ANNEXURE - I TO UPS SPECIFICATION TECHNICAL PARTICULARS OF 2 No 250 kVA Sl.No. 1.1 1.2 1.3 1.4 1.5 1.6 1.

7 1.8 Make & type Continuous rating Input voltage Input voltage variation limits Input frequency Input frequency variation limits Output voltage Output voltage variation limits SPECIFICATIONS OFFERED BY DB REPLY DB / HARMONY S+ 3300 / 250KVA 0.6 lag to Unity within KVA & KW Rating 415 VAC, Three Phase, 4 Wire .+ 15%, - 20% 50Hz .+/- 10% 400V / 415 VAC (Step Less adjustment) .+/1% for +/- 2% for unbalance Load Balance OFFERED BY NUMERIC UPS NUMERIC HPE i SERIES. 250kVA / 200kW 380/400/415V Selectable. 320V to 480V 50 / 60 Hz 10 % 380/400/415V Selectable. Load 1%

1.9

Transient voltage variation for 100% block For 0 to 100% stepload change the output shall remain within 3% for 0 to 100% and vice versa loading. +/-5% & recover to 98% within one cycle (Ref IEC 62040 -3, class 1) Voltage recovery time Up to 98% of nomiNot Applicablel voltage within for parallel Redundant System .+/- 0.1 Hz +/-2.5 Hz in Sinc Mode .+/- 0.1 Hz in Free Running Mode 3:1 < 60 msec < 20 m.sec.

1.1

1.11 1.12

Output frequency variation limits a. Synchronized to mains. b. InterNot Applicablelly generated. Crest factor Input PF at rated load

0.001Hz 2 Hz 0.1% 3:1

1.13 1.14

> 0.99 (at input full load & input nomiNot Applicablel voltage) >/= 0.99

1.15

Input PF at 50% load

0.98 (at input full load & input nomiNot Applicablel voltage)

>/= 0.99

1.16

Input to output efficiency at rated load without Upto 91% filter. Input to output efficiency filter. at rated load with Not Applicable

>/= 94%

1.17

Not Applicable

1.18

Input to output efficiency at 50% load without 0.89 filter. Input to output efficiency filter. at 50% load with Not Applicable

>/= 93.5%

1.19

Not Applicable

1.20

THD (current) at input for 100% loadat rated < 3% load without filter. THD (current) at input for 100% load at rated Not Applicable load with filter. THD (current) at input for 50% load at rated < 3% load without filter. THD (current) at input for 50% load at rated Not Applicable load with filter. Noise level at rated load Is static bypass provided. Is manual bypass facility provided. DC operating voltage range permissible Overall dimension of UPS < 72dBA Yes Yes 504 to 677 (W R : I : 1400 X 1000 x 1000 x D x 2000 X 1000 H x )

</= 3%

1.21

Not Applicable

1.22

</= 5%

1.23

Not Applicable

1.24 1.25 1.26 1.27 1.28

< 62 dBA Staic bypass is provided with each UPS Manual byapss facility is provdied with each UPS 516V mm 1000 x 850 x 1900 in mm WDH 2000 Not Applicable X x 480 L X H 480 x 1650 x 1650 - 4 Nos ) 2 mm 6 Racks of 1050 x 550 x 1900 in mm - WDH Nos 1000 kgs Not Applicable 6200 kgs All the UPS systems have built-in paralleling kit

1.29 1.3

Overall dimension of Filter Overall dimension of Battery Bank

Not Applicable (W Rack-1 1230 Rack-2 900 x 1850 Kgs (Approx) Not Applicable 6550 kgs Yes

1.31 1.32 1.33 1.34

Weight of the UPS Weight of the Harmonic Filter Weight of the Battery bank Is paralleling kit included? Cabling:

Size & specification of interconnecting cable 2 Runs of 2x70sqmm of Single Core Cu Cable between battery & UPS BATTERY BANK for 1 No. 250kVA 2.1 Make Exide

4R x 120 sqmm

Exide

Page 1 of 6

Sl.No. 2.2 2.3 2.4 2.5 2.6 Type

SPECIFICATIONS

OFFERED BY DB REPLY Sealed MainteNot Applicablence Free Batteries 96 Nos per UPS System 12 Volts 2 Volts

OFFERED BY NUMERIC UPS Sealed and MainteNot Applicablence Free VRLA 150Ah 129 Nos per UPS 12V 2V 1.6V

No of units offered Voltage per unit NomiNot Applicablel voltage per cell

Permissible end cell voltage as permanufacturer 1.75

2.7

End cell voltage considered for battery sizing.

1.75

1.75V

2.8 2.9

AH capacity Is all capacities decided based on unity P.F

200AH 0.8 PF

150Ah 129 Nos per UPS No

2.1 2.11 2.12

Battery backup time at rated load Is battery circuit breaker included. Overall dimensions of the cabinet.

30 Minutes Battery Backup Yes (W Rack-1 1230 Rack-2 900 x X x 480 L X H 480 x 1650 x 1650 - 4 Nos ) 2

30 Mins Included. mm As given above. Nos As given above.

2.13

Weight of each battery bank.

