You are on page 1of 21

PDHengineer.

com
Course E-3022

Power System Neutral Grounding Fundamentals


Thisdocumentisthecoursetext.Youmayreviewthismaterialat yourleisurebeforeorafteryoupurchasethecourse.Ifyouhavenot alreadypurchasedthecourse,youmaydosonowbyreturningtothe courseoverviewpagelocatedat: http://www.pdhengineer.com/pages/E3022.htm (Pleasebesuretocapitalizeandusedashasshownabove.) Oncethecoursehasbeenpurchased,youcaneasilyreturntothe courseoverview,coursedocumentandquizfromPDHengineersMy Accountmenu. Ifyouhaveanyquestionsorconcerns,rememberyoucancontactus byusingtheLiveSupportChatlinklocatedonanyofourwebpages, byemailatadministrator@PDHengineer.comorbytelephonetoll freeat1877PDHengineer. ThankyouforchoosingPDHengineer.com.

PDHengineer.com,aservicemarkofDecaturProfessionalDevelopment,LLC.E3022C1

Power System Neutral Grounding Fundamentals


by Louie J. Powell, PE Saratoga Springs, NY

One of the decisions that must be made in designing a power system is how the neutral of the system should be connected to ground. The designer has several options from which to choose: No intentional connection between the neutral and ground Solid (no intentional impedance) connection between neutral and ground Insertion of resistance between neutral and ground Insertion of inductive reactance between neutral and ground And within the resistance and inductive choices, the designer has a further decision regarding the relative magnitude of the impedance to be inserted into the circuit. Ultimately, each of these choices affects the way that the power system performs in response to various contingencies, so the choice between these options is not a trivial matter. It is possible to devote an entire career to studying the implications of these choices. Recently, three noted authors published a nearly 600 page book1 that addresses the concerns involved in grounding decisions in great detail. This seminal book should be included in every serious library treating power system engineering fundamentals. IEEE has published a number of standard references on the subject that should be available to every power system engineer.2 3 But it is also possible to visualize the impact of the basic choices in an intuitive fashion that does not rely on heavy use of mathematics. This course will present the basic choices as well as the resulting system performance characteristics. Introduction Figure 1 illustrates a simplified power system consisting of a three-phase voltage source connected to a set of conductors. The three-phase source consists of three Thevenin equivalent fundamental frequency sinusoidal voltage sources that are each equal in magnitude to the phaseto-ground system voltage, and that are displaced 120 electrical degrees. The electrical system is represented by a set of three inductive reactances, designated as jXL, that are equal in magnitude. There may be some unbalance on practical power systems, but the impact of unbalance between phases is beyond the scope of the present treatment. Practical power systems also include resistance, but in most instances the inductive reactance is about an order of magnitude larger than the resistance. So for the sake of this development, system resistance can be ignored. Attention is drawn to two important aspects of Figure 1. First, two terminal points have been identified in the figure. N is a terminal point at the neutral of the power system the neutral of the three-phase voltage source. G is a terminal point that is connected to ground. In this context, ground is a reference plane that is connected to earth (in Europe, the term earthing is used to convey the same meaning as the term grounding in North America) and that is the reference point for all voltages throughout the system. Those two terminal points will be retained as the figure is later transformed into an equivalent circuit for analysis so that it is possible to explore the impact of the various choices of how N and G may be interconnected.

2009 Louie J. Powell

page 1 of 20 pages

Power System Neutral Grounding Fundamentals


Figure 1 also shows that there is a capacitance, shown here as capacitive reactance, -jXC0, between each phase conductor and ground. This is a distributed capacitance that exists by virtue of the fact that the power system conductor is physically in parallel with earth. The negative sign indicates that this distributed parameter is capacitive. The suffix 0 has a meaning drawn from the study of symmetrical components. However, it is not necessary for the reader to understand symmetrical components, and it is sufficient to simply accept that the suffix is a convenient handle to assign to the distributed parameter that may reappear later in some other aspect of power system engineering analysis.

Fig 1 Typical three-phase power system with system inductive reactance (JXL) and distributed capacitance (-JXC0), and with terminal points that can subsequently be used to explore options for connecting the system neutral (N) to ground (G).

System inductive reactance in ohms can be calculated from the inductance of the system using equation 1: jXL = j 2 f L (1) where f L is system frequency is the inductance in the system in henries

Likewise, the distributed capacitive reactance (also in ohms) can be calculated using equation 2.

jXC 0 =
where f C

1 j 2 f C

(2)

is system frequency is the distributed capacitance to ground in Farads

Readers will recognize that the capacitive reactance looks a bit like a load. If fact, this capacitive reactance is a parasitic charging capacitance through which current is always flowing. The only

2009 Louie J. Powell

page 2 of 20 pages

Power System Neutral Grounding Fundamentals


reason it is normally not considered is that jXC0 is very much larger than jXL several orders of magnitude larger so it is normally negligible. Because jXC0 is much larger than jXL, it really doesnt matter where the distributed capacitors are actually connected in the equivalent circuit. In fact, we can easily move the connection point from where it is shown in figure 1 across the series inductive reactance to a set of points between the three voltage sources and their associated reactances. Having made that change, and recognizing that the voltage source is a Thevenin equivalent voltage and therefore impedanceless, we can further move those shunt capacitance elements down to the neutral of the voltage source. However, when that is done, the distributed capacitive reactances of the three phases are in parallel, and can be replaced with an equivalent distributed capacitance value of jXC0/3 as shown in figure 2.

