You are on page 1of 5

Document Name: Specifications (Mechanical) Date: March 7, 2009 Rev. Rev.

0 Project: AL RAJHI STEEL (CUT & BEND PROCESSING BLDG) - JEDDAH Owner: AL RAJHI STEEL CO.

SECTION 15870 AIR OUTLETS PART 1.01 1 GENERAL

WORK INCLUDED A. B. C. D. E. F. Supply/Return sidewall registers Supply/Return ceiling diffusers Return air grilles and exhaust grills. Door grilles. Outside louvers. Sant Trap Louvers / External Louvers

1.02

RELATED WORK A. B. C. Section 15890 Section 15910 Section 15990 : : : Ductwork Duct Accessories Testing, Adjusting, and Balancing of Environmental Systems Air Treatment Equipment(Filters)

D. 1.03

Section 15880

QUALITY ASSURANCE A. Make air flow tests and sound level measurements in accordance with applicable ADC equipment test codes and ASHRAE standards. Manufacturer shall certify catalogue performance and ensure correct application of air outlet types.

B.

1.04

REFERENCE STANDARDS A. ANSI American National Standards Institute . Methods for the Determination of Sound Power Levels in Reverberation Rooms. Air-Conditioning and Refrigeration Institute Standard for Air Outlets and Inlets. Air Diffusion Council . Equipment Test Code.

S1.21-1972

B.

ARI

650-73 C. ADC 1062R3

(SDEC) SECTION 15870

Page 1 of 5

Document Name: Specifications (Mechanical) Date: March 7, 2009 Rev. Rev. 0 Project: AL RAJHI STEEL (CUT & BEND PROCESSING BLDG) - JEDDAH Owner: AL RAJHI STEEL CO.

AD-63 TC6651 FD-72 D. AMCA 511 -

Measurement of Room-to-Room Sound Transmission Through Plenum Air Systems Air Diffusion Troffer Heat Removal Test Code. Flexible Air Duct Test Code. Air Moving and Conditioning Association Certified Ratings Program for Louvers, Dampers and Shutters American Society of Heating, Refrigerating and Air Conditioning Engineers. Air Flow Performance of Outlets and Inlets, Method of Testing for Rating. Associated Air Balance Council . National Standards for Field Measurements and Instrumentation, Total Balance System Balance, Air Distribution-Hydronic Systems, Vol. 1.

E.

ASHRAE

70-72

F.

AABC

G.

SMACNA

Sheet Metal and Air Conditioning Contractors' National Association, Inc. Air Handling Specification. Manual for the Balancing and Adjustment of Air Distribution Systems. NEEB Procedural Standards for Testing-Balancing-Adjusting for Environmental Systems.

1.05

SUBMITTALS A. B. Submit in accordance with applicable sections. Submit product data and shop drawings covering each item together with schedule of outlets include air quantity, neck or face velocity, sound power levels, pressure drop, throw & drop, diffusion range and mounting height. Submit Manufacturer's installation instructions. Manufacturer's recommended spare parts and tools list. maintenance data in accordance with Section 15050. Certificate of compliance for materials and operation. Field tests. Operating and

C. D.

E. F.

(SDEC) SECTION 15870

Page 2 of 5

Document Name: Specifications (Mechanical) Date: March 7, 2009 Rev. Rev. 0 Project: AL RAJHI STEEL (CUT & BEND PROCESSING BLDG) - JEDDAH Owner: AL RAJHI STEEL CO.

1.06

JOB CONDITIONS A. Review requirements of outlets as to size, finish, and type of mounting prior to submitting shop drawings and schedules of outlets.

B.

Check location of outlets and make necessary adjustments in position to conform with architectural features, symmetry, and lighting arrangement.

PART 2 PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. The Contractor shall submit to the Supervising Engineer the names of three manufacturers and their products which will be acceptable under this Section. Approval of the manufacturer or product must be obtained before proceeding with associated work. Units shall be product of a Manufacturer regularly engaged in the production of these units issuing complete catalog data of same. Items of same function and performance are acceptable in conformance with Section 01630. MANUFACTURERS: 1. 2. 3. 4. 2.02 APPLICATION A. B. Rate Units in accordance with ADC standards. Design levels for sound control shall be as follows: Range of Sound Level (dB A 23-35 30-40 35-45 35-45 40-50 45-65 50-70 60-80 SAUDI EURO REGISTERS, EUROPE-KSA TITUS, USA GOLDEN STAR Or approved equal.

B.

C.

D.

