INSTALLATION AND MAINTENANCE INSTRUCTIONS

FMM-1 Monitor Module


Specifications Normal Operating Voltage: Maximum Current Draw: Average Operating Current: EOL Resistance: Maximum IDC wiring resistance: Temperature Range: Humidity: Dimensions: Accessories:

12 Clintonville Rd Northford, CT 06472-1653 (203) 484-7161

15 to 32 VDC 5.1 mA (LED on) 400A (LED flashing) 47K Ohms 1,500 Ohms 32F to 120F (0C to 49C) 10% to 93% Noncondensing 412 H x 4 W x 114 D (Mounts to a 4 square by 218 deep box.) SMB500 Electrical Box

Before Installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. General Description The FMM-1 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating device circuit (IDC) for normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The module has a panel controlled LED indicator. The FMM-1 can be used to replace an MMX-1 module in existing systems. Compatibility Requirements To ensure proper operation, this module shall be connected to a compatible Notifier system control panel (list available from Notifier). Mounting The FMM-1 mounts directly to 4 square electrical boxes (see Figure 2A). The box must have a minimum depth of 218. Surface mounted electrical boxes (SMB500) are available from Notifier. Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only. 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1.
N500-48-00 1

3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. Figure 1. Removing Rotary Switch Stop:

9 8 7 6 5
LOOP

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 8 7 6 9 5 4 3 2 10

0 1 2 3 4

ADDRESS

A78-2318-07

Figure 2A. Module mounting: Note: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.

Figure 2B:

0 9
1 2 3

4 5 67 8 3 9 2 10 TE NS 1 11 0 4 5 6 7 15 1 1 12 3 8 4 3 2 9 1 0

0 9 8

4 5 67 8 3 9 2 10 TE NS 1 11 0 4 5 6 7 15 1 1 12 3 8 4 3 2 9 1 0

4
AD DR ES

4
ES DR AD

NES

ES ON

A78-2611-12

A78-2610-10

I56-1171-05

Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:


TO NEXT DEVICE
)( )+(

)( )+(

FROM PANEL OR PREVIOUS DEVICE

MONITOR
ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
9 8 7 6 5
LOOP

MODULE

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY


67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4 3 2 10

0 1 2 3 4

)( )+(

47 K EOL RESISTOR ELR-47K

COMMUNICATION LINE
32 VDC MAX. TWISTED PAIR IS RECOMMENDED
COMMUNICATION LOSS (OPTIONAL CONNECTION FOR PANELS WHICH SUPPORT THIS FEATURE)

ONES

ADDRESS

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B POWER LIMITED: 230A MAX @ 12 VDC MAX INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2280-13

Figure 4. Typical 4-wire fault tolerant initiating circuit configuration, NFPA Style D:
TO NEXT DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
9 8 7 6 5
LOOP

)( )+(

)-( )+(

FROM PANEL OR PREVIOUS DEVICE

MONITOR MODULE CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY
67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 6789 5 4

0 1 2 3 4

)( )+(

EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9.

3 2

ONES

10

ADDRESS

COMMUNICATION LINE 32 VDC MAX SHIELDED-TWISTED PAIR IS RECOMMENDED


COMMUNICATION LOSS (OPTIONAL CONNECTION FOR PANELS WHICH SUPPORT THIS FEATURE)

INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2281-58

Figure 5. Typical 2-wire initiating circuit configuration for security systems (with alarm versus short capability):
Note: For UL Listed security installations, the FMM-1 must be mounted within the control panel enclosure.
TO NEXT DEVICE ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
14K SERIES RESISTOR
)( )+(

)( )+(

FROM PANEL OR PREVIOUS DEVICE

MONITOR
MODULE

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY


9 8 7 6 5
LOOP

47 K EOL RESISTOR ELR-47K

ONES

67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 8 7 6 9 5 4 3 2 10

0 1 2 3 4

)( )+(

COMMUNICATION LINE
32 VDC MAX. SHIELDED-TWISTED PAIR IS RECOMMENDED
COMMUNICATION LOSS (OPTIONAL CONNECTION FOR PANELS WHICH SUPPORT THIS FEATURE)

ADDRESS

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B POWER LIMITED: 230A MAX @ 12 VDC MAX INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

A78-2281-59

N500-48-00

I56-1171-05 2002 Notifier