3275 kgs x 2 Banks for each UPS System.

Page 2 of 6

ANNEXURE - I TO UPS SPECIFICATION TECHNICAL PARTICULARS OF 4 No 80 kVA Sl.No. 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Make & type Continuous rating Input voltage Input voltage variation limits Input frequency Input frequency variation limits Output voltage Output voltage variation limits SPECIFICATIONS DB REPLY DB / HARMONY S+ 3300 / 80KVA 0.6 lag to Unity within KVA & KW Rating 415 VAC, Three Phase, 4 Wire .+ 15%, - 20% 50Hz .+/- 10% 400V / 415 VAC (Step Less adjustment) .+/1% for +/- 2% for unbalance Load for 100% Balance OFFERED BY NUMERIC UPS NUMERIC HPE i SERIES. 80kVA / 64kW 380/400/415V Selectable. 320V to 480V 50 / 60 Hz 10 % 380/400/415V Selectable. Load 1%

1.9

Transient loading.

voltage

variation

block For 0 to 100% stepload change the output shall remain 3% for 0 to 100% and vice versa within +/-5% & recover to 98% within one cycle (Ref IEC 62040 -3, class 1) Up to 98% of nomiNot Applicablel voltage within msec for parallel Redundant System .+/- 0.1 Hz +/-2.5 Hz in Sinc Mode .+/- 0.1 Hz in Free Running Mode 3:1 < 60 < 20 m.sec.

1.10

Voltage recovery time

1.11 1.12

Output frequency variation limits a. Synchronized to mains. b. InterNot Applicablelly generated. Crest factor Input PF at rated load

0.001Hz 2 Hz 0.1% 3:1

1.13 1.14

> 0.99 (at input full load & input nomiNot Applicablel >/= 0.99 voltage) 0.98 (at input full load & input nomiNot Applicablel >/= 0.95 voltage) >/= 92%

1.15

Input PF at 50% load

1.16

Input to output efficiency at rated load without Upto 90% filter. Input to output efficiency at rated load with filter. Not Applicable

1.17

Not Applicable

1.18

Input to output efficiency at 50% load without Upto 88% filter. Input to output efficiency at 50% load with filter. Not Applicable

>/= 92%

1.19

Not Applicable

1.20

THD (current) at input for 100% loadat rated load < 3% without filter. THD (current) at input for 100% load at rated load Not Applicable with filter. THD (current) at input for 50% load at rated load < 3% without filter. THD (current) at input for 50% load at rated load Not Applicable with filter. Noise level at rated load Is static bypass provided. Is manual bypass facility provided. < 70dBA Yes Yes

</= 4%

1.21

Not Applicable

1.22

</= 10%

1.23

Not Applicable

1.24 1.25 1.26

< 56 dBA Staic bypass is provided with each UPS Manual byapss facility is provdied with each UPS

1.27 1.28

DC operating voltage range permissible Overall dimension of UPS

504 to 677 (W 1000 X 900 D 1750 X H )

576V mm 500 x 740 x 1400 in mm - UPS 500 x 1050 x 875 in mm - Transformer Not Applicable X L X H ) mm 2 Rack of 855 x 825 x 1600 in mm - WDH x 480 x 1650 - 1 No 480 x 1650 - 1 No UPS - 280 kgs +Isolation Transformer - 425 kgs

1.29 1.30

Overall dimension of Filter Overall dimension of Battery Bank

Not Applicable (W Rack-1 1230 Rack-2 900

1.31

Weight of the UPS

875 Kgs (Approx)

1.32 1.33 1.34

Weight of the Harmonic Filter Weight of the Battery bank Is paralleling kit included?

Not Applicable 1710 kgs Yes

Not Applicable 1700 kgs All the UPS systems have built-in paralleling kit

Cabling: Size & specification of between battery & UPS interconnecting cable 2 Runs of 50sqmm of Single Core Cu Cable 4R x 50 sqmm

Page 3 of 6

Sl.No. .

SPECIFICATIONS

DB REPLY

OFFERED BY NUMERIC UPS

BATTERY BANK for 1 No. 80kVA 2.1 2.2 Make Type EXIDE Sealed MainteNot Applicablence Free Batteries Exide Sealed and MainteNot Applicablence Free VRLA

2.3 2.4 2.5 2.6

No of units offered Voltage per unit NomiNot Applicablel voltage per cell Permissible end cell voltage as permanufacturer

48 Nos per System 12 Volts 2 Volts 1.75

100Ah 48 Nos per UPS 12V 2V 1.6V

2.7

End cell voltage considered for battery sizing.

1.75

1.75V

2.8 2.9

AH capacity Is all capacities decided based on unity P.F

120 AH 0.8 PF

100Ah 48 Nos per UPS No

2.10 2.11 2.12

Battery backup time at rated load Is battery circuit breaker included. Overall dimensions of the cabinet.

30 Minutes Yes (W Rack-1 1230 Rack-2 900

25 - 30 Mins Included. X L X H ) mm As given above. x 480 x 1650 - 1 No 480 x 1650 - 1 No As given above.

2.13

Weight of each battery bank.