Fig 2 Equivalent circuit with the distributed capacitance lumped at the neutral

Note that in figure 2, terminals N and G have been retained. Finally, we can take one further step in the evolution of this equivalent circuit by observing that figure 2 is totally symmetrical it represents three phases that are equal in magnitude and displaced from each other by 120 electrical degrees. Therefore, for the sake of analysis, we can ignore two of those three phases, perform our analysis on the third phase only, and then observe that whatever we find happening on that phase will also happen on the other two phases 120o (approximately 5.555 msec) and 240o (about 11.11 msec) later, respectively. That then leads us to the simple, single phase equivalent circuit shown in figure 3. And once again, we observe that the neutral, N, and ground, G, terminals have been retained. So now the question is: considering the simplified equivalent circuit of figure 3, what is the consequence of the following options: 1. Open circuit between N and G 2. Zero-impedance connection between N and G 3. Insertion of a low magnitude of resistance between N and G 4. Insertion of a high magnitude of resistance between N and G 5. Insertion of a low magnitude of inductive reactance between N and G 6. Insertion of a high magnitude of inductive reactance between N and G

2009 Louie J. Powell

page 3 of 20 pages

Power System Neutral Grounding Fundamentals

Fig 3 Single phase equivalent circuit for a three-phase power system

In order to investigate those six options, however, we do need to make one final modification to the equivalent circuit. The basic problem that the options present relates to what happens when there is a single-phase-to-ground fault on the power system, and to represent such a fault, we need a switch. Hence, the final equivalent circuit is shown in figure 3. Closing this switch has the effect of applying a single-line-to-ground fault on the system. Leaving the switch open is equivalent to having the system unfaulted.

Fig 4 Single-phase equivalent circuit for investigating system neutral grounding options

Case 1: Open circuit between N and G This case represents the system application in which there is no intentional connection between N and G; that is, the system is nominally ungrounded. In reality, of course, the term ungrounded is inexact because the neutral is really connected to ground through the reactance of the distributed charging capacitance in the system. That is, an ungrounded system is actually capacitively grounded through jXC0/3.

2009 Louie J. Powell

page 4 of 20 pages

Power System Neutral Grounding Fundamentals


Because the impedance that actually limits ground fault current is rather high, the magnitude of current that will flow to a ground fault is often so low that automatic tripping is not required. That is the most-cited advantage of the ungrounded system the fact that ground fault tripping is not required means that system availability can be attractively high. This is especially appealing in mission critical applications such refinery and power house auxiliary systems Earlier it was noted that jXC0 is several orders of magnitude larger than jXL. Therefore, it also must be true that jXC0/3 is much larger than jXL. For this reason, jXL can be ignored, and this case then becomes a matter of capacitor switching. When the switch is open, the voltage across the switch is equal to the single-line-to-ground voltage on the system. But that voltage is also the same as the voltage source, V1. Therefore, when the switch is open, the voltage across the equivalent distributed capacitance, jXC0, must be zero (Kirchoffs voltage law requires that the voltage across the capacitor plus the voltage V1 must equal the open circuit voltage.) Closing the switch (applying the ground fault) forces the voltage across the switch to be zero. Therefore, the voltage across the capacitor must be V1 (again, Kirchoffs voltage law). But principle that most of us remember from fundamental physics is that it is not possible to change the voltage across a capacitor instantaneously. Its not possible for the voltage across the equivalent distributed capacitance to change from zero to V1 instantaneously! So that suggests another principle that we may remember from many years ago the switching of an energy storage element (such as a capacitance) always involves a differential equation, and the solution to that differential equation always includes two components: A steady-state component A transient component And the nature of these components depends on when the switching occurs. Recall that V1 was described as a fundamental frequency sinusoidal voltage. If the instantaneous value of V1 at the instant the switch is closed is zero, then the instantaneous voltage across the open switch in the instant just prior to it being closed is also zero. Because the voltage across the switch must remain zero after it is closed, then the voltage across the distributed capacitance will gradually increase to a value of V1 at the same time that the driving voltage in the network increases to V1. The steady state component of current will be the voltage divided by the magnitude of the distributed capacitive reactance, while the transient component will be zero. Since the distributed capacitive reactance is very large, then the steady state current (ground fault current) will be quite small essentially equal to the nominal capacitive charging current that would flow when the system is otherwise healthy. But if V1 is at its crest value at the instant the switch is closed, then a transient component must be generated by the switching event. That is Prior to closing the switch, the voltage across the switch is V1 and is at its crest value o The voltage source is also V1 and is also at its crest o Therefore the voltage across the equivalent capacitance must be zero But in the instant after closing the switch, the voltage across the switch is zero o The voltage source continues to be V1 and continues to be at crest. o The voltage across the equivalent capacitor must continue to be zero since it cannot change instantaneously.

2009 Louie J. Powell

page 5 of 20 pages

Power System Neutral Grounding Fundamentals


Therefore, a transient voltage of magnitude V1 (crest) must appear in the circuit in the instant after the switch closes.

