Model SIZE 1 Specification Power rating UP to KW (HP) AC Input Voltage AC Input Frequency AC Output Voltage AC Output Frequency AC Output

Current (100%) Overload Capacity (150% for 60 seconds) PWM Switching Freq. Storage Temperature SP2 0.2 (1/4) SP4 SP7 0.4 (1/2) 0.7 (1) LP2 0.2 (1/4) LP4 0.4 (1/2)

EI-MINI SIZE 2 LP7 0.7 (1) GP4 GP7 G1P5 0.4 (1/2) 0.7 (1) FP7 F1P5 1.5 0.7 (1) 1.5 (2) (2) 3 380-440 (VAC)

1 100-120 (VAC) 45~60 Hz

1 200-240 (VAC)

3 200-240 (VAC)

0 to 220V 3 Output 0 to Input Voltage, Three-Phase Output 0 to 50/60Hz or 0 to 100/120Hz 1.5A 2.2A 16KHz -40C to + 65C (-40F to 149F ) 2.4A 3.6A 4A 6A 1.5A 2.2A 2.4A 3.6A 4A 6A 2.4A 3.6A 4A 7A 2.4A 3.6A 4A 6A

6A 10.5A

Operating Temperature 0C to + 50C (32F to 122F ) Operating Modes Stop Modes Load Speed Mode, 2-Wire and 3-Wire Modes Ramp Stop, or DC Injection Constant Torque or Fan (Variable Torque)

S e t - u p
Power Connections

a n d

O p e r a t i o n

Connect the fused/protected 220 volt 50/60Hz supply to the power terminal 'R' and 'T'. Polarity is not important. Ensure the supply is adequately fused/protected depending on the latest codes of practice for electrical installation. Connect the 220 volt 3 phase motor to the power terminal 'U', 'V' and 'W'. Polarity determines direction.

Remark: Rage G & F Models are all Three-phase input basic on (R.S.T) design.

Control Connections

The control inputs


0 volt or control common (connected to -DC of power circuit) (isolated) Speed reference input from 0 to 5 volt or 0 to 10 volt or 4-20mA, select by jumper J3 Terminal V3 +5 volt output for the 5k Speed potentiometer Terminal FOR Forward run when CLOSED; stopped when OPEN Terminal REV Reverse run when CLOSED; stopped when OPEN Terminal RESET Fault Reset when CLOSED Terminal STOP In 3-WIRE mode, when CLOSED then allow to run Terminal FM Analog output signal for Frequency output Terminal V0 Terminal TRIP Terminal FUNC Terminal COM Control Common Fault output (open collector output) Multi-function output (Drive running or Drive speed agree, select by switch S1) TRIP, FUNC fuction common Terminal V1 Terminal V2

Terminals FOR REV STOP RESET FOR REV STOP RESET

Switch S3 2-wire mode switch S3 ON

3-wire mode switch S3 OFF

Action 0V connected Run Forward Run Reverse Allow to Run Reset Run Forward Run Reverse Allow to Run Stop and Reset

Disconnect from 0V Stop Stop Disable output No action No action No action Disable output No action

Speed reference select: jumper J3 0-20mA 0V-5V 0V-10V

C o n t r o l P r e s e t P o t e n t i o m e t e r s
The 5 pre-set potentiometers adjust the following parameters UL LL Sets the maximum speed available and has a range from 0Hz (fully counter clockwise) to Base Speed (or X2) (fully clockwise) depending on switch S7 and S8. Sets the minimum speed available and has a range from 0Hz (fully counterclockwise) to Base Speed (or X2) (fully clockwise) depending on switch S7 and S8. Sets the acceleration time from 0.5 sec (fully counter clockwise) to 130 sec (fully clockwise) to attain 0Hz from Base Speed (or X2) from 0Hz depending on switch S7 and S8. Sets the deceleration time from 0.5 sec (fully counter clockwise) to 130 sec (fully clockwise) to attain 0Hz from Base Speed (or X2) from 0Hz depending on switch S7 and S8. Sets the 40-100% current value for the 'lxt' calculation. (7-seg display will show 5 when measured motor current is greater than 100% of the value set by THRY, and thus 'lxt' is intergrating up.) Fully counter clockwise equals zero current for 'lxt' setting and fully clockwise equals 2.3A (0.5HP/220VAC) or 1.4A (0.25HP/110VAC) current for 'lxt' setting.

ACC

DEC

THRY

The setting range of UL and LL provide for full rotation of the external Speed Potentiometer to operate over a band width of 1Hz or more over any part of the speed range, to Base Speed X2. Setting LL greater than UL causes the minimum speed to equal the maximum speed set by UL.