Location Offices

Description Board rooms Conference rooms Executive Offices General open offices Typing pools Computer rooms Light machinery, assembly lines Foundries, heavy machinery

Factories

C. D.

Provide supply aluminum outlets with sponge rubber seal around edge. Provide baffles to direct air away from walls, columns, or other obstructions within radius of diffuser operation. Provide register boxes for flexible duct connections and diffusers. Provide plaster frame for diffusers located in plaster surfaces.
Page 3 of 5

E. F.

(SDEC) SECTION 15870

Document Name: Specifications (Mechanical) Date: March 7, 2009 Rev. Rev. 0 Project: AL RAJHI STEEL (CUT & BEND PROCESSING BLDG) - JEDDAH Owner: AL RAJHI STEEL CO.

G.

Provide anti-smudge frames or plaques on diffusers located in rough textured surfaces such as an acoustical plaster. Distribute specified quantity of air evenly without drafts, air movement faster than 0.25 m/s or dead zones. Mix room air with primary by induction to provide equalization of room temperature without stratification.

H.

2.03

SUPPLY AIR REGISTERS - (SAR), RETURN AIR REGISTER, (RAR) A. For sidewall supply registers provide streamlined and individually adjustable blades, depth of which exceeds 19mm maximum spacing. Provide spring tension or other device to set blades. Provide units with vertical or horizontal face, single or double deflection bar style grills as indicated, with opposed blade volume damper. Provide 32mm margin frame with countersunk screw holes. Fabricate of aluminum extrusions unless otherwise indicated. Provide registers with integral, gang-operated opposed blade dampers with removable key operator, operable from face. Return air registers not connected to AC return ducts shall not be provided with volume dampers. Finish in factory white anodized aluminum, or as indicated in the schedule.

B. C. D.

E.

F. 2.04

RETURN AIR GRILLE, (RAG), AND EXHAUST AIR GRILLE, (EAG) A. For ceiling return air and exhaust grilles, provide streamlined blades, depth of which exceeds (19mm) spacing. Provide spring tension or other device to set blades. Provide units with vertical or horizontal face. Provide 32mm margin frame with countersunk screw holes. Fabricate of aluminum extrusions. Provide exhaust registers, where not individually connected to exhaust fans, with integral, gang-operated opposed blade dampers with removable key operator, operable from face. Finish in factory anodized aluminum, or as indicated in the schedules.

B. C. D.

E. 2.05

SQUARE SUPPLY CEILING DIFFUSERS (SCD) / RETURN CEILING DIFFUSERS (RCD) A. Provide square ceiling diffusers, adjustable or fixed flow pattern, stamped, multicore type, diffuser to discharge air in 360 degree pattern with sectorizing baffles where indicated or required. Diffusers shall have surface mount or snap-in or inverted T-bar or spline type frame to suit ceiling. Fabricate of aluminum extrusions with anodized finish.

B.

C.

(SDEC) SECTION 15870

Page 4 of 5

Document Name: Specifications (Mechanical) Date: March 7, 2009 Rev. Rev. 0 Project: AL RAJHI STEEL (CUT & BEND PROCESSING BLDG) - JEDDAH Owner: AL RAJHI STEEL CO.

D.

E. 2.06

Provide radial opposed blade or combination splitter damper and multi-louvered equalizing grid with damper adjustable from diffuser face for supply diffusers and without damper for return diffusers. Diffuser mounting system shall be compatible with the ceiling system provided.

SUPPLY/RETURN LINEAR CEILING DIFFUSER (SLCD/RLCD) A. B. C. Provide slot type linear supply return ceiling diffusers. Diffuser face shall be free of fasteners or screws. Diffusers shall be provided with factory assembled plenum boxes with opposed blade dampers. Fabricate of aluminum extrusions with anodized finish. Diffusers located in plaster ceilings shall be provided with separate plaster stop mounting frame. Alignment clips shall be provided so that continuous sections shall appear to be one piece.

D. E.

F.

2.07

OUTSIDE LOUVERS A. Louvers shall be storm-proof, operable wall type, 150 mm deep, with blades on 45 slope, with drainable blade design. Fabricate of 12 gage (2.50 mm) extruded aluminum, welded assembly. Louver finish shall be factory-anodized. Unit to be similar or equivalent to model MO, Airstream Products Division. Provide stainless steel insect screen, 10 mm square opening, No.16 wire gauge.

B. C. D. E.

2.08

DOOR GRILLES (DG) A. B. Provide non-vision type door grille, fabricated of extruded aluminum. Provide 20 gage (0.90mm) steel frame with auxiliary frame to give finished appearance on both sides of door. Factory prime coat with anodized finish colored to suit door finish.

C.

PART 3 EXECUTION 3.01 INSTALLATION A. B. 3.02 3.03 Install items in accordance with Manufacturers' printed instructions. Paint ductwork visible behind air outlets matt black.

CLEANING: All cleaning shall conform to applicable sections. TESTING & BALANCING All field testing and balancing shall conform to applicable sections. *** END OF SECTION ***

(SDEC) SECTION 15870

Page 5 of 5

You might also like