The implications of these observations are that the application of a ground fault in a power system with the neutral ungrounded (which really means grounded through distributed capacitance) will result in generation of transient overvoltages. The magnitude of the transient overvoltage depends on both system parameters (obviously on capacitance, but also on inductance and resistance) and on when during the sinusoid of voltage on the AC system the fault occurs. One might imagine that faults are more likely to occur when the AC system voltage is nearing its crest value (because that implies the maximum stress on insulation), and unfortunately, that is exactly the condition that results in the most severe transient overvoltage. The phenomenon of excessive transient overvoltages due to ground faults on nominally ungrounded systems has most often been observed in higher voltage applications. After the fault has been on the system for a period of time the transient overvoltage will decay away leaving a voltage across the capacitor that is equal to V1 (because the voltage across a closed switch must be zero). If the fault then clears, the current required to charge the distributed capacitance will be discontinued, leaving the voltage across the capacitance at the value of V1 at the instant the fault was removed. Obviously, if this happens when V1 is at or near the crest of the sinusoid, then the capacitance will be left charged at this steady state magnitude. Then, if the fault is subsequently reapplied, depending again on when on the sinusoid of the source V1 the fault reoccurs, the transient voltage that will have to appear in the circuit can be as high as 3V1. This repeated cycle of interruptions and reignitions would normally caused by an external means say, vibration due to the rotation of a motor. The consequence of so-called repetitive restriking is to cause the sustained line-to-ground voltage to ratchet up to a value that is significantly greater than V1. Repetitive restriking has most often been observed in low-voltage systems. There is one very special application of the ungrounded neutral that should be mentioned marine systems. The concern in marine systems is for cathodic corrosion of the hull of vessels, and one way to manage that risk is to completely separate earth ground from the electrical system. This creates special problems in system design and protection that are beyond the scope of this course. Finally, the supposed advantage of the ungrounded system that automatic tripping for singleline-to-ground faults is not required is itself a potential problem. While the magnitude of current for a ground fault may not necessitate tripping, the fact is that during a ground fault an abnormally high voltage will be present on the two healthy phases, and that phenomenon may in fact accelerate the occurrence of a second fault. And with a pre-existing ground fault on the system, a second ground fault would create a line-to-line fault. Conclusions: Un-grounded systems Very low ground fault current o Essentially equal to the nominal system charging current o Generally not detectable with ordinary current-based ground fault protection technology o May not necessitate automatic tripping for ground faults Potential for hazardous transient overvoltages Potential for hazardous sustained overvoltages due to repetitive restriking in low voltage systems

2009 Louie J. Powell

page 6 of 20 pages

Power System Neutral Grounding Fundamentals


Ungrounded marine systems require special consideration Potential for accelerated second fault if the first fault is not automatically cleared.

Case 2: Zero-impedance connection between N and G Applying a zero-impedance shunt between N and G has the effect of shorting out the distributed capacitance of the system. Effectively, this is what would be accomplished by solidly grounding the system by connecting the neutral directly to ground with no intervening impedance. Obviously, the transient effects associated with system capacitance are no longer a concern (although there are other sources of transient overvoltages that would have to be addressed). However, there is a downside if jXC0 is removed from the circuit, the only impedance left to control the magnitude of ground fault current is jXL. That means that that the magnitude of ground fault current in the system would dramatically increase, and it would be the high magnitude of fault current itself that would be troublesome. Specifically: The single-phase-to-ground-fault current magnitude would be about the same as the three-phase fault magnitude. It is possible for the fault current for the current available to single-line-to-ground-faults to greatly exceed the available three-phase magnitude. This phenomenon would most likely be seen in association with solidly grounded generators or in close electrical proximity to banks of wye-connected transformers. Higher fault current implies greater stress on the circuit breakers that would have to interrupt those fault currents. Higher fault currents implies greater burning damage at the point of a fault. This is an especially important consideration with rotating machines. A stator ground fault in a motor or generator on a system where the neutral is solidly grounded will produce so much burning damage that the machine will likely be unrepairable. Higher fault current implies greater arc-flash hazard for employees in the workplace. This subject has gotten a lot of attention in recent years. The situation where the arc flash energy available in the system is so high that appropriate personnel protection clothing is simply not available would likely be viewed as completely unacceptable by many employers. Higher ground fault current implies higher earth potential gradients. While this phenomenon is not encountered often, it can be very disruptive for ground faults to expose workers to distracting and potentially hazardous electric shocks even when they are not in the immediate proximity of faulted electrical apparatus. While these adverse consequences are a consideration, there are applications where the higher fault ground fault current associated with a solidly grounded neutral has advantages. Specifically, higher fault currents are usually desirable on high-voltage transmission lines to be able to provide reliable protection over the entire length of a line. The term solidly grounded is generically descriptive and applies to the situation where the connection between N and G does not involve any intentional impedance. However, that term does not provide any guidance on the resulting system performance. The term effective grounding has been defined to apply specific technical criteria to the conditions that will exist when the neutral is solidly grounded (equations 3 and 4)4. Systems that are effectively grounded will have known performance characteristics with respect to transient overvoltages, and whether or not a system is effectively grounded is a criterion in the application of surge arresters. Most solidly grounded systems are effectively grounded. But it is possible for a solidly grounded

2009 Louie J. Powell

page 7 of 20 pages

Power System Neutral Grounding Fundamentals


system involving very long transmission or distribution circuits to not be effectively grounded, especially at the remote ends of those circuits. Criteria for effective grounding:

3 X1 R0 1 X1 X0
In these expressions, X0 X1 R0

(3) (4)

is the zero sequence inductive reactance is the positive sequence inductive reactance is the zero sequence resistance

