positive
Attachment
Top and Bottom
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.
10'- 3"
Vertical
Drop
Hanger
Wire
4'O.C.
Main Beams
2' O.C.
5/8" Exterior
Water Resistant
Gypsum Board
NOTES:
(1) Positive Attachment Top and Bottom
(2) 22 Gauge 2-1/2 Studs 2 O.C.
(3) Main Beams 2 O.C. / Cross Tees 16 O.C 2 Long
(4) #12 Hanger Wire 4 O.C.
(5) Vertical Drop 0 - 6 Minimum 22 Gauge. Not shown on
drawing. (See Chart)
DrywallGridSystem
LENGTH
STUD SPLICE
2' O.C.
Positive
Attachment
Top and Bottom
2' O.C.
18 Gauge 2-1/2"
Studs 2' O.C.
15'
Vertical
Drop
Positive
Attachment
Hanger
Wire
4'O.C.
Main Beams
2' O.C.
5/8" Exterior
Water Resistant
Gypsum Board
NOTES:
(1) 1-1/2 #16 Gauge U Channel Bracing Required
at Mid Span for 10 15 Verticle Drop
(2) Positive Attachment Top and Bottom
(3) 18 Gauge 2-1/2 Stud 2 O.C.
(4) Main Beams 2 O.C. / Cross Tees 16 O.C 2 Long
(5) #12 Hanger Wire 4 O.C.
10
DrywallGridSystem
LENGTH
STUD SPLICE
2' O.C.
Positive
Attachment
Positive
20' Attachment
Vertical
Drop
16 Gauge U
Channel Bracing
18 Gauge 3-5/8"
Studs 2' O.C.
2' O.C.
16 Gauge U
Channel Bracing
Positive
Attachment
Hanger
Wire
4'O.C.
Main Beams
2' O.C.
5/8" Exterior
Water Resistant
Gypsum Board
NOTES:
(1) 1-1/2 #16 Gauge U Channel Bracing
Required at 1/3 Points
(2) Positive Attachment Top and Bottom
(3) 18 Gauge 3-5/8 Studs 2 O.C.
(4) Main Beams 2 O.C. / Cross Tees 16 O.C 2 Long
(5) #12 Hanger Wire 4 O.C.
11
MAKING A TEMPLATE
DrywallGridSystem
Establishing an Arc
Draw radius on template (plywood, gypsum board, etc)
1. Establish a center line
2. Mark 2 increments on line
perpendicular to center line
20 20 20
5/8 2-1/4
5-1/8
Main Beam
* RC2 Clip placement
Vaults Cross tee placement in routs between cuts
Valleys Cross tee lock into rout on RC2 clip (tight radius installations
may require bending up of the flange at ends of cross tees)
Template under
Main Beam
Radius
Component
Up to 15
HD8906F08
Over 15
HD8906F16
Cut
Span of Vault
12
MAKING A TEMPLATE
DrywallGridSystem
2-1/2n or 3-5/8n
flex track
Stop
Work Platform 4b x 12b
Gypsum Wall Board
or Plywood
12b
Cut Main Beam
4b
Flex Track
Radius
Bracing for
span
Saw Horses
13
RADIUS IN FEET
DrywallGridSystem
Radius Dimension
100
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
4
6
8
2
10
20
40
110
120
21/4
2
8 1/4
91/8
19 3/8 173/8
35 5/8 30 3/4
250
260
1
3 7/8
8 3/4
133/4
1
7/8
3 3/4
3 5/8
81/2
81/2
131/8 125/8
400
410
5/8
5/8
23/8
51/2
93/4
160
170
180
190
200
210
220
230
240
17/8
13/4
15/8
11/2
75/8
7
6 1/2
6 1/8
15 5/8 14 1/4
13
12
29 1/8 26 1/8 23 3/4 213/4
140
150
11/2
5 3/4
111/8
20
13/8
5 3/8
10 3/8
1101/2
11/4
5 1/8
113/4
191/4
11/4
4 7/8
111/8
18 1/8
11/8
4 5/8
10 1/2
17
11/8
43/8
10
161/8
11/8
4 1/4
9 5/8
15 1/4
1
4
9 1/8
141/2
280
290
300
310
320
330
340
350
360
370
380
390
7/8
7/8
7/8
3/4
3/4
3/4
3/4
3/4
3/4
5/8
5/8
31/2
77/8
12
33/8
71/2
121/2
31/4
31/8
3
71/4
71/8
67/8
111/8 10 5/8 10 1/4
3