1710 kgs per Bank

Page 4 of 6

ANNEXURE - I TO UPS SPECIFICATION TECHNICAL PARTICULARS OF 1 No 40 kVA Sl.No. 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Make & type Continuous rating Input voltage Input voltage variation limits Input frequency Input frequency variation limits Output voltage Output voltage variation limits SPECIFICATIONS DB REPLY DB / HARMONY S+ 3300 / 40KVA 0.6 lag to Unity within KVA & KW Rating 415 VAC, Three Phase, 4 Wire .+ 15%, - 20% 50Hz .+/- 10% 400V / 415 VAC (Step Less adjustment) .+/1% for +/- 2% for unbalance Load Balance OFFERED BY NUMERIC UPS NUMERIC HPE i SERIES. 80kVA / 64kW 380/400/415V Selectable. 320V to 480V 50 / 60 Hz 10 % 380/400/415V Selectable. Load 1%

1.9

Transient voltage variation for 100% block loading. For 0 to 100% stepload change the output shall 3% for 0 to 100% and vice versa remain within +/-5% & recover to 98% within one cycle (Ref IEC 62040 -3, class 1) Voltage recovery time Up to 98% of nomiNot Applicablel voltage within 60 msec for parallel Redundant System .+/- 0.1 Hz +/-2.5 Hz in Sinc Mode .+/- 0.1 Hz in Free Running Mode 3:1 < < 20 m.sec.

1.10

1.11 1.12

Output frequency variation limits a. Synchronized to mains. b. InterNot Applicablelly generated. Crest factor Input PF at rated load

0.001Hz 2 Hz 0.1% 3:1

1.13 1.14

> 0.99 (at input full load & input nomiNot Applicablel >/= 0.99 voltage) 0.98 (at input full load & input nomiNot Applicablel >/= 0.95 voltage) at rated load without Upto 89% >/= 92%

1.15

Input PF at 50% load

1.16

Input to output efficiency filter.

1.17

Input to output efficiency at rated load with filter.

Not Applicable

Not Applicable

1.18

Input to output efficiency filter.

at 50% load without Upto 87%

>/= 92%

1.19

Input to output efficiency at 50% load with filter.

Not Applicable

Not Applicable

1.20

THD (current) at input for 100% loadat rated load < 3% without filter. THD (current) at input for 100% load at rated load Not Applicable with filter. THD (current) at input for 50% load at rated load < 3% without filter. THD (current) at input for 50% load at rated load Not Applicable with filter. Noise level at rated load Is static bypass provided. Is manual bypass facility provided. < 68dBA Yes Yes

</= 4%

1.21

Not Applicable

1.22

</= 10%

1.23

Not Applicable

1.24 1.25 1.26

< 56 dBA Staic bypass is provided with each UPS Manual byapss facility is provdied with each UPS

1.27 1.28

DC operating voltage range permissible Overall dimension of UPS

504 to 677 (W 600 X 900 D x 1335 X H )

576V mm 500 x 740 x 1400 in mm - UPS 500 x 1050 x 875 in mm - Transformer Not Applicable X L x 480 x 480 x H ) mm 2 Rack of 855 x 825 x 1600 in mm - WDH x 1650 - 1 No 1650 - 1 No Isolation Transformer - 425 kgs +UPS - 280 kgs X

1.29 1.30

Overall dimension of Filter Overall dimension of Battery Bank

Not Applicable (W Rack-1 1230 Rack-2 900 500 Kgs (Approx)

1.31

Weight of the UPS

1.32 1.33

Weight of the Harmonic Filter Weight of the Battery bank

Not Applicable 1180 kgs

Not Applicable 1700 kgs

Page 5 of 6

Sl.No. 1.34

SPECIFICATIONS Is paralleling kit included?

DB REPLY Yes

OFFERED BY NUMERIC UPS All the UPS systems have built-in paralleling kit

Cabling: Size & specification of between battery & UPS . BATTERY BANK for40kVA 2.1 2.2 Make Type EXIDE Sealed MainteNot Applicablence Free Batteries Exide Sealed and MainteNot Applicablence Free VRLA interconnecting cable 2 Runs of 16sqmm of Single Core Cu Cable 4R x 50 sqmm

2.3 2.4 2.5 2.6

No of units offered Voltage per unit NomiNot Applicablel voltage per cell Permissible end cell voltage as permanufacturer

48 Nos per System 12 Volts 2 Volts 1.75

100Ah 48 Nos per UPS 12V 2V 1.6V

2.7

End cell voltage considered for battery sizing.

1.75

1.75V

2.8 2.9

AH capacity Is all capacities decided based on unity P.F

65 AH 0.8 PF

100Ah 48 Nos per UPS No

2.10 2.11 2.12

Battery backup time at rated load Is battery circuit breaker included. Overall dimensions of the cabinet.

30 Minutes Yes (W Rack-1 1230 Rack-2 900 X L x 480 x 480 x X

25 - 30 Mins Included. H ) mm As given above. x 1650 - 1 No 1650 - 1 No As given above.

2.13

Weight of each battery bank.

1180 kgs per Bank

Page 6 of 6