Likewise, there are a few special instances in which effectively grounded systems are not solidly grounded. Those will be discussed later in case 5. There is one set of circumstances that requires special consideration. The voltage V1 in figure 4 is a sinusoidal ac voltage, that is V 1 = V sin (t ) (5) For example, if the three-phase system voltage is nominally 480v, then V1 will have a range of instantaneous values between zero and the crest value of the 277v. line-to-neutral voltage, or 392v. There is a minimum voltage required to sustain an arc. The magnitude of this minimum voltage depends on a variety of factors whether or not the short circuit is contained in a fashion such that ionized gas can accumulate in the vicinity of the fault, ambient temperature and humidity, etc. Generally, however, the minimum voltage is believed to be in the range of 200 300v. As the system line-to-neutral driving voltage varies between zero and its crest value, there will be periods when the voltage is unable to sustain an arc, and the arc associated with a short circuit will be extinguished. Obviously, at a subsequent point on the sinusoid of voltage the instantaneous magnitude may again exceed the threshold voltage required to sustain an arc, but because the voltage is only slightly greater than the minimum, the arc may not actually restrike in each successive half-cycle of the driving voltage. The result is a phenomenon in which arcing ground faults are intermittent. And obviously, if the arc associated with the short circuit is intermittent, the current that flows in the circuit will also be intermittent. This has two consequences. First, the effective heating value of the intermittent short circuit current (also called the rms of the short circuit current) will be lower than the magnitude of current that one would calculate from known circuit parameters. This means that protective devices that sense rms current are relatively less effective in detecting the current associated with arcing ground faults. Second, if protective devices cannot accurately measure the current associated with arcing ground faults, they may be unable to detect those faults, thereby allowing the faults to persist for extended periods. And given the intermittent nature of the arc in an arcing ground fault, the result is that extensive burning damage can result from the fault.

2009 Louie J. Powell

page 8 of 20 pages

Power System Neutral Grounding Fundamentals


The classical analysis of the arcing ground fault phenomenon would suggest that arcing ground faults will only occur on systems where the voltage is 480v or perhaps 600v. At higher system voltages, the actual instantaneous driving voltage is greater than the minimum voltage required to sustain an arc for a much greater portion of the voltage half-cycle, with the result that the arc is more likely to be re-established in every half-cycle of voltage. Conversely, at lower voltages (for example, on three-phase 208v systems), the actual phase-toneutral driving voltage is less than the nominal voltage required to sustain an arc. That leads to the traditional conclusion that arcing ground faults cant occur on 208v systems. The fact is that operators of 208v secondary network systems have experience that conflicts with this theory; there are many documented instances of intermittent arcing ground faults in 208v network vaults. The factor that may explain this discrepancy is that network vaults are confined spaces that allow for accumulation of ionized gas. The effect of this accumulation is to reduce the voltage required to sustain an arc sufficiently to allow arcing ground faults to occur. An important consideration that strongly favors solidly or effectively grounded systems is the ability to support single-phase-to-ground connected loads. Its not unusual for loads to be connected single-phase-to ground. In low voltage systems, this is a very practical way to serve individual loads; 277v lighting is very commonly applied in systems rated 480v three-phase. Also, the whole point of 208v systems is that the single-phase-to-ground voltage is 120v, constructing three-phase systems at this voltage allows large numbers of single-phase 120v loads to be served economically. In medium- and high-voltage systems, it is less common to see single-phase loads. However, it is sometimes necessary to supply small aggregations of load from these higher-voltage systems, and it is economically more appealing to install a single-phase transformer with a single bushing that is connected phase-to-ground than it is to install a single-phase transformer connected phase-tophase and must therefore have two higher-voltage bushings. When loads are connected on a single-phase basis, the concern is that it is not always possible to exactly balance the loads across the three phases. Whatever unbalance there may be appears as a single-phase-to-ground load. Fig 5 is a restatement of the equivalent circuit of fig 4 for the case of unbalanced single-phase loading.

2009 Louie J. Powell

page 9 of 20 pages

Power System Neutral Grounding Fundamentals


Fig 5 Equivalent circuit for a solidly grounded system with single-phase-to-ground connected load The fact that there is an essentially zero-impedance connection between neutral and ground means that the only impedances in this circuit are the system inductance, and the impedance of the load. More importantly, because there is no significant impedance between neutral and ground means that there is no significant voltage drop between neutral and ground resulting from the flow of single-phase load current. Therefore, the neutral and ground will have essentially the same voltage. If the system were ungrounded, the impedance XC0/3 would appear between neutral and ground. This would have two consequences. First, because that impedance is relatively large, it would severely limit the ability of the system to support the single-phase load. Also, to whatever degree the system did support single-phase loading, the fact that load current would pass through this impedance would result in a voltage drop between neutral and ground, thereby elevating the voltages on both the system neutral and on the phase conductor and resulting in a potentially hazardous condition. Conclusions: Solidly or Effectively grounded systems Very large ground fault currents o Limited only by the impedance of the system o In special cases, may be greater than the three-phase fault current magnitude o High ground fault current magnitude present potential people hazards 9 Greater arc-flash energy requiring more aggressive personnel protection 9 Earth potential gradient concerns o Automatic fault detection and clearing is mandatory Transient overvoltages associated with creating or clearly ground faults controlled to within reasonable limits allows for easier application of surge protective devices Potential for hazardous arcing ground faults in some lower voltage applications Readily supports single-phase-to-ground connected loading Case 3: Low resistance connection between N and G One of the most common options for system neutral grounding in industry involves the application of a resistor between neutral and ground. Actually, there are two options for resistive grounding. We will first consider the case where the resistor has a relatively low ohmic rating. In this context, low means that the resistor will have an ohmic value that is much smaller than XC0/3 and much larger than XL. For example, on a 13.8kV system XC0/3 will have a magnitude in the range of 1000-2000 ohms, while XL will be a fraction of one ohm. A typical situation would then be to select a resistor with an ohmic rating of 20 ohms. Given that

XC 0 >> R >> XL 3
Then, the fault current in this system will be

(6)

Ifault =

V1 R

(7)

2009 Louie J. Powell

page 10 of 20 pages

Power System Neutral Grounding Fundamentals

This leads to two important observations: 1. The magnitude of ground fault current will be determined almost exclusively by the ohmic rating of the resistor, and typically will be limited to a value that is not very different from load current. For example, in a 13.8kV system, a typical 20 ohm resistor will limit ground fault current to 400 amperes. 2. The equivalent circuit, shown in fig 6, for a ground fault is therefore a predominantly resistive circuit. That means that there are no significant switching transients associated with either applying or clearing ground fault currents.