65/8
111/2
27/8
63/8
111/2
23/4
61/4
111/8
23/4
61/8
107/8
25/8
57/8
101/2
25/8
53/4
101/4
5/8
21/2
55/8
10
420
430
440
450
460
470
480
490
500
510
520
530
540
5/8
5/8
5/8
5/8
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
23/8
53/8
91/2
23/8
51/4
91/4
21/4
51/8
9
21/8
5
87/8
21/8
47/8
85/8
21/8
43/4
81/2
21/8
45/8
81/4
2
41/2
81/8
2
41/2
77/8
2
43/8
73/4
17/8
41/4
75/8
17/8
41/4
71/2
13/4
41/4
73/8
1/2
13/4
4
71/8
550
560
570
580
590
600
610
620
630
640
650
660
670
680
690
1/2
1/2
1/2
1/2
1/2
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
13/4
4
7
13/4
37/8
67/8
13/4
37/8
63/4
13/4
33/4
65/8
15/8
33/4
65/8
15/8
35/8
61/2
15/8
35/8
63/8
15/8
31/2
61/4
11/2
31/2
61/8
11/2
33/8
6
11/2
33/8
6
11/2
31/4
57/8
11/2
31/4
53/4
11/2
31/4
53/4
3/8
13/8
31/8
55/8
700
710
720
730
740
750
760
770
780
790
800
810
820
830
840
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
13/8
31/8
51/2
13/8
31/8
51/2
13/8
3
53/8
13/8
3
51/4
13/8
3
51/4
11/4
27/8
51/8
11/4
27/8
51/8
11/4
27/8
5
11/4
23/4
5
11/4
23/4
47/8
11/4
23/4
47/8
11/4
23/4
43/4
11/4
25/8
43/4
11/4
25/8
45/8
3/8
11/8
25/8
45/8
850
860
870
880
890
900
910
920
930
940
950
960
970
980
990
3/8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1
23/8
41/8
1
21/4
41/8
1
21/4
4
1
21/4
4
1
21/4
4
1
21/4
37/8
11/8
25/8
41/2
11/8
21/2
41/2
270
130
11/8
21/2
41/2
11/8
21/2
43/8
11/8
21/2
43/8
11/8
23/8
41/4
11/8
23/8
41/4
11/8
23/8
41/4
11/8
23/8
41/8
1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700
2
4
6
8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/8
1/8
1
21/4
37/8
1
21/8
33/4
2
31/2
17/8
33/8
17/8
31/4
13/4
31/8
13/4
3
15/8
27/8
15/8
23/4
11/2
23/4
11/2
25/8
13/8
21/2
13/8
23/8
13/8
23/8
7/8
7/8
7/8
3/4
3/4
3/4
3/4
3/4
1750 1800 1850 1900 1950 2000 2100 2200 2300 2400
2
4
6
8
5/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
11/4
21/4
11/4
21/8
11/4
21/8
11/8
2
11/8
2
11/8
2
1
17/8
1
13/4
1
15/8
7/8
7/8
11/2
5/8
1/2
1/2
1/2
1/2
1/2
1/2
14
3/8
3/8
15/8
5/8
5/8
1/8
5/8
11/4
21/4
250
1/8
5/8
5/8
3/8
Additional Drywall Grid Systems are available. For more information, visit
armstrong.com/drywallgrid or call 877-ARMSTRONG to request literature.
CEILING SYSTEMS
1 877 ARMSTRONG (1 877 276 7876)
Name of your Inner Circle Contractor or Gold Circle
Distributor or Sales Representative
Customer Service Representatives
7:30 a.m. to 5:00 p.m. EST, Monday through Friday
TechLine Technical information
7:45 a.m. to 5:30 p.m. EST, Monday through Friday
FAX 1-800-572-8324 or email: techline@armstrong.com
Product literature and samples Express service or
regular delivery
Request a personal copy of the
Armstrong Ceiling Systems catalog
armstrong.com/drywallgrid
Latest product and program news
Real time selection and specification information
Contacts reps, where to buy, who will install
Submittal pages
Specification writing tool
Literature and samples information
CAD renderings