Energy Valve BACnet Protocol Implementation Conformance Statement

Date: January 9, 2012 Vendor Name: BELIMO Automation AG Product Name: P..W..EV-BAC Product Model Number: N/A Application Software Version: 1.10.1 Product Description:

Firmware Revision: 1.0.2

BACnet Protocol Revision: 1.4

The device is a characterized control valve (CCV) with adjustable flow rate, sensor-operated flow control and monitoring of power and energy. The set-point, configuration parameters and feedback values are communicated via BACnet/IP or BACnet MS/TP. The commissioning of the device (BACnet Device Address, IP Address settings, Foreign Device settings, MS/TP) is done via the integrated web-server.

BACnet Standardized Device Profile (Annex L):


BACnet Operator Workstation (B-OWS) BACnet Advanced Operator Workstation (B-AWS) BACnet Operator Display (B-OD) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)

List all BACnet Interoperability Building Blocks Supported (Annex K):


Data Sharing - ReadProperty-B (DS-RP-B) Data Sharing - ReadPropertyMultiple-B (DS-RPM-B) Data Sharing - WriteProperty-B (DS-WP-B) Device Management - DynamicDeviceBinding-B (DM-DDB-B) Device Management - DynamicObjectBinding-B (DM-DOB-B) Device Management - DeviceCommunicationControl-B (DM-DCC-B)

Segmentation Capability:

Able to transmit segmented messages Able to receive segmented messages

Window Size _______ Window Size _______ Dynamically Creatable Dynamically Deletable
O_50201 - 08/12 - Subject to change. Belimo Aircontrols (USA), Inc.

Standard Object Types Supported:


Object-Type Analog Input Analog Output Analog Value Binary Value Supported Optional Properties Supported Description Description Description Description Active_Text Inactive_Text Relinquish_Default Priority_Array Description Writable Properties Present_Value Present_Value Present_Value Object_Identifier Object_Name Location APDU_Timeout Number_Of_APDU_Retries Present_Value

Device

Multi-state Value

Description State_Text Relinquish_Default Priority_Array Description State_Text Relinquish_Default Priority_Array

Multi-state Output

Present_Value

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Energy Valve BACnet Protocol Implementation Conformance Statement


Data Link Layer Options:

BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____________ MS/TP master (Clause 9), baud rate(s): 115K,76.8K, 38.4K,19.2K,9.6K MS/TP slave (Clause 9), baud rate(s): __________ Point-To-Point, EIA 232 (Clause 10), baud rate(s): __________ Point-To-Point, modem, (Clause 10), baud rate(s): __________ LonTalk, (Clause 11), medium: __________ BACnet/ZigBee (ANNEX O)
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No

Networking Options:

Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No Does the BBMD support network address translation? Yes No
Character Sets Supported:

ISO 10646 (UTF-8) ISO 10646 (UCS-2)


Read Only Objects
O_50201 - 08/12 - Subject to change. Belimo Aircontrols (USA), Inc.

IBM/Microsoft DBCS ISO 8859 ISO 10646 (UCS-4) JIS X 0208


Writable Objects AO1 MO1 Setpoint Relative in % Override Control 1 None/Auto 2 - Open 3 - Close 4 - Vmax 5 - Vnom 6 Stop AV100 MV100 Vmax : Flow Limit in % Control Mode 1 - Position Control 2 - Flow Control MV101 DeltaT Limitation Off - Disabled On - Enabled AV103 AV104 DeltaT Setpoint in C DeltaT Setpoint in F

Supported BACnet Objects:


AI1 AI2 AI10 AI11 AI12 AI13 AI20 AI25 AI21 AI26 AI22 AI27 AI30 AI35 AI31 AI36 AI32 AI37 AI10 AI102 Relative Position in % Absolute Position in Relative Flow in % Absolute Flow in l/min Absolute Flow in m3/h Absolute Flow in gpm Temperature 1 (remote) in C Temperature 1 (remote) in F Temperature 2 (embedded) in C Temperature 2 (embedded) in F Delta Temperature in C Delta Temperature in F Power in kW Power in kBTU/h Cooling Energy in kWh Cooling Energy in kBTU Heating Energy in kWh Heating Energy in kBTU Nominal Flow in l/min Nominal Flow in gpm