Fig 6 Equivalent circuit for a system with resistance grounding The fact that low resistance grounding limits ground fault currents to moderate levels less than load current has a number of attractive features for industrial applications. Lower ground fault current means lower arc flash hazards (although it must quickly be pointed out that the arc flash hazards associated with phase-to-phase and three-phase faults remain a very serious concern). Also, when less fault current is injected into the ground, the risk of earth potential gradients is significantly reduced and in fact normally becomes a non-issue. Lower fault current also normally implies that the burning damage at the point of a fault will be significantly reduced, and this can be a very important consideration in industrial systems with large populations of medium voltage motors. The fact that the circuit is primarily resistive also has advantages. Resistance adds damping to the equivalent circuit for the fault, so much so that there are essentially no concerns for repetitive restriking or transient overvoltages associated with ground fault conditions. The price that has to be paid for these attractive features is that the available ground fault current is lower than the three-phase fault current, and in fact is not too different from load current. That raises the concern for fault detection. Fortunately, relaying schemes have been developed that can very easily discriminate between three-phase balanced load or fault current, and single-phaseto-ground fault current. The most common feature of these schemes is that they employ protective relays that measure the residual of the three phase currents rather than the individual phase currents themselves. Note that conventional fuses tend to be less effective in lowresistance grounded systems because they respond to currents on an actual per-phase basis.

2009 Louie J. Powell

page 11 of 20 pages

Power System Neutral Grounding Fundamentals

Also, the fact that a physical resistor is connected between neutral and ground means that under fault conditions, the system neutral will be elevated from ground potential. As a practical matter, the neutral-to-ground voltage can be as high as the unfaulted line-to-neutral voltage magnitude. Resistance grounded systems are clearly NOT effectively grounded systems, and the possible elevation of neutral voltage means that care has to be taken to insulate and isolate the actual system neutral. Also, the elevation of neutral voltage under ground fault conditions means that the voltage on the unfaulted phases will be elevated to the phase-to-phase voltage magnitude. This results in the need to apply higher-rated surge voltage protection compared with solidly or effectively grounded system. While limiting ground fault current can result in a reduction in fault point damage, this will be the case only if the fault can be detected and cleared automatically and immediately. In recent years, industry has come to recognize that faults in the stator winding of generators on low-resistance grounded systems may actually be exposed to incrementally greater burning damage because tripping the generator for a stator ground fault does not necessarily immediately clear the fault.5 Finally, the presence of a finite value of resistance between neutral and ground essentially eliminates the possibility of serving single-phase-to-ground loading. Conclusions: Low-Resistance grounded systems (typically 100-600 amperes) Ground fault currents limited to modest values o Limited almost entirely by the ohmic rating of the resistor o Typically on the order of load current o Automatic fault detection and clearing is mandatory o Requires relaying schemes that measure the residual of the three phase currents o Traditional fusing may not be a practical form of protection No significant concern for transient overvoltages associated with ground faults Mandates special considerations in applying surge overvoltage protection Does not support single-phase-to-ground connected loading Case 4: High resistance connection between N and G If the resistor connected between N and G presents a high magnitude of resistance, some of the simplifying assumptions made for the low resistance grounding case no longer apply. As the magnitude of R approaches the scalar magnitude of XC0/3, it is no longer possible to ignore the effect of distributed capacitance. The term high resistance grounding generally implies the situation in which equation 8 is true.

XCO 3

(8)

In this situation, the total magnitude of current that will flow to a ground fault on the system will be

Ig 2

V1 R

(9)

