Direct connection three-phase meter Measurement of active and reactive energy in 4 quadrants Single or multi-tariff meter with Built-in Real Time Clock, Ripple Control Receiver or Tariff Input Programmable load profiles Historical records Load management via relay Reading and programming by push-buttons, optical link or twisted pair bus Enhanced anti-fraud system AMR ready through 62056-31 bus
Technical features
CURRENT Range of current = 5(100) A Starting current = 25 mA Auto-consumption : - Voltage < 1W and 10VA - Current : <2,5 Va at 100A and <0,01 VA at 5A Power supply = 3x220/380 V 3x230/400 V 3x240/415 V OUTPUTS / COMMUNICATION Pulse output EN 62053 - 51* 1 or 2 relay outputs 2A* Local reading & programming by push-buttons Local reading & programming through IEC 62056-21 optical interface (IEC 62056-31 protocol) Remote reading & programming through twisted pair bus (IEC 62056-31 protocol )* RECORDING Power failure ride-through Daily record of meter data Non-volatile memory
Frequency = 50 Hz
METERING DATA Measurement of imported and exported active and reactive energy in 4 quadrants* Class 1 or 2 accuracy according to IEC 62052-11 and 62053-21 for active energy Class A or B accuracy according to EN 50470-1 and EN 50970-3 Class 2 or 3 accuracy according to IEC 62052-11 and 62053-21 for reactive energy
ANTI-FRAUD SYSTEM Record of : - Power supply time - Energy consumption time - Date & time of programming and cover openings Non-consumption indicator Phase reversal indicator Missing phase detection
Metert Constant =1000 pulses / KWh (programmable) Instantaneous measurement of U, I, P Average measurement of P, Q, S and power factor Reading without Power (Reed magnetic contact) capability*
TARIFF MANAGEMENT By built-in real time clock with 7 day supercap back-up or lithium battery (15 years)*
Dimensions (mm) : H 308, L 168, D 70 Fixing triangle DIN 43857 (mm) H : 230, B : 150, adjustable Weight : 1,2 kg
By Built-in programmable Ripple Control Receiver (RCR)/ musical frequency* - Programmable from 100 Hz to 600 Hz By Tariff Input 230 V* Up to 6 registers for imported active energy* Up to 6 Maximum Demand registers* 1 register for exported active energy* Programmable load profile* Billing periods* * According to the model PROGRAMMING SOFTWARE Programming and reading software compatible with Microsoft Windows (98 and later) CONNECTION DIN type
All rights reserved. The information and specifications included are subject to change without prior notice. Sagemcom Energy & Telecom tries to ensure that all information in this document is correct, but does not accept liability for error or omission. Non contractual document. All trademarks are registered by their respective owners. Simplified joint stock company - Capital 44.824.840 Euros - 518 250 337 RCS Nanterre. 09/2011