2009 Louie J. Powell

page 12 of 20 pages

Power System Neutral Grounding Fundamentals

Low voltage systems tend to be physically compact primarily because voltage drop is an impediment to establishing longer circuits. In low voltage systems, it is not uncommon for the capacitive charging current to be on the order of 1-2 amperes, and low resistance grounding designed in accordance with equation (8) will result in a total current that is only slightly greater in magnitude, perhaps 2-3 amperes. With ground faults limited to this extent, it may be possible to forgo automatic ground fault tripping in favor of allowing the fault to remain while diagnostic procedures determine the fault location. Since most faults originate on a single-phase-to-ground basis, the use of high-resistance grounding therefore results in an apparent improvement in system availability. The process of locating a fault on a high-resistance grounded system requires that a means be provided to cause the fault current to pulsate so that it can be distinguished from the natural distributed charging current in the system. Traditionally, this has been done by applying a contactor that cyclically shorts a portion of the resistance. An electrician can the trace the pulsating current using an ordinary clamp-on ammeter. However, it must be noted that using a clamp-on ammeter to trace a pulsating fault current may expose the electrician to energized parts and caution must be exercised to verify that the electrician is equipped with the appropriate personal protective clothing for the arc flash level available from the system. Figure 6 is appropriate for the high-resistance grounded case, but in this instance, consideration has to be given to the fact that the distributed charging capacitance is no longer negligible. The net impedance between N and G is significantly large. Therefore, when there is a fault on the system, there will be a significant voltage drop between N and G the steady-state value of this voltage will be the nominal line-to-neutral voltage, V1. That means that the system neutral will be displaced 100% in the event of a ground fault, causing the voltages on the two healthy phases to have a magnitude above ground equal to the line-to-line system voltage. The fact that the voltage on the healthy phases is displaced significantly during ground faults may be a special consideration if the application does not include automatic fault detection and clearing. The actual insulation capability of power cables is based on the presumption that voltages will not be significantly unbalanced for extended periods, and if the application presumes that the fault will be traced manually rather than tripped automatically, it may be necessary to specify cable with a higher voltage rating. When the condition of equation (8) is satisfied exactly, the circuit between N and G becomes an RC circuit with a time constant of one electrical radian, and that fact is very significant. Earlier, in the discussion of the ungrounded neutral (case 1), it was observed that it was possible for voltage to gradually build up across the equivalent system charging capacitance, XC0/3, resulting in devastatingly high phase-to-neutral voltages. With a time constant of one electrical radian, it is not possible for this voltage escalation effect to take place. Whatever voltage is trapped on XC0/3 during a fault will decay rapidly preventing the step-wise escalation of voltage described earlier as repetitive restriking. That consideration is another of the strong advantages of high-resistance grounding. Historically, high-resistance grounding was originally intended for low-voltage applications. It has also been widely used in some higher voltage applications, but there are some serious constraints that must be observed. The key point is the objective for using high-resistance grounding. There are basically two scenarios here:

2009 Louie J. Powell

page 13 of 20 pages

Power System Neutral Grounding Fundamentals

If the objective for high-resistance grounding is simply to limit the available ground fault current, thereby limiting burning damage and earth potential gradients, then the system can be applied along with equipment that automatically detects faults and initiates automatic tripping. High resistance grounding is very commonly applied at the neutrals of generators connected to the grid through dedicated unit step-up transformers. In these applications, even at unit voltages of 20kV and greater, the total natural distributed charging current rarely exceeds 5-7 amperes, and high-resistance grounding systems are typically designed to limit ground fault current to 10 amperes. Another common situation for high-resistance grounding with automatic tripping is in mining applications. There are special safety rules in the mining industry that limit the maximum earth potential gradients, and to achieve that level of personnel protection, its common to see high-resistance grounding used to limit ground fault currents to 25 amperes.

But if the objective for high-resistance grounding is to provide a traceable ground fault so that a diagnostic procedure can replace automatic tripping, then special consideration has to be given to the maximum magnitude of ground fault current in higher-voltage applications. Empirical evidence suggests that if the magnitude of ground fault current exceeds 10 amperes, the amount of burning that will take place at the fault point will increase and eventually lead to escalation into a multi-phase fault. The natural charging current present at system voltages greater than 5kV is often greater than 10 A. For that reason, when high-resistance grounding is applied at system voltages in excess of 5kV, it is usually recommended that the system be designed to automatically detect and trip for ground faults.

In low voltage applications, the circuit shown in fig 6 applies literally. In higher voltage applications, however, it is common to see a small transformer connected between N and G, with a resistor across the secondary of the transformer. In this arrangement, the effective magnitude of resistance in the circuit is the actual ohmic rating of the resistor multiplied by the square of the transformer turns ratio. This typically results in a lower cost, more compact installation than would be the case if the resistor were fully rated for the required resistance. The transformer would normally have a primary voltage rating equal to (or perhaps greater than) the line-toneutral voltage rating of the system, and would require a thermal (or kVA) rating sufficient to withstand the loading associated by a ground fault for time that the fault will be allowed to persist on the system. Conclusions: High-Resistance grounded systems Ground fault currents limited to very low values o Fault current limited to slightly greater than the natural system distributed charging current o Fundamental design criterion:

XCO 3

Traceable fault current option o Uses a contactor to cyclically short a portion of the resistor causing the fault current to pulsate o Fault location is possible using a hand-held clamp-on ammeter

2009 Louie J. Powell

page 14 of 20 pages

Power System Neutral Grounding Fundamentals


Eliminates the need for automatic ground fault tripping, resulting in an apparent increase in system availability o Electricians MUST be equipped with appropriate personal protection gear o May require impose special considerations in specifying power cable insulation o Should not be applied in systems rated above 5kV In other applications o Mining, voltages greater than 5kV, and unit-connected generators o Objective is only to limit burning damage and potential gradients o Requires automatic tripping No significant concern for transient overvoltages if design criterion is met Sustained overvoltage on healthy phases during ground faults mandates special considerations in applying surge overvoltage protection Does not support single-phase-to-ground connected loading o

Case 5: Low (inductive) reactance connection between N and G Yet another possibility is to connect an inductance between neutral (N) and ground (G) as shown in fig 7. As in the case of resistance, this comes in two flavors low inductance and high inductance.

Fig 7 Equivalent circuit for a low-inductance grounded system The first observation that can be made about low reactance grounding is that while the elements between neutral and ground form a parallel L-C circuit, the inductive reactance is many orders of magnitude smaller than the capacitive reactance, XC0/3. Therefore, the capacitance can often be neglected. There is resistance in this circuit. The typical X/R ratio of an inductor falls in the range of 60100, while the X/R ratio of typical system inductive reactances is 5 to 15 (low voltage systems tend to have a lower X/R than do higher voltage systems). And while the resistance is significant and must be considered in calculating the actual magnitude of short circuit current for the purpose of evaluating the duty on circuit breakers6, it is possible to ignore the resistive component of these impedances while examining the fundamental concepts involved in the application.

2009 Louie J. Powell

page 15 of 20 pages

Power System Neutral Grounding Fundamentals


Because the circuit has the same fundamental R-L characteristics of the basic power system, therefore, the practice of low reactance grounding does not introduce any new concerns with respect to switching and transients. While the equivalent circuit of fig 1 and its subsequent descendents is literally correct, this discussion has intentionally overlooked the question of whether these equivalent circuits contain all of the information needed to determine the actual magnitude of ground fault current for the applications they represent. The fact is that there are some additional considerations that enter into the determination of ground fault magnitudes, especially if the system neutral is solidly or effectively grounded (Case 2, fig. 5). When those factors are considered, one can conclude that the magnitude of ground fault current can sometimes exceed the available magnitude of current that would flow in the same system to a balanced, three-phase fault7. Those special circumstances include: Applications in the immediate vicinity of the solidly-grounded wye connection of delta-wye transformers (or three-phase banks of single-phase transformers). Applications at the terminals of generators whose neutrals are solidly grounded The most common situation for applying low reactance grounding is in one of these two situations where it is desired to fine-tune the available magnitude of ground fault current to a slightly lower value. Consider the multiple-transformer substation situation. While it is a relatively unusual situation, it is possible for the single-phase-to-ground fault level to exceed the interrupting ratings of circuit breakers even though those breakers have sufficient capability to switch the available three-phase fault level. This situation tends to come about when there are multiple delta--grounded-wye transformers connected together at their wye-connected terminals. In such instances, one solution is to install neutral grounding reactors (low inductance grounding) in between the neutral terminals of the transformers and ground. Whether the design limits the available single-line-toground fault level to equal the three-phase fault level, or whether an arbitrary ground fault level is merely assumed as a design objective is a decision that the system engineer must make based on both technical and economic considerations. In the generator instance, any time the neutral of a generator is solidly grounded, the available ground fault level will exceed the three-phase fault level. Obviously, this is not a problem for generators that are intended for installation in systems where the neutral is solidly grounded (especially, low voltage generators), but it can be a problem with larger (higher voltage) generators where NEMA standards do not require that the machines be mechanically braced for unbalanced fault stresses that are greater than the stresses associated with balanced three-phase faults. Again, the solution is to install low-inductance grounding at the generator neutral. Usually, the practice is to design the low-reactance grounding installation to limit the single-lineto-ground fault to equal the three-phase fault, but it is necessary for the system engineer go also consider other technical and economic factors before finalizing the design. The criteria used in designing a low-reactance grounding application depend very much on the objectives that the system is expected to support. Design is almost always a matter of compromising between competing objectives. For example, it is possible to design a lowreactance grounding application that will deliver effective grounding (as defined by equations [3] and [4]. It is also possible to design a low-reactance grounding application that supports single-phase-to-ground loading (ie, the effective low reactance inserted between N and G is small enough that the voltage drop between N and G due to unbalanced single-phase loading is acceptable. On the other hand, such designs may not limit the available single-line-to-ground fault current sufficiently to address a circuit breaker rating problem.

2009 Louie J. Powell

page 16 of 20 pages

Power System Neutral Grounding Fundamentals

And commonly, another limitation is the practicality and economics of the design. The cost of neutral grounding reactor increases as they are designed to have lower inductance, and there is a threshold below which it is not practical to build an inductor. As a consequence, it may not be economically practical to design a solution that requires only a very small incremental neutral inductance. Low-reactance grounding is one of the least common forms of system neutral grounding. The need to address multiple competing design objectives, and the amount of work involved in evaluating those options, are such that it is typically reserved for one of the two special cases cited. Conclusions: Low Reactance grounded systems Ground fault currents limited to meet a system design criterion o Limit ground fault current to an objective magnitude o Limit ground fault current to no greater than three-phase fault magnitude May or may not achieve effective grounding depending on design objectives May or may not support single-phase-to-ground connected loading depending on design objectives A relatively uncommon practice reserved for special applications Requires extensive system engineering Case 6: High (inductive) reactance connection between N and G As the name implies, high reactance grounding involves installing a high magnitude of inductive reactance between neutral (N) and ground (G). Because the inductive reactance is high, it is not possible to ignore the fact that the presence of this inductance makes the connection between N and G a parallel L-C circuit. In fact, it is the nature of that L-C circuit that gives this option its most attractive features. The design criterion for a high-inductive grounding system is given in equation 10

jXG =

XCO 3

[10]

When this criterion is met, the fundamental frequency impedance between N and G is infinite an open circuit. As a result, in steady state, high-reactance ground acts just like the ungrounded case, case 1. Specifically, there can be no ground fault current. In turn, that means that there is no fault-point damage, no mechanical distress on current-carrying conductors, no thermal distress, no earth potential gradients, and no arc flash. But there is still an electrical connection between N and G that presents impedances at frequencies other than the fundamental frequency. Therefore, those undesirable consequences of an ungrounded system that are mainly related to its performance with respect to non-fundamental frequency phenomena such as transient response and overvoltages, also do not appear. Historically, this form of grounding, also known as resonant neutral grounding or Peterson Coil Grounding (in honor of its inventor), was used to some degree in high-voltage transmission applications in North America up through the middle of the 20th century. At that point, however, its major drawback began to become an obstacle. Unlike high-resistance grounding, where it is necessary that the resistance only approximate the distributed charging reactance, in order for

2009 Louie J. Powell

page 17 of 20 pages

Power System Neutral Grounding Fundamentals


resonant grounding to work, the design criterion for resonant grounding must be met exactly. That means that each installation must be tuned to the distributed capacitance that it encounters in the system where it is installed. As transmission grids started expanding in the 1940s and 50s, it became necessary to provide a means of tuning the reactor to compensate for switching events on the system that changed the charging capacitance. Eventually, the resonant neutral grounding applications on the transmission system in North America were retired. However, there were transmission-level resonant neutral grounding applications in service in other parts of the world well into the 1970s, particularly in Asia. Another area where resonant neutral grounding was applied was at the neutrals of generators. In theory, these applications should have been ideal because, with the generator connected to the system through a dedicated generator step-up transformer, the only XC0/3 that would need to be considered was the capacitance of the generator, generator leads, and the delta-connected winding of the transformer. Practically, that means that the XC0/3 would essentially be the surge capacitors applied directly at the terminals of the generator. And the fact that resonant grounding would eliminate the risk of fault-point burning was a very attractive feature. On the other hand, experience with high-resistance grounding proved that it was just as effective in managing fault point burning, and the overall cost of the resistive approach was lower than the cost of a resonant solution. Even so, there were a number of power plants, mainly in the New England area, that were built with resonant grounding of their generators8. Today, however, resonant grounding is mainly an academic topic in North America. That is not to say that the practice has been abandoned. In fact, it is in very widespread use in mediumvoltage utility distribution applications in Europe and the UK. Conclusions: High Reactance grounded systems Ground fault currents limited to essentially zero o Design criterion

jXG =
o

XCO 3

Design criterion must be met exactly requires retuning if switching changes distributed capacitance of the system No unusual concerns for transient overvoltages Non-effective grounding requires special considerations when applying surge protection Does not support single-phase-to-ground connected loading No known installations in North America, but in wide-spread use in Europe and UK Also known as Peterson Coil or resonant neutral grounding

Applications Summary It is obviously impossible to declare that there is a single set of universally-correct answers. However, it is possible to summarize what appears to be the general application trends in system neutral grounding.

2009 Louie J. Powell

page 18 of 20 pages

Power System Neutral Grounding Fundamentals

Grounding Practice
Ungrounded neutral

Usual Applications
Generally not recommended on new systems May exist on legacy systems although a retrofit is usually recommended. Marine systems may be a special case Preferred practice for high voltage transmission systems Preferred practice on medium-voltage utility distribution systems in North America Commonly applied on low voltage systems serving single-phaseneutral loading Not recommended for medium-voltage distribution in industrial workplaces Preferred practice for medium-voltage distribution in industrial workplaces Preferred practice for unit-connected generator applications (with automatic tripping) Commonly applied in continuous process industrial applications, 5kV and below in conjunction with traceable fault technology May be used at higher voltages with automatic fault detection and tripping Cost-effective retrofit for legacy ungrounded systems Solution for managing high ground fault currents in substations Solution for generator grounding to support single-phase loading Requires extensive application engineering Rarely seen in North America today Commonly applied in medium voltage utility distribution applications in Europe and UK These approaches have been used as retrofit solution for legacy ungrounded systems. In general, these are compromise solutions and are not currently recommended practices.

Solidly grounded neutral (effective grounding)

Low resistance grounding High-resistance grounding

Low reactance grounding

High reactance grounding

Other practices including corner of the delta and midpoint grounding

Bonding and Grounding


This course has focused on the issues and practices involved in determining how the neutral of the electrical system should be connected to earth or ground. The primary objective of that focus is managing the magnitude of current that will be injected into ground as a result of a fault to ground on the electrical system. There is a closely related set of concerns associated with the design of ground grids, and the practices of bonding metallic structures. These concerns address management of the potential gradients that will arise as a result of that fault current being injected into ground. The primary criteria in establishing bonding practices is to limit the voltage to which a person can be exposed, either as a consequence of touching a metallic structure (where the voltage is the difference between the potential where the person is standing and the potential on the structure) or as a consequence of walking through a facility (where the voltage is the difference of potential across the length of the persons stride). Bonding and ground grid design is critical to personnel safety and is a specialized field in and of itself. It is mentioned here in order to emphasize that while establishment of proper system

2009 Louie J. Powell

page 19 of 20 pages

Power System Neutral Grounding Fundamentals


neutral grounding is important, it is not the complete answer and must go hand-in-hand with competent design of ground grids and bonding practices.
Dunki-Jacobs, JR; Shields, FJ and St Pierre, CR; The Industrial Power System Grounding Design Handbook, http://groundingdesignbook.com/index.html. 2 IEEE Std 80-1986, IEEE Guide for Safety in AC Substation Grounding 3 IEEE Std 142-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems (The IEEE Green Book). 4 Peterson, Harold A., Transients in Power Systems, John Wiley & Sons, New York, 1951; reprinted 1966, Dover Publishing, New York. 5 Powell, Louie J. The impact of system grounding practices on generator fault damage, IEEE Transactions on Industry Applications, vol. IA-34, Sept./Oct. 1998, pp. 923-927. 6 IEEE Std 551-2006-, IEEE Recommended Practice for Calculating Short-Circuit Currents in Industrial and Commercial Power Systems (The IEEE Violet Book) 7 Students interested in expanding their understanding of these considerations are encouraged to take the PDHengineer course on Symmetrical Components, E-4002 8 The reason these installations tended to be in New England was that the main proponent of resonant grounding of generators was the legendary Prof Eric T. B. Gross, initially at Cornell and later at Rensselaer. Many of his students spent their careers close to home in the New England area, and served as his disciples in advocating for this solution.
1

2009 Louie J. Powell

page 20 of 20 pages

You might also like